1. Field of the Invention
The invention pertains to the field of large-scale, unbalanced, power-distribution networks. More particularly, the invention pertains to robust methodologies for solving power flow equations of unbalanced power distribution networks with distributed generators.
2. Description of Related Art
Recent years have witnessed a growing trend towards the development and deployment of distributed generation or dispersed generation (DG). This trend in combination with the emergence of a number of new distribution generation technologies has profoundly changed the traditional paradigm of the power industry in distribution networks. The widespread use of dispersed generations in utility distribution feeders is more and more likely in the near future. With this tendency, it is necessary to develop analysis tools for assessment of the impacts of dispersed generations on the steady-state of distribution networks. One challenging task for the steady-state analysis of distribution networks with DGs is the issue of power flow convergence in power flow studies. Indeed, these power flow solution algorithms typically have good convergence properties when applied to distribution networks with dispersed generations modeled as P-Q (fixed power) nodes, but they encounter divergence in power flow study when the dispersed generations are modeled as P-V (fixed voltage) nodes. Hence, there is a pressing need for the development of a reliable and effective method for power flow study of distribution networks with dispersed generations.
Recent years have witnessed a growing trend towards the development and deployment of distributed generation (DG) due to government policy changes, the increased availability of small-scale generation technologies, and environment impact concerns. However, adding DGs to distribution networks imposes significant changes on operating conditions such as reverse power flow, voltage rise, increased fault levels, reduced power losses, island mode operation, harmonic problem, and stability problem. To evaluate these significant changes, detailed analysis of distribution networks with DGs is necessary. One important detailed analysis is the steady-state analysis of distribution networks with DGs.
With this tendency, it is necessary to develop analysis tools for evaluating the impacts of dispersed generations on the steady-state of distribution networks. Voltage violations due to the presence of DGs can considerably limit the amount of power supplied by these DGs. Before installing or allowing the installation of a DG, utility engineers must analyze the worst case operating scenario in order to ensure that the network voltages will not be adversely affected by the DGs by performing power flow studies. In order to determine the maximum number of DGs that can be installed without steady-state voltage violations, the network voltages are calculated using a power flow solver.
However, one challenging task is the issue of power flow divergence when it is applied to distribution networks with dispersed generations. Indeed, many power flow solvers typically have good convergence properties when applied to distribution networks with dispersed generations modeled as P-Q nodes, while they encounter divergence in the power flow studies when dispersed generations are modeled as P-V nodes. On the other hand, it is more appropriate to model DGs as P-V nodes instead of P-Q nodes. Hence, there is a critical and pressing need for the development of a reliable method for power flow study for analyzing distribution networks with dispersed generations. A high penetration of DGs in the distribution network generally makes the task of planning and operation of distribution networks more complex.
Many DG installations employ induction and synchronous machines. Usually, synchronous generators connected to distribution networks are operated as constant real power sources and they do not participate at system frequency control. There are in fact two modes of controlling the excitation system of distributed synchronous generators. One mode is to maintain the constant terminal voltage (voltage control mode) and the other mode is to maintain the constant power factor. The constant power factor mode is usually adopted by independent power producers to maximize the real power production. Hence, depending on the contract and control status, a DG may be operated in one of the following modes:
1) In “parallel operation” with the feeder, i.e., the generator is located near and designated to supply a large load with fixed real and reactive power output. The net effect is the reduced load at a particular location.
2) To output power at a specified power factor.
3) To output power at a specified terminal voltage.
The nodes with DGs in the first two cases can be well represented as P-Q nodes while a generation node in the third case must be modeled as a P-V node. If the required reactive generation for a dispersed generation (to support the specified voltage) is beyond its reactive generation capability, then the reactive generation of the dispersed generation is set to its limit and the dispersed generation is modeled as a P-Q unit.
With the modeling of dispersed generation as the P-Q model, the general-purpose solution methods designed for traditional distribution networks are still applicable with minor modifications. However, when some dispersed generations are modeled as devices which deliver a specified real power while maintaining a given voltage magnitude, i.e. the typical P-V bus used for generator buses in transmission systems, then the general-purpose distribution power flow methods may encounter severe convergence problems.
All the solution algorithms developed in the last 15 years typically have good convergence properties when applied to distribution networks with DGs modeled as P-Q nodes. However, some of these solution algorithms encounter the divergence issue in power flow study when DGs are modeled as P-V nodes. Descriptions of this difficulty of divergence associated with distribution networks with P-V buses and loops have been well documented in the literature.
Chiang and Baran (“On the existence and uniqueness of load flow solution for radial distribution power networks”, IEEE Transactions on Circuits and Systems, Vol. 37, pp. 410-416, 1990) disclose a load flow solution with feasible voltage magnitude for radial distribution networks always existing and being unique.
Miu and Chiang (“Existence, uniqueness, and monotonic properties of the feasible power flow solution for radial three-phase distribution networks”, IEEE Transactions on Circuits and Systems I: Fundamental Theory and Applications, Vol. 47, pp. 1502-1514, 2000) disclose a three-phase power flow solution with feasible voltage magnitude for radial three-phase distribution networks with nonlinear load modeling always existing and being unique.
Zimmerman (“Comprehensive Distribution Power Flow: Modeling, Formulation, Solution Algorithms and Analysis,” Ph.D Dissertation, Cornell University, January 1995) discloses formulations and efficient solution algorithms for the distribution power flow problem, which takes into account the detailed and extensive modeling necessary for use in the distribution automation environment of a real world electric power distribution system.
Chen et al. (“Distribution System Power Flow Analysis-a Rigid Approach”, IEEE Trans. on Power Delivery, Vol. 6, pp. 1146-1152, 1991) discloses an approach oriented toward applications in three phase distribution system operational analysis rather than planning analysis.
Zhu and Tomsovic (“Adaptive Power Flow Method for Distribution Systems with Dispersed Generation”, IEEE Trans. on Power Delivery, Vol. 17, No. 3, July 2002, pp. 822-827) disclose a proposed adaptive compensation-based power flow method that is fast and reliable while maintaining necessary accuracy.
The above-mentioned references are hereby incorporated by reference herein.
A method predicts the power flow in a distributed generation network of at least one distributed generator and at least one co-generator, where the network is defined by a plurality of network nonlinear equations. The method includes applying an iterative method to the plurality of network nonlinear equations to achieve a divergence from a power flow solution to the plurality of network nonlinear equations. The method also includes applying the iterative method to find a first solution to a plurality of simplified nonlinear equations homotopically related by parameterized power flow equations to the plurality of network nonlinear equations. The method further includes iteratively applying the iterative method to the parameterized power flow equations starting with the first solution to achieve the power flow solution to the plurality of network nonlinear equations. In some embodiments, the iterative method is an Implicit Z-Bus Gauss method. In other embodiments, the iterative method is Newton's method.
In the present methods, the power flow problem of general distribution network with DGs modeled as P-V, or P-Q, or P-Q(V) buses is addressed. In the present methods, robust solution methods are used for general distribution networks with DGs modeled as P-V buses.
In some embodiments, the present methods are automated. At least one computation of the present methods is performed by a computer. Preferably all of the computations in the present methods are performed by a computer. A computer, as used herein, may refer to any apparatus capable of automatically carrying out computations base on predetermined instructions in a predetermined code, including, but not limited to, a computer program.
The present methods are preferably robust methods for power flow study for practical distribution networks with dispersed generations. The robust methods are preferably developed with the following goals in mind:
1) The methods are easily implemented in the framework of current distribution power flow methods. They are preferably easily implemented in the framework of current three-phase distribution power flow programs.
2) The methods are applicable to distribution networks consisting of a three-phase source supplying power through single-, two-, or three-phase distribution lines, switches, shunt capacitors, voltage regulators, co-generators, DGs, and transformers to a set of nodes with a given load demand.
3) The methods have sound theoretical basis.
4) The methods are applicable to large-scale distribution networks.
From an implementation viewpoint, goal 1) requires that the robust power flow method is easily integrated into the existing power flow packages. From a modeling viewpoint, goal 2) requires that the robust power flow method deal with all the elements and devices in practical distribution networks. From a robust viewpoint, goal 3) requires that the robust power flow method has the global convergence property. From a practical viewpoint, goal 4) requires that the robust power flow method is applicable to large-scale distribution networks.
In the present methods, a three-stage robust power flow methodology has been developed. A design goal of this methodology is to enhance a power flow method (solver) for solving general distribution networks with DGs. Hence, the present methods preferably assist existing power flow solvers to be more robust in solving distribution networks with DGs.
The set of power flow equations describing general distribution networks with DGs modeled as P-V node are preferably the following:
F(x)=0 [1]
The set of easy power flow equations describing general distribution networks with DGs modeled as P-Q node is preferably:
G(x)=0 [2]
In the present methods, homotopy methods, sometimes called embedding path-following methods, are preferably applied to solve a system of nonlinear algebraic equations [1]. The idea behind homotopy methods is to construct a parameterized system of equations, such that the parameterized system of equations at λ=0 is easy to solve and the parameterized system of equations at λ=1 is identical to the difficult problem. The homotopy function (or equations) gives a continuous deformation between the easy problem and the problem of interest. The homotopy function represents a set of n nonlinear equations with n+1 unknowns. From a computational viewpoint, homotopy methods can then be viewed as tracing an implicitly defined curve (through a solution space) from a starting point, which is a solution of the easy problem, to an unknown solution of the difficult problem [1]. If a solution of the difficult problem [1] is obtained, this procedure is successful.
To solve a difficult problem [1], an appropriate easy problem [2] is devised, which is easier to solve or has one or more known solutions. Homotopy methods entail embedding a continuation parameter into the difficult problem [1] to form a homotopy function of a higher-dimensional set of nonlinear equations:
H(x,λ):Rn×R→Rn,xεRn [3]
which satisfy the following two boundary conditions:
H(x,0)=G(x) [3a]
H(x,1)=F(x) [3b]
A three-stage robust power flow methodology is presented as follows:
In a preferred embodiment, a continuation method is used to implement Stage III. In a preferred embodiment, the power flow method used at Stage I is also used as the corrector in the continuation method.
Since the Implicit Z-Bus Gauss method (see, for example, Sun et al., “Calculation of Energy Losses in a Distribution System”, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-99, pp. 1347-1356, 1980) and Newton's method (see, for example, Tinney and Hart, “Power Flow Solution by Newton's Method”, IEEE Transactions on Power Apparatus and Systems, Vol. PAS-86, pp. 1449-1460, 1967) are two of the most popular methods for solving general distribution network, they are applied in the next two sections to illustrate the robust power flow methodology of the present invention.
The above-mentioned references are hereby incorporated by reference herein.
The following set of power flow equations are used for represented general distribution networks with DGs and co-generators modeled as P-V buses:
I=Y
bus
V [4]
where the vector V is node voltages, the vector I is nodal current injection, and Ybus is the nodal admittance matrix for the network containing all constant Z elements, including constant Z loads. The collection of network buses is partitioned into source (1), P-V buses (such as co-generators and DGs) (2), and remaining buses (3):
If the network contains no constant power device components, then I3 is a known constant injection, and V3 is found directly from the following:
V
3
=Y
33
−1(I3−Y31V1−Y32V2) [6]
This is a direct solution using a nodal method for linear circuits.
If the network has constant S components, then these elements are linearized by replacing them with equivalent current injections based on an estimate of the bus voltages. In this case, I3 is a function of V3:
V
3
=Y
33
−1(I3(V3)−Y31V1−Y32V2) [7]
The Gauss method is applied to solve equation [7] by repeatedly updating V3, evaluating the right hand side using the most recent value of V2. When the change in V3 between iterations becomes smaller than a predetermined tolerance, the solution has been obtained. Hence, the solution strategy is to replace non-linear elements (constant S) with linear equivalents (current injection) at present voltage and then solve for voltages directly using a nodal method for linear circuits.
A robust 3-stage method for power flow study for distribution networks with DGs and co-generators modeled as P-V buses preferably proceeds by the following stages. Stage I aims to solve the power flow equations with DGs and co-generators modeled as P-V buses. As is well known, Stage I may encounter divergence problems. Stage II solves the power flow equations with DGs and co-generators modeled as P-Q buses. A preferred method, Implicit Gauss method, solves this type of problems reliably. A homotopy procedure is preferably used in Stage III so that the power flow equations with DGs and co-generators modeled as P-V buses are ‘eventually’ solved, starting from the power flow solution obtained in Stage II method. The computational scheme for implementing Stage III is a continuation method.
into triangular factors L and U.
for y via forward substitution.
for
via backward substitution. For the P-V node, maintain the voltage magnitude at a specified value
is greater than a predetermined tolerance, go to step 4).
Otherwise, terminate Stage 1.
It is known that Stage I may not converge, especially when multiple DGs that are modeled as P-V buses are present. In such a case, the method proceeds with Stage II and Stage III when Stage I of the three-stage method is unable to solve the underlying problem. In Stage II, all the P-V buses related to V2 are treated as P-Q buses, and these buses related to V2 are ‘homotopized’ into P-V buses in Stage III. The Implicit Gauss method is highly robust in solving the three-phase power flow equations in Stage II.
into the triangular factors L and U for the simple power flow equations.
for y via forward substitution.
11) Solve
for
via backward substitution.
is greater than a predetermined tolerance, go to step 9).
The resulting solution of V2 is denoted as V2(P-Q), which indicates that the solution are being obtained under the condition that DGs are modeled as P-Q buses. V2(spec) is the voltage magnitude vector specified at the P-V buses. Stage III aims to reliably compute a power flow solution with V2 equal to V2(spec). In other words, Stage III of the integrated method contains a procedure for obtaining a power flow solution achieving V2 equal to V2(spec).
The following parameterized vector is first defined:
V
2(λ)=λV2(spec)+(1−λ)V2(P-Q) [8]
The following parameterized power flow equations are then formed:
Regarding the parameterized power flow equations [8]:
I
2
=λI
2(spec)+(1−λ)I2(P-Q)
for y via forward substitution.
17) Solve
for
via backward substitution.
is less than a predetermined tolerance, go to step 14).
Both the implicit Z-bus Gauss method and the present homotopy-enhanced implicit Z-bus Gauss method were applied to the following standard test systems for illustrative purposes:
1) an IEEE 13-bus test system
2) an IEEE 123-bus test system
3) an IEEE 8,500-node test system
4) a practical 1101-node distribution network.
For each of the test systems, the popular prior art implicit Z-bus Gauss method fails in several cases, while the present homotopy-enhanced implicit Z-bus Gauss method succeeds in obtaining the power flow solution in all cases.
The convergence criteria used in each of the four test systems are the following:
For the IEEE 13-bus system, a DG is connected to node #633 and this node is modeled as a P-V node. The prior art implicit Z-bus Gauss method 10 fails on this modified test system, while the present three-stage method 15 succeeds in obtaining the power flow solution as shown in
The result of the modified IEEE 13-node feeder obtained by the present three-stage method is presented in Table 1. The DG node #633 is now modeled as a P-V node. The specified positive sequence voltage at this node is 1.0 p.u. The power flow solution is summarized in Table 1 and a comparison between the voltage magnitudes of the power flow solution with a P-V model 20 and those with a P-Q model 25 is shown in
For the IEEE 123-bus system, a DG is connected to node #34 and this node is modeled as a P-V node. The prior art implicit Z-bus Gauss method 30 fails on this modified test system, while the present three-stage method 35 succeeds in obtaining a power flow solution as shown in
In a practical power distribution network with 1101 nodes, one DG is first connected to node #1373 and modeled as a P-V node. The prior art implicit Z-bus Gauss method 40 fails on this modified distribution network while the present three-stage method 45 succeeds in obtaining a power flow solution as shown in
To evaluate the robustness of the present method, ten DGs are connected to the 1101-node industrial distribution system. The specified positive sequence voltages at these nodes are 1.0 p.u. The present 3-stage method succeeds in obtaining a power flow solution as shown in Table 2.
One DG is connected to node #m1069148 of the 8500-bus and this node is modeled as a P-V node. The prior art implicit Z-bus Gauss method fails on this test system, while the present three-stage method succeeds in obtaining a power flow solution.
Five DGs are connected to the 8500-node industrial distribution system. The specified positive sequence voltages at these nodes are 1.0 p.u. The present three-stage method succeeds in obtaining a power flow solution as shown in Table 3.
Ten DGs are connected to the 8500-node industrial distribution system. The specified positive sequence voltages at these nodes are 1.0 p.u. The present three-stage method succeeds in obtaining a power flow solution as shown in Table 4. A comparison of the voltage profiles of Phase A of the IEEE 8500-node System with the P-Q model 60 and with the P-V model 65 of ten nodes in the system is shown in
In some embodiments, a homotopy-enhanced Newton's method is used when Newton's method is used as the corrector in the homotopy procedure. From a practical viewpoint, any existing power flow method may be integrated into the present homotopy-enhanced method. In the present methodology, it is necessary to define an easy problem. Consider a 3-phase power flow equation with a constant impedance load model as an easy problem for Newton's method, in which the ZIP load model is replaced by the constant impedance model in Stage II.
A robust three-stage homotopy-enhanced Newton's method for power flow study for distribution networks with the load are modeled as ZIP combination model preferably proceeds as follows. Stage I aims to solve the power flow equations with the load being modeled as a ZIP combination model. It is known that Stage I may not converge, when the initial guess is far away from the solution or the solution is located close to a bifurcation point. The present method proceeds with Stage II and Stage III when Stage I of the 3-stage method is not able to solve the underlying problem. In Stage II, all of the load models are converted into a constant impedance model. A homotopy procedure is applied in Stage III so that the power flow equations, with the load being modeled as a ZIP combination model, are ‘eventually’ solved.
The starting point in Stage III is the power flow solution obtained in Stage II, while the computational scheme for implementing Stage III is a continuation method.
{dot over (S)}
Li
Z=αi{dot over (S)}Li0 yLi=({dot over (S)}LiZ)*/(Vi0)2 i=1, 2, . . . , N [10]
{dot over (S)}
Li
Z=αi{dot over (S)}Li0+βi{dot over (S)}Li0+γi{dot over (S)}Li0 yLi({dot over (S)}LiZ)*/(Vi0)2 i=1, 2, . . . , N [11]
In Stage III, a homotopy function is constructed:
in which loads are modeled as the original ZIP combination model,
and the set of easy power flow equations is:
in which loads are modeled as the constant impedance model.
{dot over (S)}
Li
Z(k)=αi{dot over (S)}Li0|{dot over (V)}i(k)|2+βi{dot over (S)}Li0|{dot over (V)}i(k)|2+γi{dot over (S)}Li0|{dot over (V)}i(k)|2 i=1, 2, . . . , N [15]
The following homotopy function is then constructed:
H
i(x,λ)=λFi(x)+(1−λ)Gi(x) i=1, 2, . . . , N [16]
By substitution of equations [13], [14], [15], and [16] into Hi(x,λ),
A new parameter, arclength (s), is introduced. Both x and A are considered to be functions of the arclength parameter s:x=x(s), λ=λ(s)=xn+1. The step-size along the arclength s yields the following constraint:
If the Newton power flow in Stage II diverges, then decrease the system loading of the easy problem to construct another new easy problem and repeat step 8) to step 10) until the easy problem with the decreased system loading converges.
({circumflex over (x)}ji+1)=(xji,λji)+h(xji−xji−1,λji−λji−1), i=1, 2, . . . , n+1 [21]
Both Newton's method and the present homotopy-enhanced Newton's method were applied to the following standard test systems for illustrative purposes:
1) an IEEE 8,500-node test system
2) a practical 1101-node distribution network.
For each of the test systems, the prior art Newton's method fails in the cases that are close to the loading limit (i.e. Jacobian matrices close to singular), while the present homotopy-enhanced Newton's method succeeds in obtaining the power flow solution in all cases.
Eight DGs are connected to the 8500-node distribution system. The specified positive sequence voltages at these nodes are 1.0 p.u. The present three-stage method succeeds in obtaining a power flow solution.
In a practical power distribution network with 1101 nodes, four DGs are connected to node #1007, #1371, #1266 and #1008 and modeled as P-V nodes, while the constant impedance model is applied to all the loads. Unfortunately, the prior art Newton's method fails on this modified distribution network, while the present 3-stage method succeeds in obtaining a power flow solution.
Accordingly, it is to be understood that the embodiments of the invention herein described are merely illustrative of the application of the principles of the invention. Reference herein to details of the illustrated embodiments is not intended to limit the scope of the claims, which themselves recite those features regarded as essential to the invention.