The present invention relates generally to the field of heating, ventilation and air-conditioning (HVAC). More specifically, the present invention relates to methods of dehumidification control in unoccupied spaces.
The air quality in unoccupied spaces such as homes, office buildings, and hotel rooms can become problematic if not regulated properly. In hot and humid climates such as Florida, for example, mold and mildew buildup can begin to occur within only a few days, particularly when the interior environment is within the psychrometric range above 72° F. and 60% relative humidity where mold spore growth is generally increased. In such climates, dehumidification is often required in order to maintain adequate indoor air quality (IAQ) levels within the interior space while the occupants are away for extended periods of time. During these relatively long periods of time, however, the occupants will often desire to conserve energy by setting the temperature at a higher level in order to reduce air-conditioner usage. A tradeoff thus exists between energy savings and sufficient humidity control.
The prevention of mold and mildew buildup in unoccupied spaces is typically accomplished using a thermostat, sometimes in series or parallel with a humidistat. Configuration of the humidistat to work in conjunction with the thermostat is often difficult since the user must make the correct settings on both the thermostat and humidistat before leaving. Since such configuration requires a specific change in setpoint and is rarely done (e.g., once a year), the steps needed to configure both the thermostat and humidistat are often difficult to remember. If the user sets the controllers incorrectly, the result can be either insufficient humidity control due to a lack of proper dehumidification, or an excessive energy bill resulting from the air-conditioner running more than is required. To assist in proper configuration, therefore, the installer of the HVAC system will sometimes paste a long list of instructions on the wall instructing the occupants how to properly set the fan switch, the system switch, the temperature setpoint, the humidity setpoint, as well as other settings while they are away.
In those cases where the HVAC system is not equipped with a separate dehumidifier, the air-conditioner can be used in lieu of the dehumidifier to regulate the humidity levels within the space. When operated as a dehumidifier, air flowing past the air-conditioning coils results in condensation on the coils, which removes water from the air and reduces the humidity levels within the space. Efforts to lower the inside temperature to reduce humidity levels within the space can be counterproductive, however, if the inside dewpoint temperature is greater than the room temperature within the interior space. If, for example, the inside dewpoint temperature within the space is 72° F. whereas the indoor temperature is 70° F., operation of the air conditioning unit may actually cause greater moisture to buildup within the space, increasing mold and mildew growth and decreasing the indoor air quality. This may occur, for example, when the temperature sensed at the thermostat is higher than that at other locations within the interior space such as the outlet ducts to the HVAC system, causing moisture to buildup on the walls adjacent to the ducts. In addition, if the cooling provided by the air conditioner exceeds the rate of dehumidification as is common in many oversized air conditioner systems, the rapid drop in temperature may cause the system to reach the dewpoint temperature before fully satisfying the humidity requirement.
The present invention relates to methods of dehumidification control in unoccupied spaces. An illustrative method of providing dehumidification control within the interior space of a building or room can include the steps of providing a controller having an away mode of operation that can be used to provide dehumidification within the interior space while the occupants are away for extended periods of time. Initiation of the away mode can occur, for example, when the building or room will be unoccupied for extended periods of time and where dehumidification is necessary to prevent the buildup of mold and mildew within the interior space during hot and humid weather.
When initiated, the controller can be configured to operate one or more system components adapted to control the humidity and/or temperature levels within the interior space. In some embodiments, for example, the controller can operate an air conditioner for at least one cycle to reduce the humidity levels within the interior space when the indoor humidity is at or above an away dehumidification setting programmed within the controller. When a dehumidifier is provided, the controller can be configured to operate the dehumidifier for at least one cycle if the sensed indoor humidity within the interior space is at or above the away dehumidification setting.
The controller can be configured to determine whether the indoor dewpoint temperature within the interior space plus an offset temperature amount is greater than an away low temperature limit setting configured within the controller. If the indoor dewpoint temperature plus the offset temperature is greater than the away low temperature limit setting, the controller can be configured to operate the air conditioner to overcool the interior space at the indoor dewpoint temperature plus the offset temperature. Conversely, if the indoor dewpoint temperature plus the offset temperature is at or below the away low temperature limit setting, the controller can be configured to operate the air conditioner to overcool the interior space at the away low temperature limit setting. In use, the offset temperature amount can be used to compensate for any differences that may exist between the temperature sensed at the location of the controller and that occurring at other locations.
In those systems where a humidity sensor is not available for sensing the humidity levels within the interior space, the controller can be configured to activate the air conditioner for one or more periods of time each day to cool the interior space irrespective of the actual humidity levels within the space. In certain embodiments, for example, the controller may operate the air conditioner for two different periods of time during the day to overcool the interior space and provide the desired dehumidification.
The following description should be read with reference to the drawings, in which like elements in different drawings are numbered in like fashion. The drawings, which are not necessarily to scale, depict illustrative embodiments and are not intended to limit the scope of the invention. Although examples of various programming and operational steps are illustrated in the various views, those skilled in the art will recognize that many of the examples provided have suitable alternatives that can be utilized. While the various methods and controllers illustrated herein are described with respect to HVAC systems, it should be understood that the present invention can be employed in other applications where dehumidification is desired.
Referring now to
An air intake 26 of the furnace/air-conditioner 20 can be configured to receive air from one or more of the zones 14,16 within the building 12. As shown in
A number of internal sensors can be used to sense the temperature and/or humidity within one or more of the zones 14,16. In the illustrative embodiment of
While a multi-zoned HVAC system is shown, it is contemplated that a single-zoned HVAC system can also be implemented, if desired. Moreover, while the thermostat 18 is shown in conjunction with a forced-air system employing a furnace/air conditioner 20, it should be understood that the thermostat 18 can be used in conjunction with other types of systems. Examples of other systems can include, but are not limited to, 24 VAC systems, heat-pump systems, warm air systems, hot water systems, steam systems, radiant heat systems (e.g., in-floor and non-in-floor systems), gravity fed systems, and forced air hydronic systems.
An internal sensor or sensors 60 located within the thermostat 18 can be provided to sense the temperature, humidity levels and/or other environmental conditions occurring within the building at the installation location of the thermostat 18. Alternatively, or in addition, the thermostat 18 can be configured to receive temperature and/or humidity signals from a remote sensor connected to the thermostat 18 via a communications bus. For example, the I/O interface 56 can be connected to one or more remote sensors via a wired or wireless communications bus using RF signals, infrared signals, optical signals, or other suitable means for transmitting data to and from the thermostat 18.
The I/O interface 56 may further permit the thermostat 18 to be connected to one or more remote devices 61 located away from the location of the thermostat 18 to permit the thermostat 18 to be configured and/or operated remotely. In some embodiments, for example, the I/O interface 56 can include a telephone access module (TAM), RF gateway, universal serial bus (USB) port, IEEE 394 port, or other suitable communication means for providing signals to and from a remote device 61 such as another controller or a remote computer connected to the thermostat 18, allowing the thermostat 18 to be configured and/or operated from a remote location. In certain embodiments, for example, the thermostat 18 can be networked with a remote computer via a web portal, allowing the thermostat 18 to be updated by a service provider via the Internet, if desired.
The thermostat 18 can be further equipped with a user interface 62 to permit an installer to enter various inputs or commands for setting temperature setpoints, humidity setpoints, as well as other system settings. The user interface 62 can include, for example, a dial, rotor, slide, switch, button keypad, touchpad, touchscreen, computer, graphical user interface (GUI), or other means for inputting commands into the thermostat 18. The processor 50 can be configured to run a routine, which as discussed in greater detail below, can be used to operate the thermostat 18 in either a normal mode of operation for controlling the environment within the interior space during periods of occupancy, or in a dehumidification away mode of operation for controlling the environment within the interior space for extended periods of time when the interior space is unoccupied.
The thermostat 18 can include an installation or configuration mode that can be accessed by an installer or contractor via the user interface 62 to permit programming of the various thermostat settings, including those settings relating to the away mode of operation. In some embodiments, for example, the installation or configuration mode can be accessed via the user interface 62 for programming the temperature and humidity setpoints and the fan settings to be maintained while the occupant is away for extended periods of time. The thermostat 18 can also be configured to program various settings used by other controllers connected to the thermostat 18, including, for example, any humidistats used by the system to sense and/or control the humidity levels within the interior space.
During the installation process, and as shown generally at block 68, an installer may input one or more settings to the controller to configure the controller for use in the away mode of operation. Configuration of the away mode settings can occur, for example, by initiating an installation or configuration mode of the controller via the user interface, and then entering one or more parameters related to the temperature setpoint, dehumidification setpoint and/or fan settings to be used when the away mode of operation is activated. Configuration of the away mode settings can be accomplished, for example, by presenting to the installer a number of default settings pre-programmed within the controller, which can then be either accepted by the installer or adjusted by a desired amount via the user interface. In some embodiments, configuration of the away mode settings can be accomplished remotely from another device in communication with the controller.
Once the away mode of operation has been configured by the installer at block 68, the occupant may then activate the away mode of operation during extended periods of time when the interior space is unoccupied, as indicated generally by bock 70. Activation of the away mode of operation can occur manually, for example, by the user pressing a button or combination of buttons on the user interface causing the controller to switch from normal operation to the away mode of operation. Alternatively, or in addition, activation of the away mode of operation can occur automatically at pre-selected dates and/or times such as during the summer months while the occupant is away on extended vacation, or when no activity is sensed within the interior space for a certain period of time. In some hotel rooms, for example, activation of the away mode of operation can occur automatically when no movement is detected within the hotel room for a period of several days or weeks, indicating that the hotel room will likely continue to be vacant for an extended period of time.
Once the away mode of operation has been activated at block 70, the controller at block 72 can be configured to activate one or more HVAC system components in order to provide dehumidification control within the interior space while also conserving energy usage. In those systems employing a dehumidifier, for example, the controller can be configured to automatically change the system to operate in a cooling mode, and then operate the dehumidifier at a dehumidification setpoint that is different than that used during the normal mode of operation to provide dehumidification. In those systems without a dehumidifier, the controller can be configured to automatically change the system to operate in a cooling mode, and then operate the air conditioner at a temperature setpoint that is different than that used during the normal mode of operation to provide overcooling within the interior space when dehumidification is desired.
During the away mode of operation, the controller can be configured to operate the HVAC system for at least one cycle in order to maintain the humidity levels within acceptable limits, as indicated generally by block 74. When a dehumidifier is present, for example, the controller can be configured to activate the dehumidifier for at least one cycle during the day to control the humidity levels within the interior space while activating the air conditioner if the temperature within the space is at or greater than an away temperature setpoint programmed within the controller. In those systems without a dehumidifier or where the dehumidifier is disabled or is not a whole-house dehumidifier, the controller can be configured to operate the air conditioner to overcool the interior space and maintain the humidity levels at or below an away dehumidification setpoint programmed within the controller.
In those embodiments where a humidity sensor is provided, the controller can be configured to operate the dehumidifier and, in some cases also the air conditioner, until the humidity levels within the interior space are below the away dehumidification setpoint programmed within the controller. If the system is not equipped with a humidity sensor, or if a dehumidifier is not provided or is disabled, the controller can be configured to operate the air conditioner for a predetermined period of time during each day sufficient to reduce the humidity within the interior space. When the away mode of operation is active, and in some embodiments, the controller can be configured to default to a cycles per hour (CPH) setting of “1” for all cooling stages, forcing longer compressor on times to increase moisture removal via the air conditioner coils.
As indicated generally at block 76, the user may then exit the away mode of operation at any time during the routine, causing the controller to resume its normal mode of operation.
Once initiated, the controller may prompt the installer to select whether to activate the away mode of operation, as indicated generally at block 84. If the installer indicates a “no” response at block 84, the controller can be configured to exit the away configuration mode and return to normal operation, as indicated generally at block 96. Conversely, if the installer indicates a “yes” response at block 84, the controller may continue the configuration routine and prompt the installer to select the fan setting to be used during the away mode of operation, as indicated generally at block 86. In certain embodiments, for example, the controller may prompt the installer to select between a “fan auto” fan setting that causes the fan to cycle on and off automatically when other system components such as the air conditioner are activated, a “fan on” fan setting that causes the fan to continually operate while the controller is operating in the away mode, or a “fan circulate” fan setting that causes the fan to operate when circulation is desired. In some embodiments, the controller can be configured to default to a particular fan setting such as “fan auto”, which can then be changed via the user interface if the installer desires the fan to operate differently during the away mode of operation.
The controller may further prompt the installer at block 88 to configure a low temperature setpoint to be used as a lower temperature limit by the controller during operation in the away mode. In some embodiments, for example, the controller may prompt the installer to select a low temperature limit setpoint from a range of temperature settings between 70° F. and 80° F. In some cases, the controller can provide the installer with a default low temperature limit setpoint such as 76° F., which can then be changed by the installer, if desired. During operation, the away low temperature limit setpoint can be used by the controller to provide overcooling within the interior space below the away temperature setpoint for lowering the humidity levels within the space when a dehumidifier is not present or on-line, or if a dehumidifier is present but is insufficient to provide the necessary dehumidification.
Once a lower temperature limit has been set at block 88, the controller may next prompt the installer at block 90 to configure an away temperature setting that can be used by the controller to maintain the temperature within the interior space during operation in the away mode. In some embodiments, for example, the controller may prompt the installer to select an away temperature setpoint from a range of temperature settings between 70° F. and 99° F. In some cases, the controller can provide the installer with a default temperature setpoint such as 85° F., which can then be changed upwardly or downwardly by the installer, if desired.
The controller may next prompt the installer at block 92 to select a desired dehumidification setting to be used by the controller for maintaining the humidity levels within the interior space during the away mode of operation. In some embodiments, for example, the controller may prompt the installer to select an away dehumidification setpoint from a range of settings between 55% relative humidity and 70% relative humidity. As with the fan and temperature settings, the controller can provide the installer with a default away dehumidification setpoint such as 65%, which can then be adjusted either upwardly or downwardly by the installer, if desired.
Once the installer has configured the fan, temperature, and dehumidification settings at blocks 86 though 92, the controller can be configured to prompt the installer to confirm the newly programmed settings at block 94 and then exit the configuration routine at block 96, causing the controller to return to normal operation.
If at decision block 104, however, the controller determines that the away mode of operation is currently active, the controller can be configured to default to the cool system setting and then operate the system components using the away mode settings, as indicated generally by block 104. For example, when the away mode of operation is active, the controller can be configured to operate the system components using the away mode settings discussed above with respect to
As can be further seen in
In some embodiments, and as further illustrated by arrow 120 in
If at block 132 the controller determines that the indoor dewpoint temperature plus the offset temperature is greater than the away low temperature limit setpoint, the controller can be configured to control the temperature setpoint at the indoor dewpoint temperature plus the offset, as indicated generally by block 134. If at decision block 132, for example, the away temperature setpoint is 85° F. and the sensed indoor dewpoint temperature plus the offset is 83° F. (i.e., 78°+5°), the controller can be configured to control the temperature at the offset temperature setpoint of 83° F. to prevent moisture buildup. Conversely, if at decision block 132 the indoor dewpoint temperature plus the offset temperature is at or below the away low temperature limit setpoint, the controller can be configured to control the temperature at the away low temperature limit setpoint programmed within the controller, as indicated generally by block 136.
In those systems where a humidity sensor is not provided to sense the indoor humidity levels within the interior space, the controller can be configured to control the operation of the air conditioning unit for one or more periods of time each day in order to overcool the interior space and provide dehumidification during the away mode of operation. In one such embodiment depicted in
A number of icon buttons 154,156,158,160,162 displayed on the touchscreen 144 can be utilized to access other functionality and/or to program other settings within the thermostat 142. A “SCHED” icon button 154, for example, can be provided to permit the user to enter setpoint parameters for operating the thermostat 142 on a setpoint schedule. Selection of the “SCHED” icon button 154, for example, may permit the user to program the thermostat 142 to operate on a user-defined schedule to vary the temperature setpoints at particular times of the day and/or for certain days of the week. A schedule status indicator 164 can be displayed on the touchscreen 144 indicating whether the thermostat 142 is currently following the schedule.
A “HOLD” icon button 156 can be provided on the touchscreen 144 to permit the user to either temporarily or permanently lock the operation of the thermostat 142 at the current setpoint temperature. A “CLOCK” icon button 158 can be provided on the touchscreen 144 to permit the user to adjust the clock and date settings of the thermostat 142, including the time of day 166 and the current day of the week 168. A “SCREEN” icon button 160 can be provided to permit the user to temporarily lock the touchscreen 144 for a period of time (e.g., 1 minute), allowing the user to clean the surface of the touchscreen 144 without affecting the settings of the thermostat 142. A “MORE” icon button 162 provided on the touchscreen 144 can be used to access other functionality of the thermostat 142, if desired. For example, the “MORE” icon button 162 can be used to display the current indoor humidity, the current outdoor humidity, the current outdoor temperature, and/or other useful information.
The thermostat 142 can include a configuration routine for programming various settings related to the away mode of operation, similar to that described above with respect to
When initiated, and as shown in a second screen shot in
As further shown in
To configure the thermostat controller 142 to operate in the away mode, and as further shown in
To configure the fan setting to be used during the away mode of operation, the installer may select the appropriate programming code 172 (i.e. “0391”) using the first set of up/down arrow buttons 174a,174b, and then enter the desired code using the second set of up/down arrow buttons 178a,178b, as shown in
To configure the low temperature limit setpoint to be used during the away mode, and as further shown in
To configure the dehumidification away temperature setpoint to be used during the away mode, and as further shown in
To configure the away dehumidification setting to be used during the away mode, and as further shown in
Once the installer has finished programming the various away mode settings, the installer may then select the “DONE” icon button 180 on the touchscreen 144, causing the thermostat 142 to store the settings and resume normal thermostat operation.
As shown in
A “MORE” icon button 194 on the touchscreen 144 can be used to gain access to other information while the thermostat 142 is operating in the away mode. As shown in a second screen shot in
If at any time the user desires to exit the away mode of operation and revert back to normal thermostat operation, the user may select a “CANCEL” icon button 202 on the away mode screen depicted in
Although the illustrative thermostat 142 depicted in
Having thus described the several embodiments of the present invention, those of skill in the art will readily appreciate that other embodiments may be made and used which fall within the scope of the claims attached hereto. Numerous advantages of the invention covered by this document have been set forth in the foregoing description. It will be understood that this disclosure is, in many respects, only illustrative. Changes can be made with respect to various elements described herein without exceeding the scope of the invention.
This application is a continuation of U.S. application Ser. No. 11/462,309, filed Aug. 3, 2006, entitled “METHODS OF DEHUMIDIFICATION CONTROL IN UNOCCUPIED SPACES”, which is hereby incorporated by reference.
Number | Name | Date | Kind |
---|---|---|---|
2438120 | Freygang | Mar 1948 | A |
3469412 | Giuffre | Sep 1969 | A |
3989097 | Schildknecht | Nov 1976 | A |
4003729 | McGrath | Jan 1977 | A |
4105063 | Bergt | Aug 1978 | A |
4271898 | Freeman | Jun 1981 | A |
4318508 | Glasgow et al. | Mar 1982 | A |
4350023 | Kuwabara et al. | Sep 1982 | A |
4482007 | Yoshimi et al. | Nov 1984 | A |
4540040 | Fukumoto et al. | Sep 1985 | A |
4540118 | Lortie et al. | Sep 1985 | A |
4659009 | Newell, III | Apr 1987 | A |
4850198 | Helt et al. | Jul 1989 | A |
4884214 | Parker et al. | Nov 1989 | A |
4889280 | Grald et al. | Dec 1989 | A |
4942740 | Shaw et al. | Jul 1990 | A |
5000382 | Stedman | Mar 1991 | A |
5062276 | Dudley | Nov 1991 | A |
5065585 | Wylie et al. | Nov 1991 | A |
5114070 | Lilja et al. | May 1992 | A |
5129234 | Alford | Jul 1992 | A |
5192020 | Shah | Mar 1993 | A |
5224648 | Simon et al. | Jul 1993 | A |
5228302 | Eiermann | Jul 1993 | A |
5231845 | Sumitani et al. | Aug 1993 | A |
5237826 | Baldwin et al. | Aug 1993 | A |
5259553 | Shyu | Nov 1993 | A |
5261251 | Galiyano | Nov 1993 | A |
5276630 | Baldwin et al. | Jan 1994 | A |
5297396 | Kitamoto | Mar 1994 | A |
5305822 | Kogetsu et al. | Apr 1994 | A |
5311451 | Barrett | May 1994 | A |
5326026 | Jefferson et al. | Jul 1994 | A |
5346129 | Shah et al. | Sep 1994 | A |
5390206 | Rein et al. | Feb 1995 | A |
5419146 | Sibik et al. | May 1995 | A |
5427175 | Nagasawa | Jun 1995 | A |
5450893 | Galba et al. | Sep 1995 | A |
5502975 | Brickley et al. | Apr 1996 | A |
5544809 | Keating et al. | Aug 1996 | A |
5578755 | Offenberg | Nov 1996 | A |
5598715 | Edmisten | Feb 1997 | A |
5732879 | Low | Mar 1998 | A |
5911747 | Gauthier | Jun 1999 | A |
5915473 | Ganesh et al. | Jun 1999 | A |
6070110 | Shah et al. | May 2000 | A |
6079121 | Khadkikar et al. | Jun 2000 | A |
6427454 | West | Aug 2002 | B1 |
6478084 | Kumar et al. | Nov 2002 | B1 |
6826920 | Wacker | Dec 2004 | B2 |
6843068 | Wacker | Jan 2005 | B1 |
6892547 | Strand | May 2005 | B2 |
6926079 | Kensok et al. | Aug 2005 | B2 |
6996999 | Wacker | Feb 2006 | B2 |
7155318 | Sharma et al. | Dec 2006 | B2 |
7402780 | Mueller et al. | Jul 2008 | B2 |
7418428 | Ehlers et al. | Aug 2008 | B2 |
7469550 | Chapman, Jr. et al. | Dec 2008 | B2 |
7793510 | Perry et al. | Sep 2010 | B2 |
8091375 | Crawford | Jan 2012 | B2 |
8209059 | Stockton | Jun 2012 | B2 |
8280555 | Masui et al. | Oct 2012 | B2 |
8356760 | Riley, Jr. | Jan 2013 | B2 |
8467905 | George | Jun 2013 | B2 |
20040139038 | Ehlers et al. | Jul 2004 | A1 |
20050270151 | Winick | Dec 2005 | A1 |
20070257121 | Chapman et al. | Nov 2007 | A1 |
20080217419 | Ehlers et al. | Sep 2008 | A1 |
Number | Date | Country |
---|---|---|
045509 | Nov 1991 | EP |
60169039 | Sep 1985 | JP |
6137643 | May 1994 | JP |
8156178 | Jun 1996 | JP |
8912269 | Dec 1989 | WO |
9322602 | Nov 1993 | WO |
03029728 | Oct 2003 | WO |
Entry |
---|
All Non-US Patent References Have Been Previously Cited in Parent U.S. Appl. No. 11/462,309, filed Aug. 3, 2006. |
Cummings et al., “Executive Summary: Evaluation of the Impact of Vacant Home Space Conditioning Strategies on Summer Relative Humidity, Energy, and Peak Load; Phase II,” Copyright Florida Solar Energy Center/University of Central Florida, 24 pages, Dec. 18, 2006. |
Xu et al., “A New Control Algorithm for Direct Expansion Air Conditioning Systems for Improved Indoor Humidity Control and Energy Efficiency,” Energy Conversion and Management, vol. 49, pp. 578-586, Sep. 17, 2007. |
Number | Date | Country | |
---|---|---|---|
20100212879 A1 | Aug 2010 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 11462309 | Aug 2006 | US |
Child | 12776133 | US |