1. Technical Field
This disclosure relates to controls for modulating gas valves of modulating gas furnace. More specifically, in a modulating gas with an integrated furnace control (IFC), the furnace may enter a lockout mode for any one or more of a variety of safety reasons.
2. Description of the Related Art
Modern gas furnaces are equipped with various safety features which typically include a flame proving sensor, pressure switches and limit switches. A flame sensor or flame sensing electrode detects the presence of a flame at the burner during both on and off cycles. Pressure and limit switches are used to detect abnormal pressures, temperatures or other abnormal operating conditions and prevent the burners from operating if an abnormal condition is detected. A typical gas furnace could have four or more limit switches in various locations throughout the furnace. When these limit switches trip or open, the furnace control board shuts the gas valve and may engage the main blower and the draft induced blower to dissipate as much heat as possible away from the furnace and its heat exchangers if the condition involves temperatures that exceed a predetermined safety limit.
Some of these limit switches reset themselves when the temperature or other sensed condition return to normal. After a reset of a pressure or limit switch, the integrated furnace control (IFC) board may give a small time delay before allowing the gas burners to reignite. Heat will be restored and the gas burners will continue to provide heat until the thermostat satisfies the desired room temperature or until another safety limit is reached.
At the start of a heat cycle, the IFC board may execute a limited number of attempts to light the burners, typically three to four times depending on the manufacturer and the engineering safety limits of IFC. If the IFC detects ignition failure after the limited number of attempts, it may lock the system out for a specific amount of time (e.g., 3 to 4 hours) depending on the engineering safety limits of the IFC board. After the predetermined time period, the IFC will again try for ignition unless a safety circuit is open. The IFC may stay in a permanent lockout mode until the problem is resolved, usually by an HVAC technician.
After ignition when the blower turns on, the IFC board may confirm that the blower motor turned ON by checking the blower RPM. If the blower RPM is not above a minimum RPM limit within a prescribed time period, the IFC will shut down. After a small time delay the IFC will try again and if the blower does not turn ON during a second attempt the IFC may lock the system out for a specific amount of time (e.g., 3 to 4 hours). After the predetermined time period, the IFC will again try to operate unless a safety circuit is open. The IFC may also confirm that the gas valve is not energized at the wrong time due to a short circuit or miswire. If the gas valve is energized at the wrong time due to a short circuit or miswire the IFC may engage the draft induced blower and enter a permanent lockout mode until the problem is resolved, usually by an HVAC technician.
Modern gas furnaces also include single-stage, two-stage or modulating gas valves as a part of the burner control. Single-stage burners operate with very little flexibility. The burner is fully on or operating at full heat or fully off and the ability to modify the gas flow rate delivered to the burner through the gas valve may be limited. Two-stage burners may provide two very different operational modes. During mild winter weather when the demand for heat in the home is low, the burner and gas valve operate at low stage. During colder temperatures, when the heat loss in the home is at its greatest, the burner and gas valve adjust to the high stage. Two-stage systems may cycle the furnace on and off more effectively, offering increased energy savings compared to single-stage furnaces.
Modulating burner systems have the most flexibility in adjusting to heating requirements. A modulating gas valve raises and lowers the flow rate to the burner in response to the heating demand. Modulating burner/gas valve systems may provide improved efficiency and comfort in comparison to single-stage and two-stage burner/gas valve systems.
A method is disclosed for closing a modulating gas valve of a furnace that includes a regulator with a regulator adjustment screw that is coupled between a stepper motor and a servo diaphragm. Movement of the servo diaphragm controls movement of the main diaphragm and the regulator seat. The disclosed method comprises detecting an abnormal operating condition that calls for turning the furnace off, sending a signal to a controller that is linked to the stepper motor to move the stepper motor to a home position which results in closure of the regulator seat of the gas valve.
A system for modulating gas flow through a gas valve of a gas furnace is also disclosed that comprises a furnace control linked to a gas valve. The gas valve comprises a regulator seat coupled to a main diaphragm. The gas valve further comprises a seat for receiving the regulator seat when the regulator seat is in a closed position. The regulator seat is coupled to a regulator spring that biases the regulator seat towards the closed position. The gas valve further comprises a regulator for controlling movement of the main diaphragm. The regulator comprises a servo diaphragm that is coupled to an adjustment screw by a regulator spring. The adjustment screw is coupled to a stepper motor. The stepper motor is linked to the furnace control. The furnace control is programmed to send a home command to the stepper motor when an abnormal operating condition is detected. The home signal causes the stepper motor to move to a home position which reduces the force on the servo diaphragm and in turn causes the main diaphragm to move the regulator seat to a closed position.
A furnace incorporating the disclosed system or including a furnace control programmed to carry out the disclosed method is also part of this disclosure.
Other advantages and features will be apparent from the following detailed description when read in conjunction with the attached drawings.
For a more complete understanding of the disclosed methods and apparatuses, reference should be made to the embodiments illustrated in greater detail in the accompanying drawings, wherein:
It should be understood that the drawings are not necessarily to scale and that the disclosed embodiments are sometimes illustrated diagrammatically and in partial views. In certain instances, details which are not necessary for an understanding of the disclosed methods and apparatuses or which render other details difficult to perceive may have been omitted. It should be understood, of course, that this disclosure is not limited to the particular embodiments illustrated herein.
Referring now to
The relatively cool exhaust gases then pass through the collector box 16 and the exhaust vent 17 before being vented to the atmosphere, while the condensate flows from the collector box 16 and through a condensate drain line 22 for disposal. Flow of combustion air into the air inlet 19 and through the heat exchangers 13, 14 and the exhaust vent 17 is enhanced by a draft induced blower 23, which is driven by a variable speed inducer motor 24 in response to control signals from an integrated furnace control (IFC) 29 and pressure switches 31, 32. The household air is drawn into a blower 26 which is driven by a variable speed blower motor 27, in response to signals received from the integrated furnace control (IFC) 29.
The discharge air from the blower 26 passes over the condensing heat exchanger 14 and the primary heat exchanger 13, in a counter-flow relationship with the hot combustion gases to thereby heat indoor air, which then flows from a discharge opening 28 to the duct system within the space being heated.
Referring now to
After passing through the redundant valve 47 and the main valve 43, the gas flow 40 then moves towards a regulator seat 44, which may be biased towards a closed position by regulator spring 82. Movement of the regulator seat 44 and the gas flow 40 through the regulator seat 44 may be controlled by a main diaphragm 48, which in turn may be controlled by a servo diaphragm 64, as described below. The main diaphragm 48 may divide the space downstream of the regulator seat 44 into a lower chamber 52, disposed below the diaphragm 48, and an upper chamber 50, disposed above the main diaphragm 48. Changes in gas pressure in the upper chamber 50 and/or the lower chamber 52 may control the movement of the main diaphragm 48 and the regulator seat 44, which may be connected to the main diaphragm 48 by a rod 51. The main diaphragm 48 may adjust the degree of opening and closing of the regulator seat 44 in response to pressure differentials between the upper and lower chambers 50, 52, respectively, and may therefore adjust the gas flow 40 through an outlet 45 and to the burner assembly 11 (not shown in
Still referring to
For example, referring to
In contrast, when the stepper motor 49 receives a signal through the IFC 29 and the stepper motor control 42 to lower the adjustment screw 61, more of the gas flow 40 through the control chamber 60 may be diverted to the lower chamber 52 and less flow may be diverted to the upper chamber 50. As a result, the pressure in the lower chamber 52 may be increased in comparison with the pressure in the upper chamber 50 and, the main diaphragm 48 may move upward, thereby moving the regulator seat 44 towards a more open position.
Referring now to
When the furnace 10 is in a lockout mode due to a safety issue or concern, such as: (1) when an abnormal flame indication is sensed at the flame sensor electrode (FSE) 83, (2) a failure to ignite gas after four attempts, (3) when the gas valve is energized at the wrong time due to a short circuit or miswire, (4) a failed blower motor, (5) an open pressure or limit switch, such as, a low gas pressure switch 85, a low pressure switch 86, a draft safeguard switch 89, a flame rollout switch 90 or a limit switch 91 (
In the event the IFC 29 enters a lockout mode for any one or more of a variety of safety reasons, the IFC 29 may be programmed to send a home signal to the stepper motor 49 to close the regulator seat 44, thereby reducing the outlet pressure of the gas valve 18 to zero or near zero. Even thought the IFC 29 may have several different safety lockout modes, wherein the IFC 29 prevents a heating operation for a set time period (typically 3 hours or until power is reset), an additional home command from the IFC 29 may allow the modulating gas valve 18 to position itself to a reference point such that the outlet pressure would approach zero pressure, even when the gas valve is energized at the wrong time due to a short circuit or miswire, or even mechanically stuck in the on position. By using the disclosed home command, an additional safety redundancy may be provided whenever the furnace 10 enters a lockout mode.
Further, the IFC 29 may monitor the flame proving input at the flame sensor electrode (FSE) 83 even during an off-cycle. In the event that the gas valve 18 fails to open, the IFC 29 may be programmed to sense the flame after the call for heat has ended and may turn inducer motor 24 on and flash a fault code until the flame signal is no longer present. On a modulating furnace 10 that employs a modulating gas valve 18 with a stepper motor 49, the disclosed home command allows the modulating gas valve 18 to position itself to a reference point such that the outlet pressure would approach zero pressure when the valve 18 is on or, in this case, stuck open. By using the disclosed home command, an additional safety redundancy is provided when an abnormal flame is sensed at the FSE 83.
While only certain embodiments have been set forth, alternatives and modifications will be apparent from the above description to those skilled in the art. These and other alternatives are considered equivalents and within the spirit and scope of this disclosure and the appended claims.
This is a non-provisional U.S. patent application, which claims priority under 35 U.S.C. §119(e) to U.S. Provisional Patent Application Ser. No. 61/331,135 filed on May 4, 2010, the entirety of which is incorporated by reference herein.
Number | Date | Country | |
---|---|---|---|
61331135 | May 2010 | US |