Stationary fire fighting systems have been developed for use in structures, chemical facilities and petrochemical plants for manufacturing or storage, such as existing buildings or new buildings, enclosed chemical plants, or enclosed or outdoor storage or manufacturing facilities. Stationary fire fighting systems with foam proportioning capabilities generally include a water flow meter, a controller, and a foam pump. The controller operates the foam pump based on the signal from the water flow meter to supply liquid foam concentrate or foamant to a water stream. The mixed foamant and water is then delivered through pipes in the building and sprayed with sprinklers to extinguish the fire. Currently, stationary foam proportioning systems use venturi-based technologies, such as in-line eductors, around-the-pump eductors, balanced-pressure systems, and other fixed-delivery mechanisms. However, these technologies can cause an undesirable pressure drop in water pressure. Reduced water pressure causes operating problems because the length of some pipes in buildings can be 400 to 500 feet or longer. To maintain full flow and maximize the effectiveness of the mixture being sprayed with the sprinklers, water pressure drop should be minimized.
In addition, balanced-pressure systems can be difficult to maintain. Bladder-type systems must be cleaned, the foamant must be disposed of, and the pressure vessels must be tested and reworked. During this maintenance time, the fire fighting system cannot be used and the building is left without protection. This maintenance work is also expensive, time consuming, and can cause environmental problems due to discarded foamant. During operation, balanced-pressure type foamant systems that use positive displacement pumps often “by-pass” foamant or recirculate foamant back to the foamant tank, which causes undesirable foaming and possible degradation of the new foamant in the tank.
Some embodiments of the invention provide a redundant stationary fire fighting system and d method for use in a structure. The system is coupled to a water supply and a main water pump that generates a water stream. The system can include one or more water flow meters to measure the water stream and generate a water flow signal. The system can include a primary foam proportioning system including a first foam pump, a first motor, a first foam flow meter, and a first controller. The first controller can be configured to automatically operate the first foam pump based on the water flow signal in order to inject liquid foam concentrate directly into the water stream. The system can also include a redundant secondary foam proportioning system including a second foam pump, a second motor, a second foam flow meter, and a second controller. The redundant secondary foam proportioning system can be automatically started in case of component failure in the primary foam proportioning system. The second controller can be configured to automatically operate the second foam pump based on the water flow signal in order to inject liquid foam concentrate directly into the water stream.
Before any embodiments of the invention are explained in detail, it is to be understood that the invention is not limited in its application to the details of construction and the arrangement of components set forth in the following description or illustrated in the following drawings. The invention is capable of other embodiments and of being practiced or of being carried out in various ways. Also, it is to be understood that the phraseology and terminology used herein is for the purpose of description and should not be regarded as limiting. The use of “including,” “comprising,” or “having” and variations thereof herein is meant to encompass the items listed thereafter and equivalents thereof as well as additional items. Unless specified or limited otherwise, the terms “mounted,” “connected,” “supported,” and “coupled” and variations thereof are used broadly and encompass both direct and indirect mountings, connections, supports, and couplings. Further, “connected” and “coupled” are not restricted to physical or mechanical connections or couplings.
The following discussion is presented to enable a person skilled in the art to make and use embodiments of the invention. Various modifications to the illustrated embodiments will be readily apparent to those skilled in the art, and the generic principles herein can be applied to other embodiments and applications without departing from embodiments of the invention. Thus, embodiments of the invention are not intended to be limited to embodiments shown, but are to be accorded the widest scope consistent with the principles and features disclosed herein. The following detailed description is to be read with reference to the figures, in which like elements in different figures have like reference numerals. The figures, which are not necessarily to scale, depict selected embodiments and are not intended to limit the scope of embodiments of the invention. Skilled artisans will recognize the examples provided herein have many useful alternatives and fall within the scope of embodiments of the invention.
The additive, such as foam concentrate, can be in the form of a liquid, gas, powder, or solid. In some embodiments, the system 100 can be configured for use with Class A foam concentrate capable of suppressing Class A fires. Class A fires include fires involving ordinary combustible, such as, for example, paper, wood, cloth, grass, etc. Additionally or alternatively, the system 100 can be configured for use with Class B foam concentrate capable of suppressing Class B fires (i.e., fires involving flammable liquids), as well as other types of foam concentrates. In general, the system 100 can be compatible with Class A, Class B, and other types of foam concentrate. Also, rather than foam concentrate, the system 100 can be compatible with other types of additives that help fight fires. In addition, the system 10 can be configured to comply with the following standards: NFPA 1145, NFPA 1150, NFPA 13, NFPA 13D, NFPA 13E, NFPA 13R, NFPA 11, NFPA 16, NFPA 20, NFPA 72, NFPA 409, UL 162, UL 199, UL 1626, FM 2030, as well as other fire suppression foam equipment standards.
As shown in
The primary system 102 can also include a display controller 130, a control driver 132, a variable frequency drive 134, and an AC to DC converter 136. In one embodiment, the display controller 130, the control driver 132, and the AC to DC converter 136 can be housed together in a first enclosure 138 (e.g., the enclosure shown and described in U.S. patent application Ser. No. 12/077,982). In one embodiment, the first mounting skid 110 with the foam pump 106 and motor 108 can be positioned inside a bottom portion of the first enclosure 138. In some embodiments, the display controller 130, the control driver 132, and the AC to DC converter 136 can be integrated with the variable frequency drive 134.
In some embodiments, the foam pump 106 can be an electronic, fully automatic, variable speed, direct injection, discharge side pump. The foam pump 106 can be a positive displacement pump coupled to the motor 108, and the variable frequency drive 134. In general, positive-displacement pumps displace a known quantity of liquid with each revolution of the pumping elements. This is done by trapping liquid between the pumping elements and a stationary casing. Pumping element designs can include gears, lobes, rotary pistons, vanes, and screws. Positive-displacement pumps also have relatively compact designs, high-viscosity performance, continuous flow regardless of differential pressure, and the ability to handle high differential pressure. In some embodiments, the positive displacement pump can operate at over 500 gpm and over 300 psi. In some embodiments, the positive displacement pump can operate at up to about 400 psi. In some embodiments, the foam pump 106 can include a self-test capability.
The motor 108 can be an AC type motor coupled to the positive displacement pump 106. The variable frequency drive 134 can be mounted to a base of the pump 106 or the motor 108 and can receive signals from the display controller 130 to control the motor 108. The variable frequency drive 134 can use a variable speed duty cycle and/or closed-loop control to ensure that the correct proportion of foamant (e.g., as preset by an operator) is injected into the water stream.
In some embodiments, the display controller 130 can be a digital electronic display suitable for installation on a panel of the first enclosure 138. The display controller 130 can include a microprocessor that receives inputs from the first water flow meter 116 via a line 140. The water flow meter 116 can be a paddlewheel-type flow sensor. The display controller 130 can also be connected to the control driver 132 via a line 142. In some embodiments, the display controller 130 can be configured to display or perform one or more of the following operations: display the current flow-per-minute of water; display the total volume of water discharged during and after operations are completed; display the total amount of additive consumed; display the total amount of additive remaining; simulate flow rates for manual operation and/or remote testing; perform setup, calibration, and diagnostic functions for installation and testing; display and report a “low concentrate” warning when an additive supply tank runs low; display and report a “no concentrate” warning and shut the positive displacement pump off, preventing damage to the pump 106 should the additive supply tank become empty; display and report a “power fault” when the system 100 loses an electrical power connection; and/or display and report a “test fault” when the system 100 fails any self diagnostic tests. In some embodiments, some information from the display controller 130, such as the additive level, the additive flow rate, the water flow rate, the operating mode, and the power supply status, can be remotely readable over a suitable network.
An AC input power line 144 can connect the primary system 102 to the AC to DC converter 136 in order to provide a dedicated circuit capable of providing AC or DC power, such as 120 VAC power. The AC input power line 144 can also be connected to the variable frequency drive 134. In one embodiment, the maximum power used by the primary system 102 can be less than about 1200 Watts and 10 amps in an active state (i.e., running or operating state) and less than about 24 Watts and 200 milliamps in the quiescent state (i.e., non-operating state).
The variable frequency drive 134 can be connected to the motor 108 via a line 146, to the control driver 132 via a line 148, to the foam flow meter 126 via a line 150, and to the display controller 130 via lines 152 and 153. The control driver 132 can be connected to the display controller 130 via the line 142, to the variable frequency drive 134 via the line 148, to the foam flow meter 126 via the line 150, to the AC to DC converter via a line 154.
The redundant secondary system 104 can include generally the same components as the primary system 102, as also shown in
The redundant secondary system 104 can also include a display controller 230, a control driver 232, a variable frequency drive 234, and an AC to DC converter 236. In one embodiment, the display controller 230, the control driver 232, and the AC to DC converter 236 can be housed together in a second enclosure 238 (e.g., the enclosure shown and described in U.S. patent application Ser. No. 12/077,982). In one embodiment, the second mounting skid 210 with the foam pump 206 and motor 208 can be positioned inside a bottom portion of the second enclosure 238.
The display controller 230 can include a microprocessor that receives inputs from the second water flow meter 118 via a line 240. The display controller 230 can also be connected to the control driver 232 via a line 242.
An AC input power line 244 can connect the redundant secondary system 104 to the AC to DC converter 236 in order to provide a dedicated circuit capable of providing AC or DC power, such as 120 VAC power. The AC input power line 244 can also be connected to the variable frequency drive 234.
The variable frequency drive 234 can be connected to the motor 208 via a line 246, to the control driver 232 via a line 248, to the foam flow meter 226 via a line 250, and to the display controller 230 via lines 252 and 253. The control driver 232 can be connected to the display controller 230 via the line 242, to the variable frequency drive 234 via the line 248, to the foam flow meter 226 via the line 250, and to the AC to DC converter via a line 254.
In some embodiments, while operating the primary system 102, the flow meter 116 supplies flow information to the display controller 130 to determine the water volume to treat. The display controller 130 varies the control signal sent via the line 153 to the variable frequency drive 134 to proportionally vary the speed of the positive displacement foam pump 106. The positive displacement foam pump 106 can inject foam concentrate directly into the high pressure water stream (flowing through the pipe 114) with no flow restrictions and no loss of line pressure. The positive displacement foam pump 106 can also eliminate the need for recirculating foam to the foam tank (not shown) and does not require extensive maintenance or incur environmental problems associated with calibration. In case of failure of the flow meter 116, the display controller 130, and/or the foam pump 106, the variable frequency drive 134 can automatically transfer control to the redundant secondary system 104.
The foam flowing out of the foam pump 106 passes through the foam flow meter 126 which generates (at 316) a digital pulse signal via the line 150 to the control driver 132 and to the variable frequency drive 134. The variable frequency drive 134 uses the digital pulse signal to verify that foam is flowing and to continue operations. The control driver 132 and display controller 130 compare the digital pulse signal generated by the foam flow meter 126 and recalculate (at 318) the foamant requirement in order to adjust the signal sent to the variable frequency drive 134 to increase or decrease the speed of the foam pump 106 so that it matches the expected foam output. The process is repeated by returning to step 308 and is updated substantially continuously during operation to ensure the proper amount of foamant is injected into the water stream over a wide range of water flow rates.
If no signal is received by variable frequency drive 134 from the foam flow meter 126, a water delay timer can be started (at 320). The water delay timer operates (at 322) until the delay time period has expired (at 324). After the delay time period has expired, the variable frequency drive 134 can try to detect (at 326) pulses from the foam flow meter 126. If no pulses are detected, the variable frequency drive 134 can shut down (at 328) operation of the primary system 102 and can send a signal to the redundant secondary system 104 to automatically start and/or can signal an operator that the primary system 102 is not operating properly. For example, the variable frequency drive 134 can send a signal to the display controller 230 to enable and start the process control through the redundant secondary system 104. If redundant secondary system 104 does not start, an alarm can be generated or a third foam proportioning system can be started.
Some embodiments of the system 100 can help prevent pressure drops, maintenance issues, and recirculation problems. Some embodiments of the system 100 allow a technician to test or service the system 100 using a simulated flow feature in the display controller 130 or 230 to simulate water flow. By using the calibrate/inject valve 128 or 228, the foam flow can be diverted to a container or vessel for quality testing, calibration testing, or system testing. This can be done in a service mode without actually running the main water stream or wasting valuable foam concentrate or incurring environmental disposal risk.
Other features of the system 100 include, but are not limited to, tracking the amount of water used, tracking the amount of foam concentrate used, checking for adequate levels of foam supplying the foam pump 106, and automatically stopping operations when water flow stops.
It will be appreciated by those skilled in the art that while the invention has been described above in connection with particular embodiments and examples, the invention is not necessarily so limited, and that numerous other embodiments, examples, uses, modifications and departures from the embodiments, examples and uses are intended to be encompassed by the claims attached hereto. The entire disclosure of each patent and publication cited herein is incorporated by reference, as if each such patent or publication were individually incorporated by reference herein. Various features and advantages of the invention are set forth in the following claims.
Number | Name | Date | Kind |
---|---|---|---|
3940931 | Renfro et al. | Mar 1976 | A |
3973257 | Rowe | Aug 1976 | A |
4474680 | Kroll | Oct 1984 | A |
5232052 | Arvidson et al. | Aug 1993 | A |
5494112 | Arvidson et al. | Feb 1996 | A |
6684959 | Juidici et al. | Feb 2004 | B1 |
20080236846 | Gamble et al. | Oct 2008 | A1 |
20090200045 | Hosfield et al. | Aug 2009 | A1 |
Number | Date | Country | |
---|---|---|---|
20120061107 A1 | Mar 2012 | US |