This invention relates to improvements in process control systems.
Petrochemical processing systems typically locate a number of devices in the field remote from the computer control room. Thus, sensors such as temperature and pressure gauges are mounted to processing equipment in the field. Likewise, actuators, such as valve controllers and pumps, are located in the field. These devices generally respond to digital transmission over a wired-bus system connected to one or more computers located in the control room of the petrochemical processing plant. The bus system connects the control room equipment with a twisted pair trunk cable. The field devices are connected with spur cables to the trunk by a wire terminal block in the field junction box. All of the devices are electrically parallel with the trunk cable. The cable carries power to the attached devices and a power conditioner separates the power supply from the signals on the wiring.
There are a number of problems associated with the bus configuration that can prevent it from operating and disrupt the process being controlled. For example, since the devices are connected in parallel, a short circuit in any of the devices, or in the spur cables connecting them to the trunk, short circuits the entire bus. Another point of potential failure is the power supply and associated power conditioners.
While the potential failure points can often be minimized, to do so requires additional equipment, e.g., short circuit protection circuitry at the junction box, redundant power supply and redundant power conditioner.
Yet another single point of failure is the trunk cable itself. If the trunk cable is damaged, the network's operation fails. There are no known systems available in the prior art that eliminate this single point of failure.
There are other problems associated with a bus network used for process control. Some of the devices connected to the network may be in hazardous areas that have surrounding atmospheres containing gases or vapors that can ignite or explode. Special precautions must be used in these areas. One requirement is that the power to a device in a hazardous area must be limited. Hence, the power supplied to the fieldbus network must be limited. This limits the number of devices that can be connected to the network.
There are a number of considerations that must be observed for a bus network. The trunk cable length is limited by the voltage drop that is caused by the resistance of the wires. This limitation depends on the power each device draws from the network. Spur cable lengths are typically less than 120 meters so that the signals on the network are not overly distorted. These considerations require care and expertise in designing the network.
A process control system utilizes a hub network to connect devices in the field to control room equipment. Embodiments include redundant spur cables so that if a spur cable connecting the control room with the remote devices is disabled, this will not disrupt communication or control of the remote devices located in its field. The power for operating the remote devices is brought directly to the devices and not sent over the wires from the control room. All of the spurs between the hub and the field instruments and actuators limit the voltage and current levels so as to be intrinsically safe within hazardous areas.
In one embodiment described, the power conditioning function of the prior art is eliminated by use of repeaters.
In one embodiment described, a short or failure in a remote device or its spur cables will not adversely affect the rest of the system operation,
In one embodiment described, the spur cables are connected to the hub by resistors which simultaneously (a) protects the hub's delivery of power to the other spur cables if a spur short circuits, (b) limits the power from the hub to the spur for Intrinsinc Safety (IS) purposes, and (c) provides series termination for the signals on the spur cable.
In petrochemical processing, a plant is operated in the following way: Sensors, such as temperature and pressure gauges, are located in the field with the processing equipment. There are also actuators, such a valve controllers and pumps, in the field. The sensors and the actuators communicate with each other and with computers located in the control room that operates the plant.
In the prior art system shown in
A twisted wire pair trunk cable 20 connects the control room equipment 25 with a number of devices 30, 31, 32 and 33 in the field. Examples of devices 30-31 include instruments for measuring temperatures or pressure and actuators such as remotely activated valves and pumps. The wires in the trunk cable 20 are typically in a shielded cable to reduce noise ingress (shield not shown). The field devices 30-33 are respectively connected with spur cables 40, 41, 42 and 43 to the trunk by a wire terminal block 50 in a field junction box. All the devices are electrically parallel with the trunk cable 20. A terminator (T) 60 is needed at each end of the trunk cable to allow the twisted pair of cable 20 to carry digital signals. Since the cable 20 carries power to the attached devices, a power conditioner (C) 70 is needed to separate a conventional constant voltage power supply (P) 75 from the signals on the wiring. This type of a network configuration is called a bus.
Fieldbus devices signal by consuming a variable amount of current from the spur cable. For example, a quiescent fieldbus device draws 20 mA current from the network. When the device signals, it draws alternately between 10 and 30 mA. Thus, the peak-to-peak signaling current is 20 mA. In the bus configuration of
There are several disadvantages associated with the bus configuration of
By way of specific example, since all the devices 30-33 are connected to the wires in parallel, a short circuit in any of the devices, or in the spur cables 40-43 connecting them to the trunk cable 20, short circuits the entire bus, unless an additional short circuit protection circuit is included at the junction box where the spur cable attaches to the trunk cable.
Another disadvantage of the bus configuration of
Yet another single point of failure is the trunk cable 20 itself. If the trunk cable 20 is damaged, the network's operation fails.
There are other problems associated with a bus network used for process control. Some of the devices connected to the network may be in hazardous areas that have surrounding atmospheres containing gases or vapors that can ignite or explode. Special precautions must be used in these areas. One requirement is that the power to a device in a hazardous area must be limited. Hence, the power supplied to the fieldbus network must be limited. This limits the number of devices that can be connected to the network.
There are a number of considerations that must be observed for the prior art bus network. The trunk cable length is limited by the voltage drop that is caused by the resistance of the wires. This limitation depends on the power each device draws from the network. Spur cable lengths are typically less than 120 meters so that the signals on the network are not overly distorted. These considerations require care and expertise in designing the prior art networks.
The novel process control network illustrated in
The components of the hub network 100 are shown in
Internal to each spur circuit 210, 211 is a repeater circuit (shown in
While two spur circuits 210, 211 are shown, many spur circuits will typically be used in a hub 100 as needed for the number of remote devices in this field.
The hub 100 advantageously provides Intrinsic Safety (IS) protection for hazardous areas that have explosive atmospheres. The IS technique prevents the equipment used in these hazardous areas from igniting the atmosphere. IS requires that the electrical power sent into the hazardous area be limited. This is achieved by galvanically isolating the electrical power coming from non-hazardous areas and limiting the voltage and current that can be sent into the hazardous area. Galvanic isolation is further described in the Fieldbus Wiring Guide published by Relcom, Inc. These requirements are defined by international standards. Equipment used in hazardous areas is certified by various agencies to meet these requirements.
Referring to
As described below, the IS resistor 310 limits the current that can be drawn by equipment in the hazardous area.
The hub's power supply shown in
The current limiting resistors enable a fail-safe system since if any of the remote devices 30, 31, 32 or 33 short circuits its associated spur cable 40, 41, 42 and 43, the current limited resistors limit the current to the faulty device and do not adversely affect operation of any of the other remotely connected devices.
Repeaters 225, 226 are respectively coupled to transmitters (T) 320, 321 that send signals to the spur and to receivers (R) 325, 326 that receive signals from the spur. These transmitters and receivers are also connected to the spur wires through resistors 350, 351, 352, 353, 354, 355, 356 and 357. These resistors are relatively high in value and do not affect the IS considerations of the circuit. Thus, in case a transmitter or receiver fails, the power to the spur is limited.
Resistors 310, 311, 312 and 313, have a dual function and eliminate the necessity of the prior art terminators 60 shown in
In an alternate embodiment, the resistors connecting a spur cable to the power bus 205 such as resistors 310, 311 can be combined into a single resistor used on either the positive or negative lead of the spur cable. Thus, as shown in
Thus, in the embodiments of
The hub 100 also provides a way to test the devices and spur cables. If a repeater does not receive the periodically expected signal from its spur cable, its corresponding device is either malfunctioning or the spur cable is open circuited. If the voltage at the output of the spur circuit is lower than expected, the device or the spur cable is shorted.
A circuit can be used to detect if either of the wires is shorted to the cable shield. This is not a critical error but reduces the noise immunity of the cable. These error conditions are advantageously indicated by a light on the spur circuit to aid in locating the problem. The error condition is also indicated electrically on the common alarm bus in the hub.
The hub's alarm circuit monitors the alarm bus 400 and the condition of the power supply. When the alarm circuit senses problems, it uses a standard fieldbus message to send the error condition over the network:
One device on the network is designated as the Link Active Scheduler, or LAS 500 as shown in
The alarm circuit 390 in the hub acts as a fieldbus device. When it receives a Token, it sends its alarm status message over the network. It then sends a Return Token message that indicates that it is finished using the network. The alarm message is received by another device on the network that takes the appropriate action.
These message transactions on the network are defined in fieldbus standards.
Several of the benefits of the hub topology can be summarized as follows: There is no trunk cable that can be disabled. If any spur cable is shorted, only the device attached to that spur is affected. The rest of the network continues to function normally. Redundant spur cables can be used to connect the hub in the field with the control room equipment and eliminate a trunk power carrying cable thus eliminating a single point of failure. Power to each device is provided from the hub. This eliminates all power and bus voltage calculations that are needed for the bus topology fieldbus simplifying network design. There is no separate power conditioning circuit like that required for the bus configuration fieldbus. All spurs between the hub and devices are intrinsically safe. There is no limit to the number of IS devices that can be on the network. No explicit current limiters are needed for the spur cables. The IS resistors limit the current each spur can draw. The spurs between the hub and the fieldbus device can be long. This eliminates the spur length limitation of the bus topology fieldbus. No explicit terminators are needed. A terminator is part of the spur circuit. Data transmission between the hub and each device is point-to-point. There are no distortions associated with the trunk-and-spur arrangement of the bus topology fieldbus. The hub can include a fieldbus device to send messages about wiring errors or status of the hub.
All the devices 30, 31, 32, and 33 connected to the hub 100, including the computers in the control room, communicate with each other in the same way as they would on the prior art bus configuration network of
The above presents a description of the best mode contemplated for carrying out the systems and methods for networks for process control in such full, clear, concise, and exact terms as to enable any person skilled in the art to which it pertains to make and use these systems and methods. These systems and methods are, however, susceptible to modifications and alternate constructions from that discussed above that are fully equivalent. Consequently, these systems and methods are not limited to the particular embodiments disclosed. On the contrary, these systems and methods cover all modifications and alternate constructions coming within the spirit and scope of the present invention.
This application claims priority under 35 U.S.C. § 119(e) to U.S. Provisional Application Ser. No. 60/650,909 filed on Feb. 8, 2005, the entire content of which is hereby incorporated by reference.
Number | Date | Country | |
---|---|---|---|
60650909 | Feb 2005 | US |