The present application relates generally to the use of liquid desiccants to dehumidify and cool, or heat and humidify an air stream entering a space. More specifically, the application relates to the replacement of conventional mini-split air conditioning units with (membrane based) liquid desiccant air conditioning system to accomplish the same heating and cooling capabilities as those conventional mini-split air conditioners and at the same time to provide additional functionality such as, for example, the ability for the system to heat and simultaneously humidify the space or for the system to heat and simultaneously dehumidify a space thereby providing for healthier indoor air conditions than conventional systems will provide.
Desiccant dehumidification systems—both liquid and solid desiccants—have been used parallel to conventional vapor compression HVAC equipment to help reduce humidity in spaces, particularly in spaces that require large amounts of outdoor air or that have large humidity loads inside the building space itself. (ASHRAE 2012 Handbook of HVAC Systems and Equipment, Chapter 24, p. 24.10). Humid climates, such as for example Miami, Fla. require a lot of energy to properly treat (dehumidify and cool) the fresh air that is required for a space's occupant comfort. Desiccant dehumidification systems—both solid and liquid—have been used for many years and are generally quite efficient at removing moisture from the air stream. However, liquid desiccant systems generally use concentrated salt solutions such as ionic solutions of LiCl, LiBr or CaCl2 and water. Such brines are strongly corrosive to metals, even in small quantities, so numerous attempts have been made over the years to prevent desiccant carry-over to the air stream that is to be treated. In recent years efforts have begun to eliminate the risk of desiccant carry-over by employing micro-porous membranes to contain the desiccant solution. These membrane based liquid desiccant systems have been primarily applied to unitary rooftop units for commercial buildings. However, residential and small commercial buildings often use mini-split air conditioners wherein the condenser (together with the compressor and control system) is located outside and the evaporator cooling coil is installed in the room or space than needs to be cooled, and unitary rooftop units are not an appropriate choice for servicing those spaces. In Asia in particular (which is generally hot and humid) the mini-split air conditioning system is the preferred method of cooling (and sometimes heating) a space.
Liquid desiccant systems generally have two separate functions. The conditioning side of the system provides conditioning of air to the required conditions, which are typically set using thermostats or humidistats. The regeneration side of the system provides a reconditioning function of the liquid desiccant so that it can be re-used on the conditioning side. Liquid desiccant is typically pumped or moved between the two sides, and a control system helps to ensure that the liquid desiccant is properly balanced between the two sides as conditions necessitate and that excess heat and moisture are properly dealt with without leading to over-concentrating or under-concentrating of the desiccant.
Mini-split systems typically take in 100% of room air through the evaporator coil and fresh air only reaches the room through ventilation and infiltration from other sources. This often can result in high humidity and cool temperatures in the space since the evaporator coil is not very efficient for removing moisture. Rather, the evaporator coil is better suited for sensible cooling. On days where only a small amount of cooling is required, the building can reach unacceptable levels of humidity since not enough natural heat is available to balance the large amount of sensible cooling. Equally on colder humid days, such as in the rainy season, heating the air would be preferred while also dehumidifying it. Mini-split systems are typically unable to provide dehumidification, although they will provide heating if they are setup as a heat pump.
In many smaller buildings a small evaporator coil is hung high up on a wall or is covered by a painting as for example the LG LAN126HNP Art Cool Picture frame. A condenser with compressor is installed outside and high pressure refrigerant lines connect the two components. Furthermore a drain line for condensate is installed on the indoor coil unit to remove moisture that is condensed on the evaporator coil to the outside. A liquid desiccant system can significantly reduce electricity consumption and can be easier to install without the need for high pressure refrigerant lines. The advantage of such an approach is that a significant portion of the cost of a mini-split system is the actual installation (the running, filling and testing of refrigerant line) that need to be installed on site. Furthermore, since the refrigerant lines run into the space, the refrigerant selections are limited to non-flammable and non-toxic substances. By keeping all of the refrigerant components outside, the number of available refrigerants can be expanded to include ones that otherwise would not be allowed, such as propane etc.
There thus remains a need to provide a retrofittable cooling system for small buildings with high humidity loads, wherein the cooling and dehumidification of indoor air can be accommodated at low capital and energy costs.
Provided herein are methods and systems used for the efficient cooling and dehumidification of an air stream especially in small commercial or residential buildings using a mini-split liquid desiccant air conditioning system. In accordance with one or more embodiments, the liquid desiccant flows down the face of a support plate as a falling film. In accordance with one or more embodiments, the desiccant is contained by a microporous membrane and the air stream is directed in over the surface of the membrane and whereby both latent and sensible heat are absorbed from the air stream into the liquid desiccant. In accordance with one or more embodiments, the support plate is filled with a heat transfer fluid that ideally is flowing in a direction counter to the air stream. In accordance with one or more embodiments, the system comprises a conditioner that removes latent and sensible heat through the liquid desiccant into the heat transfer fluid and a regenerator that rejects the latent and sensible heat from the heat transfer fluid to another environment and a heat dump coil that rejects excess heat to the other environment as well. In accordance with one or more embodiments the system is able to provide cooling and dehumidification in a summer cooling mode, humidification and heating in a winter operating mode and heating and dehumidification in a rainy season mode.
In accordance with one or more embodiments, in a summer cooling and dehumidification mode, the heat transfer fluid in the conditioner is cooled by a refrigerant compressor. In accordance with one or more embodiments, the heat transfer fluid in the regenerator is heated by a refrigerant compressor. In accordance with one or more embodiments, the refrigerant compressor is reversible to provide heated heat transfer fluid to the conditioner and cold heat transfer fluid to the regenerator and the conditioned air is heated and humidified and the regenerated air is cooled and dehumidified. In accordance with one or more embodiments, the conditioner is mounted against a wall in a space and the regenerator and heat dump coil are mounted outside of the building. In accordance with one or more embodiments, the regenerator supplies concentrated liquid desiccant to the conditioner through a heat exchanger. In one or more embodiments, the conditioner receives 100% room air. In one or more embodiments, the regenerator receives 100% outside air. In one or more embodiments the heat dump coil receives 100% outside air. In accordance with one or more embodiments a heat exchanger receives hot refrigerant and sends hot heat transfer fluid to a regenerator, while at the same time hot refrigerant is also directed to a heat dump coil and a cold refrigerant is used to send cold heat transfer fluid to a conditioner where cool, dehumidified air is created. In accordance with one or more embodiments there is a set of four 3- and one 4-way refrigerant valves that allows the hot refrigerant to be switched to heat the previously cold heat transfer fluid in a winter operating mode so that the conditioner receives the now hot heat transfer fluid and the cold heat transfer fluid is directed to the heat dump coil and regenerator. In accordance with one or more embodiments the set of refrigerant valves can also be switched so that the hot refrigerant is directed to the heat exchanger in a rainy season mode, wherein the hot refrigerant creates a hot heat transfer fluid for a regenerator, while at the same time the valving system is directing cold refrigerant to the heat dump coil and the conditioner receives no heat transfer fluid so that liquid desiccant in the conditioner absorbs moisture adiabatically.
In accordance with one or more embodiments the refrigerant valves contain a set of two 4-way and one bypass valve. In accordance with one or more embodiments the first 4-way valve is switched so that hot refrigerant from a compressor flows to a first heat exchanger and then to the second 4-way valve, from which it flows to a heat dump coil, through an expansion valve and to a second heat exchanger before flowing back to the first 4-way valve in a summer cooling and dehumidification mode. In one or more embodiments the first heat exchanger is coupled by means of a heat transfer fluid to a regenerator. In one or more embodiments the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments the regenerator delivers concentrated liquid desiccant to a conditioner. In one or more embodiments the second heat exchanger is coupled by means of a heat transfer fluid to a conditioner. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner receives concentrated liquid desiccant from a regenerator. In accordance with one or more embodiments the first 4-way valve can be switched to a winter heating and humidification mode such that the hot refrigerant first flows to the second heat exchanger, then through an expansion valve into the heat dump coil and through the second 4-way valve to the first heat exchanger and through the first 4-way valve back through the compressor. In accordance with one or more embodiments the first 4-way valve is switched so that hot refrigerant from a compressor flows to a first heat exchanger, through a second 4-way valve through an expansion valve and the now cold refrigerant flows through a heat dump coil where heat is added to the cold refrigerant by the coil, after which the refrigerant flows through the second 4-way valve through the bypass valve, back through the first 4-way valve to the compressor in a rainy season heating and dehumidification mode. In one or more embodiments, the first heat exchanger is coupled by means of a heat transfer fluid to a regenerator. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments, the regenerator delivers concentrated liquid desiccant to a conditioner. In one or more embodiments, the second heat exchanger is coupled by means of a heat transfer fluid to a conditioner. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner receives concentrated liquid desiccant from a regenerator. In one or more embodiments, the conditioner is only receiving concentrated desiccant from the regenerator but no heat transfer fluid is flowing in the rainy season mode.
In accordance with one or more embodiments a compressor delivers a hot refrigerant through a 4-way valve into a first heat exchanger where a hot heat transfer fluid is created in a summer cooling mode. The cooled refrigerant is then directed through a first expansion valve where it become cold to a second heat exchanger where it creates a cold heat transfer fluid. The hot heat transfer fluid in the first heat exchanger is directed through means of a series of valves to a liquid desiccant regenerator, where a concentrated liquid desiccant is produced as well as to a heat dump coil where excess heat can be rejected. In one or more embodiments, the regenerator and heat dump coil are located outside a building. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. The cold heat transfer fluid in the second heat exchanger is directed through a series of valves to a liquid desiccant conditioner where a concentrated liquid desiccant is received and used to dehumidify an air stream. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner is located inside a building. In one or more embodiments, the 4-way valve can be switched so that the hot refrigerant is directed to the second heat exchanger in a winter heating and humidification mode. In one or more embodiments, the second heat exchanger delivers a hot heat transfer fluid to a conditioner which in turn creates a warm, humid air stream for heating and humidifying a space. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner is located inside a building. In one or more embodiments, the cooler refrigerant leaving the second heat exchanger is directed through a second expansion valve and the cold refrigerant is not directed to the first heat exchanger wherein a cold heat transfer fluid is created. The cold heat transfer fluid in the first heat exchanger is now directed to a regenerator where heat and moisture are removed from an air stream and a heat dump coil where additional heat can be picked up from a second air stream. In one or more embodiments, the regenerator and heat dump coil are located outside a building. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In accordance with one or more embodiments a compressor delivers a hot refrigerant flowing through the 4-way valve to a first heat exchanger wherein a hot heat transfer fluid is created. The hot heat transfer fluid can be re-directed by the series of valves to flow to the regenerator only in a rainy season operating mode. The cooler refrigerant now flows through an expansion valve wherein the refrigerant gets cold and flows to a second heat exchanger wherein a cold heat transfer fluid is created. The cold heat transfer fluid in the second heat exchanger can be now be directed to the heat transfer coil. In one or more embodiments, the regenerator receives the hot heat transfer fluid and a diluted desiccant and provides a concentrated desiccant and a humid, warm air stream. In one or more embodiments, the concentrated desiccant is flowing to a conditioner. In one or more embodiments, the conditioner is dehumidifying an air stream. In one or more embodiments, the conditioner is not receiving a heat transfer fluid and the dehumidification takes place adiabatically. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner receives concentrated liquid desiccant from a regenerator. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments, the conditioner is only receiving concentrated desiccant from the regenerator but no heat transfer fluid is flowing in the rainy season mode.
In accordance with one or more embodiments a liquid desiccant membrane system employs an evaporator, a geothermal loop wherein a heat transfer fluid is rejecting heat to a ground loop or geothermal loop, or a cooling tower to generate a cold heat transfer fluid wherein the cold heat transfer fluid is used to cool a liquid desiccant conditioner. In one or more embodiments, the water supplied to the evaporator is potable water. In one or more embodiments, the water is seawater. In one or more embodiments, the water is waste water. In one or more embodiments, the evaporator uses a membrane to prevent carry-over of non-desirable elements from the seawater or waste water to the air stream. In one or more embodiments, the water in the evaporator is not cycled back to the top of the indirect evaporator such as would happen in a cooling tower, but between 20% and 80% of the water is evaporated and the remainder is discarded. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner receives concentrated liquid desiccant from a regenerator. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments, the regenerator receives a hot heat transfer fluid from a heat source. In one or more embodiments, the heat source is a gas-fired water heater, a solar thermal or PVT (Photovoltaic and Thermal) panel, a combined heat and power system such as for example a fuel cell, a waste heat collection system or any convenient heat source. In one or more embodiments, the cool heat transfer fluid flows from the liquid desiccant conditioner to a heat exchanger and back to the evaporator where it is cooled again. In one or more embodiments, the heat exchanger only receives the cool heat transfer fluid but no flow occurs on the opposite side in a summer cooling and dehumidification mode. In accordance with one or more embodiments, the conditioned air stream is directed to an indirect evaporative cooler. In one or more embodiments, the indirect evaporative cooler is used to provide additional sensible cooling. This allows the system to provide cool, dehumidified air to a space in summer conditions. In accordance with one or more embodiments a liquid desiccant membrane system employs an evaporator or cooling tower to generate a cold heat transfer fluid in a summer cooling and dehumidification mode, but the evaporator is idled in a winter heating and humidification mode. In one or more embodiments, water, seawater or waste water is instead directed to a water injection module wherein the water, seawater or waste water flows on the one side and a concentrated desiccant flows on the opposite side. In one or more embodiments, the desiccant on the opposite side is diluted by the water, seawater or waste water. In one or more embodiments, the diluted desiccant is directed to a conditioner in a space. In one or more embodiments, the conditioner also receives a hot heat transfer fluid from a heat source. In one or more embodiments, the conditioner provides a warm, humid air stream to a space. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner receives diluted liquid desiccant from a regenerator. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments, the hot heat transfer fluid comes from a heat source. In one or more embodiments, the heat source is a gas-fired water heat, a solar panel, a combined heat and power system, a waste heat collection system or any convenient heat source.
In accordance with one or more embodiments a liquid desiccant membrane system employs an evaporator, a geothermal loop wherein a heat transfer fluid is rejecting heat to a ground loop or geothermal loop, or a cooling tower to generate a cold heat transfer fluid in a summer cooling and dehumidification mode, but the evaporator is idled in a winter heating and humidification mode as well as in a rainy season heating and dehumidification mode. In one or more embodiments, the liquid desiccant membrane system contains a regenerator generating a concentrated desiccant. In one or more embodiments, the concentrated desiccant is directed to a conditioner in a space. In one or more embodiments, the conditioner provides a warm, humid air stream to a space. In one or more embodiments, the conditioner is a 3-way liquid desiccant membrane conditioner. In one or more embodiments, the conditioner sends a diluted liquid desiccant back to the regenerator. In one or more embodiments, the regenerator is a 3-way liquid desiccant membrane regenerator. In one or more embodiments, the regenerator receives a hot heat transfer fluid from a heat source. In one or more embodiments, the heat source is a gas-fired water heat, a solar panel, a combined heat and power system, a waste heat collection system or any convenient heat source. In one or more embodiments, the hot heat transfer fluid from the heat source is also directed to a heat exchanger. In one or more embodiments, the heat exchanger provides heat to the opposite side where a second heat transfer fluid flows. In one or more embodiments, the second heat transfer fluid provides heat to the liquid desiccant conditioner in a space. In one or more embodiments, the conditioner receives both a concentrated desiccant and a warm heat transfer fluid in a rainy season heating and dehumidification mode.
In no way is the description of the applications intended to limit the disclosure to these applications. Many construction variations can be envisioned to combine the various elements mentioned above each with its own advantages and disadvantages. The present disclosure in no way is limited to a particular set or combination of such elements.
The liquid desiccant is collected at the bottom of the wavy conditioner plates at 111 and is transported through a heat exchanger 113 to the top of the regenerator 102 to point 115 where the liquid desiccant is distributed across the wavy plates of the regenerator. Return air or optionally outside air 105 is blown across the regenerator plate and water vapor is transported from the liquid desiccant into the leaving air stream 106. An optional heat source 108 provides the driving force for the regeneration. The hot transfer fluid 110 from the heat source can be put inside the wavy plates of the regenerator similar to the cold heat transfer fluid on the conditioner. Again, the liquid desiccant is collected at the bottom of the wavy plates 102 without the need for either a collection pan or bath so that also on the regenerator the air flow can be horizontal or vertical. An optional heat pump 116 can be used to provide cooling and heating of the liquid desiccant. It is also possible to connect a heat pump between the cold source 107 and the hot source 108, which is thus pumping heat from the cooling fluids rather than the desiccant.
The liquid desiccant 428 leaves the conditioner 403 and is moved through the optional heat exchanger 426 to the regenerator 422 by pump 425. If the desiccant lines 427 and 428 are relatively long they can be thermally connected to each other, which eliminates the need for heat exchanger 426.
The chiller system 430 comprises a water to refrigerant evaporator heat exchanger 407 which cools the circulating cooling fluid 406. The liquid, cold refrigerant 417 evaporates in the heat exchanger 407 thereby absorbing the thermal energy from the cooling fluid 406. The gaseous refrigerant 410 is now re-compressed by compressor 411. The compressor 411 ejects hot refrigerant gas 413, which is liquefied in the condenser heat exchanger 415. The liquid refrigerant 414 then enters expansion valve 416, where it rapidly cools and exits at a lower pressure. It is worth noting that the chiller system 430 can be made very compact since the high pressure lines with refrigerant (410, 413, 414 and 417) only have to run very short distances. Furthermore, since the entire refrigerant system is located outside of the space that is to be conditioned, it is possible to utilize refrigerants that normally cannot be used in indoor environments such as by way of example, CO2, Ammonia and Propane. These refrigerants are sometimes preferable over the commonly used R410A, R407A, R134A because of their lower greenhouse gas potential or over R1234YF and R1234ZE refrigerants, but they are undesirable indoor because of flammability or suffocation or inhalation risks. By keeping all of the refrigerants outside, these risks are significantly reduced. The condenser heat exchanger 415 now releases heat to another cooling fluid loop 419 which brings hot heat transfer fluid 418 to the regenerator 422. Circulating pump 420 brings the heat transfer fluid back to the condenser 415. The 3-way regenerator 422 thus receives a dilute liquid desiccant 428 and hot heat transfer fluid 418. A fan 424 powered by electricity 420 brings outside air 421 (“OA”) through the regenerator 422. The outside air picks up heat and moisture from the heat transfer fluid 418 and desiccant 428 which results in hot humid exhaust air (“EA”) 423.
The compressor 411 receives electrical power 412 and typically accounts for 80% of electrical power consumption of the system. The fan 402 and fan 424 also receive electrical power 405 and 429 respectively and account for most of the remaining power consumption. Pumps 408, 420 and 425 have relatively low power consumption. The compressor 411 will operate more efficiently than the compressor 510 in
Besides the compressor 510, the outdoor components comprise a condenser coil 516 and a condenser fan 517 as well as a four-way valve assembly 511. The four-way valve 512 (which for convenience has been labeled the 512-“A” position) has been positioned inside the valve body 511 so that the hot refrigerant 513 is directed to the condenser coil 516 through line 515. The fan 517 blows outside air 518 through the condenser coil 516 where it picks up heat from the compressor 510 which is rejected to the air stream 519. The cooled liquid refrigerant 520 is conducted to a set of valves 521, 522, 524 and 525, with the addition of an “O” for open or a “C” for closed. As can be seen in the figure, the refrigerant 520 goes through the check valve 521-O and bypasses the expansion valve 522-C. Since the second check valve 524-C is closed, the refrigerant moves through line 523 and to the second expansion valve 525-O in which the refrigerant expands and cools. The cold refrigerant 526 is then conducted to the evaporator 501 where it picks up heat and expands back to a gas. The gas 509 is then conducted to the 4-way valve 511 and flows back to the compressor 510 through line 514.
In some instances the system can have multiple compressors or multiple condenser coils and fans. The primary electrical energy consuming components are the compressor 510, the condenser fan 516 and the evaporator fan 502. In general the compressor uses close to 80% of the electricity required to operate the system, with the condenser and evaporator fans taking about 10% of the electricity each.
Refrigerant compressor 615 compresses a refrigerant gas to high pressure and the resulting hot refrigerant 616 is directed to a 4-way valve assembly 617. The valve 618 is in the “A” position as before labeled 618-A in the figure. In this position the hot refrigerant gas is directed through line 619 to two heat exchangers: a refrigerant to liquid heat exchanger 620, and a refrigerant to air heat exchanger 622 through 3-way switching valve 621-A also in the “A” position which directs the refrigerant to the heat exchanger 622. The refrigerant leaves the heat exchanger 622 through 3-way switching valve 626-A which is also in an “A” position, which directs the refrigerant through line 627. The refrigerant from heat exchanger 620 is combined and both streams flow to a set of valves 628, 629, 630 and 631. The check valve 628-O is open and allows the refrigerant to flow to expansion valve 631-O which expands the liquid refrigerant to become cold in line 632. Check valve 630-C is closed as is expansion valve 629-C. The refrigerant next encounters another 3-way switching valve 633-A in the “A” position. The cold refrigerant now picks up heat in the aforementioned heat exchanger 614. The warmer refrigerant then moves through line 634 to the 4-way valve 617, where it is directed back to the compressor 615 through line 635. The liquid to refrigerant heat exchanger 620 is supplied with a heat transfer fluid (usually water) through line 639 by pump 638. The heated heat transfer fluid is then directed through line 640 to a regenerator membrane module 643, which is similar in construction as the module from
In
Refrigerant compressor 715 compresses a refrigerant gas to high pressure and the resulting hot refrigerant 716 is directed to a 4-way valve assembly 717. The valve 718 is in the “A” position as before, and is labeled 718-A in the figure. In this position the hot refrigerant gas is directed through line 719 to a refrigerant-to-liquid heat exchanger 720. The refrigerant leaves the heat exchanger 720 and is directed through line 721 to a second 4-way valve assembly 722 with the valve 723-A in an “A” position, which directs the refrigerant through line 724 and subsequently to condenser coil 725. Condenser coil 725 receives an air stream 726 moved by fan 727 resulting in a heated exhaust air stream 728. The cooler refrigerant leaves the coil 725 through line 729 and is directed to the open valve 730-O. Expansion valve 731-C is closed and inactive in this operating mode. The refrigerant moves back to 4-way valve 722 through line 732 and is directed through line 733 and line 736 to expansion valve 738-O which expands the refrigerant. Check valve 737-C is closed and inactive. The cold refrigerant enters the heat exchanger 714 through line 739 and removes heat from the heat transfer fluid on the opposite side of the heat exchanger 714. The warmer refrigerant is then moved through line 740 and 741 to 4-way valve 717 where it is directed through line 742 back to the compressor 715. Line 734 and valve 735-C are inactive or closed respectively.
The refrigerant to liquid heat exchanger 720, receives a heat transfer fluid (usually water or a water/glycol mixture but generally any heat transfer fluid will do) pumped by pump 743 through line 744. The heat from the compressed refrigerant in line 719 is transferred in the heat exchanger 720 to the heat transfer fluid and the hot heat transfer fluid is directed through line 745 to a set of regenerator plates 748 similarly constructed to those as described in
The system of
Similar to described before in
As before the hot heat transfer fluid flowing through lines 840 and 831 is picking up heat from the refrigerant in heat exchanger 824. The hot fluid is directed to regenerator 843 which receives an air stream 841 through fan 844 resulting in a hot exhaust air stream 849. Pump 839 moves the heat transfer fluid through line 840 and optionally through line 837 and valve 838-A in the “A” position so the heat transfer fluid is either cooled by air stream 835 and fan 834 in coil 833 resulting in a hot exhaust air stream 836, or simply flowing through line 840 back to the heat exchanger 824. Valve 832A is also in the “A” position and simply directs the cooled heat transfer fluid back into the fluid line 831. The regenerator 843 also receives a diluted, or weak desiccant through line 844 which is re-concentrated by means of the heat transfer fluid coming in through line 831. The re-concentrated desiccant is directed through line 846 into optional desiccant tank 847. Pump 845 removes some diluted desiccant and moves it to the regenerator 843 through line 844. Lines 817 and 850 are not used in this mode.
The cooling tower contains a wetting media 917 and also contains a basin 921 which provides cold water as well as an air intake 916 and fan 918 and an exhaust air stream 920. Make-up water is provided through line 919 and an optional valve 941-A which in the “A” position directs the make-up water to the cooling tower wetting media 917. Valve 941-A can also be switched to deliver water to a water injection unit 942, which can be used to add water to the liquid desiccant flowing in line 912. Such a water injection system is further described in U.S. patent application Ser. No. 14/664,219 incorporated by reference herein and is used to control the desiccant concentration particularly in dry conditions. Valve 941-A could also be replaced with two individual valves if water needs to be delivered to the cooling tower or injection unit at the same time which can be used in hot, dry conditions. In other embodiments, the cooling tower could be replaced with a geothermal loop, in which the heat transfer fluid of line 904 is simply pumped through a geothermal heat exchanger, which is commonly located in the ground or river or lake near the facility where the system is located.
The regenerator 926 receives a hot heat transfer fluid 925 from a heat source 924, which can be any convenient heat source such as a gas-fired water heater, solar hot water system or waste heat collection system. Valve 940-A in the “A” position directs the hot heat transfer fluid 925 to the regenerator 926. The cooler hot heat transfer fluid 936 that is leaving the regenerator is pumped by pump 937 the valve 938-A in the “A” position through line 939 back to the heat source 924. The regenerator 926 also receives a dilute (weak) desiccant through line 930 as well as an air stream 927 moved by fan or blower 928 resulting in a hot, humid exhaust air stream 929. The re-concentrated desiccant flows through line 932 back to tank 933 from where it is send to the conditioner 903 where it is re-used.
It is possible to add a second stage cooling system 943 (labeled IEC Indirect Evaporative Cooler in the figure). The indirect evaporative cooling system 943 provides additional sensible cooling if desired and receives water 944 from the water supply line 919. The IEC may also be used in the various other embodiments disclosed herein to provide additional sensible cooling to the supply air stream.
Concentrated desiccant in line 908 is now directed through optional tank 910 through line 911 to tank 933 where it is pumped by pump 931 to the regenerator. The regenerator will allow the desiccant to absorb moisture assuming that the air stream 927 has enough moisture in it and diluted desiccant will flow through line 932 and tank 933, pump 934 and water injection unit 942 to line 912 back to tank 910 where it can be directed to the conditioner 903 and continue to moisten the air stream 906. If not enough humidity is available in the air stream 927, the water injection module 942 can be used to add water to the desiccant and to eventually moisten the air stream 906 as described more fully in U.S. Patent Application No. 61/968,333.
The cooling tower wetting media assembly (917) can also be replaced with a set of membrane modules similar to the conditioner membrane modules as is shown in
Having thus described several illustrative embodiments, it is to be appreciated that various alterations, modifications, and improvements will readily occur to those skilled in the art. Such alterations, modifications, and improvements are intended to form a part of this disclosure, and are intended to be within the spirit and scope of this disclosure. While some examples presented herein involve specific combinations of functions or structural elements, it should be understood that those functions and elements may be combined in other ways according to the present disclosure to accomplish the same or different objectives. In particular, acts, elements, and features discussed in connection with one embodiment are not intended to be excluded from similar or other roles in other embodiments. Additionally, elements and components described herein may be further divided into additional components or joined together to form fewer components for performing the same functions. Accordingly, the foregoing description and attached drawings are by way of example only, and are not intended to be limiting.
This application claims priority from U.S. Provisional Patent Application No. 62/082,753 filed on Nov. 21, 2014 entitled METHODS AND SYSTEMS FOR MINI-SPLIT LIQUID DESICCANT AIR CONDITIONING, which is hereby incorporated by reference.
Number | Name | Date | Kind |
---|---|---|---|
1791086 | Sperr | Feb 1931 | A |
2221787 | Downs et al. | Nov 1940 | A |
2235322 | Martin | Mar 1941 | A |
2433741 | Crawford | Dec 1947 | A |
2988171 | Arnold et al. | Jun 1961 | A |
3193001 | Meckler | Jul 1965 | A |
3718181 | Reilly et al. | Feb 1973 | A |
4100331 | Fletcher et al. | Jul 1978 | A |
4164125 | Griffiths | Aug 1979 | A |
4176523 | Rousseau | Dec 1979 | A |
4205529 | Ko | Jun 1980 | A |
4209368 | Coker et al. | Jun 1980 | A |
4222244 | Meckler | Sep 1980 | A |
4235221 | Murphy | Nov 1980 | A |
4239507 | Benoit et al. | Dec 1980 | A |
4259849 | Griffiths | Apr 1981 | A |
4324947 | Dumbeck | Apr 1982 | A |
4399862 | Hile | Aug 1983 | A |
4429545 | Steinberg | Feb 1984 | A |
4435339 | Kragh | Mar 1984 | A |
4444992 | Cox, III | Apr 1984 | A |
4583996 | Sakata et al. | Apr 1986 | A |
4607132 | Jarnagin | Aug 1986 | A |
4612019 | Langhorst | Sep 1986 | A |
4649899 | Moore | Mar 1987 | A |
4691530 | Meckler | Sep 1987 | A |
4703629 | Moore | Nov 1987 | A |
4766952 | Onodera | Aug 1988 | A |
4786301 | Rhodes | Nov 1988 | A |
4832115 | Albers et al. | May 1989 | A |
4872578 | Fuerschbach et al. | Oct 1989 | A |
4882907 | Brown, II | Nov 1989 | A |
4887438 | Meckler | Dec 1989 | A |
4900448 | Bonne et al. | Feb 1990 | A |
4910971 | McNab | Mar 1990 | A |
4939906 | Spatz et al. | Jul 1990 | A |
4941324 | Peterson et al. | Jul 1990 | A |
4955205 | Wilkinson | Sep 1990 | A |
4976313 | Dahlgren et al. | Dec 1990 | A |
4979965 | Sannholm | Dec 1990 | A |
4984434 | Peterson et al. | Jan 1991 | A |
4987750 | Meckler | Jan 1991 | A |
5005371 | Yonezawa et al. | Apr 1991 | A |
5181387 | Meckler | Jan 1993 | A |
5182921 | Yan | Feb 1993 | A |
5186903 | Cornwell | Feb 1993 | A |
5191771 | Meckler | Mar 1993 | A |
5221520 | Cornwell | Jun 1993 | A |
5351497 | Lowenstein | Oct 1994 | A |
5375429 | Tokizaki et al. | Dec 1994 | A |
5462113 | Wand | Oct 1995 | A |
5471852 | Meckler | Dec 1995 | A |
5528905 | Scarlatti | Jun 1996 | A |
5534186 | Walker et al. | Jul 1996 | A |
5582026 | Barto, Sr. | Dec 1996 | A |
5595690 | Filburn et al. | Jan 1997 | A |
5605628 | Davidson et al. | Feb 1997 | A |
5638900 | Lowenstein et al. | Jun 1997 | A |
5641337 | Arrowsmith et al. | Jun 1997 | A |
5661983 | Groten et al. | Sep 1997 | A |
5685152 | Sterling | Nov 1997 | A |
5685485 | Mock et al. | Nov 1997 | A |
5797272 | James | Aug 1998 | A |
5832993 | Ohata et al. | Nov 1998 | A |
5860284 | Goland et al. | Jan 1999 | A |
5860285 | Tulpule | Jan 1999 | A |
5928808 | Eshraghi | Jul 1999 | A |
5933702 | Goswami | Aug 1999 | A |
6018954 | Assaf | Feb 2000 | A |
6083387 | LeBlanc et al. | Jul 2000 | A |
6103969 | Bussey | Aug 2000 | A |
6138470 | Potnis et al. | Oct 2000 | A |
6156102 | Conrad et al. | Dec 2000 | A |
6171374 | Barton et al. | Jan 2001 | B1 |
6216483 | Potnis et al. | Apr 2001 | B1 |
6216489 | Potnis et al. | Apr 2001 | B1 |
6244062 | Prado | Jun 2001 | B1 |
6247604 | Taskis et al. | Jun 2001 | B1 |
6266975 | Assaf | Jul 2001 | B1 |
6417423 | Koper et al. | Jul 2002 | B1 |
6442951 | Maeda et al. | Sep 2002 | B1 |
6463750 | Assaf | Oct 2002 | B2 |
6487872 | Forkosh et al. | Dec 2002 | B1 |
6488900 | Call et al. | Dec 2002 | B1 |
6497107 | Maisotsenko et al. | Dec 2002 | B2 |
6497749 | Kesten et al. | Dec 2002 | B2 |
6502807 | Assaf et al. | Jan 2003 | B1 |
6514321 | Lehto et al. | Feb 2003 | B1 |
6539731 | Kesten et al. | Apr 2003 | B2 |
6546746 | Forkosh et al. | Apr 2003 | B2 |
6557365 | Dinnage et al. | May 2003 | B2 |
6660069 | Sato et al. | Dec 2003 | B2 |
6684649 | Thompson | Feb 2004 | B1 |
6739142 | Korin | May 2004 | B2 |
6745826 | Lowenstein et al. | Jun 2004 | B2 |
6766817 | da Silva et al. | Jul 2004 | B2 |
6854278 | Maisotsenko et al. | Feb 2005 | B2 |
6854279 | Digiovanni et al. | Feb 2005 | B1 |
6918404 | Dias da Silva et al. | Jul 2005 | B2 |
6938434 | Fair | Sep 2005 | B1 |
6976365 | Forkosh et al. | Dec 2005 | B2 |
6986428 | Hester et al. | Jan 2006 | B2 |
7066586 | da Silva et al. | Jun 2006 | B2 |
RE39288 | Assaf | Sep 2006 | E |
7143597 | Hyland et al. | Dec 2006 | B2 |
7191821 | Gronwall et al. | Mar 2007 | B2 |
7197887 | Maisotsenko et al. | Apr 2007 | B2 |
7258923 | van den Bogerd et al. | Aug 2007 | B2 |
7269966 | Lowenstein et al. | Sep 2007 | B2 |
7279215 | Hester et al. | Oct 2007 | B2 |
7306650 | Slayzak et al. | Dec 2007 | B2 |
7337615 | Reidy | Mar 2008 | B2 |
7430878 | Assaf | Oct 2008 | B2 |
7758671 | Kesten et al. | Jul 2010 | B2 |
7938888 | Assaf | May 2011 | B2 |
8337590 | Herencia et al. | Dec 2012 | B2 |
8353175 | Wohlert | Jan 2013 | B2 |
8496732 | Culp et al. | Jul 2013 | B2 |
8499576 | Meijer | Aug 2013 | B2 |
8500960 | Ehrenberg et al. | Aug 2013 | B2 |
8623210 | Manabe et al. | Jan 2014 | B2 |
8641806 | Claridge et al. | Feb 2014 | B2 |
8648209 | Lastella | Feb 2014 | B1 |
8695363 | Tang et al. | Apr 2014 | B2 |
8696805 | Chang et al. | Apr 2014 | B2 |
8769971 | Kozubal et al. | Jul 2014 | B2 |
8790454 | Lee et al. | Jul 2014 | B2 |
8800308 | Vandermeulen et al. | Aug 2014 | B2 |
8876943 | Gottlieb et al. | Nov 2014 | B2 |
8881806 | Xie et al. | Nov 2014 | B2 |
8968945 | Fasold et al. | Mar 2015 | B2 |
20010015500 | Shimanuki et al. | Aug 2001 | A1 |
20020023740 | Lowenstein et al. | Feb 2002 | A1 |
20020026797 | Sundhar | Mar 2002 | A1 |
20020098395 | Shimanuki et al. | Jul 2002 | A1 |
20020104439 | Komkova et al. | Aug 2002 | A1 |
20020139245 | Kesten et al. | Oct 2002 | A1 |
20020139320 | Shimanuki et al. | Oct 2002 | A1 |
20020148602 | Nakamura | Oct 2002 | A1 |
20030000230 | Kopko | Jan 2003 | A1 |
20030029185 | Kopko | Feb 2003 | A1 |
20030033821 | Maisotsenko et al. | Feb 2003 | A1 |
20030051498 | Sanford | Mar 2003 | A1 |
20030106680 | Serpico et al. | Jun 2003 | A1 |
20030121271 | Dinnage et al. | Jul 2003 | A1 |
20030230092 | Lowenstein et al. | Dec 2003 | A1 |
20040040697 | Pierre et al. | Mar 2004 | A1 |
20040061245 | Maisotsenko et al. | Apr 2004 | A1 |
20040109798 | Chopard et al. | Jun 2004 | A1 |
20040112077 | Forkosh | Jun 2004 | A1 |
20040118125 | Potnis et al. | Jun 2004 | A1 |
20040134212 | Lee | Jul 2004 | A1 |
20040168462 | Assaf | Sep 2004 | A1 |
20040194944 | Hendricks et al. | Oct 2004 | A1 |
20040211207 | Forkosh et al. | Oct 2004 | A1 |
20040230092 | Thierfelder et al. | Nov 2004 | A1 |
20040231512 | Slayzak et al. | Nov 2004 | A1 |
20040261440 | Forkosh et al. | Dec 2004 | A1 |
20050106021 | Bunker et al. | May 2005 | A1 |
20050109052 | Albers et al. | May 2005 | A1 |
20050133082 | Konold et al. | Jun 2005 | A1 |
20050210907 | Gillan et al. | Sep 2005 | A1 |
20050218535 | Maisotsenko et al. | Oct 2005 | A1 |
20050257551 | Landry | Nov 2005 | A1 |
20060042295 | Assaf | Mar 2006 | A1 |
20060124287 | Reinders | Jun 2006 | A1 |
20060156750 | Lowenstein et al. | Jul 2006 | A1 |
20060156761 | Mola | Jul 2006 | A1 |
20060278089 | Theilow | Dec 2006 | A1 |
20070169916 | Wand et al. | Jul 2007 | A1 |
20070175234 | Pruitt | Aug 2007 | A1 |
20070234743 | Assaf | Oct 2007 | A1 |
20080127965 | Burton | Jun 2008 | A1 |
20080156471 | Han et al. | Jul 2008 | A1 |
20080196758 | McGuire | Aug 2008 | A1 |
20080203866 | Chamberlain | Aug 2008 | A1 |
20080302357 | DeNault | Dec 2008 | A1 |
20080314567 | Noren | Dec 2008 | A1 |
20090000732 | Jacobine et al. | Jan 2009 | A1 |
20090056919 | Hoffman et al. | Mar 2009 | A1 |
20090095162 | Hargis et al. | Apr 2009 | A1 |
20090173096 | Wohlert | Jul 2009 | A1 |
20090200022 | Bravo et al. | Aug 2009 | A1 |
20090238685 | Santa Ana | Sep 2009 | A1 |
20100000247 | Bhatti et al. | Jan 2010 | A1 |
20100018322 | Neitzke et al. | Jan 2010 | A1 |
20100051083 | Boyk | Mar 2010 | A1 |
20100084120 | Yin et al. | Apr 2010 | A1 |
20100170776 | Ehrenberg et al. | Jul 2010 | A1 |
20100319370 | Kozubal et al. | Dec 2010 | A1 |
20110073290 | Chang et al. | Mar 2011 | A1 |
20110100618 | Carlson | May 2011 | A1 |
20110101117 | Miyauchi et al. | May 2011 | A1 |
20110126885 | Kokotov et al. | Jun 2011 | A1 |
20110132027 | Gommed et al. | Jun 2011 | A1 |
20120052785 | Nagamatsu et al. | Mar 2012 | A1 |
20120114527 | Hoglund et al. | May 2012 | A1 |
20120118148 | Culp et al. | May 2012 | A1 |
20120118155 | Claridge et al. | May 2012 | A1 |
20120125020 | Vandermeulen et al. | May 2012 | A1 |
20120125021 | Vandermeulen et al. | May 2012 | A1 |
20120125031 | Vandermeulen et al. | May 2012 | A1 |
20120131937 | Vandermeulen | May 2012 | A1 |
20120131939 | Vandermeulen et al. | May 2012 | A1 |
20120132513 | Vandermeulen et al. | May 2012 | A1 |
20120152318 | Kee | Jun 2012 | A1 |
20130056177 | Coutu et al. | Mar 2013 | A1 |
20130101909 | Fasold et al. | Apr 2013 | A1 |
20130186121 | Erb et al. | Jul 2013 | A1 |
20130199220 | Ma et al. | Aug 2013 | A1 |
20130227982 | Forkosh | Sep 2013 | A1 |
20130255287 | Forkosh | Oct 2013 | A1 |
20130340449 | Kozubal et al. | Dec 2013 | A1 |
20140054004 | LePoudre et al. | Feb 2014 | A1 |
20140054013 | LePoudre et al. | Feb 2014 | A1 |
20140150481 | Vandermeulen | Jun 2014 | A1 |
20140150656 | Vandermeulen | Jun 2014 | A1 |
20140150657 | Vandermeulen et al. | Jun 2014 | A1 |
20140150662 | Vandermeulen et al. | Jun 2014 | A1 |
20140223947 | Ranjan et al. | Aug 2014 | A1 |
20140245769 | Vandermeulen et al. | Sep 2014 | A1 |
20140250935 | Prochaska et al. | Sep 2014 | A1 |
20140260367 | Coutu et al. | Sep 2014 | A1 |
20140260369 | LePoudre | Sep 2014 | A1 |
20140260371 | Vandermeulen | Sep 2014 | A1 |
20140260398 | Kozubal et al. | Sep 2014 | A1 |
20140260399 | Vandermeulen | Sep 2014 | A1 |
20140262125 | Erb et al. | Sep 2014 | A1 |
20140262144 | Erb et al. | Sep 2014 | A1 |
20140264968 | Erb et al. | Sep 2014 | A1 |
20140360373 | Peacos et al. | Dec 2014 | A1 |
20140366567 | Vandermeulen | Dec 2014 | A1 |
20150323216 | Wallin | Nov 2015 | A1 |
20150338140 | Vandermeulen | Nov 2015 | A1 |
Number | Date | Country |
---|---|---|
100366981 | Feb 2008 | CN |
100476308 | Apr 2009 | CN |
102282426 | Dec 2011 | CN |
202229469 | May 2012 | CN |
1120609 | Aug 2001 | EP |
1563229 | Aug 2005 | EP |
1781995 | May 2007 | EP |
2256434 | Dec 2010 | EP |
2306100 | Apr 2011 | EP |
2787293 | Oct 2014 | EP |
S54-77443 | Jun 1979 | JP |
S62-297647 | Dec 1987 | JP |
02306067 | Dec 1990 | JP |
H08-105669 | Apr 1996 | JP |
H10-220914 | Aug 1998 | JP |
H11-351700 | Dec 1999 | JP |
2000-230730 | Aug 2000 | JP |
2002206834 | Jul 2002 | JP |
2004-524504 | Aug 2004 | JP |
2005-134060 | May 2005 | JP |
2006-263508 | Oct 2006 | JP |
2006-529022 | Dec 2006 | JP |
2009-517622 | Apr 2009 | JP |
04273555 | Jun 2009 | JP |
2009-281668 | Dec 2009 | JP |
2009-293831 | Dec 2009 | JP |
2010-247022 | Nov 2010 | JP |
2011-163682 | Aug 2011 | JP |
20040026242 | Mar 2004 | KR |
10-0510774 | Aug 2005 | KR |
2014-0022785 | Feb 2014 | KR |
201009269 | Mar 2010 | TW |
1997021061 | Jun 1997 | WO |
1999022180 | May 1999 | WO |
2000011426 | Mar 2000 | WO |
2000055546 | Sep 2000 | WO |
WO-2002066901 | Aug 2002 | WO |
WO-2002086391 | Oct 2002 | WO |
2003004937 | Jan 2003 | WO |
2004046618 | Jun 2004 | WO |
2006006177 | Jan 2006 | WO |
2008037079 | Apr 2008 | WO |
2009094032 | Jul 2009 | WO |
2009144880 | Dec 2009 | WO |
2011062808 | May 2011 | WO |
2011150081 | Dec 2011 | WO |
2011161547 | Dec 2011 | WO |
2012071036 | May 2012 | WO |
2012082093 | Jun 2012 | WO |
2014152905 | Sep 2014 | WO |
2014201281 | Dec 2014 | WO |
2015077364 | May 2015 | WO |
Entry |
---|
Open Absorption System for Cooling and Air Conditioning using Membrane Contactors—Annual Report 2005, Publication No. Publication 260097, Project: 101310—Open Absorption System for Cooling and Air Conditioning using Membrane Contactors, Date of publication: Jan. 31, 2006, Author: Manuel Conde-Petit, Robert Weber, Contractor: M. Conde Engineering. |
Open Absorption System for Cooling and Air Conditioning using Membrane Contactors—Annual, Report 2006, Publication No. Publication 260098, Project: 101310—Open Absorption System for Cooling and Air Conditioning using Membrane Contactors, Date of publication: Nov. 14, 2006, Author: Manuel Conde-Petit, Robert Weber, Contractor: M. Conde Engineering. |
Open Absorption System for Cooling and Air Conditioning Using Membrane Contactors—Final Report, Publication No. Publication 280139, Project: 101310—Open Absorption System for Cooling and Air Conditioning using Membrane Contactors, Date of publication: Jul. 8, 2008, Author: Viktor Darer, Manuel Conde-Petit, Robert Weber, Contractor: M. Conde Engineering. |
Conde-Petit, M. 2007. Liquid Desiccant-Based Air-Conditioning Systems—LDACS, Proc. of the 1st European Conference on Polygeneration—Technologies and Applications, 217-234, A. Coronas, ed., Tarragona—Spain, Oct. 16-17, Published by CREVER—Universitat Rovira I Virgili, Tarragona, Spain. |
Conde-Petit, M. 2008. Open Absorption Systems for Air-Conditioning using Membrane Contactors,Proceedings '15. Schweizerisches Status-Seminar «Energie- und Umwelfforschung im Bauwesermi», Sep. 11-12—ETH Zurich, Switzerland. Published by BRENET—Eggwilstr. 16a, CH-9552 Bronschhofen—Switzerland (brenet@vogel-tech.ch). |
Third Party Observations for PCT/US2011/037936, dated Sep. 24, 2012. |
Ashrae, et al., “Desiccant Dehumidification and Pressue Drying Equipment,” 2012 ASHRAE Handbook—HVAC Systems and Equipment, Chapter 24, pp. 24.1-24.12. |
Beccali, et al., “Energy and Economic Assessment of Desiccant Cooling,” Solar Energy, Issue 83, pp. 1828-1846, Aug. 2009. |
Fimbres-Weihs, et al., “Review of 3D CFD modeling of flow and mass transfer in narrow spacer-filled channels in membrane modules,” Chemical Engineering and Processing 49 (2010) pp. 759-781. |
Lowenstein, “A Solar Liquid-Desiccant Air Conditioner,” Solar 2003, Proceedings of the 32nd ASES Annual Conference, Austin, TX, Jul. 2003. |
Li, F., et al., “Novel spacers for mass transfer enhancement in membrane separations,” Journal of Membrane Science, 253 (2005), pp. 1-12. |
Li, Y., et al., “CFD simulation of fluid flow through spacer-filled membrane module: selecting suitable cell types for periodic boundary conditions,” Desalination 233 (2008) pp. 351-358. |
Liu, et al., “Research Progress in Liquid Desiccant Air Conditioning Devices and Systems,” Frontiers of Energy and Power Engineering in China, vol. 4, Issue 1, pp. 55-65, Feb. 2010. |
Mathioulakis, “Desalination by Using Alternative Energy,” Desalination, Issue 203, pp. 346-365, 2007. |
Russell, et al., “Optimization of Photovolatic Thermal Collector Heat Pump Systems,” ISES International Solar Energy Conference, Atlanta, GA, vol. 3, pp. 1870-1874, May 1979. |
“Siphon.” Encyclopedia Americana. Grolier Online, 2015. Web. Apr. 3, 2015. 1 page. |
Welty, “Liquid Desiccant Dehumidification,” Engineered Systems, May 2010, vol. 27 Issue 5, p. 34. |
International Search Report and Written Opinion for PCT/US2015/062117, dated Mar. 16, 2016. |
Perry “Perry's Chemical Engineers handbook” 1999 McGraw Hill p. 11-52,11-53. |
Number | Date | Country | |
---|---|---|---|
20160187011 A1 | Jun 2016 | US |
Number | Date | Country | |
---|---|---|---|
62082753 | Nov 2014 | US |