The present invention relates to load management and balancing systems operating in conjunction with a renewable energy source such as one or more photovoltaic solar energy panels and methods of their operation.
Adoption of renewable energy is becoming very popular across the globe. Distributed energy generation employing photovoltaic solar energy systems is gaining popularity as the cost of these systems are coming down. However due to the varying nature of the solar radiation, even during the day time, a majority of the photovoltaic solar energy systems rely on an expensive battery storage subsystem and inefficiently manage the load connected to the system in order to store the direct current (DC) energy which is then converted to usable alternating current (AC) energy using a DC-AC inverter subsystem.
Currently radiation meters located in the site near the solar panels provide an estimate of the available power in a location. However such estimates are not specific to the solar panels and does not take into account various factors that may affect the output of a solar panel.
Disclosed herein is a load management circuit that is configured to work in conjunction with a solar energy system with one or more photovoltaic generators and associated DC-AC inverters. In the off-grid mode of operation of the system, the load management circuit is configured to constantly monitor the power demand from the active load circuits and the available power from the photo voltaic generators and manage the active load circuits in a manner such that the power demand from the active loads does not exceed the available power.
Also disclosed is a programmable load balancing algorithm residing in one of the DC-AC inverters designated as the master to enable sharing of the load by all the DC-AC inverters in a balanced manner through communication with the remaining DC-AC inverters in the array. During the off-grid mode of operation of the solar energy system, the algorithm computes the total power demand from the system and allocates a power limit for each one of the DC-AC inverters in the system and communicates the limit to each one of the DC-AC inverters through power-line communication.
This summary is provided to introduce a selection of concepts in a simplified form described below in the detailed description. This summary is not intended to identify key features or essential features of the claimed subject matter, nor is it intended to be used to limit the scope of claimed subject matter.
The detailed description is set forth with reference to the accompanying figures. In the figures, the left-most digit(s) of a reference number identifies the figure in which the reference number first appears. The use of the same reference numbers in different figures indicates similar or identical components or features.
In the following detailed description of embodiments, specific detailed examples are given in order to provide an understanding of the embodiments. However, it is to be appreciated that the embodiments may be practiced without these specific details. Furthermore, the techniques and systems disclosed herein are limited to the described embodiments. Numerous modifications, changes, variation, substitutions and equivalents will be apparent to those skilled in the art.
The DC voltage output from the PV sources Vdc1,2,3 . . . N are connected to the input 103-1,2,3 . . . N of the DC-AC inverters 105-1,2,3 . . . N. In the off-grid mode of operation of the solar energy system, the AC output 107-1,2,3 . . . N are connected to the off-grid voltage Vac bus 108.
The communication modules 111-1,2,3 . . . N of the DC-AC inverters 105-1,2,3 . . . N are interconnected via data links 135-1,2,3 . . . N and are in turn connected to the communication module 126 of the of the controller subsystem 127 of the load manager circuit 109 via the data link 136.
The controller subsystem 127 in the load manager circuit 109 is configured to sense the presence or absence of grid voltage 123, and/or sense off-grid voltage 129, and to receive inputs from the AC load current sensors 119-1,2,3 . . . M, and input DC voltage values Vdc1,2,3 . . . N from the from the DC-AC inverters 105-1,2,3 . . . N.
When the grid voltage Vgrid is present, the load manger circuit is connected to the grid via link 115 and selector relay 117. In this case the load manager simply acts like a pass-through and allows all the load segments 137 to be connected to the grid.
When the grid voltage Vgrid is absent, the load manger circuit operates in the off-grid mode. In the off-grid mode of operation of the solar energy system, the off-grid voltage Vac bus 108 is connected to the selector relay 117 through connector 113, and the selector relay 117 is connected to the load selector relays 118-1,2,3 . . . M of the load selector 118. The load selector relays 118-1,2,3 . . . M are associated with the load segments 137-1,2,3 . . . M respectively. Each of the load segments 137-1,2,3 . . . M may be assigned a priority which may be stored in the controller subsystem 127 of the load management circuit 109. The AC load current sensors 119-1,2,3 . . . M are configured to measure the AC current in the load segments 137-1,2,3 . . . M respectively and transmit the values of measured AC current to the controller subsystem 127.
One of the DC-AC inverters 105-1,2,3 . . . N may be designated as the master (for example 105-1 in this example). The designated master is configured to receive the AC current output from each of the other DC-AC inverters 105-2,3 . . . N, compute the total power demanded from the PV solar energy system 100 and allocate the power demand to each of the DC-AC inverters 105 in a balanced manner by setting a current limit for each one of the other DC-AC inverters 105-2,3 . . . N and communicating the current limit to the other DC-AC inverters 105-2,3 . . . N via the data links 135-1,2,3 . . . N.
The horizontal axis represents the DC voltage output of the solar panel, for example the solar panel may be a 60 or 72 cell polycrystalline solar module representing any one of the PV sources 101-1, 101-2, 101-3, . . . 101-N in the example photovoltaic (PV) solar energy system 100, which ranges from 0 to 40 Volts DC in this example. The vertical axis represents the corresponding solar power in watts that can be generated from the solar panel at different solar radiation levels ranging from 400 W/m2 (watts/meter squared) to 1000 W/m2·in this example. Photovoltaic solar energy systems are designed to operate in the voltage range to the right of the DC output voltage corresponding to the peak power points (P1, P2, P3 and P4 in this example). The DC output voltage range to the left of the peak power points (P1, P2, P3 and P4 in this example) is considered a non-operating region as shown in
Focusing on the operating range (30-40 Volt in this example), for a given radiation level, as the power drawn by the load connected to the solar panel increases, the DC output voltage decreases along the Power Vs. Voltage curve corresponding to the radiation level. In the case of a fully characterized solar panel (Power vs. Voltage curves at different radiation levels), a predictive algorithm may predict the total available power from the solar panel employing the measured DC voltage of the panel at a known level of power drawn from the panel by the connected load.
The illustration of the “Zoomed view of voltage vs. Power curve at 50 W load” in
Table 1 is an example of Power available computed employing the predictive algorithm and real time data of Solar panel voltage and the load power drawn at four different power output levels drawn from the solar panel.
From the data available in the look up table, it is possible to derive an empirical relationship between total power available and solar panel voltage and power drawn from the panel at any given time. In the case of look up tables, interpolation techniques can be used with the values from the look up tables to get more accurate values for the available power from the PV source.
Such lookup tables or empirical formula representing the look up table for each of the solar PV sources 101-1,2,3 . . . N may be computed and stored in the DC-AC inverters 105-1,2,3 . . . N or the controller subsystem 127 of load manager circuit 109 associated with the solar energy system 100, and these lookup tables or empirical formula can be readily used to determine the available power PAV-i for each of the PV source “i”. The total available power for the PV solar energy system 100 PAV-Total may be computed by summation of the available power from each PV source 101-1,2,3 . . . N (PAV-Total=PAV-1+PAV-2+PAV-3+ . . . PAV-N).
In step 302 the system initialization parameters are set to appropriate values. The number of DC-AC inverters in the system is set to value N, the number of load segments is set to value M. An excess power threshold value PEx and a reserve power threshold value PRes are set to appropriate values. As an example for a Photovoltaic solar energy system of 3000 Watts capacity, N may be set to 10 (each inverter with 300 W capacity, for example), M may be set to 4 (the load circuits segmented into 4 segments), the excess power threshold PEx may be set to 500 Watts, and the reserve power threshold value PRes may be set to 100 Watts. At the system start-up, the highest priority load segment may be set to active status through selector switch 118-1 and all other segments may be set to inactive status though selector switches 118-2,3, . . . M. Set the active segment value Q−1 and set timer value t=0.
In step 304 the total power demand PD-Total from the active load segments is computed. For this computation the off-grid bus voltage Vac, AC current sensor 119-1,2,3 . . . M output values Iac-1, Iac-2, Iac-3, . . . Iac-M are acquired and total power demand is computed as PD-Total=Vac (Iac-1+Iac-2+Iac-3+ . . . +Iac-M). For the example system, Vac may be equal to 220 Volts, and (Iac-1+Iac-2+Iac-3+ . . . +Iac-M) value may be equal to 4 amps, representing a total power demand PD-Total equal to 880 Watts.
In step 306 the total available power PAV-Total for the system is computed. The DC voltage input for each inverter Vdc-1, Vdc-2, Vdc-3 . . . Vdc-N, is combined with the corresponding DC current values Idc-1, Idc-2, Idc-3, . . . Iac-N and used to compute the DC power drawn from each PV source Pdc-1, Pdc-2, Pdc-3 . . . Pdc-N. Using the power and the associated DC voltage values, the available power from each PV source PAV-1, PAV-2, PAV-3 . . . PAV-N is computed from the look up table (e.g., Table 1), as discussed in the previous section. Total available power for the system is then computed as PAV-Total=PAV-1+PAV-2+PAV-3 . . . +PAV-N. For the example system, PAV-Total may be equal to 1200 Watts.
In step 308 systems ability to activate a load segment that is not currently active is determined based on a comparison of total available power PAV-Total with the total power demand PD-Total+excess power threshold, PEx. If it is determined, based on the comparison at step 308, that PAV-Total is greater than PD-Total+PEx, then the process 300 follows the “yes” route from step 308 to step 309 where selector switch with the highest priority among the ones which are currently inactive will be activated and the corresponding load segment connected to the system output.
If, at step 308, PAV-Total is not greater than PD-Total+PEx, then the process 300 follows the “no” route from step 308 to step 310, where the system ability to de-activate a load segment that is currently active is determined based on a comparison of the total available power PAV-Total with the total power demand PD-Total+a reserve power threshold, PRes. If it is determined, based on the comparison at step 310, that PAV-Total is less than PD-Total+PRes, then process 300 follows the “yes” route from step 310 to step 311 where the selector switch with the lowest priority among the ones which are currently active will be deactivated and the corresponding load segment disconnected from the system output.
Either following the “no” route from step 310, after activating the highest priority selector switch at step 309, or after deactivating the lowest priority selector switch at step 311, the process 300 proceeds to step 312 to repeat the steps 304 to 310 in periodic intervals of time Δt in order to continuously monitor the power available from solar energy sources 101-1,2, 3 . . . N connected to the DC-AC inverters 105-1,2,3 . . . N and power demand from the active loads 137-1,2,3 . . . M connected to the load manager circuit 109, and actively managing the loads such that total demanded power PD-Total is less than the total available power PAV-Total.
In step 402 the system initialization parameters are set to appropriate values. The number of DC-AC inverters 105 in the system is set to value N, and one of the DC-AC inverters 105-1 is designated as the master. A low voltage threshold Vac-L-T value and a high voltage threshold value Vac-H-T are set. As an example Vac-L-T may be set to 205 volts and Vac-H-T may be set to 235 volts. In this step, a current increment or decrement size ΔI is set. As an example ΔI may be set to 25 milli amps. Set inverter current buffer value Iac-Buffer. As an example the value of Iac-Buffer may be set as 100 milli amps. A time interval Δt at which the balancing process is repeated is also set at this step. As an example the value of Δt may be set as 400 milli seconds. Set initial timer value t=0.
In step 404 total AC current drawn Iac-Total by the loads is computed as the sum of current values Iac-1, Iac-2, Iac-3, . . . Iac-M from the current sensors 119-1, 119-2, 119-3 . . . 119-M respectively. This total AC current value Iac-Total is allocated to each inverter as a current limit value Iac-limit. As an example the total AC current value Iac-Total may be allocated substantially equally to each of the N inverters 105 in the system.
In step 405, the inverter 105-1 designated as the master is set to operate in the voltage control mode within the operating voltage range of Vac-L-T<Vac<Vac-H-T and the current limit value Iac-limit set to (Iac-Total÷N.)+Iac-Buffer. Examples of operating in the voltage control mode is described in U.S. Pat. No. 9,444,366, entitled “DUAL MODE MICRO-INVERTER SYSTEM AND OPERATION,” and U.S. Pat. No. 9,590,528, entitled “DUAL MODE DC-AC INVERTER SYSTEM AND OPERATION,” the contents of which are herein incorporated by reference.
In step 406 the AC bus voltage Vac is compared with low voltage threshold Vac-L-T value. If it is determined, based on the comparison at step 406 Vac is less than Vac-L-T then the process 400 follows the “yes” route from step 406 to 407, where the current injected by inverter “x” is incremented by value ΔI.
If it is determined, based on the comparison at step 406 Vac is not less than Vac-L-T then the process 400 follows the “no” route from step 406 to 408.
In step 408 the AC bus voltage Vac is compared with high voltage threshold Vac-H-T value. If it is determined, based on the comparison at step 408 Vac is greater than Vac-H-T then the process 400 follows the “yes” route from step 408 to 409 If where the current injected by inverter “x” is decreased by value ΔI.
If it is determined, based on the comparison at step 408 Vac is not greater than Vac-H-T then the process 400 follows the “no” route from step 408 to 410.
In step 410 the output current of inverter “x” is compared with current limit Iac-limit. it is determined, based on the comparison at step 410 output current of inverter “x” is greater than Iac-limit then the process 400 follows the “yes” route from step 410 to 411 where the current injected by inverter “x” is decreased by value ΔI. it is determined, based on the comparison at step 410 output current of inverter “x” is not greater than Iac-limit then the process 400 follows the “no” route from step 410 to 412.
In step 412 the inverter ID value “x” is incremented by one. In step 414 boundaries for the value of “x” set as between 2 and N.
Steps 406-414 are executed on a continuous basis in order for the system 100 to adequately support the active load segments and maintain the off-grid AC bus voltage between low voltage threshold Vac-L-T and high voltage threshold Vac-H-T.
Step 416 is an indication for repeating the steps 404 to 414 in periodic intervals of time Δt in order to periodically compute the total AC current Iac-Total and set the appropriate current limits Iac-limit for all the inverters in order for the system to function in a balanced manner.
In closing, although the various embodiments have been described in language specific to structural features and/or methodological acts, it is to be understood that the subject matter defined in the appended representations is not necessarily limited to the specific features or acts described. Rather, the specific features and acts are disclosed as example forms of implementing the claimed subject matter.
This application is based on and claims priority to U.S. Provisional Application No. 62/325,888, filed on Apr. 21, 2016, entitled, “LOAD MANAGER FOR RENEWABLE ENERGY SYSTEMS,” the contents of which are herein incorporated by reference.
Number | Date | Country | |
---|---|---|---|
62325888 | Apr 2016 | US |