The various features, advantages and other uses of the present heating and cooling control apparatus will become more apparent by referring to the following detailed description and drawings in which:
In addition to the drawings above, this description describes multiple aspects of a removed and relocated thermostat system as illustrated in the above referenced drawings. However, there is no intent to limit this disclosure to a single aspect onto the multiple aspects that are disclosed herein. On the contrary, the intent is to cover multiple alternatives, modifications, and equivalents included within the spirit and scope of this disclosure and as defined by the appended claims.
This disclosure describes several means for relocating an otherwise fixed thermostat location for a heating, ventilating, and cooling system (HVAC system). The apparatus allows an individual to relocate the central thermostatic control of a heating or cooling system to a room or location different from that where it was originally located in the structure. In some cases, the current location of the thermostatic control system is not desirous due to it being in a hot or cold zone of the structure. In one aspect, the Move-a-Thermostat apparatus consists of a receiver that is mounted in the location of the current thermostat and connected to the control wire that leads to the heating and cooling devices. Additionally, there is a transmitting thermostat that includes the main temperature selection control. This apparatus interacts with the receiver by hardwire or wireless means. This apparatus is illustrated in
In another aspect, the apparatus provides for two transmitting thermostats to be located one in a typically warm room and one in a typically cold room. Both thermostats transmit to the single receiver which is to be placed in the location of the original, removed and replaced thermostat. The receiver allows the user to select one thermostat (room) or the other or to select both. If the user selects both, he/she is able to provide priority to one or the other by means of a dial or switch. This may also be administered by a programmable receiver unit. This apparatus is illustrated in
In another aspect, the apparatus provides for three or more transmitting thermostats to be located in any or all of the rooms of the environment. All of the thermostats transmit to the single receiver which is to be placed in the location of the original, removed and replaced thermostat. The receiver allows the user to select one, any two, or all of the thermostats to be active. If the user selects more than one, he/she can assign priority to each thermostat by means of a dial or switch. An algorithm determines whether heating or cooling should be called for. This may also be administered by a programmable receiver unit. This apparatus is illustrated in
Throughout the following description the term “room” will be understood to have its conventional meaning as well as to encompass an area or zone covering one or more rooms whose temperature is being controlled.
The thermostat 11 may actually embody an existing type of thermostat with appropriate dials, digital display and pushbuttons with the addition of a transmitter for wireless operation and a processor which is capable of providing digital binary data to the transmitter specifying the set temperature and the sensed or existing temperature so as to create a demand or trigger signal for heating or cooling for the room. The processor or control circuitry mounted within the thermostat housing may also provide a thermostat I.D. to prevent miscommunication with other wireless devices in the room or other thermostats, as described hereafter, which may transmit temperature-related data to the single receiver 12. The processor or control circuitry is capable of arranging the temperature-related digital data in the proper order or packet format required for a particular wireless or hardwired communication protocol.
The thermostat housing is capable of being mounted by various means, such as mechanical hangers or fasteners, double-backed tape, adhesive, etc., to a wall surface to enable the thermostat 11 to be located on any wall surface in a room and then moved to a different location if accurate temperature readings are not obtained.
If the receiver 12 receives a signal from the remote thermostat 11 to call for heating/cooling, the receiver 12 or a signal generator in the receiver 16 generates the appropriate signal and transmits this signal to the furnace/air conditioner 16 through the original wires that the old, removed and replaced thermostat used. If the remote thermostat 11 communicates to the receiver 12 by wireless means 13, there are many known to those skilled in the art and include, but are not limited to, Bluetooth technology, RF communication, and infrared transmission.
In terms of transmission of data, this system works in the same way that the single thermostat system does except that the transmitting thermostats 21, 22 transmit not only the binary data for need for heating/cooling but also: 1) the actual temperature of its environment (T), and 2) the set and desired temperature (S). The receiver 27 receives this data and applies a logic sequence and algorithm to determine whether heating or cooling should be called for.
The priority dial 32 may be rotatable over a pre-set output range of values or magnitudes, such as 0.1 to 1.0 units over an approximate 300° range of rotation. Full left rotation of the priority dial 32 can cause the priority dial or associated circuitry, such as a potentiometer, to generate an appropriate signal equal to a low-priority i.e.; “0.1”, while a full rightward rotation of the priority dial 32 can generate a high-priority output i.e., “1.0”, for the selected hot room or cold room.
For example, when both the hot room and cold room buttons 30 and 31 are selected, the priority dial 32 may be rotated to the full right-most position to indicate 100% priority for the hot room control with respect to the cold room control. Alternately, one of the rooms, such as the hot room, for example, may be selected by the setting of the priority dial 32 as a percentage of the full range of motion or output magnitude of the priority dial 32, i.e., 75% with the related magnitude or value being (25%) provided as the priority of the cold room. For example, with the priority dial 32 set at 75% towards the hot room thermostat settings and output receive priority over the related cold room settings on a factor of 3:1.
Further, separate priority dials 32 may be provided for each of the hot room and the cold room to provide individual priority settings between 0% and 100%.
The priority dial 32 allows the user to determine which thermostat 21 or 22 takes precedence and by how much it does so. Also in this scenario, steps 110 and 111 of
Th=Hot Room Temperature
Tc=Cold Room Temperature
Sh=Hot Room Set Temperature
Sc=Cold Room Set Temperature
TRh=Trigger Hot Room Thermostat (1=call for heat, 0=not calling for heat)
TRc=Trigger Cold Room Thermostat (1=call for heat, 0=not calling for heat)
PD=Setting on the priority dial (0.1-1.0, 0.1 for cold/1 for hot)
Δh=Sh−Th
Δc=Sc−Tc
IF (TRh=1 AND TRc=1) THEN Trigger for Heating, ELSE - - -
IF (TRh=0 AND TRc=0) THEN No Trigger, ELSE - - -
IF (Δh≧0 AND Δh≧PD*Δc) THEN, Trigger for Heating, ELSE - - -
IF (Δh<0 AND |Δh|≧Δc/PD) THEN, Trigger for Heating, ELSE No Trigger.
Similarly, one version of the algorithm for cooling mode 210 is as follows:
IF (TRh=1 AND TRc=1) THEN Trigger for Cooling, ELSE - - -
IF (TRh=0 AND TRc=0) THEN No Trigger, ELSE - - -
IF (Δh≦0 AND Δh≦PD*Δc) THEN, Trigger for Cooling, ELSE - - -
IF (Δh>0 AND Δh≧|Δc|/PD) THEN, Trigger for Cooling, ELSE No Trigger
Those skilled in the art of programming such devices understand that these algorithms and logic are just one version or example and describe a linear relationship between the position of the priority dial 32 and the outcome of the algorithm. Many other versions are possible including, but not limited to, non-linear relationships, such as logarithmic, exponential, quadratic and others.
Alternatively, the user may decide to select two or more thermostats to be active. In this scenario, priority dials 47, 48, or 49 become active. The priority dials 47, 48, 49 allow the user to determine which thermostat 41, 42, or 43 takes precedence and by how much it does so. The priority dials 47, 48 and 49 operate in the same manner as the priority dial 32 in that each is rotatable over a maximum range of rotation, such as 300° and by itself or in combination with suitable circuitry, generates an output signal ranging between 0.1% for a full left rotation of any of the dials 47, 48, and 49 up to 100% of maximum output value at a full right rotation position of any of the dials, 47, 48 and 49, by example.
In this manner, any one or any combination of two or all of the priority dials 47, 48, and 49 may be made active when any one or combination of two or all three of the room buttons 44, 45, and 46 are depressed. Any of the dials 47, 48, and 49 can be set by the user at position corresponding to an output value between 0 and 100 to determine the priority of control provided by the associated thermostat.
Also in this scenario, steps 306 and 307 of
Definitions same as above
PS=Priority Setting
PD1=Priority Dial Setting Thermostat 1 (1-100)
PD2−Priority Dial Setting Thermostat 2 (1-100)
PD3=Priority Dial Setting Thermostat 3 (1-100)
PD
1
=PD
1
+PD
2
+PD
3
PS
1=(PD1/PDt)*100 (for purposes of simplifying the algorithm, this is assigned to the PS of the highest value)
PS
2=(PD2/PDt)*100 (as above, this is assigned to the PS with the middle value)
PS
3=(PD3/PDt)*100 (as above, this is assigned to the PS with the lowest value)
F
1
=PS
2
/PS
1
F
2
=PS
3
/PS
1
F
2
=PS
3
/PS
2
IF (TR1=1 AND TR2=1 AND TR3=1) THEN Trigger for Heating, ELSE - - - IF (TR1=0 AND TR2=0 AND TR3=0) THEN No Trigger, ELSE - - -
IF (Δ1≧0 AND Δ2≧0 AND (Δ1≧F1*Δ2 OR Δ1≧F2*Δ3 OR Δ2≧3*Δ3) THEN, Trigger for Heating, ELSE - - -
IF (Δ1<0 AND Δ2<0 AND (|Δ1|≧Δ2/F1 OR |Δ1|≧Δ3/F2 OR |Δ2|≧Δ3/F3) THEN, Trigger for Heating, ELSE No Trigger.
Similarly one version of the algorithm for cooling mode 406, is the following:
IF (TR1=1 AND TR2=1 AND TR3=1) THEN Trigger for Cooling, ELSE - - -
IF (TR1=0 AND TR2=0 AND TR3=0) THEN No Trigger, ELSE - - -
IF (Δ1≦0 AND Δ2≦0 AND (Δ1=F1*Δ2 OR Δ1≦F2*Δ3 OR Δ2≦F3*Δ3) THEN, Trigger for Cooling, ELSE - - -
IF (Δ1>0 AND Δ2<0 AND (Δ1≧|A2|/F1 OR Δ1≧|Δ3|/F2 OR Δ2≧Δ3/F3) THEN, Trigger for Cooling, ELSE No Trigger.
Those skilled in the art of programming such devices understand that these algorithms and logic are just one version or example and describe a linear relationship between the position of the priority dials 47, 48 and 49 and the outcome of the algorithm. Many other versions are possible including, but not limited to, non-linear relationships, such as logarithmic, exponential, quadratic and others.
This application claims the benefit of priority of provisional patent application Ser. No. 60/819,566 filed on Jul. 10, 2006, the entire contents of which are incorporated herein.
Number | Date | Country | |
---|---|---|---|
60819566 | Jul 2006 | US |