1. Field of the Disclosure
This disclosure relates to beverage cooling systems. More particularly, this disclosure relates to a modular beverage cooling system having modules that are independently removable from and connectable to the remainder of the main assembly.
2. Description of Related Art
A conventional beverage cooler contains all the major refrigeration components, such as compressor and evaporator, integrally within a single cooler carcass. The refrigeration system is configured so that the evaporator is contained in a waterbath and the other refrigeration components are situated in an area commonly referred to as the “fridge compartment”. The evaporator is hermetically connected to the other refrigeration components most commonly by rigid copper or stainless steel pipework, via permanent or semi-permanent soldered or brazed joints. Therefore, the fridge compartment and waterbath are essentially inseparable in service, other than by a service person skilled and trained in the art of refrigeration, and having all the necessary specialist equipment to safely carry out the operation. In almost all instances, in the event of a failure in the refrigeration system, such as a micro-leak of refrigerant, or a compressor failure, the entire beverage cooler must be disconnected from the installation, and replaced. In many instances, this may be a major and expensive operation, requiring at least two service engineers and a complete replacement beverage cooler.
Further with a conventional beverage cooler, the cooling capacity is determined by the size, or displacement of the compressor. It is not possible to increase the cooling capacity of an installed beverage cooler. So, if a conventional cooler is correctly sized to suit a trading account at the time of installation, it may not have sufficient capacity to accommodate a significant increase in drinks sales in a future changing market. It does not make financial sense, both from an acquisition cost or energy consumption perspective, to install over-sized coolers where sales do not warrant it at the time of installation. Likewise, a long-term downturn in sales could leave an end user with a cooler that is over-sized for the prevailing market, incurring higher than necessary energy costs and wasted capacity. The preferred solution in both circumstances may be to replace the existing cooler with an alternative cooler more appropriately sized for the new trading environment. This is a costly and disruptive operation, usually requiring two service operatives and significant downtime.
Moreover, conventional beverage coolers are designed and constructed with a specific refrigerant type included. The refrigerant type may be a customer preference, or may be dictated by environmental regulations. Once constructed and commissioned, it is unlikely that a change of refrigerant would be feasible during an individual cooler's operational lifetime. So, any change in a customer's preference, or further environmental legislation against an existing refrigerant, or even a new refrigerant entering the market with significant advantages over the current range of refrigerants could mean an entire population of beverage coolers might have to be replaced, simply to accommodate a change of refrigerant.
Additionally, the conventional beverage cooler is installed in a pre-determined space within the trading account. In many cases, this space may be unsuitable for a variety of reasons. For example, the conventional beverage cooler may be sited in a very restrictive area, where air circulation is poor; this may compromise the efficiency and performance of the conventional beverage cooler, and may result in premature component failure, high energy consumption, or repeated service calls for warm drinks. Alternatively, the conventional beverage cooler could be sited in an area where excessive heat or cold is experienced for large parts of the day; these extremes may also impact on performance, energy consumption and reliability. Little can be done to alleviate these conditions, once the conventional beverage cooler is installed and commissioned.
Further, when a conventional cooler has experienced a failure of the refrigeration system, the entire cooler must be removed from the trading account and returned to the original equipment manufacturer or an approved repair agent, irrespective of the fact that no other part of the dispense system is faulty. This leads to a situation where large coolers awaiting refrigeration repairs consume a disproportionate amount of factory space.
Accordingly, there is a need for a modular beverage cooler that has a refrigeration module, a pumping and control module, and a beverage cooling module that are independently removable from and connectable to the remainder of a main assembly. There is a further need for a modular beverage cooler that has a second cooling medium that is circulated in a cooling tank and that is cooled by a refrigeration system having a first cooling medium. There is still a further need for a modular beverage cooler that has a first refrigerant that flows into a condenser or gas cooler where the first refrigerant is cooled by a fan, and a second refrigerant that is cooled by the refrigeration system that is circulated by a pump where the pump and the fan are operated by the same motor.
A beverage cooling system is provided that includes a main assembly having a refrigeration module, a pumping and control module, and a beverage cooling module. The refrigeration module has a refrigeration system cooling a cooling medium. The beverage cooling module has a cooling tank cooled by the refrigeration system. The pumping and control module has a pump to pump a beverage ingredient cooled by the refrigeration system. Each of the refrigeration module, the pumping and control module, and beverage cooling module are independently removable from and connectable to the remainder of the main assembly.
A beverage cooling system is also provided that includes a refrigeration module having a refrigeration system cooling a first cooling medium, and a beverage cooling module connected to the refrigeration module. The beverage cooling module has a cooling tank that cools at least one beverage ingredient. The beverage cooling module has a second cooling medium cooled by the refrigeration system that is circulated in the cooling tank.
A beverage cooling system is additionally provided that includes a refrigeration system cooling a first refrigerant. The first refrigerant flows into a condenser or gas cooler where the first refrigerant is cooled by a fan. A second refrigerant is cooled by the refrigeration system that is circulated by a pump in a cooling tank to cool at least one beverage ingredient. The pump and the fan are operated by the same motor.
The above-described and other features and advantages of the present disclosure will be appreciated and understood by those skilled in the art from the following detailed description, drawings, and appended claims.
Other and further benefits, advantages and features of the present disclosure will be understood by reference to the following specification in conjunction with the accompanying drawings, in which like reference characters denote like elements of structure and:
Referring to
Referring to
Cooling housing 102 has connection receptacles 108 and latches 110 for connection to and detachment from one or both of refrigeration module 1 and pumping and control module 2.
Referring to
Referring to
Referring to
Referring back to
The second cooling medium is continuously recirculated until a predetermined temperature in tank 5 has been reached, or a predetermined amount of ice (the icebank) has formed on heat exchanger coil 6. The predetermined temperature, or predetermined amount of ice in tank 5, is measured by a temperature or resistance sensor (not shown) fixed in tank 5, which signals both refrigeration system 112 and pump 11 to operate or switch off by a controller, dependent upon the predetermined temperature, or predetermined amount of ice in tank 5 measured by the temperature or resistance sensor.
Pump 11 and fan 12 are connected to dual spindle motor 13 to drive both pump 11 and fan 12. The benefits of using dual spindle motor 13 include: 1. reduced component count; 2. reduction of the space required in refrigeration module 1; 3. increased reliability (fewer components to fail); 4. reduced assembly time; 5. improved serviceability; 6. reduced electrical wiring complexity; and 7. potential reduction in energy consumption. Alternatively, pump 11 and fan 12 would normally be powered by separate motors. In this instance, a single motor 13 is employed to operate both system elements.
Alternative arrangements of motors for pump 11 and cooling fan 12 include separate induction-type motors. The benefits of separate induction-type motors include low cost, and mass produced for a wide selection of choices available.
Another alternative arrangement of motors for pump 11 and cooling fan 12 includes separate electronically commutated motors. The benefits are separate electronically commutated motors include high reliability, low energy consumption, low heat output, the ability to control a shaft rotation speed of the motors to optimize performance for prevailing operating conditions, and low lifetime costs.
Still another alternative arrangement of motors for pump 11 and cooling fan 12 includes a dual spindle induction motor. The benefits of the dual spindle induction motor are use of a single motor to drive two separate components, compact system—space saving, relatively low cost, reduced spare parts requirement.
Still another alternative arrangement of motors for pump 11 and cooling fan 12 includes dual spindle electronically commutated motor. The benefits of the dual spindle electronically commutated motor include use of a single motor to drive two separate components, compact system—space saving, high reliability, low energy consumption, low heat output, ability to control a shaft rotation speed of the motor to optimize performance for prevailing operating conditions, reduced spare parts requirement, and low lifetime costs.
Referring to
Pumping and control module 2 also contains a programmable electronic controller 19 and a circuit board which may include, among other features, such features as intelligent diagnostics, energy management, telemetry, remote diagnostics, asset tracking and an operator interface screen.
Referring to
Referring to
Referring to
Referring to
Button 410 is used to navigate to a set outputs screen shown in
Referring back to
Next page key 410 is pressed to navigate from the temperature display screen to the status page 1 screen, status page 2 screen and status page 3 screen shown in
Next page key 410 is pressed to navigate from status page 1 screen, status page 2 screen and status page 3 screen to the change parameter screen shown in
The user presses buttons 412b and 412d to choose a parameter and buttons 412a and 412c to change values of the parameter. When buttons 412a and 412c are pressed the enter password screen is displayed. Once the password is entered, all parameters values can be changed until the change parameter screen is exited. A predetermined amount of time, for example, one minute, is allowed for password entry of the change parameters screen will automatically be displayed. If no buttons are pressed for a predetermined amount of time, for example, 3 minutes, user interface 400 will display the home screen.
Next page key 410 is pressed to navigate from the change parameter screen to the set outputs screen shown in
The home page shows faults as shown in
“To clear fault” will only be displayed if the fault can be reset by the user.
Referring to
In operation, as shown in
A reduction may be possible in beverage cooling system 10 in a weight of refrigerant used to charge refrigeration system 112, whilst maintaining the cooling output of a similar sized conventional design. In the case of the hydrocarbon refrigerant R290 (Propane), a charge limit of 150 grams is set on all refrigerating equipment in the classification “Category A Occupancies”. Beverage cooling system 10 can fall into this category, and as such is restricted to a maximum refrigerant charge of 150 grams.
There is a limiting effect on the size and cooling capacity of a conventional beverage cooler that may be designed for use with R290 refrigerant. However, replacing a conventional copper tube evaporator with a heat exchanger evaporator with heat exchanger coil 6, and compressor 8 that can be a low-volume condenser replacing the conventional condenser, a charge reduction of more than 30% (by weight) may be achieved for a similar overall cooling performance.
The size and cooling capacity of existing beverage coolers, using R290 refrigerant with a conventional evaporator and condenser, is limited to a compressor size of typically 15 cc displacement, due to the restriction on refrigerant charge weight. This gives a typical average useful cooling duty of approximately 900 watts during the icebank-building, or “recovery” phase of the refrigerant cycle.
Whereas conventional beverage coolers using R290 refrigerant are limited by the 150 grams refrigerant charge weight to a maximum compressor size of typically 15 cc displacement, the use of the heat exchanger evaporator with heat exchanger coil 6, and compressor 8 that can be a low-volume condenser (which may, for example, be a gas cooler of the type used in an R744 [CO2] refrigerant system) may permit an increase in the maximum size and capacity of an R290 beverage cooler. The larger capacity cooler might contain a compressor, for example, compressor 8, of typically up to 21 cc displacement, with a useful cooling capacity in excess of 1,200 watts, whilst remaining within the “Category A Occupancies” classification. Thus, maximum cooling capacity may be increased by typically 30% over equivalent conventional designs, whilst remaining within the 150 grams refrigerant charge limit.
In beverage cooling system 10, the conventional evaporator is replaced with a liquid heat exchanger with heat exchanger coil 6, which may be a copper or stainless steel coil, through which passes, for example, a solution of chilled anti-freeze, which may be a solution of propylene glycol. As refrigerant is no longer transported through the system into the waterbath evaporator, it is not necessary to connect the fridge compartment and waterbath with rigid semi-permanent or permanently jointed metal tubing. The transport tubing for the anti-freeze, for example, coolant transfer tubing 14, may be flexible plastic tubing, and the joints, for example, valves 106, may be of a quick-release type, for example the “John Guest Speedfit®” design. The addition of plastic isolating valves, for example, valves 106, allows the waterbath-based heat exchanger with heat exchanger coil 6 to be isolated from the supply system, thereby permitting the waterbath in tank 5 and refrigeration module 1 to be quickly and easily separated. Refrigeration module 1 can be removed and replaced using one trained operative, who is not necessarily skilled in the art of refrigeration. This may be done independently of the rest of beverage cooling system 10, minimizing the cost of the service call and replacement parts, and the downtime and loss of sales incurred by the end user.
Beverage cooling system 10 has the advantage that a single service operative may quickly and easily replace refrigeration module 1 for one more appropriate to the demand, with no downtime to the end user whatsoever. Likewise, beverage cooling module 3 also be easily exchanged for one with a greater or smaller capacity icebank, with minimal downtime, by a single service operative.
Beverage cooling system 10 permits a change in refrigerant to be accommodated with virtually no disruption to the end user, and at minimal service cost. Refrigeration module 1 may be disconnected from the remainder of beverage cooling system 10, and a replacement for refrigeration module 1 containing the new refrigerant may simply be connected, by a single service operative, to the remainder of beverage cooling system 10 via the quick release/connect fittings, without the need to exchange complete coolers or melt-back and re-produce icebanks.
Beverage cooling system 10 may allow refrigeration module 1 to be disconnected and sited remotely from the remainder of beverage cooling system 10, in an area more suited to its requirements for optimum performance. Flexible insulated tubes would transport the secondary coolant to and from beverage cooling module 3, with electrical extension wires providing a link to refrigeration controls and power source.
Beverage cooling system 10 allows just the failed module of refrigeration module 1, pumping and control module 2, and beverage cooling module 3 to be removed from the remainder of the main assembly of beverage cooling system 10 and returned, thus saving a substantial amount of factory space, or permitting a higher volume of parts awaiting repair to be stored in the available space.
The present invention having been thus described with particular reference to the preferred forms thereof, it will be obvious that various changes and modifications may be made therein without departing from the spirit and scope of the present invention as defined in the appended claims.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/US2014/036987 | 5/6/2014 | WO | 00 |