Traditional fuses protect against unwanted voltage and/or current conditions but need to be replaced after blowing, requiring physical access to the blown fuse which may not always be practical. Moreover, changing equipment may require different fuse characteristics as well as opening the system and changing the fuse to match the equipment.
The use of traditional fuses can be an effective means of protecting wiring and/or equipment in a system from voltage and/or current conditions which can damage the wiring and/or equipment. Unfortunately, once the fuse disconnects the faulty equipment in the system by blowing, it must be physically reset and/or replaced. In systems that are difficult to access, the act of replacing the fuse alone can introduce risk to both the operator and the system and incur costly downtime.
An alternative technology to a physically blowable fuse called a resettable fuse can have the benefit of providing trip protection and does not need to be replaced under normal circumstances. However, a resettable fuse does not completely disconnect the faulty equipment and must actually maintain a slight connection or small amount of current to the faulty equipment in order to maintain its protective operation. A complete disconnection of the faulty equipment may be required for critical applications that require no current flow at all. The small amount of current allowed to flow could have detrimental effects on both the operator and the system itself. Over time this small amount of current can lead to corrosion that can ultimately damage the system. If a particular piece of equipment were to disallow the flow of enough current to keep a resettable fuse in its protective state, this type of fuse may continuously cycle on and off leading to possibly undesirable current spikes, not to mention unpredictable behavior of the equipment itself.
Both a traditional fuse and especially a resettable fuse do not have precisely predictable protection behavior. Traditional fuse characteristics are defined by a curve that is created by sample points of a given current and its associated time to blow. Both current and time are typically on a logarithmic scale. A reference to fast or slow blow fuses is defined by the slope or shape of the characteristic curve. At very small time bases of typically less than 1 millisecond, where adiabatic conditions prevail, a melting point or I2T value is given to describe its trip characteristic. Resettable fuses are typically defined by an allowable continuous current and a trip current with one sample current/protection time point. While the traditional fuse defines the curve based on average behavior, both the traditional and resettable fuse also reveal a variance in protection based on temperature. The protection dependence on temperature for a resettable fuse is especially pronounced. In testing of traditional fuses, the actual performance was significantly different than its provided curve, presumably since the curve is based on an average. Since the resettable fuse does not even provide a characteristic curve, the expected protection behavior is widely undefined.
Both types of fuses basically depend on the current through them to activate their protective behavior. The amount of current allowed to flow before the protection occurs can cause the source voltage powering the faulty device to drop significantly. If this source is shared with other working equipment, the voltage drop caused by the faulty equipment can be seen by and negatively affect the working equipment.
If a piece of equipment in the system is changed and its protection requirements are different, either type of fuse would need to be changed to match the new equipment. The same adverse issues of risk and cost to access and change the fuse would apply.
The various drawings herein illustrate aspects of the invention described herein.
Referring now to
Each controller 10 typically comprises active logic 12; memory 16 operatively in communication with active logic 12; and data resident in memory 16. Typically, there is a single controller 10 associated with a single programmable fuse 11.
Electrical circuit sensor 15 may comprise a source voltage sensor and/or a source current sensor operatively in communication with one or more electrical circuits 2 of the set of electrical circuits 2. Although illustrated as being disposed in electrical circuit 2 between solid state switch 13 and ground, electrical circuit sensors 15 may be disposed where and as needed.
As illustrated in
In certain embodiments, programmable fuse system 1 further comprises one or more relays 20 operatively in communication with a predetermined set of programmable fuses 11 of the plurality of individual programmable fuses 11 and with a predetermined set of associated devices 150. In these embodiments, each relay 20 may further be operatively connected to solid state switch 13 usually disposed in series with relay 20. If solid state switch 13 is present, one or more electrical circuit sensors 15 may be placed on either or both sides of solid state switch 13. Additionally, one or more switches 23, which may comprise mechanical and/or solid state switches, may be operatively in communication with one or more relays 20. Typically, each programmable fuse 11 has one relay 20 and one switch 23, which are coordinated with each other through individual control of each.
Programmable fuse 11 is typically able to remain completely disconnected until commanded to turn back on, such as by a command issued from controller 10. In
However, referring to
Referring additionally to
In the operation of exemplary embodiments, programmable fuse system 1 (
As described below, programmable fuse system 1 (
In general, a characteristic current/trip time curve is loaded into a data store of programmable fuse system 1 (
As described herein, programmable fuse system 1 (
An added benefit of having programmable fuse system 1 (
The basic idea of how programmable fuse system 1 (
Other basic fusing technologies could be used with some programmable means of selecting different values. By way of example and not limitation, a peak trip limit could be employed that does not necessarily follow a fuse but provides protection. Basic under-voltage lockout or short circuit technology may also be employed though it might not be programmable.
Referring back to
When a disconnect situation is encountered, an appropriate programmable fuse 11 is tripped, i.e. opened, such as if sensed voltage indicates a short circuit. Typically, if a disconnect command is to be sent, controller 10 sends a command to a predetermined programmable fuse 11 of the plurality of individual programmable fuses 11 that is operatively in electrical circuit 2 with the fault to completely disconnect that electrical circuit 2 without the need to physically replace programmable fuse 11 and without reliance on any small current to maintain circuit protection. If such a disconnect command is sent, electrical circuit 2 with the fault may then be kept completely disconnected until controller 10 issues a command to that programmable fuse 11 operatively in the electrical circuit 2 with the fault to reestablish electrical continuity in the electrical circuit 2 with the fault. It is understood that all such commands may be generated by each controller 10 independently or under the control, whether exclusive or cooperative, of master controller 100 (
The disconnect command may be sent at any time, including independently of a fault detection. Such disconnect commands may be operative to disconnect electrical circuit 2.
Controller 10 typically uses data resident in memory 16, the data representing one or more characteristic current/trip time curves, to determine if and when to issue a command to a programmable fuse 11 operatively in electrical circuit 2 with the fault to completely disconnect that electrical circuit 2. As noted above, these data may comprise data representative of protection tailored for an under-voltage and/or a short-circuit condition. By way of example and not limitation, the data resident in the memory may also represent a set of characteristic current/trip time curves, where curves are used to trip if current goes too high, with data operative to trip a programmable fuse if sensed voltage drops too low in order to prevent affecting working equipment that shares the same source voltage. It is noted that a voltage drop setting is typically separate from current/trip time curves.
In certain embodiments, data resident in memory 16 may be changed dynamically such as via computer 50 (
Further, a history of monitored current and source voltage may be accumulated by controller 10 and/or master controller 100 (
As noted above, and referring still to
In reality some amount of breaking current is actually recommended for a relay during its lifetime. The act of breaking current on a relay can clean oxidation from its contacts, ensuring better conductivity when it is closed. Programmable fuse system 1, therefore, may be programmed to periodically open relay 20 before one or both of solid state switch 13 and/or solid state switch 23. Typically, this occurs only if the breaking current is below the breaking capacity specification for relay 20. In preferred embodiments, relay 20 and solid state switch 23 operate in conjunction and cannot operate independently. In these embodiments, relay 20 can operate before solid state switch 13.
In various embodiments, data in the set of data may further comprise data sufficient to accommodate preventing damaging relay 20 when protecting against current that can exceed the breaking capacity of relay 20. In various embodiments, the predetermined breaking capacity of relay 2 is known. Once a switch, e.g. switch 13, is closed, then relay 20 is closed, allowing current to flow which can be measured. When programmable fuse 11 is tripped or otherwise opened, switch 13 is typically opened first because, as opposed to relay 20, switch 13 does not have a current limit for opening.
Occasionally, relay 20 may be opened first to allow a spark and de-oxidation of the relay contacts. Accordingly, the current may be checked first to make sure it does not exceed the breaking capacity of relay 20 before allowing relay 20 to open before switch 13.
In various embodiments, electrical circuit sensor 15 may be used to sense current in electrical circuit 2 and, if the sensed current is below the breaking capacity specification for relay 20 in communication with electrical circuit 2, controller 10, at a predetermined set of times such as are represented by data in memory 16, issues a command to open that relay 20 before its associated solid state switch 23. In these embodiments, electrical circuit sensor 15 may also be used to sense current in electrical circuit 2 and solid state switch 13 and/or solid state switch 23 opened first to break a detected high current in a precise manner, although switch 23 would not be opened first since this is the switch that operates relay 20. Switch 13 would open first, then the relay. Once the high current is diminished, relay 20 may be opened to allow a complete disconnection from the fault. It is noted that this sequencing may operate to extend the useful life of relay 20 such as by having its contacts de-oxidized by electrical arcing.
If relay 20 is present, electrical continuity may be restored by issuing a command from controller 10 to relay 20 to reenergize relay 20. Relay bounce may be ameliorated or even eliminated on restoring electrical continuity by turning relay 20 on first followed by solid state switch 13.
The foregoing disclosure and description of the inventions are illustrative and explanatory. Various changes in the size, shape, and materials, as well as in the details of the illustrative construction and/or an illustrative method may be made without departing from the spirit of the invention.
This application claims the benefit of, and priority through, U.S. Provisional Application 62/016,931, titled “Programmable Fuse With Under-voltage/short-circuit Protection,” filed Nov. 25, 2014.