Power supply for electric utility underground equipment

Information

  • Patent Grant
  • 11947374
  • Patent Number
    11,947,374
  • Date Filed
    Tuesday, February 4, 2020
    4 years ago
  • Date Issued
    Tuesday, April 2, 2024
    8 months ago
Abstract
The present disclosure uses a capacitive voltage divider to supply a voltage that can be more readily handled by mainstream semiconductor and magnetic components (generally less than 1000 volts). The divided system voltage, expected to be between 500 and 1000 volts, is then converted to a power supply voltage to be used by the measuring equipment. For safety reasons, this voltage is frequently required to be less than approximately 50 volts if it is delivered via a connectorized cable with exposed contacts.
Description
INCORPORATION BY REFERENCE

All publications and patent applications mentioned in this specification are herein incorporated by reference to the same extent as if each individual publication or patent application was specifically and individually indicated to be incorporated by reference.


FIELD

The present application relates generally to distribution line monitoring, sensor monitoring, and sensing and identifying electrical characteristics of a power distribution line. More specifically, this disclosure provides a novel power source for use in electric utility underground equipment applications.


BACKGROUND

Electric utilities have two fundamental choices for distributing electric power to customers; underground or overhead construction. New construction and major replacement projects generally favor underground construction. The primary advantages are improved customer acceptance (i.e., better aesthetics) and higher reliability. The primary disadvantages are the generally higher cost for new construction and the higher cost to locate and implement repairs to existing equipment.


The present disclosure is intended to support measurement equipment that can be used to assist in the ongoing maintenance of underground equipment. This measurement equipment can, for example, report current and voltage present on the underground cable. This measurement data can be returned to an electric utility control center via a communications link (hard-wire, optical, or radio link). The measurement data is valuable not only to locate faulty equipment more efficiently, but for a number of other uses also, for example, load leveling, partial discharge detection, etc.


Underground construction requires most of the same support equipment used in overhead construction, for example, distribution transformers, sectionalizing switches, etc. For underground, this equipment is contained either in a vault (frequently completely below ground level) or in a pad mounted cabinet. Equipment for these two enclosure types is designed using either “live front” or “dead front” construction. As the terms hint, live front equipment has exposed conductors at the system voltage inside the cabinet, dead front equipment has no exposed conductors and all system voltage conductors are insulated.


To support underground measurement equipment, a power source capable of supplying 2 to 10 watts of power is generally needed. Existing solutions obtain this power either using a locally installed PT (voltage transformer) or by inductively harvesting power from the current flowing in one or more of the underground cables. The PT solution has seen limited application due to its high installation cost and also the space required is frequently not available. Inductive harvesting offers a relatively easy installation at moderate cost. The major disadvantage is that the power produced is dependent on the current flowing in the conductor the harvesting transformer is attached to. In many applications, these conductor currents are too small to produce the required 2 to 10 watts of power.





BRIEF DESCRIPTION OF THE DRAWINGS

The novel features of the invention are set forth with particularity in the claims that follow. A better understanding of the features and advantages of the present invention will be obtained by reference to the following detailed description that sets forth illustrative embodiments, in which the principles of the invention are utilized, and the accompanying drawings of which:



FIG. 1 shows a capacitive voltage divider with the bottom divider component as the “Divider Voltage Control Impedance” block.



FIG. 2 shows a transformer implementation of a voltage divider.



FIG. 3 shows a DC converter implementation of a voltage divider.



FIGS. 4A-4B shows circuits that implements a variable resistance load function.



FIG. 5 is a side-view of one example of an elbow connector for an underground power system.





SUMMARY OF THE DISCLOSURE

A method of powering an electrical component with underground power lines is provided, comprising the steps of electrically coupling a power supply device to a conductor of the underground power lines, providing an input voltage from the conductor to a voltage divider of the power supply device, and regulating an output voltage of the voltage divider to support variable loads on the voltage divider.


In some embodiments, the electrically coupling step comprises attaching a connector of the power supply device to a connector of the underground power lines.


In some embodiments, the input voltage comprises 500 to 1000 volts, or alternatively, 1000 to 2000 volts.


In one embodiment, the output voltage comprises less than or equal to 50 volts.


In some implementations, the voltage divider comprises a capacitor and the divider voltage control electronics.


In one embodiment, regulating the output voltage further comprises producing a reasonably fixed impedance with the divider voltage control electronics regardless of the variable load present on the tap of the voltage divider.


In another embodiment, the voltage divider comprises a resistor and the divider voltage control electronics.


In some embodiments, the method further comprises providing impulse protection from surge events with a surge resistor placed in series with the capacitor.


A power supply device configured to power an electrical component with underground power lines is also provided, comprising a connector configured to electrically couple the power supply device to a conductor of the underground power lines, and a voltage divider configured to receive an input voltage from the conductor, the voltage divider comprising a capacitor and divider voltage control electronics, wherein the divider voltage control electronics are configured to regulate an output voltage of the voltage divider to support variable loads on the voltage divider.


In one embodiment, the divider voltage control electronics comprise a transformer.


In another embodiment, the divider voltage control electronics comprise a variable resistance load circuit configured to maintain a maximum voltage across a filter capacitor.


In one embodiment, the device further comprises a surge resistor placed in series with the capacitor and configured to provide impulse protection from surge events.


DETAILED DESCRIPTION

The present disclosure describes systems and methods configured to supply a voltage from an underground power conductor that can be more readily handled by mainstream semiconductor and magnetic components, such as underground measurement equipment (generally less than 1000 volts). Some implementations described herein are intended to support dead front installations for underground power networks. In some embodiments, the devices described herein are very similar in appearance to a standard elbow connector. It can be connected to either a panel-mounted equipment bushing or a “T” elbow connector of the underground power network. The devices described herein can use the voltage present on the underground conductor it is attached to produce power usable by the aforementioned underground measurement equipment.


The present disclosure can include a voltage divider to supply a voltage that can be more readily handled by mainstream semiconductor and magnetic components (generally less than 1000 volts). The divided system voltage, which can be between 500 and 1000 volts, can then converted to a power supply voltage to be used by measuring equipment. For safety reasons, this voltage is frequently required to be less than approximately 50 volts if it is delivered via a connectorized cable with exposed contacts.



FIG. 1 illustrates a schematic diagram of a power supply device 100 configured to connect to an underground power network 102. As shown in FIG. 1, the power supply device 100 can include a connector 104 configured to electrically couple the power supply device 100 to the underground power network 102. The power supply device 100 can further include a divider component 106, a divider voltage control impedance block 108, and a divider output 110. The divider component 106 and the divider voltage control impedance block 108 together create a voltage divider in the power supply device 100. The underground power network 102 can include a system voltage 112, a cable/conductor 114, and a bushing 116 that provides an electrical connection to the cable/conductor 114.


The embodiments described herein and illustrated in FIG. 1 provide a controlled divider output voltage (also referred to as a power supply voltage) that is controlled with a divider voltage control impedance block. In some embodiments, is desirable for the controlled divider output voltage to be as large as possible to limit the current needed to be sourced through the divider. This limits the power dissipation in the divider components.


Two basic implementations are described herein, one uses a transformer to convert the divided system voltage to the desired power supply voltage (“Transformer Implementation”). The second converts the divided system voltage to DC and uses a switching converter to supply the desired DC power supply voltage (“DC Converter Implementation).


Both of the implementations mentioned above start with the same basic device construction. A standard elbow connector construction can be used to house the device components (shown in more detail in FIG. 5 and described below). This elbow connector construction is used in currently available devices that provide voltage measurement (for example, a resistive divider), impulse protection (for example, lightning and surge arrestors), and fuses.


Referring to FIG. 1, the divider component can be a capacitor designed to support the majority of the system voltage (approximately Vsystem—500-1000V, or alternatively, up to 2000V). Capacitors intended for use in electric utility voltage divider applications are commercially available and have proven reliability in field. In some examples, this capacitor can occupy a significant portion of the length of the elbow connector construction of the device, however its length will be dependent on the system voltage the device is designed to support. In this example, the divider component was chosen to be capacitive rather than resistive to limit the component power dissipation and thereby the heat generated in the component. However, it should be understood that a resistive component can also be implemented.


To obtain a reasonably fixed divider output voltage, the components that make up the divider voltage control impedance block must produce a reasonably fixed impedance regardless of the load present on the divider tap. The described solutions to this problem are described below.


Referring still to FIG. 1, at the system frequency, generally 50 or 60 Hertz, the divider component 106 will have a fixed impedance of 1/(2π*f*C). In a voltage divider application, when the divider voltage control impedance block 108 has a fixed impedance, the divider output 110 will be determined by the ratio of the two fixed impedances. To obtain an accurate voltage divider ratio, the load on the divider output 110 must also be fixed. In this disclosure, the divider output 110 is connected to a variable load, necessitated by the varying power requirements of the attached equipment. It would be desirable to have this load on the divider output vary from infinite (open circuit) to whatever load impedance is present when the attached measurement device is providing its maximum designed power output. At the block diagram level, this function of varying the load on the divider output is provided by the divider voltage control impedance block 108 of the present disclosure. This function can be implemented in numerous ways. Two possible solutions are described below.


Transformer Implementation



FIG. 2 illustrates one embodiment of a power supply device 200 that implements the divider voltage control impedance block from FIG. 1 as a transformer 218. The connector 204 and the divider component 206 correspond to the same structures as described in FIG. 1. In this embodiment, the power supply device 200 can further include a surge resistor 214 and a transient-voltage-suppression (TVS) diode 216 to protect the device and the equipment it powers from impulse events. This is described further below. Transformer 218 is designed and configured to inductively support a target voltage of 500 to 1000 volts as previously described.


The divider component 206 can be sized and configured to supply the transformer 218 the primary current needed to produce the desired power out of the secondary winding. Given this, the divider component 206 can have different values for each system voltage class (for example, 15 kV, 25 kV, 35 kV). This requires a different model of device for each voltage class.


For the target 1000 volt divider voltage previously mentioned, a secondary voltage of 20 volts might be chosen. If the divider components were sized to deliver, for example, 5 mA of current through the divider, the secondary would be capable of sourcing 250 mA at 20 volts ([1000/20]*5 mA), or 5 watts in a lossless transformer.


In one implementation, it is proposed to use the transformer magnetic core behavior to control the maximum voltage that can appear on the secondary winding. Again using the example 1000 volt target divider voltage, the primary winding and magnetic core would be designed to support that voltage with good transformer function efficiency (for example, greater than 95%). The transformer can be designed to start saturating the magnetic core as the primary voltage is increased beyond 1000 volts. As the voltage is increased, the primary winding impedance becomes less as the permeability of the core drops. At 1500 or 2000 volts, for example, the primary winding impedance is low enough that the primary winding voltage can no longer increase. Should the transformer primary voltage limit to 2000 volts, for example, the secondary voltage will limit to 40 volts, a safe level for a connectorized implementation.


The Surge Resistor and the TVS Diode shown in FIG. 2 are configured to protect the device and the attached equipment from transient overvoltages. The primary concern are lightning impulses. While these impulses are short in duration (typically less than 200 usec for reasonably proximate strikes that still have significant peak voltage), they can contain significant energy. Semiconductor overvoltage protection devices designed for the expected energy levels are readily available. The TVS diode 216 was chosen here for its tight clamping voltage control and its multiple strike tolerance. TVS diodes are typically available up to 500 volts. In some embodiments, the design can use two or more TVS diodes in series in this application. The surge resistor 214 is included to absorb the majority of the energy during an impulse as little voltage is expected to be dropped across the divider component 206 during impulse events. The sur be designed to dissipate a small amount of power during normal operation (for example, less than 2 watts). The resistor and surrounding insulation will need to support the impulse voltage event.


Switching transients are also common events in electrical distribution systems. While these can be much longer in duration than the lightning impulse (typically less than 10 msec) the peak voltages rarely exceed two times the system voltage. The existing proposed circuitry would be designed to handle these events also.


In some embodiments, the transformer secondary winding lower connection 220 shown in FIG. 2 could be directly connected to ground. The connection shown can be used to isolate the equipment being powered from the expected ground potential rise caused by a transient current event passing through the ground connection inductance. This ground connection may be many feet in length (for example, greater than 10 feet). For the connection shown, this potential rise would be isolated by the transformer.


DC Converter Implementation



FIG. 3 illustrates one embodiment of a power supply device 300 that implements the divider voltage control impedance block from FIG. 1 as a DC converter 322. The connector 304, divider component 306, TVS diode 316, and divider output 310 correspond to the same structures as described in FIGS. 1 and 2 above. The power supply device 300 can further include diode rectifier 323, filter capacitor 324, switching power supply 326, and variable resistance load 328. The divider voltage is first fullwave rectified and filtered as shown in FIG. 3.


The switching power supply 326 is used to provide the DC power output of the device and to provide ground bounce transient voltage isolation during impulse events as previously described. A major advantage of this implementation is the magnetic component required is considerably smaller and lighter than that required for a 50 or 60 Hertz transformer. The voltage the small geometry transformer can support will drive the required size.


Divider output voltage control is provided by the variable resistance load 328 function shown in FIG. 3. This function provides a variable load that maintains a maximum voltage across filter capacitor 324. An example circuit for the function of the variable resistance load 328 is shown in FIG. 4A as variable resistance load 428.


Referring to FIG. 4A, when the voltage on the positive input of amplifier 430 is below the reference voltage 432, the transistor gate shown is driven low, turning off transistor 434. As the voltage on the positive input is increased above the reference voltage 432, the transistor turns on, drawing the necessary current to maintain the desired voltage across the filter capacitor. When the device is not connected to a load, resistor 436 will need to dissipate the design full power output (2 to 10 watts). This amount of power may be advantageously dissipated through the device earth ground connection. The resistor can be thermally bonded to the ground, but electrically isolated. The electrical isolation barrier would need to support the voltage across filter capacitor 424 plus a smaller transient ground bounce voltage.


Another possible implementation of the circuit in FIG. 3 places the variable resistance load 328 at the output of the switching power supply. This implementation is illustrated in FIG. 4B. The components described in FIG. 4B correspond to the same structures as described above in FIG. 4A. This requires a signal that represents the voltage across filter capacitor 424 be available at the power supply output. This can be implemented as a high value resistive divider as the design does not require galvanic isolation. With this solution, resistor 436 can be thermally bonded to earth ground and require only readily available dielectric isolation solutions. This alternative implementation loses ground bounce isolation compared to the implementation of FIG. 4A, and the switching power supply must support the full design power load continuously. It has the minor advantage of providing a useable power supply for both the reference voltage and OP Amp functions. Both of these functions could be implemented with power supply current requirements of less than say, 100 uA. An inexpensive and reliable linear power source would dissipate 1000V*200 ua=200 mW.


All of the implementations described above, including the transformer implementation and the DC converter implementation, provide a divider voltage control impedance block (or circuit) that is configured to regulate the voltage on the divider output to support variable loads.


Elbow Connector



FIG. 5 illustrates a power supply device 500 that comprises an “elbow connector” housing 501. The device 500 can include many components described and illustrated above, including a connector 504 and insulation 503 disposed between the housing 501 and the connector 504. Device 500 can further include a surge resistor 514, divider component 506, divider voltage control electronics 508 (corresponding to divider voltage control impedance block 108 in FIG. 1), a ground wire 505, and a power supply cable which provides a divided output 510, as described above. In some embodiments, the elbow connector housing 501 can house all the illustrated components. However, in another embodiment, the housing 501 can house only the connector 504, insulation 503, surge resistor 514, and divider component 506, and an additional divider voltage control housing 507 can house the divider voltage control electronics 508. In this alternative embodiment, the additional divider voltage control housing 507 and divider voltage control electronics 508 can be modular and can be attached to a standard elbow connector to add-on the features described herein, namely the ability to regulate the voltage on the divider output to support variable loads.


The device 500 can be grounded and it also makes the ground connection to the outer housing. A separate ground wire and power supply cable are shown. These could be included as a single cable assembly, however it can be beneficial to separate them as shown for surge response performance as described above. The insulation 503 shown does not include insulation system design details required to manage the E-field gradients surrounding the connector components as well as the divider surge resistor and the divider component.


As for additional details pertinent to the present invention, materials and manufacturing techniques may be employed as within the level of those with skill in the relevant art. The same may hold true with respect to method-based aspects of the invention in terms of additional acts commonly or logically employed. Also, it is contemplated that any optional feature of the inventive variations described may be set forth and claimed independently, or in combination with any one or more of the features described herein. Likewise, reference to a singular item, includes the possibility that there are plural of the same items present. More specifically, as used herein and in the appended claims, the singular forms “a,” “and,” “said,” and “the” include plural referents unless the context clearly dictates otherwise. It is further noted that the claims may be drafted to exclude any optional element. As such, this statement is intended to serve as antecedent basis for use of such exclusive terminology as “solely,” “only” and the like in connection with the recitation of claim elements, or use of a “negative” limitation. Unless defined otherwise herein, all technical and scientific terms used herein have the same meaning as commonly understood by one of ordinary skill in the art to which this invention belongs. The breadth of the present invention is not to be limited by the subject specification, but rather only by the plain meaning of the claim terms employed.

Claims
  • 1. A method for powering an electrical component with underground power lines, comprising: electrically coupling a power supply device to a conductor of the underground power lines, wherein a connector and a voltage divider of the power supply device are within an elbow connector housing;providing an input voltage from the conductor to the voltage divider of the power supply device, the voltage divider including a fixed impedance portion in series with a variable impedance portion; andregulating an output voltage of the voltage divider by modifying impedance of the variable impedance portion to support variable loads on the voltage divider, wherein a cable carrying the regulated output voltage exits the elbow connector housing.
  • 2. The method of claim 1, wherein electrically coupling the power supply device further comprises attaching the connector of the power supply device to a connector of the underground power lines.
  • 3. The method of claim 1, wherein the input voltage comprises 1000 to 2000 volts.
  • 4. The method of claim 1, wherein the output voltage comprises less than or equal to 50 volts.
  • 5. The method of claim 1, wherein the fixed impedance portion comprises a capacitor and the variable impedance portion comprises divider voltage control electronics.
  • 6. The method of claim 5, wherein regulating the output voltage comprises modifying the variable impedance portion to match an output of the voltage divider with a load impedance of the variable loads.
  • 7. The method of claim 1, wherein the fixed impedance portion comprises a resistor and the variable impedance portion comprises divider voltage control electronics.
  • 8. The method of claim 1, wherein regulating the output voltage further comprises limiting the output voltage of the voltage divider.
  • 9. The method of claim 1, the variable impedance portion comprising a transformer.
  • 10. The method of claim 1, the variable impedance portion comprising a direct current (DC) converter with a switching power supply.
  • 11. The method of claim 1, further comprising providing ground bounce transient voltage isolation during an impulse event on the underground power lines.
  • 12. A method for powering an electrical component with underground power lines, comprising: electrically coupling a power supply device to a conductor of the underground power lines, wherein a connector and a voltage divider of the power supply device are within an elbow connector housing;providing an input voltage from the conductor to the voltage divider of the power supply device, the voltage divider comprising a capacitor in series with divider impedance control electronics;regulating an output voltage of the voltage divider to support variable loads on the voltage divider, wherein a cable carrying the regulated output voltage exits the elbow connector housing; andproviding impulse protection from surge events with a surge resistor placed in series with the capacitor.
  • 13. The method of claim 12, wherein the divider impedance control electronics comprise at least one of: a transformer or a direct current (DC) converter with a switching power supply.
  • 14. The method of claim 12, further comprising providing ground bounce transient voltage isolation during an impulse event on the underground power lines.
  • 15. The method of claim 12, wherein electrically coupling the power supply device further comprises attaching the connector of the power supply device to a connector of the underground power lines.
  • 16. A power supply device for connection to underground power lines, comprising: an elbow connector housing comprising a connector and a voltage divider;an output cable that exits the elbow connector housing;the connector configured to be attached to a conductor of the underground power lines having a voltage greater than 1000 volts;the voltage divider comprising a capacitor in series with divider impedance control electronics;the divider impedance control electronics being configured to regulate an output voltage of the voltage divider to support variable loads on the voltage divider; andthe output cable carries the output voltage regulated by the divider impedance control electronics.
  • 17. The power supply device of claim 16, further comprising a surge resistor in series with the capacitor.
  • 18. The power supply device of claim 16, further comprising a ground wire that exits the elbow connector housing.
  • 19. The power supply device of claim 18, wherein the ground wire and the output cable comprise a single cable assembly.
  • 20. The power supply device of claim 16, wherein the voltage greater than 1000 volts is inaccessible externally via the power supply device.
CROSS REFERENCE TO RELATED APPLICATIONS

This application claims the benefit of U.S. Provisional Application No. 62/800,926, filed Feb. 4, 2019, herein incorporated by reference in its entirety.

PCT Information
Filing Document Filing Date Country Kind
PCT/US2020/016626 2/4/2020 WO
Publishing Document Publishing Date Country Kind
WO2020/163367 8/13/2020 WO A
US Referenced Citations (196)
Number Name Date Kind
3075166 Peek Jan 1963 A
3435294 Lemma Mar 1969 A
3558984 Smith Jan 1971 A
3676740 Schweitzer, Jr. Jul 1972 A
3686531 Decker Aug 1972 A
3702966 Schweitzer, Jr. Nov 1972 A
3708724 Schweitzer Jan 1973 A
3715742 Schweitzer Feb 1973 A
3720872 Russell Mar 1973 A
3725832 Schweitzer Apr 1973 A
3755714 Link Aug 1973 A
3768011 Swain Oct 1973 A
3777217 Groce Dec 1973 A
3814831 Olsen Jun 1974 A
3816816 Schweitzer Jun 1974 A
3866197 Schweitzer, Jr. Feb 1975 A
3876911 Schweitzer, Jr. Apr 1975 A
3957329 McConnell May 1976 A
3970898 Baumann Jul 1976 A
4063161 Pardis Dec 1977 A
4152643 Schweitzer, Jr. May 1979 A
4262256 Blais Apr 1981 A
4339792 Yasumura Jul 1982 A
4378525 Burdick Mar 1983 A
4396794 Stiller Aug 1983 A
4396968 Stiller Aug 1983 A
4398057 Shankle Aug 1983 A
4408155 Mcbride Oct 1983 A
4466071 Russell, Jr. Aug 1984 A
4558229 Massey Dec 1985 A
4559491 Saha Dec 1985 A
4570231 Bunch Feb 1986 A
4584523 Elabd Apr 1986 A
4649457 Talbot Mar 1987 A
4654573 Rough Mar 1987 A
4709339 Fernandes Nov 1987 A
4714893 Smith-vaniz Dec 1987 A
4723220 Smith-vaniz Feb 1988 A
4728887 Davis Mar 1988 A
4746241 Burbank, III May 1988 A
4766549 Schweitzer, III Aug 1988 A
4775839 Kosina Oct 1988 A
4808916 Smith-vaniz Feb 1989 A
4827272 Davis May 1989 A
4829298 Fernandes May 1989 A
4881028 Bright Nov 1989 A
4886980 Fernandes Dec 1989 A
4904932 Schweitzer, Jr. Feb 1990 A
4937769 Verbanets Jun 1990 A
5006846 Granville Apr 1991 A
5125738 Kawamura Jun 1992 A
5138265 Kawamura Aug 1992 A
5159561 Watanabe Oct 1992 A
5181026 Granville Jan 1993 A
5182547 Griffith Jan 1993 A
5202812 Shinoda Apr 1993 A
5206595 Wiggins Apr 1993 A
5220311 Schweitzer, Jr. Jun 1993 A
5428549 Chen Jun 1995 A
5438256 Thuries Aug 1995 A
5473244 Libove Dec 1995 A
5495169 Smith Feb 1996 A
5537044 Stahl Jul 1996 A
5550476 Lau Aug 1996 A
5565783 Lau Oct 1996 A
5600248 Westrom Feb 1997 A
5608328 Sanderson Mar 1997 A
5650728 Rhein Jul 1997 A
5656931 Lau Aug 1997 A
5682100 Rossi Oct 1997 A
5696788 Choi Dec 1997 A
5712796 Ohura Jan 1998 A
5729144 Cummins Mar 1998 A
5737203 Barrett Apr 1998 A
5764065 Richards Jun 1998 A
5839093 Novosel Nov 1998 A
5841204 English Nov 1998 A
5892430 Wiesman Apr 1999 A
5905646 Crewson May 1999 A
5990674 Schweitzer, Jr. Nov 1999 A
6002260 Lau Dec 1999 A
6016105 Schweitzer, Jr. Jan 2000 A
6043433 Schweitzer, Jr. Mar 2000 A
6061259 DeMichele May 2000 A
6133723 Feight Oct 2000 A
6133724 Schweitzer, Jr Oct 2000 A
6288632 Hoctor Sep 2001 B1
6292340 Oregan Sep 2001 B1
6347027 Nelson Feb 2002 B1
6433698 Schweitzer, Jr. Aug 2002 B1
6459998 Hoffman Oct 2002 B1
6466030 Hu Oct 2002 B2
6466031 Hu Oct 2002 B1
6477475 Takaoka Nov 2002 B1
6483435 Saha Nov 2002 B2
6525558 Kim et al. Feb 2003 B2
6549880 Willoughby Apr 2003 B1
6559651 Crick May 2003 B1
6566854 Hagmann May 2003 B1
6577108 Hubert Jun 2003 B2
6601001 Moore Jul 2003 B1
6622285 Rust Sep 2003 B1
6677743 Coolidge Jan 2004 B1
6718271 Tobin Apr 2004 B1
6734662 Fenske May 2004 B1
6798211 Rockwell Sep 2004 B1
6801027 Hann et al. Oct 2004 B2
6822457 Borchert Nov 2004 B2
6822576 Feight Nov 2004 B1
6879917 Turner Apr 2005 B2
6894478 Fenske May 2005 B1
6914763 Reedy Jul 2005 B2
6917888 Logvinov Jul 2005 B2
6927672 Zalitzky Aug 2005 B2
6949921 Feight Sep 2005 B1
6963197 Feight Nov 2005 B1
6980090 Mollenkopf Dec 2005 B2
7023691 Feight Apr 2006 B1
7046124 Cope May 2006 B2
7053601 Fenske May 2006 B1
7072163 McCollough, Jr. Jul 2006 B2
7076378 Huebner Jul 2006 B1
7085659 Peterson Aug 2006 B2
7106048 Feight Sep 2006 B1
7158012 Wiesman Jan 2007 B2
7187275 McCollough, Jr. Mar 2007 B2
7203622 Pan Apr 2007 B2
7272516 Wang Sep 2007 B2
7295133 McCollough, Jr. Nov 2007 B1
7304872 Yakymyshyn Dec 2007 B1
7355867 Shuey Apr 2008 B2
7400150 Cannon Jul 2008 B2
7424400 McCormack Sep 2008 B2
7449991 Mollenkopf Nov 2008 B2
7450000 Gidge Nov 2008 B2
7508638 Hooper Mar 2009 B2
7518529 Osullivan Apr 2009 B2
7532012 Cern May 2009 B2
7557563 Gunn Jul 2009 B2
7626794 Swartzendruber Dec 2009 B2
7633262 Lindsey Dec 2009 B2
7672812 Stoupis Mar 2010 B2
7683798 Rostron Mar 2010 B2
7701356 Curt Apr 2010 B2
7714592 Radtke May 2010 B2
7720619 Hou May 2010 B2
7725295 Stoupis May 2010 B2
7742393 Bonicatto Jun 2010 B2
7764943 Radtke Jul 2010 B2
7795877 Radtke Sep 2010 B2
7795994 Radtke Sep 2010 B2
7804280 Deaver, Sr. Sep 2010 B2
7930141 Banting Apr 2011 B2
8421444 Gunn Apr 2013 B2
8497781 Engelhardt Jul 2013 B2
8594956 Banting Nov 2013 B2
8786292 Parsons Jul 2014 B2
9182429 Saxby Nov 2015 B2
9229036 Kast Jan 2016 B2
9448257 Saxby et al. Sep 2016 B2
9581624 Rostron et al. Feb 2017 B2
9954354 Baker Apr 2018 B2
9984818 Rumrill May 2018 B2
20030146815 Zhou Aug 2003 A1
20040156154 Lazarovich Aug 2004 A1
20050073200 Divan Apr 2005 A1
20070109827 DelaCruz May 2007 A1
20080077336 Fernandes Mar 2008 A1
20090033293 Xing et al. Feb 2009 A1
20090058582 Webb Mar 2009 A1
20090309754 Bou Dec 2009 A1
20100085036 Banting Apr 2010 A1
20110032739 Juhlin Feb 2011 A1
20120039062 Mcbee Feb 2012 A1
20120236611 Alexandrov Sep 2012 A1
20130162136 Baldwin Jun 2013 A1
20140062221 Papastergiou Mar 2014 A1
20140145858 Miller May 2014 A1
20140174170 Davis Jun 2014 A1
20140192458 Valdes Jul 2014 A1
20140226366 Morokuma Aug 2014 A1
20140260598 Miller Sep 2014 A1
20150198667 Krekeler et al. Jul 2015 A1
20160061862 Nulty Mar 2016 A1
20160116505 Kast et al. Apr 2016 A1
20170047694 Huo Feb 2017 A1
20170199533 McCollough Jul 2017 A1
20170202087 Murray Jul 2017 A1
20180143234 Saxby May 2018 A1
20180316124 Fleming Nov 2018 A1
20200088772 Rumrill Mar 2020 A1
20200088779 Rumrill Mar 2020 A1
20200091721 Rumrill Mar 2020 A1
20200116772 Pierce et al. Apr 2020 A1
20200174048 Reader et al. Jun 2020 A1
20200191877 Petit Jun 2020 A1
Foreign Referenced Citations (5)
Number Date Country
104822192 Aug 2015 CN
1508146 Feb 2005 EP
2350764 Aug 2011 EP
1938159 Aug 2016 EP
2340592 Nov 2019 EP
Non-Patent Literature Citations (8)
Entry
Final office action received for U.S. Appl. No. 16/781,837, dated Jun. 28, 2022, 8 pages.
Chen et al.; Development of arc-guided protection devices against lightning breakage of covered conductors on distribution lines; IEEE Trans. Power Deliv.; 25(1); Jan. 2010; pp. 196-205.
Chen Yang Technologies; Split core hall effect dc current sensor CYHCT-C2TC; retrieved from the internet Jan. 5, 2015 (http://www.hallsensors.de/CYHCT-C2TC.pdf) (Product Information); 4 pages.
International Preliminary Report on Patentability received for PCT application No. PCT/US2020/016626, dated Aug. 19, 2021, 8 pages.
International search report and written opinion received for PCT application No. PCT/US2020/016626, dated Jun. 3, 2020, 8 pages.
Saha et al.; Fault Location on Power Networks (Power Systems); Springer-Verlag; London, UK; 2010 (Preface: Oct. 2009), 216 pgs.
Shepard et al.; An overview of rogowski coil current sensing technology; 13 pages.
Stringfield et al.; Fault location methods for overhead lines; in Transactions of the American Institute of Electrical Engineers; Amer Inst. of Electrical Eng.; New York, NY; Part. III; vol. 76; Aug. 1957; pp. 518-530.
Related Publications (1)
Number Date Country
20220103059 A1 Mar 2022 US
Provisional Applications (1)
Number Date Country
62800926 Feb 2019 US