The invention relates generally to the control of power flow in electric power transmission lines, and more particularly to power flow dispatch strategies for optimizing power transfer.
Flexible Alternating Current Transmission Systems (FACTS) are used for the dynamic control of voltage, impedance and phase angle of high voltage alternating current (ac) electrical power transmission lines. Since the concept of FACTS was introduced, a family of power electronic equipment has emerged for controlling and optimizing the flow of electrical power in electrical power transmission lines. This equipment makes use of large rating (4500 V to 6000 V, 4000 A to 6000A) gate turn-off thyristors (GTOs) in high power inverter configurations that can be controlled to behave as three-phase sinusoidal voltage sources. FACTS controllers are operated synchronously with the transmission line and can be connected either in parallel, producing controllable shunt reactive current for voltage regulation, or in series with the line, for controlling the flow of power directly. The family of FACTS controllers includes the Static Synchronous Compensator (STATCOM), the Synchronous Series Compensator (SSSC), the Unified Power Flow Controller (UPFC), the Interline Power Flow Controller (IPFC), and the Generalized Unified Power Flow Controller (GUPFC). The basic theory behind the UPFC is described in L. Gyugyi, et al., “The Unified Power Flow Controller: A New Approach to Power Transmission Control,” IEEE Transactions on Power Delivery, vol. 10, pp. 1085-0193, 1995. The basic theories behind the IPFC and the GUPFC can be found in, respectively, S. Zelingher et al., “Convertible Static Compensator Project—Hardware Overview,” Proc. IEEE Winter Power Meeting, vol. 4, pp. 2511-2517, 2000, and B. Fardanesh et al., “Multi-Converter FACTS Devices: The Generalized Unified Power Flow Controller (GUPFC),” Proc. IEEE Winter Power Meeting, vol. 4, pp. 2511-2517, 2000.
For Voltage-Sourced Converter (VSC) based FACTS controllers, a maximum power transfer typically occurs when the controller is operated at its rated capacity (e.g., maximum current, voltage, or MVA rating). For STATCOM and SSSC devices, power transfer at rated capacities can be achieved by relaxing certain operating parameters or setpoints to ensure reliable power transfer. For UPFC, IPFC and GUPFC devices, however, a reliable power transfer at rated capacities is more complex because of the ability of these controllers to circulate active power.
One problem with operating a FACTS device at its rated capacity is the heightened risk of voltage collapse. Voltage collapse occurs when a power controller attempts to serve more load than the output voltage of the controller can support. Thus, a FACTS device operating at its rated capacity should provide maximum power transfer, while avoiding voltage collapse, i.e., maintain voltage stability.
Accordingly, what is needed is a power dispatch strategy for enabling a FACTS device to provide maximum power transfer and voltage stability, while operating at or below its rated capacity. Such a dispatch strategy should be easily integrated into existing FACTS designs, including without limitation UPFC, IPFC and GUPFC designs.
The disclosed embodiments overcome the deficiencies of conventional systems and methods by providing a power flow controller responsive to power circulation demand for optimizing power transfer in a power network. When a power flow controller operates at its rated capacity, the coupled voltage-sourced converters in the power flow controller can no longer regulate from-bus voltage setpoints, line power flow setpoints, or both. In such cases, the power flow controller switches to a power circulation setpoint control without exceeding the rated capacities of the voltage-sourced converters. By replacing a number of control variables having complex interactions with a single circulating power control variable, the role of a power system operator in selecting a power dispatch strategy is greatly simplified, thus resulting in a dispatch strategy that is more efficient and less prone to human error than conventional dispatch strategies, where the system operator may have to specify multiple control variables in real-time under post-contingency conditions.
In some embodiments, a power flow controller includes a controller responsive to a circulating power demand. A first voltage-sourced converter is coupled to the controller and adapted to be coupled to a transmission line. The first voltage-sourced converter is configured by the controller to control power flow in the transmission line.
In some embodiments the power flow controller includes a second voltage-sourced converter coupled to the first voltage-sourced converter via a direct current link and adapted to be coupled to the transmission line. The second voltage-sourced converter is also configured by the power controller to control power flow in the transmission line.
In some embodiments, a method of controlling power flow in a transmission line using a power flow controller operated at rated capacity includes: determining if a power flow controller coupled to the transmission line is operating at rated capacity; determining a circulating power demand in response to the power flow controller operating at rated capacity; and configuring the power flow controller based on the circulating power demand to control power flow in the transmission line.
In some embodiments, the circulating power demand is efficiently computed in a Newton-Raphson (NR) algorithm based on an injected series voltage model, which takes into account various constraint equations that govern the operation of coupled VSCs at or below their rated respective capacities.
Overview of UPFC Architecture
While the following description is based on a UPFC architecture, the disclosed embodiments can be extended to other types of FACTS devices having two or more coupled VSCs, including without limitation IPFC and GUPFC devices.
The series VSC 108 provides the primary function of the UPFC system 100 by injecting a voltage {right arrow over (V)}m2 with controllable magnitude Vm2 and phase angle in series with the transmission line 116 via the series transformer 102. The injected voltage {right arrow over (V)}m2 acts essentially as a synchronous ac voltage source. The transmission line 116 current {right arrow over (I)} flows through this voltage source resulting in reactive and real power exchange between the voltage source and the ac system. The reactive power flow Q exchanged at the terminal of the series transformer 102 is generated internally by the series VSC 108. The real power flow P exchanged at the terminal of the series transformer 102 is converted into dc power, which appears at the dc link as a positive or negative real power demand.
The shunt VSC 106 supplies or absorbs the real power flow P demanded by the series VSC 108 at the dc link to support a real power exchange resulting from series voltage injections into the transmission line 116 by the series VSC 108. The dc link power demand of the series VSC 108 is converted back to ac by the shunt VSC 106 and coupled to the transmission line 116 via the shunt transformer 104. In addition to the real power need of the series VSC 108, the shunt VSC 106 can also generate or absorb controllable reactive power flow Q to provide independent shunt reactive compensation for the transmission line 116.
In some embodiments, the shunt and series VSCs 104, 108, each include a number of asymmetric turn-off devices, such as Gate Turn-off Thyristors (GTOs) with a parallel diode connected in reverse. In other embodiments, the turn-off devices are Insulated Gate Bipolar Transistors (IGBTs), which typically have a parallel reverse diode built in as part of a complete integrated device suitable for VSCs. The basic operation of a VSC is to generate ac voltage from dc voltage by alternately closing and opening the turn-off devices in accordance with an appropriate gate pattern logic.
The controller 110 includes shunt converter controls 112 and series converter controls 114 for controlling the shunt and series VSCs 106, 108, respectively. The shunt converter controls 112 and the series converter controls 114 receive as inputs various measured parameters and power regulation parameters (e.g., setpoints), which are used to generate injection voltages and phase angles in accordance with a circulation power desired dispatch strategy, as described more fully with respect to
UPFC Load Flow Model
[{right arrow over (V)}1{right arrow over (V)}2. . . {right arrow over (V)}N{right arrow over (V)}m1{right arrow over (V)}m2]T, (1)
where {right arrow over (V)}i=Viεjθ
By coupling the dc capacitors of the VSCs, a power flow controller can operate with the flexibility of circulating active power Pc between two VSCs. For the power flow controller model in
Because the net active power generation by the two coupled VSCs is zero, neglecting power losses, the loadflow equations are as follows:
where Pd and Qd are the desired line active and reactive powers, respectively, flowing into Bus 2 (i.e., the to-bus) and V1d is the desired voltage magnitude at Bus 1 (i.e., the from-bus). Equations (3) are generally valid for a UPFC operating at below its rated capacity.
Newton-Raphson Algorithm
In some embodiments, a solution to the loadflow equations (3) can be determined using a fast converging Newton-Raphson (NR) algorithm with an extended Jacobian matrix to include the sensitivities of the VSC control variables. For example, in an N-bus power network with Ng generators and a UPFC, the loadflow equations can be formulated as N−1 equations fP for the active power bus injections P, N-Ng equations fQ for the reactive power bus injections Q, and four VSC equations FVSC of setpoints and power circulation equations (3). The equations can be represented mathematically as:
fP(ν)=P (4a)
fQ(ν)=Q (4b)
fVSC(ν)=R (4c)
where R=[V1dPdQd0] and ν=[V1 . . . VNθ1 . . . θNVm1Vm2 α1α2]T is a 2(N+2)−Ng−1 vector variable of bus voltage magnitudes and angles, with Ng generator bus voltage magnitudes and the angle of the swing bus removed, and injected VSC voltage magnitudes and angles.
To apply the NR algorithm, starting from the solution νl at the lth iteration, the updated solution is:
νl+1=νl+βΔνl, (5)
where β is a scalar step size to facilitate the convergence, and Δνl is solved from
J(νl)Δνl=ΔS, (6)
with ΔS being the mismatch vector and the Jacobian matrix given by,
Thus, NR algorithm equations (5) through (7) can be readily built into an existing conventional NR algorithm, such as is described in C. R. Fuerte-Esquivel et al., “A Comprehensive Newton-Raphson UPFC Model for the Quadratic Power Flow Solution of Practical Power Networks,” IEEE Transaction on Power Systems, vol. 15, pp. 102-109, 2000, which article is incorporated by reference herein. For large data sets, sparse factorization techniques can be used to achieve an efficient solution. Because the NR algorithm updates all the variables in ν simultaneously, it achieves quadratic convergence when the iteration is close to the solution point.
An important step in the NR algorithm is the selection of initial conditions for the UPFC system 100. Based on the initial From-Bus and To-Bus voltages V1 and V2, equations (3) can be used to initialize the voltages {right arrow over (V)}m1 and {right arrow over (V)}m2.
UPFC Operating Limits
There are a number of practical operating limits that need to be imposed on a UPFC, which are important when assessing its impact on maximum power transfer capability. The following is a list of the limits, where the subscripts max and min denote maximum and minimum values, respectively.
1. Shunt VSC current:
|Ish|≦Ish max (8)
2. Shunt VSC voltage magnitude:
Vm1≦Vm1 max (9)
3. Shunt VSC MVA rating:
|Ssh|≦Ssh max, (10)
where Ssh is the complex power injected into the UPFC from-bus (Bus 1) by the shunt VSC 104.
4. Series VSC voltage magnitude:
Vm2≦Vm2 max, (11)
5. Line current through series VSC:
|Ise|≦Ise max, (12)
6. Series VSC MVA rating:
|Sse|≦Sse max, (13)
7. Maximum and minimum line-side voltages of the UPFC:
Vmin≦V2|≦Vmax, (14)
8. Real power transfer between the series and shunt VSCs:
|Psh|,|Pse|≦Pc max. (15)
The above limits are included in the NR loadflow program, but are enforced when it is determined that the UPFC is operating at one or more of the limits. When any one of the limits is reached, some setpoints for the UPFC cannot be regulated. For example, if the MVA rating of the shunt VSC 106 is reached, it can no longer keep the from-bus voltage V1 at the desired setpoint V1d. Thus, when the UPFC is operating at one or more of the limits described above, equations (3) can be replaced by limit constraint equations, as described in detail below.
Circulation Power Dispatch Strategy
For a power flow controller operated at or below its rated capacity, a common strategy is to specify three desired setpoints: the desired from-bus voltage V1d and the desired line active and reactive power flow Pd and Qd, respectively, as determined by the loadflow equations (3). Power system planners and operators can readily provide proper values of the setpoints V1d and Pd. Although the reactive power flow Qd affects the voltages at the to-bus, and any buses connected to the to-bus, the specification of the desired line reactive power flow Qd is not always obvious. Further, the circulating power Pc typically comes as a by-product of the Qd specification and is not specified directly.
As stated previously, when a power flow controller is operated at any of its limits, one or more of the setpoints V1d, Pd, and Qd can no longer be enforced. Instead of arbitrarily discarding one of these equations, a circulation power Pc can be specified when capacity saturation takes place. Using the MVA rating, current magnitude limit, and injected voltage magnitude limit as examples, some exemplary setpoints and constraints used in the dispatch strategy are summarized in Table I. When the shunt VSC saturates, the circulation power Pc and one of the limits Ssh max, Ish max, or Vm1 max are enforced as appropriate. Similarly, when the series VSC saturates, the circulation power Pc and one of the limits Sse max, Ise max, or Vm2 max are enforced.
For example, suppose the MVA rating of the series VSC 108 is reached and at least one of the equations (3b) and (3c) cannot be enforced. In this scenariou, Equation (3b) can be replaced by the limit equation:
{square root}{square root over (Pse2+Qse2)}=Sse max, (16)
where Qse is the reactive power injected into the line by the series VSC 108, given by
Additionally, equations (3c) and (3d) can be replaced by:
Psh=−Pc, (18)
Pse=Pc, (19)
so that the desired circulating power Pc is specified.
On the other hand, if the shunt VSC 106 reaches its MVA rating, then Equation (3a) can be replaced by the following limit equation:
{square root}{square root over (Psh2+Qsh2)}=Ssh max (20)
where Qsh is the reactive power injected into Bus 1 by the shunt VSC 106, given by:
Additionally, equations (3c) and (3d) are replaced by circulating power equations (6) and (7).
If both the shunt VSC 106 and the series VSC 108 reach their MVA ratings, then equations (3a) and (3b) are replaced by equations (20) and (16), and equations (3c) and (3d) are replaced by equations (18) and (19).
Similarly, when the UPFC reaches other operating limits, the limit equations (16) and (20) can be activated, and specify power circulation (18) and (19). For the VSC injected voltage magnitude limits, the limit equations are to enforce Vm1 and Vm2 at Vm1max and Vm2max, respectively. For the current magnitude limits, the limit equations are
The circulation power dispatch strategy described by the equations (16) through (21) is particularly suitable for computing the maximum power transfer limited by voltage stability where both VSCs 106, 108, will operate at their rated capacities. By specifying the power circulation Pc, the amount of coupling between the VSCs 106, 108, can be systematically evaluated to achieve optimal results. For example, if Pc=0, then the two VSCs are operated separately as a STATCOM and an SSSC. Intuitively, it is expected that by increasing or decreasing Pc from zero (i.e., increasing or decreasing the coupling), the power transfer is improved until the power circulation Pc provides no further benefit or the loadflow equations (3) cease to have a solution.
To implement this circulation power dispatch strategy in the NR loadflow algorithm, the ratings of the VSCs in power flow controller need to be monitored at the end of each iteration. Once it is determined that either the shunt VSC 106 or the series VSC 108 or both VSCs will be operated at rated capacities, the proper limit equations with the power circulation equations (18) and (19) will be utilized as the VSC equations Fvsc (4c), and the Jacobian matrix (7) will be modified as described in Appendix A.
The circulation power dispatch strategy discussed above can be used to generate useful graphs (e.g., PV curves) for operators and planners, as discussed more fully with respect to
Generation of PV Curves
A common approach to voltage stability analysis is to increase the power system loading Pload and observe the resulting voltage variation V on the critical buses. Such an analysis is commonly presented in the form of power-voltage (PV) curves, which are being used in many power control centers.
To generate consistent PV curves, in some embodiments the UPFC control strategy described above can be modified slightly by enforcing a desired circulating power Pc at multiple operating conditions, regardless of whether the VSCs 106, 108, are at their rated capacities or not. That is, if both VSCs 106, 108, are below their rated capacities, then besides requesting a specific power circulation level via equations (6) and (7), the shunt VSC 106 will regulate the from-bus voltage V1d and the series VSC 108 will regulate the line active power flow Pd. The line reactive power flow Qd is not enforced. In a real-time implementation, the UPFC can be operated from the (V1d, Pd, Qd) setpoint control to the power circulation control by adjusting the power circulation continuously to the desired operating point using the PV curves.
Test System
Note that the shunt transformer 104 and the series transformer 102 of UPFC 302 have reactances of Xt1=0.1 pu and X12=0.002 pu, respectively.
By increasing the load Pload on Bus 3 and the necessary amount of generation at Bus 1, the variation of the Bus 3 voltage V3 can be observed with and without the UPFC 302. For the compensated system (switch A closed, switch B open), power circulations of Pc=−10, −5, 0, 5, 10 MW are observed. Note that a positive Pc denotes that power is circulating from the shunt VSC 106 to the series VSC 108. With no saturation, the shunt voltage setpoint and the series active power flow set point are enforced at V1d=1.03 pu and with Pd at 80% of the load active power Pload, respectively. Whenever a VSC rating limit is reached, the voltage or flow setpoint is no longer enforced, but replaced by an MVA limit equation. The resulting set of PV curves for Bus 3 are shown in
As shown in
The sets of PV curves in
The PV curves described above can be used by a system operator to provide maximum power transfer while maintaining voltage stability on one or more buses in a power system. In some embodiments, the operator can read the appropriate value from a PV curve and enter a circulating power demand Pc (e.g., via a keyboard), which can be used by an automatic power flow controller to inject the appropriate amounts of injection voltages {right arrow over (V)}m1, {right arrow over (V)}m2 and/or to achieve maximum power transfer with voltage stability while one or both of the VSCs 106, 108, are operating at their rated capacity. In other embodiments, PV curves can be stored in look-up tables or other data structures, which are indexed by a supervisory computer in response to a limit computer detecting that one or both VSCs are operating at rated capacity, and then automatically commanding a particular circulating power Pc without operator intervention using a UPFC controller.
While the circulation power dispatch strategy discussed above can be used to generate useful graphs (e.g., PV curves) for operators and planners as discussed with respect to
Automatic Power Flow Control Using Circulating Power
The limit computer 118 determines if the shunt VSC 106 is operating at a certain operating limit and selects the appropriate control block 602, 604, 606, 608, for providing gate signals via switch 610. A command signal 603 from the limit computer 118 coupled to the switch 612 is used to enable one of the control blocks 602, 604, 606, 608, and a command signal 605 from the limit computer 118 to the switch 610 is used to enable only the gate signals provided by the selected control block to be passed to the shunt VSC 106. Each regulation control block 602, 604, 606, 608, implements a control strategy, depending on the limit violation scenario. For example, if there is no limit violation for the shunt VSC 106, the V1ref and Pc regulation control block (Sh1) 602 is activated. If the shunt VSC 106 is operating at the maximum voltage magnitude limit, the Vm1 and Pc regulation control block (Sh2) 604 is activated. Similarly, if the shunt VSC 106 is operating at the current magnitude limit or the MVA limit, the Ish and Pc regulation control block (Sh3) 605 or the Ssh and Pc regulation control block (Sh4) 608 is activated, respectively. Note that the shunt converter control system 112 can include more or fewer control blocks, as needed, depending upon the configuration of the power network and the limit violations to be monitored.
Shunt Converter Regulation Control Blocks
In some embodiments, the regulation control block 602 uses a synchronous reference frame established with the phase-locked loop 820 to produce a reference phase angle θ1, which is the phase angle of the UPFC from-bus voltage {right arrow over (V)}1. The circulation power Pc is regulated to ultimately achieve the desired value of a performance variable J, which can be the voltage on a particular bus, the weighted average voltage value of a number of buses, or the reactive power flow on a line. The performance signal error amplifier 802 is configured to accommodate the error in the variable J due to the difference of the real system and a model of the system (e.g., PV curves). The output of the performance signal error amplifier 802 is an incremental circulation power component, which is added to the circulation power setpoint Pc*. In some embodiments, the setpoint Pc* is computed based on a model of the system, which in practice may not be exactly the same as the real power network. The incremental adjustment will ensure that the variable J will be achieved without error. The regulation of V1ref and Pc is achieved by controlling the shunt current Ish. The desired real shunt current ishp* is computed from the real current computer 804 using the equation
ishp*=Pc/V1, (24)
where V1 is the measured from-bus voltage magnitude. The reference of reactive shunt current ishq*, however, is generated from the voltage error amplifier 806 to achieve the setpoint V1ref. The desired real currents ishp* and reactive current ishq* are compared against the measured real and reactive current values ishp and ishq, respectively, and the error is imported into the current error amplifier 810 to drive the active and reactive shunt voltage component Vshp and Vshq, which provide the shunt converter voltage magnitude Vm1 and angle ρ1 with respect to the from bus voltage {right arrow over (V)}1 using the magnitude and angle computer 812. Because the real and reactive power components p-q are calculated with respect to the from-bus voltage {right arrow over (V)}1, the resulting voltage angle ρ1 is added to the from-bus voltage angle θ1 before generating the proper gate signals using shunt converter gate pattern logic 818. Note that the voltage magnitude limiter 816 ensures that the voltage output Vm1 does not exceed the voltage magnitude limit at the present control step. If the voltage magnitude reaches the limit, then in the next control step the limit computer 118 will select the control strategy to enforce the Vm1 setpoint at the limit value.
In this control strategy, Vm1* can either be the maximum voltage limit or specified by the operator to achieve a fixed voltage injection operation. With the desired voltage magnitude Vm1*, the voltage angle ρ1 can be directly calculated by the voltage phase angle computer 904 using the equation:
Pc=Vm1*Ish cos(ρ1−ρish), (25)
where Ish is the measured shunt current magnitude and ρish is the current angle with respect to the from bus voltage {right arrow over (V)}1. The voltage angle ρ1 computed from equation (23) does not include the operating losses of the shunt VSC 106. However, the performance signal error amplifier 902 will compensate the errors in performance variable J. The voltage angle ρ1 computed from equation (25) is added to the from-bus voltage angle η1 from the phase-locked loop 906. The sum of these angles and the desired voltage magnitude Vm1* are provided to the shunt converter gate logic 908 to provide the appropriate gate signals to the shunt VSC 106.
In some embodiments, the current magnitude reference Ish* can be either the maximum current limit or a specification from the operator. With the reference shunt current magnitude Ish* and circulation power Pc, the desired current phase angle ρish* can be calculated with respect to the from-bus voltage by the current phase angle computer 1004 using the equation
Pc=−V1Ish* cos ρish*, (26)
where V1 is the measured from-bus voltage magnitude. From Ish and ρish*, the real and reactive current components ishp* and ishq* can be computed by the real and reactive current computer 1006 and compared with the measured shunt real and reactive currents ishp and ishq computed by the real and reactive current computer 1008, to drive the shunt converter voltage. Although equation (26) neglects operating losses, the error in shunt current will be compensated by the current error amplifier 1010. The performance signal error amplifier 1002, magnitude and angle computer 1012, phase-locked loop 1014, voltage magnitude limiter 1016 and shunt converter gate pattern logic 1018 operate as previously described with respect to
From the desired MVA output Ssh* and the circulation power Pc, the current angle and magnitude computer 1104 can compute the desired shunt current magnitude Ish* and current angle ρish* with respect to the from bus voltage by
Ish*=Ssh*/V1
Pc=Ish*V1 cos ρish*, (27)
where V1 is the measured from-bus voltage magnitude. Although equation (27) neglects operating losses, the error in the current will be compensated by the current error amplifier 1110. The performance signal error amplifier 1102, real and reactive current computers 1106, 1108, magnitude and angle computer 1112, phase-locked loop 1114, voltage magnitude limiter 1116 and shunt converter gate pattern logic 1118 operate as previously described with respect to
Series Converter Regulation Control Blocks
The desired real the reactive current components ip* and iq* with respect to the from-bus voltage {right arrow over (V)}1 are determined using the real and reactive current computer 1204 and the setpoints Pref and Pc by:
where V1εjθ
In some embodiments, the reference Vm2* can be either the maximum voltage limit or a specification from the operator to achieve a fixed series voltage injection operation, which is a useful operation mode especially in post-contingencies. With reference Vm2*, the voltage angle ρ2 can be directly calculated from
Pc=−Vm2*Ise cos(ρ2−ρise), (29)
where Ise is the measured current magnitude and ρise is the current angle with respect to the from bus voltage. Although the voltage angle ρ2 computed by the voltage phase angle computer 1304 using equation (29) does not include operating losses of the series converter VSC 108, the performance signal error amplifier 1302 will compensate errors in performance variable J. The phase-locked loop 1306 and the series converter gate pattern logic 1308 operate as previously described.
In some embodiments, the current magnitude reference Ise* can either be the maximum current limit or specified from an operator. With the desired series current magnitude Ise* and the circulation power Pc, the desired current phase angle ρise can be calculated with respect to from-bus voltage using
Pc=V2Ise* cos(θ2−θ1−ρise)−V1Ise* cos ρise*, (30)
where V1 is the measured from-bus voltage magnitude, and V2 and θ2 are the measured to-bus voltage magnitude and angle, respectively. From the desired Ise* and ρise*, the real and reactive currents ip* and iq* can be computed by the real and reactive current computer 1406 and compared against the measured shunt currents ip and iq provided by the real and reactive current computer 1418 to drive the series voltages Vp and Vq, yielding the voltage magnitude Vm2 and angle ρ2. The performance signal error generator 1402, the current phase angle computer 1404, the current error amplifier 1408, the magnitude and angle computer 1410, the phase-locked loop 1412, the voltage magnitude limiter 1414 and the series converter gate pattern logic 1416 operate as previously described with respect to
From the desired series MVA output Sse* and the circulation power Pc, the desired series current magnitude Ise* and angle ρise* is provided by the current magnitude and angle computer 1504, which implements the equations
Pc=V2Ise* cos(θ2−θ1−ρise*)−V1Ise* cos ρise*
{square root}{square root over (Sse*2−Pc2)}=V2Ise* sin(θ2−θ1−ρise*)−V1Ise* sin ρise*, (31, 32)
where V1εjθ
The foregoing description, for purpose of explanation, has been described with reference to specific embodiments. However, the illustrative discussions above are not intended to be exhaustive or to limit the invention to the precise forms disclosed. Many modifications and variations are possible in view of the above teachings. The embodiments were chosen and described to best explain the principles of the invention and its practical applications, to thereby enable others skilled in the art to best utilize the invention and various embodiments with various modifications as are suited to the particular use contemplated.
For the UPFC model shown in
Psh=−Vm1V1 sin(θ1−α1)/Xt1
Qsh=V1(Vm1 cos(θ1−α1)−V1)/Xt1
Psefrom=−Vm2V1 sin(θ1−α2)/Xt2
Qsefrom=Vm2V1 cos(θ1−α2)/Xt2 (A.1)
Pseto=Vm2V2 sin(θ2−α2)/Xt2
Qseto=−Vm2V2 cos(θ2−α2)/Xt2
Pse=Psefrom+Pseto
where Psh, Qsh are the power injections into the UPFC from-bus due to the shunt VSC. Psefrom and Qsefrom are the power injections into the from-bus due to the series VSC; Pseto and Qseto are the power injections into the UPFC to-bus due to the series VSC. Pse is the active power generation of the series VSC.
From equation (A.1), a perturbation analysis can be performed to calculate the additional elements in the augmented loadflow Jacobian:
In practice, the direct and quadrature series voltages are used, rather than the voltage magnitude and angle. The direct and quadrature voltages are defined as
Vmd=Vm2 cos(α2)
Vmq=Vm2 sin(α2) (A.3)
This transformation of the variables avoids any ambiguity associated with the circular periodicity of the voltage angle. In terms of (A.3), the Jacobian matrix elements are modified to
When no saturation occurs for the UPFC, the default loadflow equations fVSC are (3a,b,c,d) and the corresponding Jacobian matrix terms for fVSC in (7) are ΔV1, ΔPseto in (A.4), ΔQseto in (A.4), and ΔPsh+ΔPse in (A.2), with each representing one row of the Jacobian matrix. When the UPFC is operating at rated capacity, the Jacobian terms for fVSC in (7) need to be modified accordingly, as discussed below.
If only the shunt VSC operates at the rated capacity and the series VSC is not, the loadflow equations are (3b), (18), (19), and the limit equation of the shunt VSC, such as (20) or (22). The Jacobian matrix terms for fVSC are the four rows corresponding to ΔPseto (A.4), ΔPsh (A.2), ΔPse (A.2), and the limit equation Jacobian ΔSsh, ΔVm1, or ΔIsh, depending on the limit equation, where
ΔSsh=(PshΔPsh+QshΔQsh)/{square root}{square root over (Psh2+Qsh2)}, (A.5)
If only the series VSC operates at the rated capacity and the shunt VSC is not, the loadflow equations are (3a), (18), -(19), and the limit equation of the series VSC, such as (16) or (23). The Jacobian matrix terms for fCSC are the four rows corresponding to ΔV1, ΔPsh (A.2), ΔPse (A.2), and the limit equation Jacobian ΔSse, ΔVm2 or ΔIse, depending on the limit equation, where
If both shunt VSC and series VSC operate at the rated capacity, the loadflow equations are (18), (19), and the corresponding limit equations of the shunt VSC and the series VSC. The Jacobian matrix terms for fVSC are the four rows corresponding to ΔPsh (A.2), and ΔPse (A.2), and the proper limit equation Jacobian, such as ΔSsh (A.5) and ΔSse (A.7), or ΔIsh (A.6) and ΔVm2 (A.8).
Note that in the Jacobian matrix (7) the upper rows for fP and fQ do not change when the dispatch strategy switches due to the saturation. However, for the Jacobian terms with respect to the bus active power injections fP, the active powers ΔPsh+ΔPsefrom and ΔPseto injected by the UPFC should be inserted in the rows corresponding to the UPFC from bus and to bus, respectively. Similarly, for the Jacobian matrix terms related to fQ, the reactive power ΔQsh+ΔQsefrom and ΔQseto injected by the UPFC should be inserted in the rows corresponding to the UTPFC from bus and to bus, respectively.
This application claims the benefit of priority of U.S. Provisional Application No. 60/483,694, filed Jun. 30, 2003, which provisional patent application is incorporated by reference herein in its entirety.
Number | Date | Country | |
---|---|---|---|
60483694 | Jun 2003 | US |