Microprocessor-based combination smoke and carbon monoxide detector having intelligent hush feature

Information

  • Patent Grant
  • 6753786
  • Patent Number
    6,753,786
  • Date Filed
    Friday, August 11, 2000
    24 years ago
  • Date Issued
    Tuesday, June 22, 2004
    20 years ago
Abstract
A microcontroller-based hazardous condition detector having an intelligent hush feature is presented. The microcontroller controls the operational mode of the detector by monitoring a single user-actuated switch, the inputs from a smoke chamber and a carbon monoxide detector circuit, and the current operating mode of the detector. When in a normal or no-alarm mode, actuation of the switch will cause the microcontroller to place the detector in a test mode of operation. If the detector is in a carbon monoxide alarm mode, actuation of the switch will act to reset the accumulator function of the microprocessor for the carbon monoxide alarm sensing. If the detector is in a smoke alarm mode, actuation of the switch may place the detector in a hush mode if the level of smoke is sufficiently low, or will have no effect if the level of smoke is too high. Once in the hush mode, actuation of the switch will place the detector into the smoke alarm mode. The microcontroller will also place the detector in the smoke alarm mode if the level of smoke increases beyond a certain limit, and after the expiration of a hush mode time limit. To coordinate this operation, the sensitivity of the detector is not changed in any mode of operation, and the microcontroller monitors both an alarm and a hush threshold.
Description




FIELD OF THE INVENTION




This invention relates generally to the hazardous condition detectors, and more specifically to the hush feature of such detectors.




BACKGROUND OF THE INVENTION




In the past, many people died in their sleep because there was no warning system to awaken them during the early stages of a dwelling fire. Likewise, without a system that could detect the presence of a fire early in its development, many people were trapped in burning buildings once the fire escalated to a point that became easily detectable. Luckily, smoke detectors have been developed which reliably provide an early warning to individuals that a fire may be present. These smoke detectors are so effective in saving lives that they have been mandated as required appliances in many types of dwellings. Current smoke detectors utilize an Application-Specific Integrated Circuit (ASIC), such as the Motorola MC 14467. These ASIC's and their corresponding analog circuitry allow for long battery life, reliable operation, and relatively low cost for these smoke detectors.




It goes without saying that to be effective a smoke detector must be operational. However, since smoke detectors are typically silent, consumers may not know whether or not their detector is operational. While many manufacturers include a feature that provides a periodic chirp as the battery is running low, many individuals desire the capability to affirmatively test the operability of their smoke detector. As such, modern smoke detectors include a push button that, when held in its actuated position, will place the smoke detector in a test mode of operation. This test mode will typically sound the smoke detector alarm after the test button is held for a period of two to three seconds.




While the alarm from a smoke detector is quite effective at warning occupants that smoke has been detected, such smoke does not always mean that a fire exists in the dwelling. Instead, the source of the detected smoke may be under the control of the occupant as, for example, in the situation where the occupant may be cooking in the kitchen. Occasionally, such cooking activities result in the generation of smoke to such a degree that the smoke detector is triggered. In such and other situations the sounding of the smoke detector alarm becomes more of an annoyance than a help.




To accommodate consumer desires to silence the alarm in such situations, while at the same time maintaining functionality of the smoke detector, a hush feature was introduced into conventional smoke detector design. Such a hush feature operates in conventional ASIC-based smoke detectors to reduce the sensitivity of the smoke detectors so that the smoke resulting from consumer-controlled conditions do not result in the sounding of the smoke detector alarm. In such a reduced sensitivity mode of operation, the conventional ASIC-based smoke detectors will sound an alarm if a level of smoke sensed continues to increase beyond the reduced sensitivity level. In this way, the consumers will again be provided with an audible warning indicating that the level of smoke within their dwelling has continued to increase since the hush feature was initiated.




While both the hush feature and the test feature satisfied consumer demands, many smoke detectors provided separate push-button switches to initiate these different modes of operation. Unfortunately, it was found that many consumers were inadvertently actuating the wrong push-button switch and, as a result, were confused by the subsequent operation of their smoke detector. As an example, if the hush button were actuated when the consumer actually wished to determine operability of the smoke detector by entering the test mode of operation, the alarm would not sound, possibly causing the consumer to believe that smoke detector is defective. Likewise, in the situation where the source of smoke is a known consumer-controlled event, actuation of the test button will not silence the smoke detector alarm as desired by the consumer. Such may result in the consumer believing that a larger problem exists within his dwelling, or that the smoke detector is malfunctioning. These problems in selecting the wrong switch are exacerbated by the fact that most smoke detectors are located on or near the ceiling where it is difficult to read the labeling provided for each of these two switches.




In an attempt to provide the desired functionality of both the test mode of operation and the hush mode of operation, many modern smoke detectors are beginning to utilize a single push-button switch, which is capable of actuating both the test mode and the hush modes of operation. One such detector having a hush feature is described in U.S. Pat. No. Re. 33,920 for a SMOKE DETECTOR HAVING VARIABLE LEVEL SENSITIVITY, issued to Tanguay et al. (hereinafter the Tanguay et al. '920 patent). The Tanguay, et al. '920 patent describes an application specific integrated circuit (ASIC) based analog smoke detector circuit having variable level sensitivity for allowing operation exclusively in a normal mode or in a hush mode, and having a test mode, both operable via a single switch.




The Tanguay, et al. '920 patent utilizes a conventional smoke detector ASIC such as the Motorola MC14467. As is conventional with such a smoke detector ASIC, a reference voltage is supplied to pin P


13


of the chip. This voltage input is coupled to an input of an analog voltage comparator within the ASIC, and establishes the alarm threshold value against which the output analog voltage from the smoke chamber


30


will be compared. The output voltage from a conventional ionization chamber is coupled to pin P


15


, which is the other input to the analog voltage comparator within the smoke detector ASIC. As is conventional with this type of device, when the voltage on pin P


15


drops below the voltage on pin P


13


the ASIC generates an output alarm signal to sound an audible alarm and to light a visible LED.




The smoke detector of the Tanguay, et al. '920 patent also includes a user-actuated switch that initiates both a test mode and a hush mode of operation. Unfortunately, both modes of operation are always entered when the user-actuated switch is activated. That is to say, that hush mode of operation is actuated even if the smoke detector is not currently in an alarm condition and the user solely wishes to check the operability of the detector. In accordance with the teachings of Tanguay, et al. '920, the detector test is initiated by contact of the user-actuated switch to the container of the ionization chamber. As described, this reduces the voltage supplied to the ionization chamber, resulting in a reduced output voltage therefrom. This reduced output voltage is sufficient for the smoke detector ASIC to generate an output alarm signal.




At the same time that the output from the ionization chamber is reduced due to the user-actuated switch completing a circuit to ground from the ionization chamber thereby reducing its input voltage, a test switch sensor circuit conducts current flow to an inhibit control circuit and a time constant circuit. These elements control the hush mode of operation once the user-actuated switch is released. Specifically, during actuation of the switch current flows into the time constant circuit to charge a capacitor through the test switch sensor transistor and a diode. Once the user releases the switch, the time constant circuit now begins operation by draining off the charge of the capacitor through the resistor divider network of R


12


and R


13


. The voltage generated through this resistor divider network is sufficient to turn on the Darlington configured transistor, which reduces the voltage at pin P


13


. The level to which the voltage on pin P


13


is lowered may be adjusted through the proper selection of resistors R


15


and R


16


and the transistor. These three elements form what is termed a sensitivity control means in the specification of Tanguay, et al. '920. The Darlington configured transistor is referred to in the specification as a diminishing means which diminishes the sensitivity of the smoke detector in response to user actuation of the switch.




While the above-described system attempts to overcome certain problems in the art, it unfortunately introduces other problems that seriously compromise the effectiveness and operability of the detector. Specifically, the limitation that the ASIC introduces with regard to its ability to only sense a single threshold limits the detector to operation solely within the normal sensitivity mode of operation or the reduced sensitivity mode of operation, exclusively. The reduced sensitivity mode remains active even if the amount of smoke in the atmosphere reduces to the point where the normal alarm mode would not be entered. As such, the subsequent generation of a level of smoke that would sound the alarm in a normal sensitivity mode of operation will fail to do so because the detector continues to operate in the reduced sensitivity mode, even though the original condition necessitating the reduced sensitivity mode of operation has long since cleared.




The continued operation in the reduced sensitivity mode of operation highlights another shortcoming of the prior design in that it relies on external timing circuitry as the only mechanism for exiting the reduced sensitivity mode of operation. As described above, once this reduced sensitivity mode of operation has been entered, it will only be exited once the external time-delay circuitry has timed out, regardless of the atmospheric conditions existing within the environment of the detector. Further, while the above-described design attempts to simplify the user interface by providing a single switch to initiate both the test and the hush mode of operation, the use of an analog ASIC design results in both modes of operation being entered upon actuation of the single switch. That is, when the single switch is actuated, both the test mode of operation and the hush mode of operation are entered. As a result, the sensitivity of the detector is reduced even if the user merely wanted to test the operational readiness of the detector. The inadvertent entrance into the reduced sensitivity mode of operation will result in the detector having a reduced sensitivity to smoke for the entire period of the time-out delay.




There is a need existing in the art, therefore, for a smoke detector that utilizes a simplified user interface, but that provides selective initiation of the test mode of operation and the hush mode of operation. Further, there is a need existing in the art for a smoke detector that cancels the hush mode of operation in an intelligent fashion, or as a result of user de-selection thereof. In this way, the hush mode of operation is not continued when the conditions that necessitated its initiation no longer exist.




In addition to smoke detectors, recent advances in hazardous condition detection technology have allowed for the emergence of carbon monoxide detectors supplied to the general public. Such carbon monoxide detectors typically include a sensing element that provides an input to a microprocessor. The microprocessor calculates the total exposure dosage of CO through an accumulator function that correlates carbon monoxide concentration and exposure time. With continuing advances in the carbon monoxide detector technology, these detectors are now available at such a cost and with such a reliability that many manufacturers are now marketing combined smoke and carbon monoxide detectors for use in homes and dwellings.




However, these combination devices typically merely include a conventional ionizing-type smoke detector on the same chassis as a conventional carbon monoxide detector. These two detectors share the same power source and the same alarm system, but they typically independently perform sensing according to the technology of their individual, conventional sensors. Thus, the conventional combination smoke and carbon monoxide detector is not much more than an aggregation. That is, the two units will function independently through independent circuits to sense their independent parameters, but will use the same horn for the alarm. Indeed, the smoke detector portion of the combination units typically still utilizes the Application-Specific Integrated Circuit used in the individual units, and the carbon monoxide portion uses a separate microprocessor for calculating the accumulation dosage of carbon monoxide.




While such aggregate units are being marketed, the cost of these units still reflects the aggregation of both the ASIC and the microprocessor used for the separate smoke and carbon monoxide detection, respectively. Further, in order to allow for the accumulator to be reset a separate carbon monoxide detector reset switch is typically employed in these aggregate units. However, since the functionality of the CO detector is not integrated with the control of the smoke detector (and the initiation of the hush and test modes of operation), this results in two switches once again appearing on the combined detector. As discussed above, multiple switches on the detector may add to consumer confusion.




SUMMARY OF THE INVENTION




In view of the above, it is an object of the instant invention to provide a new and improved smoke detector overcoming the above described and other problems existing in the art. More particularly, it is an object of the instant invention to provide a new smoke detector having an intelligent hush feature and an intelligent test feature. It is a further object of the invention to provide such a detector that utilizes only a single button


18


to intelligently initiate either of these features.




It is an additional object of the invention to provide a combined smoke and carbon monoxide detector having these features. Further, it is an object of the invention that the control for both the smoke and CO detectors is integrated within a single microprocessor or microcontroller


12


. It is an additional object of the instant invention to provide a combined smoke and CO detector that utilizes a single push button switch


18


to intelligently initiate the hush mode, the test mode, or reset the CO accumulator. Additionally, it is an object of the instant invention that initiation of any mode or reset of the accumulator will not inadvertently initiate any other mode of operation or inadvertently reset the accumulator.




Fundamentally, the hazardous condition detector of the instant invention represents an advance in technology that provides a more feature-rich detector than has previously been available. As described above, conventional smoke detectors are based on a special purpose ASIC that performs an analog comparison of the smoke chamber


30


voltage against a threshold, and generates an alarm based on the comparison. The new generation detector enabled by the instant invention will perform the comparison and alarm logic digitally in a microcontroller


12


. Use of the microcontroller


12


will also allow a true combination detector for smoke and carbon monoxide (CO), in which a common microcontroller


12


handles measurement, calibration and alarm logic for both detectors.




With regard to the smoke detector specific aspect of the invention, additional functionality is provided. The capability to concurrently compare the smoke chamber


30


output with two or more thresholds, impossible in the conventional ASIC design as discussed above, provides a new form of self-clearing, intelligent hush. Conventional smoke detectors lose the ability to monitor the original alarm threshold when in the hush mode, and therefore must rely on a timer circuit to reset hush. In the detector of the instant invention, both the alarm and hush thresholds are concurrently monitored in hush, allowing the hush condition to self clear when the smoke clears from the detector. A digital timing function is provided as a backup to reset hush if the detector has not cleared within the UL mandated reset period. The user is also provided with the heretofore-unavailable option of entering or exiting hush by separately depressing the hush button


18


with an appropriate level of smoke detected. The test mode of operation is entered by depressing the push button switch


18


only if the detector is not in an alarm condition or the hush mode of operation.




With respect to the CO detector specific aspect of the invention, the resetting of the accumulator is accomplished via the same, single push button switch


18


as initiates the hush and test modes of operation. The selectivity provided by the common microcontroller


12


ensures that the accumulator is not inadvertently reset when the user is attempting to enter either the hush or test modes of operation. Specifically, the actuation of the user switch


18


resets the CO accumulator only if the detector is in a CO alarm condition. This selective, intelligent functionality is enabled by the use of a single microcontroller


12


for both the smoke and CO detector portions of the combined unit.




Other objects and advantages of the invention will become more apparent from the following detailed description when taken in conjunction with the accompanying drawings.











BRIEF DESCRIPTION OF THE DRAWINGS




While the appended claims set forth the features of the present invention with particularity, the invention, together with its objects and advantages, may be best understood from the following detailed description taken in conjunction with the accompanying drawings of which:





FIG. 1

is a simplified block diagram illustrating a combination smoke and carbon monoxide (CO) detector constructed in accordance with the teachings of the instant invention;





FIG. 2

is a simplified schematic diagram illustrating an aspect of the instant invention;





FIG. 3

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates an aspect of the intelligent hush feature of the instant invention;





FIG. 4

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates an additional aspect of the intelligent hush feature of the instant invention;





FIG. 5

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates yet an additional aspect of the intelligent hush feature of the instant invention;





FIG. 6

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates a further aspect of the intelligent hush feature of the instant invention;





FIG. 7

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates a still further aspect of the intelligent hush feature of the instant invention;





FIG. 8

is a graphical illustration of a smoke chamber


30


output voltage versus time that illustrates a further additional aspect of the intelligent hush feature of the instant invention; and





FIG. 9

is a simplified logic diagram illustrating an embodiment of the control logic of the detector of the instant invention.











While the invention will be described in connection with certain preferred embodiments, there is no intent to limit it to those embodiments. On the contrary, the intent is to cover all alternatives, modifications and equivalents as included within the spirit and scope of the invention as defined by the appended claims.




DETAILED DESCRIPTION OF THE PREFERRED EMBODIMENTS




Turning now to the drawings,

FIG. 1

illustrates a simplified block diagram of an embodiment of a detector


10


constructed in accordance with the teachings of the instant invention. Specifically, in this embodiment of the instant invention a combined smoke and carbon monoxide detector


10


is illustrated, although it must be noted that alternate embodiments of the instant invention incorporating the teachings thereof may not utilize all of the components illustrated therein. However, in the embodiment illustrated in

FIG. 1

a single microcontroller


12


receives input from a conventional ion or photoelectric smoke chamber


14


and a carbon monoxide detector circuit


16


. It will be understood from the following that the particular technology of the detector circuits


14


,


16


is not a limiting aspect of the invention. Further, while the following discussion will refer to a microcontroller


12


, one skilled in the art will recognize that the functionality and intelligence of the instant invention described herein for this element may be alternatively embodied in a microprocessor with associated input/output and buffering circuits, in a programmable logic device (PLD), in an application specific integrated circuit (ASIC), of other intelligent, programmable device. Therefore, the use of the term microcontroller herein shall be construed to cover all of these alternative structures as well.




The microcontroller


12


also receives a single user-actuated switch


18


input. The microcontroller


12


utilizes the inputs from these components


14


,


16


, and


18


to generate an output alarm condition when the sensed environmental conditions so dictate. A single alarm circuit


20


is utilized to broadcast via alarm


22


the appropriate audible sound, depending on which condition has been detected. The alarm circuit


20


may include both tone and synthesized voice message generation capabilities, or may be a simple piezo-electric type device. The detector


10


of the instant invention may also include a visual warning system, such as the Light-Emitting Diode (LED) flash circuit


24


and accompanying LED


26


. As may also be seen from this simplified block diagram of

FIG. 1

, the microcontroller


12


simulates a hazardous smoke condition via line


28


to allow the microcontroller


12


to test the functionality of the detector


10


.




When there is a hazardous level of smoke present, the detector


10


will enter the smoke alarm mode. Actuation of the switch


18


will cause the microcontroller


12


to place the detector


10


in the hush mode. In one embodiment, upon entry into the hush mode a voice synthesized message will be announced once (“Hush Activated”), and a green LED


26


will blink about once every 2 seconds to signify it is in hush mode. Under the normal mode the LED


26


is constantly on, when the unit is in the initiating alarm mode the LED


26


blinks once every second, and when the detector


10


is powered by battery only the LED


26


blinks once every 5 seconds. When the hush mode is canceled for any reason, a voice synthesized message will be announced once (“Hush Canceled”), and the LED


26


will stop blinking every 2 seconds.




As may be seen in the simplified schematic of

FIG. 2

, an embodiment of the detector


10


of the instant invention is a microcontroller-based detector that includes a conventional smoke chamber


30


and a single user-actuated push button


18


to initiate the hush mode and the test mode. Operation of the smoke chamber


30


is conventional, i.e. the output voltage varies as the amount of smoke entering the chamber


30


increases and decreases. Specifically, the output voltage on line


32


from the smoke chamber


30


varies inversely as a function of the amount of smoke sensed by the chamber


30


. As the amount of smoke is increased, the output voltage of the chamber


30


decreases.




This output voltage is then buffered or amplified by Op Amp


34


to increase the resolution of the simple analog-to-digital (A/D) converter (not shown) of the microcontroller


12


. After the output voltage of the smoke chamber


30


has been converted to a digital value, the internal control logic of the microcontroller


12


compares this digital value to a preprogrammed digital number threshold to determine an alarm condition. Once an alarm condition has been set, the microcontroller utilizes a slightly higher digital threshold to reset the alarm condition, in effect utilizing digital hysteresis to set and reset the smoke alarm condition. No external analog circuitry is required to perform this function as the digital integer threshold values for the set and reset functions are internally stored within the memory of the microcontroller


12


.




In an embodiment of the invention a single user-actuated push-button switch


18


is included to initiate either a test mode of operation or a hush mode of operation. The entry into either of these modes is controlled exclusively within the microcontroller


12


based upon the current state of the system


10


at the time the button


18


is actuated. The push button input is sensed only by the microcontroller


12


, and does not require any analog connection to circuitry other than the microcontroller


12


.




If the smoke detector


10


is not in an alarm condition, actuation of the push button


18


sensed by the microcontroller


12


results in the microcontroller


12


placing the smoke detector


10


in a test mode. Once the microcontroller


12


has entered the test mode, it reduces the supply voltage to the smoke chamber


30


through resistor


36


. The output


32


of the conventional smoke chamber


30


is dependent not only on the amount of smoke sensed therein, but also on the input supply voltage. Therefore, as a result of the microcontroller


12


reducing the supply voltage to the smoke chamber


30


, the smoke chamber's output voltage


32


decreases. This decreasing smoke chamber


30


output voltage


32


is sensed by the microcontroller


12


which then initiates an alarm. Once the microcontroller


12


has completed its test cycle, it returns the supply voltage to the smoke chamber


30


to its normal value. With the normal supply voltage returned, the output voltage


32


of the smoke chamber


30


again rises to its normal level, which is sensed by the microcontroller


12


. The microcontroller


12


then resets the alarm condition.




If the user-actuated switch


18


is depressed during an alarm condition, the microcontroller


12


places the system in the hush mode. Upon detection of user button actuation, the microcontroller


12


first silences the continuous alarm. As illustrated in

FIGS. 3-8

, the alarm detecting algorithm compares the digitized signal from the smoke chamber


30


against two thresholds, the original threshold


38


and a hush threshold


40


of reduced sensitivity. If the smoke level is above both the hush threshold


40


and the original threshold


38


(signal level less than the stored integer threshold) the alarm sounds at full volume. If the smoke level produces a digitized signal between the two thresholds


38


,


40


, a hush mode alarm is generated. As soon as the smoke level produces a digitized signal level greater than both thresholds


38


,


40


, the alarm is silenced and hush is automatically terminated. The microcontroller


12


also increments an internal digital timer


42


for so long as the digitized signal is between thresholds


38


,


40


, and will terminate hush and sound a continuous alarm if the timer times out. However, by continuing to monitor both threshold values


38


,


40


, the microcontroller


12


may return the detector


10


to normal alarm generation levels at a time potentially much sooner than a traditional time out. This increases the safety of the detector by allowing early warning of a new smoke generation condition.




To inform the user that the unit


10


is in hush and the digitized signal level is between the two thresholds


38


,


40


, a hush alarm is sounded. In an embodiment, the hush alarm will take the form of a flashing LED


26


, periodic audible chirps, or both. In an alternative embodiment, a quiet hush alarm will be sounded which will be a continuous (or possibly intermittent) sounding of the alarm at substantially reduced volume. These audible and visible alarms will continue for so long as the detector


10


remains in hush and the microcontroller


12


determines that the digitized signal level remains between the thresholds


38


,


40


. The hush mode can be exited by any of several conditions detected by the microcontroller


12


: (a) the clearing of the smoke chamber


30


, (b) an increase in smoke level above the hush threshold


40


, (c) user actuation of the hush switch


18


, or (d) time out of the digitized hush interval


42


. It is important to this hush mode of operation that the smoke detector


10


sensitivity at all times remains the same. The microcontroller


12


must continue to compare actual detector readings against both stored limits


38


,


40


, the hush limit


40


and the alarm limit


38


to determine which of its operating modes should be active (clear, hush, or alarm).




The quiet hush feature of an alternate embodiment emphasizes the significant differences in functionality provided by the new microcontroller-based design. Unlike the typical hush feature implemented in various detectors currently available on the market that completely silences the warning alarm unless the environmental condition increases beyond a new threshold value, the “quiet hush” feature reduces the volume of the alarm to a much reduced decibel level, such as 5 or 10 dB.




By introducing a “quiet hush” mode as opposed to a silent hush mode, consumers are given an unambiguous signal that the smoke detector is still functional, that the smoke level is being measured, and is between the two thresholds


38


,


40


. The microcontroller


12


continues to monitor both the normal


38


and the hush


40


threshold levels as described above, and maintains the alarm at the lower volume so long as the level of smoke remains between these two levels


38


,


40


. If the level of smoke increases beyond the lower hush threshold setting, the detector will again increase the decibel output of the alarm signal to at least the required minimum of 85 dB. In addition to increasing the output volume of the alarm, the detector


10


also cancels the hush mode of operation, as described above. Alternatively, if the level of smoke or other detected condition decreases below the normal threshold value


38


at which the original alarm was sounded, the lower volume alarm and the hush mode will be canceled.




Having now introduced generally the intelligent hush feature enabled by the microcontroller-based detector of the instant invention, attention is now directed to

FIGS. 3-8

for a detailed explanation and illustration of each of the various operational aspects of the intelligent hush feature. Turning first to

FIG. 3

wherein the smoke chamber


30


output voltage is plotted versus time under varying conditions of smoke in the environment of the detector


10


, trace


44


illustrates the smoke chamber


30


output voltage under an increasing smoke condition causing the output voltage


44


to drop below the alarm threshold


38


. As the output voltage


44


crosses the threshold


38


, an alarm condition is initiated. At point


46


the user push-button switch


18


(see

FIG. 1

) is actuated. The microcontroller


12


then places the detector


10


in the hush mode of operation because the output of the smoke chamber is between the alarm threshold


38


and the hush threshold


40


. As may be seen from this figure, if the output voltage illustrated as trace


44


remains within these two thresholds


38


,


40


, the microcontroller


12


will automatically disable the hush feature after a predetermined duration


42


. Preferably this duration is approximately ten (10) minutes, although any duration that meets regulatory requirements is possible. Once this time period


42


has expired, the microcontroller


12


then places the detector


10


back into the alarm mode without the necessity of any user intervention.




As may be seen from the graph of

FIG. 4

, as the output voltage


44


decreases below the alarm threshold


38


, the microcontroller


12


places the detector


10


into an alarm condition as described above. Likewise, actuation of the user switch


18


at point


46


places the detector


10


in the hush mode of operation. However, as may be seen from this

FIG. 4

, if the output voltage


44


were to continue to drop below the hush threshold


40


as illustrated at point


48


, the microcontroller


12


automatically disables the hush mode of operation and places the detector


10


into an alarm condition. Unlike prior hush designs, if the output voltage


44


increases above hush threshold


40


but remains below alarm threshold


38


, the detector


10


will remain in an alarm condition unless and until the user-actuated switch


18


is again depressed. Prior systems that rely solely on a time-out to reset the hush mode of operation may again disable the alarm once this hush threshold had been crossed, even though the increased amount of smoke had necessitated the exit from hush mode just prior to a level of smoke subsiding somewhat. However, since the microcontroller


12


of the instant invention utilizes digital logic to determine the appropriate mode of operation of the detector


10


, such inadvertent operation is precluded once the hush mode of operation has been exited.




In addition to automatic control,

FIG. 5

illustrates the microcontroller's ability to allow user intervention once the hush mode of operation has been entered. Specifically, trace


44


once again illustrates the increasing amount of smoke causing the output voltage of the smoke chamber


30


to decrease below the alarm threshold


38


. As with the prior figures, the user actuates switch


18


at point


46


to cause the detector


10


to enter the hush mode of operation. Since the microcontroller receives the push-button input, and utilizes its control algorithms to determine appropriate detector state, actuation of the push-button


18


during the hush mode of operation at point


50


results in the microcontroller


12


disabling the hush mode of operation. Since the level of smoke remains below the alarm threshold


38


, the detector


10


will again be placed in the alarm mode of operation by the microcontroller


12


. This will clearly provide an indication to the user that the detector


10


is fully operational and sensing a level of smoke that is greater than the alarm threshold. If the user were to actuate the push-button switch


18


once again, the hush mode of operation would again be entered, so long as the output voltage


44


remains between the two thresholds


38


,


40


.




An additional aspect of the automated control for the hush feature provided by microcontroller


12


is illustrated in FIG.


6


. As the output from the smoke detector


44


drops below the alarm threshold


38


, the microcontroller


12


places the detector


10


into the alarm mode of operation. As with the above, the user-actuated switch is depressed during this alarm mode at point


46


to place the detector in the hush mode of operation. If the output voltage


44


were to increase above threshold


38


, indicating that the amount of smoke sensed by the smoke chamber


30


had decreased, the microcontroller


12


disables the hush mode of operation. If the amount of smoke again increases as indicated in

FIG. 6

by the decrease of voltage trace


44


below threshold


38


at point


54


, the microcontroller


12


will again place the detector


10


in an alarm mode of operation.




This presents a significant safety advantage over conventional hush designs, especially where point


52


and point


54


are within the hush time-out of the conventional detectors. With these conventional detectors, once the hush mode of operation has been entered, it will remain active until the time-out circuitry expires. Therefore, a second smoke-generating condition will not produce an alarm until the hush level has been crossed. With the system of the instant invention, once the initial smoke-generating event has ended or subsided to the point where the alarm threshold is no longer crossed, the re-appearance of smoke will again be signaled to the user at the original alarm level


38


. In such a situation, the user is provided with an earlier warning that a new condition exists, or that the prior condition has not fully been extinguished. Since the original alarm threshold


38


is used to provide this early warning, the user may attend to the condition before it generates a significant amount of smoke such to cross the hush threshold


40


.





FIG. 7

illustrates a further advantage provided by the microcontroller-controlled hush feature. In this illustration, the user-actuated switch


18


is not depressed until after the output voltage


44


has crossed both the alarm threshold


38


and the hush threshold


40


. In such a situation, the microcontroller


12


does not place the system


10


into the hush mode of operation because the level of smoke is too great at the point of switch actuation


46


. If the amount of smoke were to subside slightly such that the output voltage


44


was to cross the hush threshold


40


at point


56


, the alarm condition is maintained. This also illustrates a distinction between the microcontroller-based hush feature of the instant invention and conventional ASIC/analog-based systems. Specifically, in the prior systems, the only way to terminate the hush mode of operation and return the detector to its normal level of sensitivity is for the time-out circuitry to expire. This is so even though the hush mode of operation was never properly entered because the level of smoke was too great at the time of user switch actuation. However, under such circumstances the alarm would be disabled at point


56


because the reduced sensitivity mode of operation would still dominate the analog circuitry until the time-delay circuitry expired. This may provide the users of a false sense of security thinking that the smoke condition has cleared.




In the system of the instant invention, on the other hand, since the hush condition is never properly entered, the microcontroller


12


continues to maintain the alarm condition until the level of smoke reduces below the alarm threshold


38


. This will ensure that the detector continues to provide an audible alarm unless and until the smoke clears below the alarm threshold level, or the user actuates the switch to enter the hush mode of operation once the smoke has reduced to a point such that the hush threshold


40


is no longer breached. As illustrated in

FIG. 7

, this would be after point


56


. If the switch were actuated after point


56


, the hush mode of operation will be entered as described above.




In a similar manner as illustrated in

FIG. 8

, if the user were to depress the push button


18


at a point


46


when the output voltage


44


is above the alarm threshold


38


, the hush mode of operation will not be entered. As such, an increase in smoke in the smoke chamber


30


resulting in the output voltage


44


dropping below alarm threshold


38


at point


58


will generate an alarm condition. As with the above, this presents a significant advantage over prior hush systems that do not have the intelligence to recognize that the hush mode should not be entered (which reduces their sensitivity) when the button is pushed if the detector is not in an alarm condition with a moderate level of smoke, and over prior hush systems that relied solely on the time-out of a time-delay circuit to return the detector to its normal level of sensitivity to smoke once hush has been initiated. That is, if the level of smoke were to increase such that point


58


was achieved prior to the expiration of the time-delay circuitry, no alarm would be generated to warn the user that the level of smoke had increased above the normal alarm level. Indeed, the conventional ASIC/analog design would not provide an alarm signal to warn the occupants of the increasing amount of smoke until the hush threshold


40


were actually crossed. With the microcontroller


12


of the instant invention, an earlier warning may be provided at point


58


as soon as the original alarm threshold


38


is breached.




With the functional operation of the microcontroller hush feature now well in hand, attention is directed to

FIG. 9

, which illustrates an embodiment of the control logic contained within microcontroller


12


. This control logic within the microcontroller


12


receives the user-actuated switch


18


input through an analog-to-digital converter


60


. Also, the input voltage from smoke chamber


30


is received through an analog-to-digital converter


62


. The input from the carbon monoxide detector is also conditioned through an analog-to-digital converter (not shown), and a carbon monoxide alarm condition


64


is generated in accordance with conventional accumulation techniques within the microcontroller.




This carbon monoxide alarm signal


64


is utilized by the microcontroller


12


to place the detector


10


into the correct state upon sensing user actuation of switch


18


. The actual generation of the CO alarm signal is in keeping with conventional techniques and will not be described further herein. However, if the detector


10


is in a carbon monoxide alarm condition


64


, and the user-actuated switch


18


is depressed, the microcontroller


12


will generate an accumulator-reset signal


66


. Once this accumulator-reset signal


66


has been generated by AND gate


68


, this signal is latched by S/R latch


70


. This latched signal disables AND gate


68


and removes the accumulator-reset signal


66


, so that the accumulator may again begin processing the input carbon monoxide information. Repeated actuation of switch


18


when the carbon monoxide alarm signal


64


has been generated may be precluded from continuously resetting the carbon monoxide accumulator through the use of this latch


70


until either power is cycled to the detector indicated by the power-up reset signal


72


, or after a period of delay as set by time-delay


74


. In an alternative embodiment, this accumulator-reset signal


66


is not disabled via latch


70


, and instead is dependent solely on the existence of the CO alarm signal


64


and the actuation of button


18


.




With attention now on the portion of the microcontroller's logic related to the smoke detector,

FIG. 9

illustrates that the test mode of operation indicated by signal


76


may be entered after the button


18


has been held longer than a time-delay


78


if the detector is not in an alarm condition as indicated by the absence of signal


80


. That is, AND gate


84


generates the test signal


76


when the push button


18


is held for longer than the preset time-delay


78


when the detector is not in an alarm condition. As illustrated in this

FIG. 9

, the smoke chamber analog-to-digital input is processed by control block


82


, which compares the input digital count against various preset alarm limits used therein. Signal


80


indicates that the smoke chamber output voltage is below the alarm threshold


38


, and output signal


86


indicates that the smoke chamber output voltage is below the hush threshold. This control block


82


implements digital hysteresis by utilizing thresholds slightly higher than thresholds


38


and


40


to reset the alarm and hush conditions once those conditions have been set. The amount of digital hysteresis employed is dependent on the sensitivity and resolution of the sensing circuitry


30


, the amplification circuitry


34


, and the resolution of the analog-to-digital converter


62


, as well as on the user specifications.




The hush mode of operation is indicated by signal


88


, which is the latched output of latch


90


whose reset conditions


92


override its set conditions


94


. By having the reset conditions


92


override the set conditions


94


of latch


90


, the normal alarm mode providing early indication to the user of a hazardous condition will be entered if both the reset and set conditions are true at the same point. This provides an additional safety feature of the control logic of the instant invention. To generate the set conditions


94


, AND gate


96


requires that the button


18


be depressed, that the smoke chamber output voltage be below the alarm threshold but above the hush threshold, and that the system is not currently already in the hush mode of operation prior to the button push. This control logic may reset the hush condition via OR gate


98


after the expiration of time-delay


100


, upon actuation of the user button while in the hush mode as calculated by AND gate


102


, as soon as the smoke chamber voltage rises above the alarm threshold, or as soon as the output of the smoke chamber drops below the hush threshold. As will be recognized, each of these four conditions for disabling the hush mode of operation are illustrated in

FIGS. 3

,


5


,


6


, and


4


, respectively.




While

FIG. 9

illustrates a control-logic diagram illustrating the control logic used by the microcontroller


12


to intelligently control the system mode of operation upon detection of the user-actuated switch


18


, one skilled in the art will recognize that this control logic may be coded in different fashions utilizing algorithms which vary from the exact structure of the logic illustrated in

FIG. 9

, but which results in system operation as illustrated

FIGS. 3-8

. Therefore, it must be recognized that the control logic of

FIG. 9

is presented by way of illustration, and not by way of limitation.




The foregoing description of various preferred embodiments of the invention has been presented for purposes of illustration and description. It is not intended to be exhaustive or to limit the invention to the precise forms disclosed. Obvious modifications or variations are possible in light of the above teachings. The embodiments discussed were chosen and described to provide the best illustration of the principles of the invention and its practical application to thereby enable one of ordinary skill in the art to utilize the invention in various embodiments and with various modifications as are suited to the particular use contemplated. All such modifications and variations are within the scope of the invention as determined by the appended claims when interpreted in accordance with the breadth to which they are fairly, legally, and equitably entitled.



Claims
  • 1. A hazardous condition detector, comprising:a smoke chamber positioned to sense an atmospheric condition, the smoke chamber generating an output indicative of an amount of smoke sensed therein; a user-actuated switch; an alarm circuit; a microcontroller coupled to receive the output of the smoke chamber and the switch, and further operably coupled to the alarm circuit for controlling generation of an alarm therefrom, the microcontroller having an alarm threshold and a hush threshold stored therein, and being operable to place the detector in an alarm mode when the output from the smoke chamber drops below the alarm threshold, in a hush mode upon sensing actuation of the switch when in the alarm mode and when the output of the smoke chamber is above the hush threshold, and in a test mode upon sensing actuation of the switch when not in the alarm mode and not in the hush mode.
  • 2. The detector of claim 1, wherein the microcontroller is further operable in the hush mode to place the detector in the alarm mode upon expiration of a time delay.
  • 3. The detector of claim 1, wherein the microcontroller is further operable in the hush mode to place the detector in the alarm mode when the output from the smoke chamber drops below the hush threshold.
  • 4. The detector of claim 3, wherein the microcontroller is further operable to maintain the detector in the alarm mode until the output from the smoke chamber rises above the alarm threshold.
  • 5. The detector of claim 1, wherein the microcontroller is further operable in the hush mode to place the detector in the alarm mode upon sensing actuation of the switch.
  • 6. The detector of claim 1, wherein the microcontroller is further operable in the hush mode to place the detector in a normal mode when the output from the smoke chamber rises above the alarm threshold.
  • 7. The detector of claim 1, wherein the microcontroller commands the alarm circuit to generate no alarm in the hush mode.
  • 8. The detector of claim 1, wherein the microcontroller commands the alarm circuit to generate an alarm of substantially reduced volume in the hush mode as compared to the alarm mode.
  • 9. The detector of claim 8, wherein the alarm of substantially reduced volume is less than 10 dB.
  • 10. The detector of claim 8, wherein the alarm of substantially reduced volume is approximately 5 dB.
  • 11. The detector of claim 1, wherein the alarm circuit produces tone and voice synthesized messages, and wherein the alarm circuit produces a voice synthesized announcement upon entering and exiting hush mode.
  • 12. The detector of claim 1, further comprising a visual alert circuit, and wherein the microcontroller is operable to command the visual alert circuit to provide separate visual indications for the alarm mode and the hush mode.
  • 13. The detector of claim 1, further comprising a carbon monoxide detector positioned to sense an atmospheric condition, wherein the carbon monoxide detector provides information indicative of an amount of carbon monoxide sensed thereby, and wherein the microcontroller accumulates the information to determine a carbon monoxide alarm condition, the microcontroller resetting the accumulation of the information upon sensing actuation of the switch when in the carbon monoxide alarm condition.
  • 14. A hazardous condition detector, comprising:a carbon monoxide detector circuit positioned to sense an atmospheric condition, the carbon monoxide detector circuit operable to produce an output indicative of the amount of carbon monoxide detected thereby; a smoke chamber positioned to sense an atmospheric condition, the smoke chamber operable to generate an output indicative of an amount of smoke sensed therein; an alarm circuit; a microcontroller coupled to receive the output of the carbon monoxide detector circuit and the output of the smoke chamber, and operably coupled to the alarm circuit, the microcontroller having an alarm threshold and a hush threshold stored therein, and being operable to place the detector in a smoke alarm mode commanding the alarm circuit to generate an alarm when the output of the smoke chamber descends below the alarm threshold stored therein, and in a carbon monoxide alarm mode when an accumulation of the output of the carbon monoxide detector circuit exceeds an accumulation threshold stored within the microcontroller.
  • 15. The detector of claim 14, further comprising an user-actuated switch, the microcontroller controlling an operating mode of the detector based on a current operating mode upon sensing actuation of the switch.
  • 16. The detector of claim 15, wherein the microcontroller places the detector in a hush mode upon sensing actuation of the switch when in the alarm mode and when the output of the smoke chamber is above a hush threshold.
  • 17. The detector of claim 16, wherein the microcontroller places the detector in a test mode upon sensing actuation of the switch when not in the alarm mode and not in the hush mode.
  • 18. The detector claim 16, wherein the microcontroller places the detector in the alarm mode upon expiration of a time delay after initiation of the hush mode.
  • 19. The detector of claim 16, wherein the microcontroller places the detector in the alarm mode when the output from the smoke chamber drops below the hush threshold when in the hush mode.
  • 20. The detector of claim 19, wherein the microcontroller is further operable to maintain the detector in the alarm mode until the output from the smoke chamber rises above the alarm threshold.
  • 21. The detector of claim 16, wherein the microcontroller places the detector in the alarm mode upon sensing actuation of the switch when in the hush mode.
  • 22. The detector of claim 16, wherein the microcontroller places the detector in a normal mode when the output from the smoke chamber rises above the alarm threshold.
  • 23. The detector of claim 15, wherein the microcontroller resets the accumulation of carbon monoxide information upon actuation of the switch when in the carbon monoxide alarm mode.
  • 24. The detector of claim 15, wherein the microcontroller places the detector in a test mode upon actuation of the switch when in a normal mode.
  • 25. The detector of claim 16, wherein the microcontroller commands the alarm circuit to generate no alarm in the hush mode.
  • 26. The detector of claim 16, wherein the microcontroller commands the alarm circuit to generate an audible alarm of substantially reduced volume in the hush mode as compared to the alarm mode.
  • 27. The detector of claim 26, wherein the audible alarm of substantially reduced volume is less than 10 dB.
  • 28. The detector of claim 26, wherein the audible alarm of substantially reduced volume is approximately 5 dB.
  • 29. The detector of claim 14, wherein the alarm circuit produces tone and voice synthesized messages, and wherein the alarm circuit produces a voice synthesized announcement upon entering and exiting a hush mode.
  • 30. The detector of claim 14, further comprising a visual alert circuit, and wherein the microcontroller is operable to command the visual alert circuit to provide separate visual indications for the alarm mode and the hush mode.
  • 31. A smoke detector, comprising:a smoke chamber positioned to sense an atmospheric condition, the smoke chamber generating an output indicative of an amount of smoke sensed therein; an alarm circuit; a microcontroller coupled to receive the output of the smoke chamber, and further operably coupled to the alarm circuit for controlling generation of an alarm therefrom, the microcontroller having an alarm threshold stored therein, and being operable to place the detector in an alarm mode when the output from the smoke chamber drops below the alarm threshold, said microcontroller further having an alarm off threshold stored therein, and being operable to place the detector in a no alarm mode when the output from the smoke chamber rises above the alarm off threshold when in the alarm mode.
  • 32. The smoke detector of claim 31, further comprising:a user actuatable switch having an output coupled to the microcontroller; and wherein said microcontroller contains a hush threshold stored therein, said microcontroller operable to place the detector in a hush mode upon sensing actuation of the switch when in the alarm mode and when the output of the smoke chamber is above the hush threshold.
  • 33. The smoke detector of claim 31, further comprising:a user actuatable switch having an output coupled to the microcontroller; and wherein said microcontroller places the detector in a test mode upon sensing actuation of the switch when not in the alarm mode.
  • 34. The smoke detector of claim 31, further comprising:a user actuatable device having an output coupled to the microcontroller; and wherein said microcontroller contains a hush threshold stored therein, said microcontroller operable to place the detector in a hush mode upon sensing actuation of the switch when in the alarm mode and when the output of the smoke chamber is above the hush threshold, the microcontroller further operable to place the detector in a test mode upon sensing actuation of the switch when not in the alarm mode and not in the hush mode.
  • 35. A hazardous condition detector, comprising:a detector circuit positioned to sense an atmospheric condition, the detector circuit generating an output indicative of the condition sensed; a user-actuated switch; an alarm circuit; and a microcontroller coupled to receive the output of the detector circuit and the switch, and further operably coupled to the alarm circuit for controlling generation of an alarm therefrom, the microcontroller having a first value and a second value stored therein; wherein the microcontroller is operable to place the detector in an alarm mode when the output from the detector circuit drops below the first value, and in a hush mode upon sensing actuation of the switch when in alarm mode and when the output of the detector circuit is above the second value.
  • 36. A hazardous condition detector of claim 35, further comprising an amplifier for amplifying the output of the detector circuit.
US Referenced Citations (26)
Number Name Date Kind
3909813 Scheidweiler et al. Sep 1975 A
3953844 Barr et al. Apr 1976 A
4081795 Ogawa Mar 1978 A
4097850 Conforti Jun 1978 A
4196426 Ogawa Apr 1980 A
4222046 Pinckaers et al. Sep 1980 A
4254414 Street et al. Mar 1981 A
4302753 Conforti Nov 1981 A
4313110 Subulak et al. Jan 1982 A
4316184 Nagel Feb 1982 A
4335378 Coleman Jun 1982 A
4401978 Solomon Aug 1983 A
4517555 Marsocci et al. May 1985 A
4688021 Buck et al. Aug 1987 A
4788530 Bernier Nov 1988 A
4792797 Tanguay et al. Dec 1988 A
4814748 Todd Mar 1989 A
4975684 Guttinger et al. Dec 1990 A
RE33920 Tanguay et al. May 1992 E
5422629 Minnis Jun 1995 A
5428964 Lobdell Jul 1995 A
5726634 Hess et al. Mar 1998 A
5801633 Soni Sep 1998 A
5990797 Zlotchenko et al. Nov 1999 A
6346880 Schroeder et al. Feb 2002 B1
6426703 Johnston et al. Jul 2002 B1