The present invention relates generally to a system for transferring electrical energy without contact by induction and to an installation comprising such a system of transfer for loading battery equipped electrical vehicles. More specifically, the invention relates to an inductive contact-free electric power transmission system through an air gap between a primary coil located on or in the ground and a secondary coil usually located on the lower part of a movable vehicle. While inductive coupling without contact and without ferro-magnetic circuit in between the primary and secondary circuits has been known since a long time, there are still unsolved problems when transfer of energy occurs at certain power levels, for example levels suitable to load battery operated public or private vehicles (between 10 kW and 500 KW). One of the unsolved and specific problem relates to the magnetic field radiation generated by the electromagnetic coupling between the primary coil and the secondary coil. None of the prior art document related to contact-free transfer of energy systems address this specific problem. However there exists, amongst others, a European directive specifying the maximum of intensity of a radiating magnetic field admitted specifically for the people working or standing in an exposed environment. This also apply to users of a public transportation system in which the vehicles use contact-free transmission of energy to be energized.
It is therefore the aim of the present invention to solve this problem by providing a contact-free energy transmission system and installation allowing to reduce drastically the magnetic field surrounding the transmission zone, while maintaining a transmission efficiency>95% in the range of a power suitable to operate public or private vehicles. This goal is achieved by a contact-free inductive power transmission system having the characteristics recited in claim 1.
Other features and advantages of the present invention will become apparent from the reading of the following detailed description of preferred embodiments made with reference to the annexed drawings in which:
The principle of contact free energy transfer is represented schematically on
The magnetic field determination is based on the superposition principle applied to the two conductors of the coil. As an hypothesis, a long coil in the direction perpendicular to the plan of
with
r
1
=√{square root over (xx2+yy2)}
This field can be broken down into 2 components, a vertical and a horizontal component Hv1 and Hh1 where:
Similarly, the field generated by the right part of the coil is:
The field amplitude in (xx,yy) is given by
H=√{square root over ((Hv1+Hv2)2+(Hh1+Hh2)2)}{square root over ((Hv1+Hv2)2+(Hh1+Hh2)2)}
and the corresponding flux density is: B=μ0H
These expressions are applicable for any point outside the copper coil.
With 2 coils, the superposition principle is applicable.
The Lentz' law defines the induced current as creating a field opposed to the cause. This means that the instantaneous current induced in the secondary coil is approximately in the opposite direction of the primary current. Consequently, the minimum of magnetic field is obtained when both currents are in phase opposition and if: n1I1≅n2I2 where n1 is the number of turns of the primary coil and n2 the number of turns of the secondary coil.
These conditions depend on the coil internal area, the number of turns, the power transferred, the frequency and the voltage, but also of the electrical scheme. Referring now to
Having, as an example, imposed frequency, coil area, power and distance between the primary and secondary coils, it is possible to find a solution with a minimum of magnetic field by carefully dimensioning the two serial capacitors C1s and C2s as well as the number of turns in the primary coil and in the secondary coil.
As previously said, in order to obtain a minimum of the radiating magnetic field, the objective is to have the same volume of current circulating in the primary and in the secondary coils 9,10, and in phase opposition and where n1I1≅n2I2. This can only be achieved if a relation between the primary tension, the frequency and the number of turns in the primary coil as well the power transferred is fulfilled. This relation is determined expressing the value of the equivalent load secondary resistance allowing to reach exactly the required power; it is given below using the following definitions:
f=operating frequency
n1, n2=number of turns of the primary and secondary coils
L12=mutual inductance between the primary and the secondary
Λ12=mutual permeance between the primary and the secondary
Pu=useful power at the secondary
The mutual inductance L12=n1n2Λ12
The limit primary voltage U1lim allowing that the currents i1 at the primary and i2 at the secondary i2 are in phase opposition is given by the following equation:
The condition to be fulfilled is that U1 the primary tension alimenting the primary coil is lower or equal to U1lim as given above.
Therefore, considering that the power to be transferred is determined by the type of application and that the operating frequency is usually fixed by the source alimenting the primary coil, it is possible to determine the value of the number of turns, and the value of the two serial capacitor C1s and C2s respectively at the primary and at the secondary as well as the primary tension to deliver in order to fulfill the above mentioned requirement. It is to be noted that an optional parallel capacitor may be provided at the primary but is usually only optional as the power factor cosφ seen from the primary is generally almost equal to 1. However, as the number of turns can obviously only be an integer, a parallel capacitor at the primary can be used in case of consumption of reactive power in order to avoid the later to be debited by the source. On the other hand, the two serial capacitors at the primary C1s and at the secondary C2s are essential because without them, the above condition cannot be fulfilled.
It is also to be noted that the above mentioned condition U1<U1lim, cannot be fulfilled without correctly dimensioning the serial capacitor C1s at the primary. The serial capacitor C2s at the secondary is automatically fixed as it is used to cancel the reactive component of the inductance at the secondary, transforming the secondary into an equivalent resistance. This is however not the case for the primary serial capacitor C1s as it not sufficient for the system to be simply resonant, this is clearly where reside the heart of this invention as it could have appeared obvious to use a resonant system. The condition of having the same volume of current in the primary and the secondary and currents in phase opposition cannot be fulfilled at resonance condition because it is the power factor (cosφ) as a whole seen from the source that should be considered. It is not sufficient to compensate the inductance at the primary with the primary serial capacitor C1s, but the mutual inductance must also be compensated. This cannot be achieved if the primary tension U1 is not inferior to U1lim as defined above. The optimal serial capacitor C1s at the primary also depends of the number of turns n2 at the secondary and of the leak reactance at the primary and the secondary. In order to minimize costs, the number of turns n1 and n2 in the primary and secondary coil are tried to be kept at a minimum.
Power transferred: 108 kW
Coil size rectangular: length 4 m*width 2 m
Distance between the primary and secondary coil d 0.115 m
Primary voltage: 500 V
Floor level above primary coil: 0.3 m
Primary capacitor C1s: 0.435 pF
Secondary capacitor C2 0.928 pF
Primary power factor: 1.0
Primary number of turns n1 1
Secondary number of turns n2 1
Primary current 217 A
Secondary current 167 A
At
On
On the
According to another aspect of the invention, it will now be disclosed an installation using the system for transferring energy previously described. The main possibilities to store energy on electrical vehicles are chemical batteries and super-capacitors. Using chemical batteries the transfer time from main power supply to the vehicle through a rectifier is generally long (in the range of hours). On super-capacitors however, the same time can be very short in the range of seconds.
For a given amount of transferred energy Wst, the corresponding average power Ptr is equal to: Ptr=Wst/Ttr where Ttr is the transfer time.
Using super-capacitors, the power can be very high.
As an example for a 2 Ton vehicle with an autonomy of around 1 km, the necessary energy is in the range of 1 MJ and the corresponding power is 100 kW for a transfer time of 10 s.
The fast loading operation requires an important power peak on the main power supply which is not desirable. The following installation offers the possibility to smooth such a transfer with very limited power amplitude on the main power supply generally connected to the common supply network.
To that extent, the solution is to use an intermediate energy storage facility at the loading station, also based on super-capacitors. This loading station is energized with a constant limited power from the main supply. As an example, if a vehicle is loaded in 10 seconds every 2 minutes, the average power removed from the main power supply is only 8.33 kW.
Using a contact free power transmission system as disclosed removes the necessity to connect the vehicle at the loading station, allowing therefore a very short time to reload the vehicle. Loading stations may be installed at different locations corresponding to bus stop in case of a public transportation system for example.
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/IB2009/000311 | 2/20/2009 | WO | 00 | 10/13/2011 |