The present disclosure relates to solvent depressurization and storage systems, and more particularly a system that stores and provides solvent at low pressure for use in the context of a solvent-based phytochemical extraction system or other solvent-based industrial process.
Many phytochemical extraction processes rely on volatile solvents, such as propane or butane. As such solvents are gaseous at ambient pressure, they are typically stored under pressure, in liquid form. Facilities that utilize solvents stored and transported under pressure need to be designed and implemented to meet high-pressure safety standards (e.g., American Society of Mechanical Engineers Boiler & Pressure Vessel Code), resulting in considerable start-up costs. The techniques described herein address the shortcomings with the conventional approaches to solvent storage, delivery, and utilization.
As shown in
The expansion tank 101 is placed outside the working environment (“extraction facility”) 105. Such tanks are available in several standard sizes (e.g., 250, 320, 500, and 1000 gallons), and are engineered to hold liquid propane at high pressure (e.g., 350-400 psi). It is also possible to instead use a lower pressure tank, since the described system functions far below the rated pressure of pre-engineered propane tanks. The facility 105 is typically an enclosed building, but could also be an open air area at which the extraction tank 103 and system 104 are located.
The expansion tank 101 is fluidly connected via stainless steel tubing (e.g., ½″×0.035″ wall) or similar conduit to the manifold 102. The manifold 102 is further described with respect to
Initially the entire system 100 is pulled down to a deep vacuum. The vacuum may be established by way of a pump, not shown. Then, the evacuated system is charged (e.g., from a delivery truck or fixed connection to a solvent source) with a certain mass of solvent: butane, isobutane, propane, or a mix thereof. The suitable mass of solvent is calculated by considering the volume that mass will expand to in vapor form at the ambient air temperature, up to a certain maximum allowed pressure. This is a simple calculation involving Boyle's Law, and a gas conversion chart that describes the relationship between a mass (or volume) of liquid solvent and its corresponding volume in gaseous form. For example, a gallon of liquid propane yields approximately 36 cubic feet of gas at a temperature of 60 F. Similarly, a gallon of liquid butane yields approximately 31 cubic feet of gas at a temperature of 60 F.
If the system 100 is never raised above 1 atm relative (2 atm absolute), then the entire system is never considered a “pressure vessel,” and does not need to conform to any ASME (“American Society of Mechanical Engineers”) pressure vessel rules to be certified for use. The system 100 thus becomes a low-pressure or unpressurized system, and therefore not subject to the regulations that govern the configuration and operation of high pressure systems.
The manifold 102 includes two valves 110 and 111. Valve 110 is a one-way check valve with low cracking pressure leading in (e.g., 0.3 psi). Valve 110 is relative or differential in operation. That is, the valve 110 opens when the difference in pressure between inlet and outlet exceeds the cracking pressure, in this example 0.3 psi.
Valve 111 is a one-way valve that has three ports: an input port 112, an output port 113, and a test port 114. Valve 111 measures the difference between the input port 112 and the test port 114, and releases from the input port 112 to the output port 113 (connected to the external expansion tank 101) so long as the measured pressure exceeds a specified limit. In this example, the test port 114 is open to the atmosphere, and the release pressure is set to 15 psi. This means that valve 111 will release gas to the external expansion tank (via the output port 113) whenever the pressure on the internal portion of the system exceeds 15 psi above atmospheric pressure. Other pressure ranges or limits can be used. For example, depending on the solvent mix, a higher release pressure (e.g., 30-50 psi) can be used for valve 111.
The manifold 102 guarantees that the internal portion of the system 100 never experiences a pressure greater than some limit established by valve 111 (e.g., 15 psi). If the pressure in the internal portion exceeds the specified limit, valve 111 vents gas to the expansion tank 101. If the pressure on the external portion of the system 100 exceeds another specified limit, then various options are contemplated, including venting excess gas into the atmosphere, or capturing excess gas in a secondary tank, as described below.
At ambient temperatures, the liquid solvent charged into the external expansion tank 101 all changes to vapor phase and expands to fill both the external expansion tank 101 and the internal storage tank 103. At this point the gas within the system 100 will be at its maximum allowable low-pressure, as determined by the mass of solvent charging the system 100.
When the cooling system 120 is started, the internal storage tank 103 will be reduced to −40 to −100 F, condensing and liquefying all of the solvent vapor throughout the system (via diffusion of gas molecules toward the tank 103). The liquefied solvent collects in the inside storage tank 103, where it can be used at a cold temperature in the extraction system 104. The vapor pressure of cold butane is below 1 atm, so this is considered a partial vacuum vessel, rather than a pressure vessel. The vapor pressure of N-butane is −25 to −28 in Hg at the described low temperatures.
When the cooling system 120 is turned off, or fails (e.g., due to mechanical failure or a power outage), the pressure will rise as the solvent warms and evaporates. As the pressure rises beyond the limit pressure of the manifold 102, the gas will pass through the manifold 102 and then to the external vapor storage tank 101.
Pre-engineered external expansion tanks typically include a pressure relief set to around 350-400 psi. In some embodiments, the external expansion tank is also fitted with a secondary relief valve set to a cracking pressure of 100-150 psi. This guarantees that the internal portion of the system will never experience pressures greater than the level set by the secondary valve. Another advantage is that emergency pressure relief takes place external to the facility.
Some embodiments include a secondary external (“back-up tank”). In this case, the primary external tank 101 includes a sensor and an associated pump that moves (recom presses) solvent from the expansion tank to the back-up tank, such as in the case of emergency or simply to purge the system of all solvent (e.g., when the operator wants to utilize a different type or mix of solvent).
The described system provides numerous benefits in the case of fire. A fire inside of the facility heats and gasifies solvent in the internal storage tank 103, which causes all solvent to exit the facility via the manifold, rendering the internal environment relatively safe.
Expressed in terms of the ideal gas law (PV=nRT), the system internal to the extraction facility can be modeled thusly: R is constant; V of the system is fixed; P is held constant by the manifold at 15 psi (for example); therefore as T increases, n must decrease, which occurs by gas passing through the manifold back to the external expansion tank 101.
Establishing a low pressure environment on the inside of the facility 105 provides substantial economic, engineering, and industrial process advantages. First, because the internal facility operates at low pressure, equipment that is not certified for high pressure use may be employed, yielding savings in terms of certification, inspection, engineering effort, and the like. The low pressure characteristic may also allow facilities to be located in building or activity zones where high pressure extraction facilities would not ordinarily be authorized due to safety concerns. The low pressure environment also allows considerable design flexibility in terms of parts and components.
In general, when the described system experiences a high pressure condition, solvent is simply recaptured by the external expansion tank 101, rather than being vented into the environment, as is typical in the industry. This property reduces pollution and increases safety for the surrounding community.
Some embodiments employ a gasometer (also known as a “gas holder”) in place of the external expansion tank 101. A gasometer is a large container that stores gas at near atmospheric pressure, by having a variable volume. The volume of the gasometer changes based on the quantity of gas stored, so as to maintain a near constant pressure within the gasometer. (See, https://en.wikipedia.org/wiki/Gas_holder.)
A pre-engineered propane tank employed as tank 101 has a fixed volume, resulting in variable pressure conditions in the system, depending primarily on the temperature of the internal storage tank 103. In contrast, a gasometer used as tank 101 yields a system having variable volume, fixed pressure. As the internal storage tank 103 is cooled, condensing the gas in the system, the gasometer volume decreases, maintaining an overall constant (or substantially constant) pressure.
Some embodiments provide a method for of operating the described solvent depressurization system. The process first evacuates the solvent depressurization system, but using a pump or similar mechanism to remove substantially all of the air. Different internal pressure levels may be utilized, including less than one of 0.1, 0.09, 0.08, 0.7, 0.06, 0.05, 0.04, 0.03, 0.02, 0.01 atmosphere.
The process next charges the external expansion tank with a mass of solvent (e.g., propane, butane), wherein the mass of solvent is less than the amount that would raise the internal pressure of the solvent depressurization system to twice atmospheric pressure at ambient temperature (e.g., 65-80 degrees).
The process then cools the internal storage tank, thereby causing gaseous solvent to flow from the external expansion to the internal storage tank via the manifold, wherein the gaseous solvent condenses in the internal storage tank. The internal storage tank is cooled to below the boiling point of the solvent, for example less than −42 degrees C. for propane or −1 degrees C. for butane.
The process then provides, from the internal storage tank, the solvent in liquid form to the solvent user. The solvent user may be a phytochemical extraction system or similar system/process that utilizes solvent in liquid form.
After utilization of the solvent, the process warms the internal storage tank, thereby causing solvent to evaporate and flow to the external expansion tank via the manifold. The internal storage tank is typically warmed passively. That is, no specific warming apparatus is needed, as it is sufficient to turn off the cooling system for the internal storage tank and allow the tank to warm in the environment of the system facility.
Note that while embodiments have been described as providing solvent in the context of a phytochemical extraction system and process, the described system is not limited to use only in that context. In particular, the described system can store and provide solvent (or other volatile material) for any industrial process that requires a ready source of solvent or similarly volatile material.
While embodiments of the invention have been illustrated and described, as noted above, many changes can be made without departing from the spirit and scope of the invention. Accordingly, the scope of the invention is not limited by the above disclosure.
This application claims the benefit of U.S. Provisional Patent Application No. 62/360,737, entitled “Solvent Depressurization Devices, System, and Methods,” filed on Jul. 11, 2016, the content of which is incorporated herein by reference in its entirety.
Number | Date | Country | |
---|---|---|---|
62360737 | Jul 2016 | US |