1. Field of the Invention
The present invention is a method and system to interconnect several conventional or alternative power generators, loads, and/or energy storage elements physically separated from each other in a DC distribution system.
2. Prior Art
Distributed DC systems are used to exchange power among multiple sources (mainly renewable energy resources), loads, and energy storage elements by connecting those elements to a common DC bus using power converters or direct connection in a concept generally called DC microgid. DC microgrids could be as simple as solar+storage installation or as complex as multi MW systems with many types of different generators, multiple ratings and varieties of loads, several different types of energy storage elements and multiple inverters connected or separated from the grid.
The reliability of a DC microgrid depends on the control of the DC bus voltage within specified limits, which depends on balancing the power production with the power consumption. Because renewable energy sources are intermittent in nature and loads can suddenly change, fast response from power converters and capacitive energy storage in the DC bus provide the means to instantaneously maintain the DC bus. Methods to control the DC bus voltage are well known and developed where one or multiple elements connected to the DC bus change their power quickly as the DC bus voltage drifts from the set point to balance the total power in the bus and maintain the DC bus voltage within acceptable limits.
In addition to maintaining the DC bus voltage, in most cases it is necessary to execute additional functions in the DC distributed system such as an energy management strategy to maintain the energy storage elements within their charge limits or grid ancillary functions (load shifting, grid support, etc). Frequently, these additional functions are executed by the inverters connected to the AC utility grid but they are still needed when operated independent from the AC utility or in systems with low power interconnection to the AC utility. These additional functions (SECONDARY FUNCTION) demand additional coordination and communication amongst the different components connected to the DC bus.
Wired and wireless communication means are commonly used to achieve power and energy balance between the different elements at the expense of extra cost and low flexibility. Intentionally changing the average value of the DC bus voltage has been used as a mean of communication amongst elements in a DC distributed system. The present implementations and their limitations can be divided in two groups:
In general, all of these proposals require major re-engineering when additional resources or loads are added to the DC microgrid or when a new installation with different ratings is implemented.
Use of DC-Link Voltage for Communication among Components in a DC Distributed Systems for Energy Management
During modeling and analysis of the distributed PV system, it was conceived a method to achieve power balance and energy management automatically using only the DC bus voltage as mean of communication. The proposed method uses one element on the microgrid as the brain of the microgrid operation (MAIN ELEMENT). In most cases, this element will be one or multiple energy storage devices provided with fast responding power converters. However, in other cases, this element could be an inverter connected to the utility grid.
Because the DC-link is connected to each of the power converters so they can feed their processed power, all of them will have access to a DC-link voltage measurement (normally this voltage measurement is part of the power converters as it is needed for control and protection). The DC-link voltage is maintained in a classical way by the MAIN ELEMENT executing a control algorithm. However, the MAIN ELEMENT collects information and executes an algorithm to coordinate the SECONDARY FUNCTION. The output of this algorithm is a change in DC voltage set point such that the average DC voltage is slightly drifted from the nominal value. Because the MAIN ELEMENT has the capability to maintain the DC bus voltage, only a modification in its software is needed to intentionally vary the average DC-link voltage depending on the SECONDARY FUNCTION.
The range in variable average DC-link voltage should be limited such that the maximum and minimum voltages Vnom +/−ΔVmax do not result in any degradation in performance or incorrect operation of any of the components and the time constant of the controller should be slow enough to allow for the distributed converters to react to the change in DC-link voltage.
All the elements connected to the DC bus except the MAIN ELEMENT are measuring the average DC link voltage and reacting to it by changing their output power such that the full effect is the fulfillment of the SECONDARY FUNCTION. All these elements are not aware of the requirements, limitations, or constrains of the SECONDARY FUNCTION but simply follow the direction from the MAIN ELEMENT that has been communicated using the average DC link voltage. Note than only the MAIN ELEMENT is responsible for the fast regulation of the DC bus voltage while all the other elements respond to the much slower average voltage. This increases the stability of the system and enables calibration
It was also realized that the algorithm to set the average DC-link voltage can be any relation that may include linear, quadratic, integral, or derivate terms amongst others. Furthermore, these terms may depend on state of charge, energy, power, current, temperature or any other variable that can be regulated based on average power. The variable to be used depends on the specific constrains for each application. The average DC bus voltage can be continuously changed by the MAIN ELEMENT within a small range to produce smooth and sequenced responses from all the other components in the DC distributed system. Since the changes are smooth and progressive, the system is robust against tolerances in the DC bus voltage measurement of the different components. In other words, if a small change in the average DC bus voltage does not produce the expected response, the average DC bus voltage is changed even more until the desired response is achieved.
It is also clear that power function change as function of the average Dc bus voltage for elements except the MAIN ELEMENT can be not only power functions but can also use other variables such as current, fuel injection, etc. Furthermore, this function does not necessarily have to follow a linear relationship with voltage. Instead if may include other linear or non-linear terms depending on the specific properties of each distributed resource. For example in a system combining solar with wind and/or Fuel Cells in a DC distribution system, it may be preferable that the operation of the fuel cell is maintained close to maximum power in order to maximize the efficiency and lifetime of the generator while the solar and wind can be ramped without penalty. In that case, the fuel cell power can be stepped down when the average DC-link voltage reaches a high value while the solar and wind would be ramped when the voltage exceeds the nominal value. In general the average DC-link voltage is variable according to a function preprogrammed in the MAIN ELMENT as in (1), and the power, current, energy, or other adjusted variable from each component in the distribution system is decided based on the average DC-link voltage using a pre established equation as in (2)
Vdc
Link
=f(F,E,I) (1)
F,E,I=f(VdcLink) (2)
The limiting functions for the different generators and loads may be determined by cost, performance, or durability decisions and may differ from one generator to another in the same DC distribution system.
The smooth control of the average DC bus voltage and the progressive response of the components connected to the DC bus enable a plug and play type of system where new resources and loads can be programmed with specific response curves and then be added to the bus without the need to reconfigure the element controlling the average DC bus voltage or other sources and loads in the system. In a similar way, resources and loads can be removed without any effect on the rest of the installation.
Example of a DC Micro-grid with Variable DC-link Voltage for Energy Management
An example of the general concept of the use of variable average DC voltage for optimization of distributed sources and loads is shown in
Although the example in
This application is a continuation-in-part of U.S. patent application Ser. No. 13/828,290 filed Mar. 14, 2013 and claims priority on U.S. Provisional Patent Application Ser. No. 62/182,788, filed Jun. 22, 2015.
Number | Date | Country | |
---|---|---|---|
62182788 | Jun 2015 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 13828290 | Mar 2013 | US |
Child | 14858856 | US |