The present invention relates to a performance diagnosis device and a performance diagnosis method for an air conditioner.
As a device for cooling a relatively large space such as various factories and buildings, a heat-driven chiller or an electric chiller is used. Since the primary energy consumption of the chiller accounts for about 20% to 30% of the entire building, promotion of energy saving has been particularly required in recent years.
Generally, the chiller controls a cooling output according to a required cooling load, and the output changes in a complicated manner, such as high output during the midsummer period of July and August, and low output during the middle period such as May and October.
Further, since it is assumed that a chiller is used for a long period of time, it is important not only to select high-efficiency equipment at the time of installation but also to maintain system performance after aging for energy saving. The above-mentioned chiller has a water circuit that carries cold heat from the chiller to the space to be cooled, and a cooling water circuit that radiates heat to the chiller and heat of the space to be cooled. Scale adheres to pipes over time, and the device itself is deteriorated. In order to maintain a predetermined system performance, it is necessary to eliminate the performance degradation by regular maintenance.
PTL 1 discloses a chiller deterioration diagnosis device and a chiller deterioration diagnosis method for the purpose of accurately separating tube cleaning and overhaul as maintenance contents to be performed for performance deterioration of a chiller. In the technique, an evaluation actual COP and an evaluation actual LTD indicating actual performance under an evaluation operating condition based on evaluation operating situation data are calculated, a COP change amount indicating a difference between the evaluation actual COP and an evaluation reference COP and an LTD change amount indicating a difference between the evaluation actual LTD and an evaluation reference LTD are calculated, and it is determined whether a change amount ratio R between the COP change amount and the LTD change amount at an evaluation time is within a predetermined determination region Q. Here, LTD is an abbreviation of Leaving Temperature Difference, which is one of the indexes indicating the cooling efficiency of a chiller. PTL 1 also describes a reference COP estimation model represented as a band-shaped curved surface in a three-dimensional space.
PTL 1: JP 2016-205640 A
Since the comfort of a building to be cooled or heated (air conditioning) is significantly impaired during midsummer when the cooling load is large, or midwinter when the heating load is large, it is desirable that a period when performance degradation will occur be predicted and maintenance that involves shutting down the air conditioner be performed in spring and autumn when the air conditioning load is less. Of course, when only the cooling operation is performed without performing the heating operation, the cooling operation may be performed during no load such as in the winter.
In addition, a performance diagnostic system that detects an abnormality before it interferes with operation and outputs a signal requesting maintenance takes into account dimensional errors of each device, differences in installation conditions, and differences in operating conditions and operating situations for more accurate diagnosis.
Regarding the creation of a reference COP estimation model used for diagnosing deterioration of a chiller, PTL 1 describes that it is possible to generally use chiller operating situation data obtained before the evaluation time.
However, the reference COP estimation model described in PTL 1 is an estimation model composed of model input data and a reference COP indicating reference performance before deterioration obtained from the chiller, and the reference COP is a COP indicating the performance obtained from a new chiller or a chiller immediately after overhaul. Therefore, if the chiller is not new, a desired operation may not be possible until an event requiring overhaul occurs.
Further, while the chiller (air conditioner) is used for a long period of time, the system configuration itself may be changed from the initial installation due to a change in heat load of the space to be cooled or maintenance. In such a case, the plurality of learned relational expressions do not hold, and there is a possibility that the sign cannot be captured from the change in data.
An object of the invention is to provide a deterioration diagnosis technology that can update unique reference values that reflect the dimensional errors of each device, differences in installation conditions, and differences in operating conditions to appropriate values with respect to the deterioration of the performance of air conditioners.
A performance diagnosis device of an air conditioner of the invention includes a data collection unit that collects and records operation data of the air conditioner, and a model database that is a data group indicating performance corresponding to each operating condition of an air conditioner. Further, the performance diagnosis device includes a reference data creation unit that uses the operation data and the model database to obtain reference data that is a combination of a plurality of operating conditions and a reference value, a performance evaluation unit that compares the reference data and evaluation data that is operation data to be evaluated, and evaluates the performance of the air conditioner, and a reference data update unit that compares the reference data and the evaluation data when the operating conditions match with each other, and updates the reference data in a predetermined case.
According to this invention, it is possible to provide a deterioration diagnosis technology that can update unique reference values that reflect the dimensional errors of each device, differences in installation conditions, and differences in operating conditions to appropriate values with respect to the deterioration of the performance of air conditioners.
A performance diagnosis device and a performance diagnosis method for an air conditioner of the invention are suitable as a technology for monitoring an air conditioner from a remote place.
In the following description, a cooling operation of a chiller is mainly described. However, in the case of a heat pump capable of performing not only the cooling operation but also the heating operation, it is necessary to consider an air conditioning load including a cooling load and a heating load. This specification discloses a technique applicable to a case where only the cooling operation is performed and a case where both the cooling operation and the heating operation are performed. Chillers, heat pumps, and the like are collectively referred to as “air conditioners”. An air conditioning load rate described later means a load rate of the air conditioner that performs at least one of the cooling operation and the heating operation.
The air conditioner may be any of an electric type and a heat driven type.
An electric air conditioner includes an electric compressor. On the other hand, examples of the heat-driven air conditioner include an absorption chiller, an absorption heat pump, an adsorption chiller, and an adsorption heat pump. The heat source of the heat-driven air conditioner is combustion heat of gas, petroleum, etc., and factory exhaust heat.
Hereinafter, a performance diagnosis device and a performance diagnosis method of an air conditioner (chiller) according to an embodiment of the invention will be described in detail with reference to the drawings.
First, the configuration of the performance diagnosis device of
A performance evaluation device 1 of a chiller 2 (hereinafter also referred to as “performance diagnosis device”) is connected to the chiller 2 via an operation data monitor 3 (display unit) and an operation data collection unit 4 that is a transmitter. The operation data acquired by the operation data collection unit 4 includes a signal from a sensor provided in the chiller 2, and includes raw data obtained from the chiller 2 that is actually operating. The operation data collection unit 4 has a function of measuring data corresponding to a desired evaluation parameter via a sensor provided in the chiller 2, and a function of recording the measured time-series data as history data. In this embodiment, the configuration in which the operation data transmission unit is provided outside the performance evaluation device 1 will be described, but the operation data transmission unit may be provided inside the performance evaluation device 1.
In this embodiment, a turbo chiller is assumed as the chiller 2, and details of its configuration will be described later with reference to
The performance evaluation device 1 includes a main memory device 10 (first memory unit), a sub memory device 11 (second memory unit), an interface 12, a CPU 13 (central processing unit), an input device 14 (input unit), and an output device 15 (output unit) to diagnose a change in performance of the chiller 2. The main memory device 10 includes a reference data creation unit 10A, an evaluation data collection unit 10B, a system performance evaluation unit 10C (performance evaluation unit), a reference data update unit 10D, and an output unit 10E. The first memory unit and the second memory unit can be simply referred to as a “memory unit”.
The sub memory device 11 stores a model database.
The turbo chiller mainly forms a refrigerant circuit by sequentially connecting a turbo compressor 21 which obtains power from an electric motor 20, a condenser 22, an expansion mechanism 23, and an evaporator 24 using a refrigerant pipe.
As measurement sensors, a chilled water inlet temperature sensor 24b, a chilled water outlet temperature sensor 24c, a cooling water inlet temperature sensor 22b, a cooling water outlet temperature sensor 22c, a chilled water flow meter 24a, and a cooling water flow meter 22a are provided at various locations.
In the evaporator 24, chilled water is generated such that the temperature measured by the chilled water outlet temperature sensor 24c becomes a predetermined value. The chilled water is sent to a cooled space 27 (such as a room in a building) by the power of a water circulation pump 28, and absorbs heat from the cooled space 27. The chilled water whose temperature has increased due to heat absorption exchanges heat with the refrigerant in the evaporator 24 and is cooled. Then, the refrigerant in the evaporator 24 is carried to the condenser 22 through the refrigerant pipe, and radiates heat to the cooling water. The cooling water is sent to a cooling tower 26 by a water circulation pump 25. In the cooling tower 26, a cooling tower fan 26a is controlled so that the temperature measured by the cooling water inlet temperature sensor 22b becomes a predetermined value, and the heat of the cooling water is radiated to the atmosphere.
The device configuration and operation of the chiller illustrated in
The reference data creation unit 10A of
The model database of this embodiment is a data group covering operating conditions that satisfy the specifications of the chiller. The model database is a data group indicating the performance corresponding to each operating condition of the air conditioner, and may be compiled from the results of the performed quality confirmation test measured using a testing machine before shipment to be included in the design values of chillers and catalogs issued by chiller manufacturers. A COP (Coefficient of Performance) equivalent to the system performance of the chiller changes depending on the air conditioning load rater, cooling water inlet temperature, and chilled water outlet temperature. However, in this drawing, the chilled water outlet temperature is fixed, and the air conditioning load rate (hereinafter, also simply referred to as “load rate”), the COP, and the cooling water inlet temperature are used as evaluation parameters and are arranged in three axes of an X axis, a Y axis, and a Z axis.
As illustrated in this drawing, when the load rates are equal, the COP is higher under the condition where the cooling water inlet temperature is low (spring, autumn, and winter). On the other hand, the COP is low under conditions where the cooling water inlet temperature is high (summer).
The evaluation target of this embodiment is a water-cooled chiller, but in an air-cooled chiller that does not require cooling water, the ambient air temperature of the condenser may be used as an evaluation parameter instead of the cooling water inlet temperature.
Here, the air conditioning load rate is a value obtained by dividing the amount of heat to be processed in the indoor unit by the rated capacity of the air conditioning. When cooling water is cooled by an evaporator in the cooling operation and supplied to the indoor unit, the air conditioning load rate is a value obtained by dividing the difference between the chilled water outlet temperature and the chilled water inlet temperature of the actually operating chiller by the difference between the chilled water outlet temperature and the chilled water inlet temperature which are set as design values of the chiller. Specifically, in
Generally, in the case of a compression chiller (heat pump), it is possible to perform a heating operation using heat generated in a condenser. In this case, when the hot water is heated by the condenser and supplied to the indoor unit, the air conditioning load rate is a value obtained by dividing the difference between a hot water outlet temperature and a hot water inlet temperature of the actually operating heat pump by the difference between the hot water inlet temperature and the hot water outlet temperature which are set as the design values of the heat pump. When the heating operation by the compression chiller (heat pump) is performed using air as a heat medium circulating between the indoor unit and the condenser, the temperatures of the air on the upstream and downstream sides of the condenser are measured. Then, the air conditioning load rate is calculated as the inlet temperature and the outlet temperature by the same calculation as in the case of hot water.
In the case of the heating operation in the absorption heat pump, the hot water is heated by heat generated in at least one of the condenser and an absorber, and the hot water is sent to the indoor unit to perform heating. Therefore, the air conditioning load rate is a value obtained by dividing an average value of the difference between the hot water outlet temperature and the hot water inlet temperature of the absorption heat pump actually operating, for the hot water returned from the indoor unit, by the difference between the hot water outlet temperature and the hot water inlet temperature that are set as the design values of the absorption heat pump.
By the way, the system performance of an actual chiller generally does not match the model database due to the influence of the installation status and the like, even in a state where the system performance in the initial stage of installation does not deteriorate. In this embodiment, in order to accurately grasp the system performance in a state where there is no deterioration for each device, a part of the data stored in the operation data collection unit 4 is used to correct the model database so as to create unique reference data (combination data group of operating conditions and reference values; hereinafter, also referred to as “individual characteristic surface”) of the chiller 2.
Most of the causes of deterioration of the system performance of the chiller arise due to the adhesion of scale or the like to the inside of the heat transfer tube for cooling water or chilled water. In the heat transfer tube, minerals and the like in the water crystallize due to heating and evaporation of the circulating water, and these are deposited to form scale.
From
Therefore, the reference data creation unit 10A illustrated in
Therefore, the system performance evaluation unit 10C compares the operation data measured after acquiring the normal data (operation data at a time different from the normal data) with the individual characteristic surface to evaluate the performance of the air conditioner. Further, the operation data to be compared may include the normal data.
As described above, the corrected reference data is obtained based on the actual operation data acquired for each model, so that a slight performance deterioration of the chiller 2 can be detected.
Hereinafter, a method for creating the individual characteristic surface in the above-described reference data creation unit 10A will be described with reference to
First, in S100, the evaluation parameter input from the input device 14 is obtained, and the normal data is obtained from the operation data collection unit 4. In this embodiment, the evaluation parameters are the load rate, the COP, and the cooling water inlet temperature.
Here, the load rate is a ratio of the difference between the chilled water inlet temperature sensor 24b and the chilled water outlet temperature sensor 24c in the actual operation data to the difference between the chilled water inlet temperature and the chilled water outlet temperature that is the maximum in the model data. The COP is a value obtained by dividing the value obtained by multiplying the difference between the temperatures, obtained by the chilled water outlet temperature sensor 24c and the chilled water inlet temperature sensor 24b, by the measurement value of the chilled water flow meter 24a, by the power consumed by the electric motor 20 which is the power source of the turbo compressor 21. The cooling water inlet temperature is a value measured by the cooling water inlet temperature sensor 22b.
Next, in S101, in order to evaluate the system performance, the normal data is classified for each operating condition, with a load rate other than the COP and the cooling water inlet temperature corresponding to the system performance of the chiller 2 in the evaluation parameters as operating conditions.
Subsequently, in S102, a model database is obtained from the sub memory device 11. Then, in S103, a correction coefficient for matching the normal data and the model data is calculated for each operating condition. Although there is no normal data depending on the operating condition of the chiller 2, interpolation or extrapolation of the correction coefficient of a portion where the operating condition matches is performed, and the correction coefficient is calculated in the entire operating range in the model database. By calculating the correction coefficient in this manner, even when the normal data obtained from the chillers (actually installed chillers) installed in different conditions is less, the correction coefficient in the entire operating range corresponding to the normal data can be calculated.
Finally, in S104, each piece of data in the model database is multiplied by a corresponding correction coefficient for each operating condition to create an individual characteristic surface which is a system performance without deterioration of the chiller 2 actually installed. This data is not only a data group similar to the model database, but also the load rate of the evaluation parameter, the COP, and the cooling water inlet temperature are output from the output unit 10E of the main memory device 10 as a three-dimensional graph with three axes of X axis, Y axis, and Z axis, and displayed in the operation data monitor 3 through the output device 15.
As illustrated in this drawing, when the cooling water inlet temperature is low and the load rate is high, the COP is high. On the other hand, when the cooling water inlet temperature is high and the load rate is low, the COP is low.
The evaluation parameters may be configured by items corresponding to the performance and operating conditions of the chiller, and can be appropriately changed by a measurement sensor installed in the chiller to be evaluated.
As described above, the individual characteristic surface obtained from the model database and the normal data of the chiller different from the test chiller installed in the building to be actually air-conditioned can be used as correct approximate data of a chiller as a reference in the entire operating range. The individual characteristic surface is reference data in the entire operating range in consideration of the installation state including the arrangement of the piping of the chiller, the inclination of the apparatus, and the like, and the installation state of measurement sensors and the like slightly different for each apparatus. Further, the model database is complete with data groups in all areas of the required load rate and evaluation parameters calculated from the data groups. These data groups also include data under operating conditions with a low load rate, and may be design values of chillers and data accurately measured before shipment using a test chiller (test machine).
Case 1 corresponds to
The evaluation parameters X and Z illustrated in
Further, the number of evaluation parameters serving as external factors affecting the performance of the air conditioner may be three or more.
In summary, the individual characteristic surface includes two or more evaluation parameters (operating conditions) that are external factors affecting the performance of the air conditioner, and the two or more evaluation parameters are arranged in relation to another evaluation parameter (an index of performance evaluation).
In the case of an absorption chiller, as an evaluation parameter that is an external factor affecting the performance of the air conditioner, the cooling water for removing heat generated in at least one of the absorber and the condenser or the inlet temperature of the cooling air may be used. The evaluation parameter serving as an index for performance evaluation may be the amount of heat input to a regenerator.
Further, the evaluation parameter serving as an external factor affecting the performance of the air conditioner may be a function related to the air conditioning load rate.
Further, an LTD may be used as an evaluation parameter. In this case, the LTD is treated as Y.
Next, a method for evaluating system performance according to this embodiment will be described.
First, in S110, evaluation target data is acquired from the operation data collection unit 4. The evaluation target data is operation data of the chiller 2 (
Next, in S111, the evaluation target data is classified for each operating condition. This operating condition is made to match the evaluation parameter of the operating condition of the individual characteristic surface, and in this embodiment, is the cooling water inlet temperature. After that, in S112, the operating condition with the highest appearance frequency (the most frequent operating condition) in the classified evaluation target data is extracted. Here, the most frequent operating condition is the load rate with the highest appearance frequency in this embodiment. In addition, when the operating condition for classifying the evaluation target data in S111 is a load rate, the most frequent operating condition is the cooling water inlet temperature with the highest appearance frequency.
Further, in S113, the COP is calculated from the evaluation target data in the load rate with a high appearance frequency extracted for each cooling water inlet temperature condition, and is used as representative evaluation data. Then, an average value of the evaluation target data is calculated. As the representative evaluation data, the power consumption used in Cases 2 and 3 of
On the other hand, in S114, the individual characteristic surface created by the reference data creation unit 10A is acquired.
Then, in S115, data that matches the operating condition of the representative evaluation data is extracted from the individual characteristic surface, and is set as a reference value. Therefore, the reference value is a value of the individual characteristic surface (the value of the Y axis (COP) in
In S116, the representative evaluation data of S113 (representative evaluation data of the evaluation data) is compared with the reference value of S115 (the reference value of the reference data). Specifically, the deviation of the evaluation target data from the normal data is calculated. The result and the unique reference data are accumulated in the system performance evaluation unit 10C each time the evaluation is performed, and the degree of deterioration is evaluated from the change in the system performance with respect to the elapsed time. In other words, the system performance evaluation unit 10C has a function of accumulating the unique reference data and the result obtained by comparing the operation data collected at a plurality of different times with the unique reference data, and determines a change in performance of the air conditioner using these values.
Finally, in S117, the data is output from the output unit 10E of the main memory device 10 and displayed on the operation data monitor 3 via the output device 15.
Next, a method for updating the reference data update unit according to this embodiment will be described. The reference data update unit 10D of
First, in S201, an individual characteristic surface is acquired from the reference data creation unit 10A, and evaluation data that is a part of the operation data of the operation data collection unit 4 is collected from the evaluation data collection unit 10B.
Thereafter, in S202, the acquired evaluation data is compared with the operating condition of the individual characteristic surface. Since the individual characteristic surface, which is the reference data of this embodiment, is a data group of the system performance in a state where there is no deterioration in the entire expected operating range of the chiller 2, the reference data in this embodiment has the operating condition of the evaluation data. Therefore, in S202, it is determined that the operating conditions match, and the process proceeds to step S203. The case where the operating conditions do not match in S202 will be described later in a second embodiment.
In S203, the performance of the reference data and the performance of the evaluation data under the same operating conditions are compared. Here, the performance can be compared with the COP (which may be a predicted value of the COP). If the performance of the reference data is superior to or equal to the performance of the evaluation data, the process proceeds to S204, and a deviation of the evaluation target data from the reference data is calculated as an evaluation result. On the other hand, if the performance of the reference data is inferior to the performance of the evaluation data, the reference data is updated based on the value of the evaluation data (S207). That is, as illustrated in the data processing (
The updated new reference data is used again in S203 for performance comparison. However, since the same data is compared here, the process proceeds to S204, and the deviation of the evaluation target data from the reference data is calculated as an evaluation result. This result is accumulated in the system performance evaluation unit 10C every time the evaluation is performed, and the degree of deterioration is evaluated from the change in the system performance with respect to the elapsed time. Further, the system performance evaluation unit 10C accumulates not only the deviation but also an update history (update time and value) of the reference data.
These results are output from the output unit 10E of the main memory device 10 and displayed on the operation data monitor 3 via the output device 15.
The above deviation is calculated from a narrow range of evaluation target data within a specified period, but since the correction coefficient corresponding to the normal data is obtained for the entire region of the unique reference data, it is possible to perform a trial calculation on how much the annual power consumption increases and how much the running cost increases when the chiller is continuously operated without performing the maintenance. This can provide the user with persuasive data on the need for maintenance.
Specifically, using the operation data acquired in spring, fall, winter, and the like when the air conditioning load rate is low, the evaluation parameters in a range of all the operating conditions including the operating condition with the high air conditioning load rate can be estimated by the correction coefficient. Therefore, the current degree of performance degradation can be determined in consideration of annual power consumption, running costs, and the like.
More specifically, based on the maximum value of the air conditioning load rate at the time when the air conditioning load rate becomes high (in the case of a chiller, generally in the summer season), the air conditioning load rate is a ratio to the maximum value. For example, a rate collected during a period (in the case of a chiller, spring, fall, winter, etc.) when the rate is 50% or less is used to calculate an estimated value of the operation data in the region where the ratio exceeds 50%, and the estimated value and the individual characteristic surface data may be compared. The estimated power may be used to calculate annual power consumption, running cost, and the like. The current degree of performance degradation can be determined in consideration of annual power consumption, running costs, and the like. The above determination may be made using data collected at a time when the above ratio is 30% or less.
In addition, the performance evaluation device 1 of this embodiment has a function of updating the reference value even in a case where, for example, an introduction timing of the performance evaluation device 1 is delayed with respect to the start of operation of the chiller, and the data collection unit cannot obtain operation data immediately after the operation of the chiller to be evaluated, that is, a case where there is a possibility that deterioration is included in the normal data. Therefore, the reference data finally created by the reference data creation unit can be set to an ideal value having no deterioration while reflecting a dimensional error of each device, a difference in an installation state, and a difference in an operating condition and an operating situation. As a result, a highly accurate deterioration diagnosis technique can be provided.
Furthermore, when the reference data is updated, the reference data before the update and the new reference data are written together and displayed on the operation data monitor 3 via the output device 15, thereby improving the performance after the maintenance, and easily confirming the frequency of maintenance of the chiller. Therefore, it makes it easy for the user to set a maintenance plan.
In this drawing, the description is made on the assumption that the maintenance is required and the evaluation is performed at a COP reduction rate of 25%. The chiller 2 began collecting data in April 2005. The performance was reduced by 25% or more in July 2005 with respect to the COP compared to the reference value as of April 2005. Therefore, the maintenance was performed as of August 2005. Subsequently, when measurement was performed in August 2005, the performance was superior to the reference value. Therefore, the performance was newly evaluated using the performance in August 2005 as the reference value. From September 2005 to January 2006, the COP declined moderately, indicating that no maintenance was required at this point.
In this drawing, data for each month is illustrated, but the invention is not limited to this. For example, data for each week may be acquired, and the necessity of maintenance may be determined using the data.
As a result, small changes in individual chillers can be accurately and frequently acquired, and deterioration can be determined at an early stage.
In addition, by illustrating the previous reference value together with the updated new reference value, it is easy for users to understand the effect of improving the performance of the chiller by the maintenance, and to plan the time for the next maintenance in advance.
In addition, based on the maximum value of the air conditioning load rate at the time when the air conditioning load rate becomes high (in the case of a chiller, generally in the midsummer), in the case of a chiller, the air conditioning load rate becomes generally 50% or less (half of less) with respect to the maximum value during the periods of spring, fall, and winter. In such periods, performance evaluation using the operation data collected at that time makes it possible to perform maintenance that involves shutting down the air conditioner without significantly impairing the comfort inside the building, as necessary. More preferably, the above ratio is 30% or less.
According to the performance evaluation device of this embodiment, the following effects are obtained.
First, by creating individual characteristic surfaces for air conditioners with different initial system performances even for the same model depending on the installation location and operating conditions, the system performance without deterioration is obtained in the entire expected operating range. Therefore, the degree of deterioration can be diagnosed using the system performance in the condition without deterioration under the same operating conditions as the evaluation target data as the reference value, and the deterioration of the system performance of the air conditioner can be detected in a short period of time. In other words, performance deterioration of the air conditioner can be detected more quickly.
With the function of updating the reference value, even if the reference data created at the time of starting the data collection contains deterioration, ultimately, a value without deterioration to which a dimensional error of each device, a different in the installation state, a difference in the operating condition and the operating situation are reflected can be set as a reference value. Therefore, a more accurate chiller deterioration diagnosis technique can be provided.
In addition, despite the fact that deterioration detection is performed with high accuracy, the number of measurement sensors is small, and the introduction cost can be reduced.
The performance diagnosis can be performed in accordance with the operating conditions of the evaluation target data, regardless of the operating conditions of the air conditioner. For this reason, the performance deterioration can be detected at a time when the cooling load is low, and as a result, it is possible to perform the maintenance involving stopping the operation of the air conditioner without impairing the comfort in the building.
The performance diagnosis device for this embodiment has the same configuration as the device described in the first embodiment, but is applied to a diagnostic method that detects an abnormality when the deviation is large, with a change amount of evaluation data with respect to normal data as a deviation.
Specifically, the performance diagnosis device of this embodiment is different from the first embodiment in the content of the model database stored in the sub memory device 11 illustrated in the block diagram of
First, in the reference data creation unit 10A of this embodiment, for example, data for the first one year in the operation data stored in the operation data collection unit 4 is assumed to be data containing no deterioration, and all the data is set as the reference data (hereinafter referred to as “learning data”). The learning data includes not only raw data of the sensors collected by the operation data collection unit 4 but also calculated values using the raw data.
Next, a method for evaluating system performance according to this embodiment will be described.
First, in S120, the evaluation target data is acquired from the operation data collection unit 4. Next, in S121, the evaluation target data is classified for each operating condition. This operating condition is the cooling water inlet temperature in this embodiment. The operating conditions need only to be non-dependent on the performance of the chiller, and may be, for example, a load rate.
Meanwhile, in S122, learning data is acquired from the reference data creation unit 10A. Subsequently, the process proceeds to S123, where the operating conditions of the learning data and the evaluation data are compared. If the operating conditions are the same, the process proceeds to S124, where the deviation of the evaluation target data with respect to the learning data is calculated for each of the retained pieces of data, and the total sum is used as the evaluation result. Finally, the evaluation result is output from the output unit 10E of the main memory device 10 and displayed on the operation data monitor 3 via the output device 15 in S125.
On the other hand, if the operating conditions are different, the process proceeds to S126, where the reference data update unit 10D adds the learning data. This corresponds to S206 of the flowchart (
First, in S220, evaluation target data is acquired from the operation data collection unit 4, and learning data is acquired from the reference data creation unit 10A. Next, in S221, data that does not match the operating conditions of the learning data is extracted from the evaluation target data.
At the same time, in S222, a model database is acquired from the sub memory device 11. In the model database of this embodiment, a relational expression representing the relationship between the load rate and the COP is stored for each cooling water inlet temperature condition. In S223, based on these relational expressions and the learning data, a predicted value of the COP under operating conditions not included in the learning data in the evaluation target data is calculated. Here, the predicted value may be calculated by an interpolation method or an extrapolation method using the above relational expression or the like. Thus, under any operating condition, if there is a predicted value such as the COP above the individual characteristic surface as illustrated in
Subsequently, in S224, the predicted value is compared with the evaluation data. If the evaluation data is superior, the process proceeds to S225, where the evaluation data is added to the learning data.
On the other hand, if the learning data is superior to the evaluation data in S224, the process proceeds to S226, and it is determined that the learning data is not changed.
The evaluation data processed by the reference data update unit 10D is returned to the system performance evaluation unit 10C again, regardless of whether the learning data is added, and is provided for processing.
According to the performance evaluation device of this embodiment, the following effects are obtained.
First, the deviation of the evaluation target data with respect to the learning data is calculated for all sensor data and calculated values, and the total sum is used as the evaluation target, so that the change in performance can be evaluated in multiple aspects compared to a detection method in which one of the changes in performance such as the COP is monitored. Therefore, it is possible to detect an abnormality of the chiller at an earlier stage.
In addition, with a configuration that updates the learning data, it is possible to prevent erroneous detection due to mere differences in operating conditions, and learning data is accumulated as the operating time elapses, enabling more accurate sign detection.
Further, performance can be easily evaluated even under operating conditions different from the maximum load condition, so that occurrence of errors due to data conversion or the like can be suppressed.
Number | Date | Country | Kind |
---|---|---|---|
2017-220648 | Nov 2017 | JP | national |
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/JP2018/033175 | 9/7/2018 | WO | 00 |