All publications and patent applications mentioned in this specification are herein incorporated by reference to the same extent as if each individual publication or patent application was specifically and individually indicated to be incorporated by reference.
The present application relates generally to distribution line monitoring, sensor monitoring, and sensing and identifying electrical characteristics of a power distribution line. More specifically, this disclosure provides a novel power source for use in electric utility underground equipment applications.
Electric utilities have two fundamental choices for distributing electric power to customers; underground or overhead construction. New construction and major replacement projects generally favor underground construction. The primary advantages are improved customer acceptance (i.e., better aesthetics) and higher reliability. The primary disadvantages are the generally higher cost for new construction and the higher cost to locate and implement repairs to existing equipment.
The present disclosure is intended to support measurement equipment that can be used to assist in the ongoing maintenance of underground equipment. This measurement equipment can, for example, report current and voltage present on the underground cable. This measurement data can be returned to an electric utility control center via a communications link (hard-wire, optical, or radio link). The measurement data is valuable not only to locate faulty equipment more efficiently, but for a number of other uses also, for example, load leveling, partial discharge detection, etc.
Underground construction requires most of the same support equipment used in overhead construction, for example, distribution transformers, sectionalizing switches, etc. For underground, this equipment is contained either in a vault (frequently completely below ground level) or in a pad mounted cabinet. Equipment for these two enclosure types is designed using either “live front” or “dead front” construction. As the terms hint, live front equipment has exposed conductors at the system voltage inside the cabinet, dead front equipment has no exposed conductors and all system voltage conductors are insulated.
To support underground measurement equipment, a power source capable of supplying 2 to 10 watts of power is generally needed. Existing solutions obtain this power either using a locally installed PT (voltage transformer) or by inductively harvesting power from the current flowing in one or more of the underground cables. The PT solution has seen limited application due to its high installation cost and also the space required is frequently not available. Inductive harvesting offers a relatively easy installation at moderate cost. The major disadvantage is that the power produced is dependent on the current flowing in the conductor the harvesting transformer is attached to. In many applications, these conductor currents are too small to produce the required 2 to 10 watts of power.
The novel features of the invention are set forth with particularity in the claims that follow. A better understanding of the features and advantages of the present invention will be obtained by reference to the following detailed description that sets forth illustrative embodiments, in which the principles of the invention are utilized, and the accompanying drawings of which:
A method of powering an electrical component with underground power lines is provided, comprising the steps of electrically coupling a power supply device to a conductor of the underground power lines, providing an input voltage from the conductor to a voltage divider of the power supply device, and regulating an output voltage of the voltage divider to support variable loads on the voltage divider.
In some embodiments, the electrically coupling step comprises attaching a connector of the power supply device to a connector of the underground power lines.
In some embodiments, the input voltage comprises 500 to 1000 volts, or alternatively, 1000 to 2000 volts.
In one embodiment, the output voltage comprises less than or equal to 50 volts.
In some implementations, the voltage divider comprises a capacitor and the divider voltage control electronics.
In one embodiment, regulating the output voltage further comprises producing a reasonably fixed impedance with the divider voltage control electronics regardless of the variable load present on the tap of the voltage divider.
In another embodiment, the voltage divider comprises a resistor and the divider voltage control electronics.
In some embodiments, the method further comprises providing impulse protection from surge events with a surge resistor placed in series with the capacitor.
A power supply device configured to power an electrical component with underground power lines is also provided, comprising a connector configured to electrically couple the power supply device to a conductor of the underground power lines, and a voltage divider configured to receive an input voltage from the conductor, the voltage divider comprising a capacitor and divider voltage control electronics, wherein the divider voltage control electronics are configured to regulate an output voltage of the voltage divider to support variable loads on the voltage divider.
In one embodiment, the divider voltage control electronics comprise a transformer.
In another embodiment, the divider voltage control electronics comprise a variable resistance load circuit configured to maintain a maximum voltage across a filter capacitor.
In one embodiment, the device further comprises a surge resistor placed in series with the capacitor and configured to provide impulse protection from surge events.
The present disclosure describes systems and methods configured to supply a voltage from an underground power conductor that can be more readily handled by mainstream semiconductor and magnetic components, such as underground measurement equipment (generally less than 1000 volts). Some implementations described herein are intended to support dead front installations for underground power networks. In some embodiments, the devices described herein are very similar in appearance to a standard elbow connector. It can be connected to either a panel-mounted equipment bushing or a “T” elbow connector of the underground power network. The devices described herein can use the voltage present on the underground conductor it is attached to produce power usable by the aforementioned underground measurement equipment.
The present disclosure can include a voltage divider to supply a voltage that can be more readily handled by mainstream semiconductor and magnetic components (generally less than 1000 volts). The divided system voltage, which can be between 500 and 1000 volts, can then converted to a power supply voltage to be used by measuring equipment. For safety reasons, this voltage is frequently required to be less than approximately 50 volts if it is delivered via a connectorized cable with exposed contacts.
The embodiments described herein and illustrated in
Two basic implementations are described herein, one uses a transformer to convert the divided system voltage to the desired power supply voltage (“Transformer Implementation”). The second converts the divided system voltage to DC and uses a switching converter to supply the desired DC power supply voltage (“DC Converter Implementation).
Both of the implementations mentioned above start with the same basic device construction. A standard elbow connector construction can be used to house the device components (shown in more detail in
Referring to
To obtain a reasonably fixed divider output voltage, the components that make up the divider voltage control impedance block must produce a reasonably fixed impedance regardless of the load present on the divider tap. The described solutions to this problem are described below.
Referring still to
Transformer Implementation
The divider component 206 can be sized and configured to supply the transformer 218 the primary current needed to produce the desired power out of the secondary winding. Given this, the divider component 206 can have different values for each system voltage class (for example, 15 kV, 25 kV, 35 kV). This requires a different model of device for each voltage class.
For the target 1000 volt divider voltage previously mentioned, a secondary voltage of 20 volts might be chosen. If the divider components were sized to deliver, for example, 5 mA of current through the divider, the secondary would be capable of sourcing 250 mA at 20 volts ([1000/20]*5 mA), or 5 watts in a lossless transformer.
In one implementation, it is proposed to use the transformer magnetic core behavior to control the maximum voltage that can appear on the secondary winding. Again using the example 1000 volt target divider voltage, the primary winding and magnetic core would be designed to support that voltage with good transformer function efficiency (for example, greater than 95%). The transformer can be designed to start saturating the magnetic core as the primary voltage is increased beyond 1000 volts. As the voltage is increased, the primary winding impedance becomes less as the permeability of the core drops. At 1500 or 2000 volts, for example, the primary winding impedance is low enough that the primary winding voltage can no longer increase. Should the transformer primary voltage limit to 2000 volts, for example, the secondary voltage will limit to 40 volts, a safe level for a connectorized implementation.
The Surge Resistor and the TVS Diode shown in
Switching transients are also common events in electrical distribution systems. While these can be much longer in duration than the lightning impulse (typically less than 10 msec) the peak voltages rarely exceed two times the system voltage. The existing proposed circuitry would be designed to handle these events also.
In some embodiments, the transformer secondary winding lower connection 220 shown in
DC Converter Implementation
The switching power supply 326 is used to provide the DC power output of the device and to provide ground bounce transient voltage isolation during impulse events as previously described. A major advantage of this implementation is the magnetic component required is considerably smaller and lighter than that required for a 50 or 60 Hertz transformer. The voltage the small geometry transformer can support will drive the required size.
Divider output voltage control is provided by the variable resistance load 328 function shown in
Referring to
Another possible implementation of the circuit in
All of the implementations described above, including the transformer implementation and the DC converter implementation, provide a divider voltage control impedance block (or circuit) that is configured to regulate the voltage on the divider output to support variable loads.
Elbow Connector
The device 500 can be grounded and it also makes the ground connection to the outer housing. A separate ground wire and power supply cable are shown. These could be included as a single cable assembly, however it can be beneficial to separate them as shown for surge response performance as described above. The insulation 503 shown does not include insulation system design details required to manage the E-field gradients surrounding the connector components as well as the divider surge resistor and the divider component.
As for additional details pertinent to the present invention, materials and manufacturing techniques may be employed as within the level of those with skill in the relevant art. The same may hold true with respect to method-based aspects of the invention in terms of additional acts commonly or logically employed. Also, it is contemplated that any optional feature of the inventive variations described may be set forth and claimed independently, or in combination with any one or more of the features described herein. Likewise, reference to a singular item, includes the possibility that there are plural of the same items present. More specifically, as used herein and in the appended claims, the singular forms “a,” “and,” “said,” and “the” include plural referents unless the context clearly dictates otherwise. It is further noted that the claims may be drafted to exclude any optional element. As such, this statement is intended to serve as antecedent basis for use of such exclusive terminology as “solely,” “only” and the like in connection with the recitation of claim elements, or use of a “negative” limitation. Unless defined otherwise herein, all technical and scientific terms used herein have the same meaning as commonly understood by one of ordinary skill in the art to which this invention belongs. The breadth of the present invention is not to be limited by the subject specification, but rather only by the plain meaning of the claim terms employed.
This application claims the benefit of U.S. Provisional Application No. 62/800,926, filed Feb. 4, 2019, herein incorporated by reference in its entirety.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/US20/16626 | 2/4/2020 | WO | 00 |
Number | Date | Country | |
---|---|---|---|
62800926 | Feb 2019 | US |