This invention generally relates to energy conservation systems, and more particularly to energy conservation systems to be employed with gas burning appliances to reduce standby losses associated therewith.
It has now been recognized that the world's environment is suffering too much from global warming caused by greenhouse gas exposure in the atmosphere. To address this problem governments are now starting to adopt targets for reducing the emission of greenhouse gases to the environment and play their part to address this problem for future generations. While some countries have not adopted a firm goal, other countries, for example Australia, have adopted a policy for the reducing greenhouse gases by 20% by the year 2020.
Greenhouse gases can be emitted from cars, industry, farming, and households to name a few. While certainly not as apparent as a large factory with tall smokestacks, within a normal household the gas burning appliances, such as furnaces, water heaters, etc., all release such greenhouse gases as a by-product of the combustion process itself. While the appliance industry has taken a leading role in energy efficiency and environmental concern, further improvement is always foremost in mind of the appliance design engineer.
With such further improvement in mind, especially with the increased awareness of global climate change and changing governmental regulations, it is noted that hot water heaters, both internal and externally installed units, can be one of the more fairly inefficient appliances in energy conservation, and therefore require the burning of additional fuel to maintain the set point temperature. This, of course, results in the additional production of greenhouse gas beyond that which a more efficient appliance would produce.
A typical hot water heater includes a vertical tank with a centrally located flue pipe. A gas burner is positioned underneath the tank and is controlled by a combination gas controller. The combination gas controller incorporates an On/Off valve, a pilot safety circuit, pilot and main burner pressure regulators and their associated supply pipe connections, as well as a thermostat to control the hot water heater to maintain the water in the storage tank at a predetermined temperature.
Upon the thermostat calling for more heat, the main gas valve opens to allow gaseous fuel (gas) to flow to the main burner where it is ignited by the pilot light. Ignition and combustion of the gas results in hot flue gas being generated. The heat from the hot flue gases is transferred to the cold water via the bottom of the tank and through the walls of the central flue pipe. The flue gases exit out the top of the hot water heater.
There are generally two types of hot water heaters used throughout the world classified by their installation location. For an indoor water heater such as used in the North American market, the hot flue gases exit through a draft diverter that is connected to a flue pipe which pipes the flue gases safety to an outside location. Air for combustion of the gas is drawn into the combustion chamber at the bottom of the hot water heater. For an outdoor hot water heater such as used in the Australian market, the flue gases pass safely through a balanced flue terminal at the top of the heater to the outside atmosphere. The balanced flue terminal is so designed to allow a continuous supply of air for combustion irrespective whether the burner is on or off under all types of wind conditions. The air for combustion is transferred to the bottom of the heater internally within the appliance.
One of the current disadvantages for hot water heaters is the overall service efficiency of the appliances. Service efficiency is defined as the energy delivered to the hot water from the hot water heater each day, divided by the energy burnt in the gas to heat the water and to maintain the hot water in the tank at the desired temperature. The service efficiency may vary from around 0.50 or 50% for poor performing appliances, to appliances just complying to US regulations around 0.59, to superior products from 0.64 or 64% service efficiency. Low service efficiency may be due to poor thermal efficiency of the heat into the water when the burner is on and/or excessive heat losses when the burner is off.
While a small percentage of the heat loss may be caused by poor insulation from the outside of the tank, the majority of the losses are more likely a result of excessive losses from the hot primary flue pipe (heat exchanger) in the middle of the heater. This pipe is in contact with the hot water in the tank, and is designed to provide excellent heat transfer with the water to improve the “heat in” efficiency.
However, just as heat is transferred into the water when the burner is on, heat is also transferred out of the water when the burner is off. As a result of this standby heat loss, relatively cold air is continually being heated up and flows out of the hot water heater due to a thermo-syphoning effect by the flue pipe when the burner is off. Since the main burner is only on for one to two hours per day heating the stored water to keep it ready for use, the surfaces inside the flue pipe are exposed to the relatively cooler air for the remaining 22 hours. This natural cooling of the heated water via the flue pipe forces the thermostat to occasionally turn on the burner to continually top up the stored hot water to the desired temperature.
Recognizing this standby heat loss problem, there have been many attempts at providing some form of a flue damper that closes to limit the escape of heat through the flue pipe when the burner is turned off and that reliably opens to let the flue gases escape when the burner is on. Indeed, laboratory tests have proven that dampers can reduce the standby losses of a hot water heater by up to approx. 50%. This relates to approx. 500 Btu/h (0.50 Mj/h), which is a huge amount of energy considering the product life to 10 to 15 years. While such a damper could be electrically powered, such a damper would require additional power use and would need to be driven by a reliable supply. Gas powered dampers, that is dampers driven by the gas used for combustion, alleviate the problems of additional electrical power use and reliable supply. Unfortunately, the appliance industry generally and hot water heater manufacturers specifically have been frustrated by the fact that gas operated dampers “nearly work”. They are not popular and commonly have many problems and service issues.
One significant problem experienced by gas operated flue dampers relates to candling of the diminishing flame on shut down of conventional burners and low NOx burners. This candling effect results from the draining of the gas in the burner feed pipe that leads from the damper actuator valve to the burner after the burner has been commanded off. Since the gas operated damper valve is located on the flue pipe at the top of the hot water heater and the burner is located at the bottom, the gas pipe from the valve to the burner runs at least the length of the storage tank. As a result of the existence of gas in the pipe after the valve have been shut, a small flame at the injector continues to burn until the pipe is drained, which results in the gradual build up of soot on the burner. This, in turn, often results in poor combustion, further increasing the production of greenhouse and other dangerous gasses. Candling is especially a problem with installations where the gaseous fuel used is heavier than air such as propane, butane gas, etc.
To address the systemic problem of candling with prior gas operated dampers, some designs incorporate an additional damper valve bleed line, a flow orifice member, and a separate vent pilot. Unfortunately, such additional plumbing and components increase the complexity and cost of such systems, as well as reducing the overall reliability of the system due to the increase in components. In the highly cost competitive appliance industry, even with the overall lifetime cost of operation reduction and with the reduction in production of greenhouse gasses, such additional expense makes such hot water heaters undesirable by consumers.
Another problem with some gas controlled damper valves is that they can trap gas within the valving damper system. This often results in allowing the damper only partially to close the damper, reducing the energy savings by allowing some flow therethrough.
There is a need, therefore, for a gas operated damper system for gas burning appliances, such as a hot water heater, to reduce standby losses therefrom that overcomes the above described and other problems existing in the art. Embodiments of the invention provide such an energy savings damper system. These and other advantages of the invention, as well as additional inventive features, will be apparent from the description of the invention provided herein.
In view of the above, embodiments of the present invention provide a new and improved standby heat loss control system that overcomes one or more of the problems exiting in the art. More specifically, embodiments of the present invention provide a new and improved gas operated damper system for a hot water heater to enable hot water heaters to operate more efficiently thus reducing greenhouse gases. Preferably, embodiments of the present invention provide a new and improved gas operated damper that reduces the standby heat losses that occur as a result of thermo-syphoning of the heat from the hot water in the storage tank of a hot water heater by the flue pipe when the burner is off.
In particular, embodiments of the present invention provide a damper actuator valve and safety relay valve downstream of the combination gas controller. Both valves are operated in series by the use of bleed gas supplied by the combination gas controller. The bleed gas pressure operates the appliance damper actuator system in a controlled and defined safe manner, then supplies gas to operate the safety relay valve.
In one embodiment, the safety relay valve is configured to bypass a small amount of gaseous fuel to the damper actuator valve when the thermostat in the combination gas controller calls for heat. The bleed gas flows to the damper actuator valve and causes operation of the damper via a damper flapper valve to open the flue pipe. When the damper is open, and only then, the damper actuator valve, via a damper actuator safety valve, allows the bleed gas to be piped back down to the safety relay valve to actuate it, opening it and allowing gas to flow to the main burner of the hot water heater.
In one of the preferred embodiments, the system automatically opens and closes the damper actuator valve, its associated mechanism and the safety relay valve in a defined and controlled manner. The valving is designed so that no gas can physically pass to the main burner if the damper actuator valve and connected mechanisms have not moved open sufficiently for good combustion. In addition, the damper actuator valve and connected mechanism automatically and safely close off the appliance's flue pipe (heat exchanger) from free ventilation immediately after the burner off cycle is completed.
The configuration of valves prevents gas from passing to the main burner until the piped bleed gas pressurizes a damper actuator valve diaphragm, which in turn moves the diaphragm and the corresponding linkage attached to the top (air side) of the diaphragm to open the damper flapper valve at the outlet of the water heater flue pipe.
In one embodiment, the damper diaphragm has underside linkages to a damper actuator safety valve on the gas side. Continued diaphragm movement after opening the damper finally drags a damper actuator safety valve from its seat, thereby allowing bleed gas to pass. This bleed gas then pressurizes the safety relay valve. A diaphragm in the safety relay valve is forced to move by this pressurizing bleed gas, which opens the main relay valve to allow gas to flow to the main burner. The bleed gas, as it is continually being passed from the combination gas controller, through the damper actuator valve, and back to the safety relay valve, is finally mixed into the main gas to the burner.
Other aspects, objectives and advantages of the invention will become more apparent from the following detailed description when taken in conjunction with the accompanying drawings.
The accompanying drawings incorporated in and forming a part of the specification illustrate several aspects of the present invention and, together with the description, serve to explain the principles of the invention. In the drawings:
While the invention will be described in connection with certain preferred embodiments, there is no intent to limit it to those embodiments. On the contrary, the intent is to cover all alternatives, modifications and equivalents as included within the spirit and scope of the invention as defined by the appended claims.
Turning now to the drawings, there is illustrated in
Returning specifically to
In this embodiment, standby heat loss is substantially reduced by the inclusion of a damper actuator valve 114 that is located at the top of the hot water heater 100. A damper flapper valve crank shaft rod 116 driven by the damper actuator valve 114 is connected to a damper flapper valve 118 located on the flue pipe 110. This damper flapper valve 118 is used, as will be described more fully below, to close off the flue pipe 110 when the burner is off. The shape of the damper flapper valve 118 is normally round to close off the typical round flue pipe 110, although it would be square to close off square ducting, etc.
As may be seen from the enlarged partial view of
Returning to the illustration of
Although not recognized by prior gas operated damper designs, the safety relay valve 122 should be located immediately after the water heater combination gas controller 130 but as close as possible to the burner so to reduce the effect of pre-ignition and candling. Pre-ignition is defined as attempting to ignite the issued air/gas mixture from the burner ports too early (pressure within the burner head unstable) causing the explosive mixture to flash back through the burner ports and ignite within the burner head. Candling is defined as the draining of the gas in the burner feed pipe after the burner has been commanded off, so as to cause a small flame at the injector resulting in the gradual sooting up of the burner and bad combustion. This is especially a problem with gases heavier than air such as propane, butane gas.
As discussed above, markets outside of North America, such as in Australia, install their hot water heaters outside of the dwellings. An embodiment of one such outdoor hot water heater 136 is illustrated in
The damper actuator valve 114 is located inside the terminal 140, attached to the outside of the transfer duct, which is adjacent to the heater flue pipe as it exits into the transfer duct (show in this illustration as 110 for ease of understanding). In this embodiment the damper actuator valve 114 is located close to the cylinder flue pipe 110 outlet in order to reduce standing losses as discussed above. As shown in
The damper flapper valve 118 to closed off the flue pipe 110 is located immediately over the outlet of the flue pipe 110 inside the transfer duct and is in communication with the damper actuator valve 114 via the damper flapper valve crank shaft rod 116. Small bore piping 120, 128 is used to connect the safety relay valve 122 to the damper actuator valve 114 as in the previous embodiment. The outlet gas feed pipe 132 from the combination gas controller 130 is now connected to the safety relay valve 122, which in turn connected is to the burner feed pipe 134 on supply gas to the burner. The tank 106 is insulated within the square jacket 138, which also provides internal pathways for the air to be transferred from the top terminal 140 to the burner at the bottom of the appliance.
To help understand the control provided by the various components of embodiments of the present invention, an understanding of a typical water heater combination gas controller 130 must first be had. To aid this, attention is now directed to the block diagram of
With this basic understanding in mind, attention is now directed to
In either physical layout, the combination gas controller 130 remains unchanged in operation as discussed above. However, instead of having the gas regulator 146 coupled to the burner feed pipe 134, it is coupled to the safety relay valve 122, which is then coupled to the burner feed pipe 134. As discussed above, small bore pipe 120, 128 is used to couple the safety relay valve 122 to the damper actuator valve 114 to drive the damper flapper valve 118. The advantage of using bleed gas to control the position of the damper flapper valve 118 and the operation of the safety relay valve 122, as opposed to using the main gas flow in prior designs, will be discussed more fully below once the details of an embodiment of the various components are better understood.
The details of one embodiment of a safety relay valve 122 are shown in the cross sectional illustration of
A diaphragm 170 is positioned within the diaphragm control chamber 168, and is operatively coupled to the main valve control shaft 172. Displacement of the diaphragm 170 based on pressure within the diaphragm control chamber 168 will operate to open or allow the main controlling valve 158 to close under pressure of spring 160 as will be discussed more fully below. Diaphragm vent passage 180 will prevent any net pressure build up below the diaphragm 170 during displacement thereof. Once the main controlling valve 158 has been opened, gas is allowed to flow from the inlet 156 through the outlet 162 to the burner via the burner feed pipe 134.
In the illustrated embodiment of
If a booster pilot is not desired or included in the particular installation, the bleed gas from the second connection port 166 can be distributed internally through passage 176 down stream of the valve 158, to outlet 162. This will allow proper timing and operation of the system 102 as will be discussed more fully below.
Turning now to
As indicated above, upon the thermostat calling for heat gas is supplied to inlet of the closed safety relay valve 122. Gas is then supplied to the damper actuator valve inlet 124 pressuring the diaphragm 188. The displacement of the diaphragm 188 forces the push rod 192 to move which in turn rotates the crankshaft rod 190 to open the damper flapper valve 118 sufficiently for good combustion. The continued pressurising and resulting further displacement of the diaphragm 188 finally drags a damper actuator safety valve 200 off its seat, which allows gas to be bled back to the safety relay valve 122 through outlet 126. This function of the gas safety valve being finally dragged off its seat when the flapper valve is opened sufficiently for good combustion may be defined as a damper actuator safety valve drag distance. This distance must be accurately controlled for safety and may be accomplished in many ways.
As shown in this
Also shown in
As may be seen in this
With a thorough understanding of various embodiments of the components of the standby energy loss prevention system 102 of the present invention, attention will now be turned to
As illustrated in
The damper actuator valve 114 is pressurised as shown in
As illustrated in
As illustrated in
Once the combination gas controller 130 determines that the water temperature has reached its set point temperature, it turns off all gas to the safety relay valve 122. Gas drains out of the damper of the damper actuator valve 114 where upon the return spring, returns the push rod 192 to the original position rotating the crankshaft 190 which closes the damper flapper valve 118 and damper actuator safety valve inside the damper actuator valve 114. Gas continues to drain from the damper actuator safety valve bypass and from the diaphragm chamber of the safety relay valve 122, which allows the return spring to close off the main gas valve thus stopping all gas to the burner. The burner main flame is extinguished as well as the booster pilot leaving only the pilot or micro-pilot on.
All references, including publications, patent applications, and patents cited herein are hereby incorporated by reference to the same extent as if each reference were individually and specifically indicated to be incorporated by reference and were set forth in its entirety herein.
The use of the terms “a” and “an” and “the” and similar referents in the context of describing the invention (especially in the context of the following claims) is to be construed to cover both the singular and the plural, unless otherwise indicated herein or clearly contradicted by context. The terms “comprising,” “having,” “including,” and “containing” are to be construed as open-ended terms (i.e., meaning “including, but not limited to,”) unless otherwise noted. Recitation of ranges of values herein are merely intended to serve as a shorthand method of referring individually to each separate value falling within the range, unless otherwise indicated herein, and each separate value is incorporated into the specification as if it were individually recited herein. All methods described herein can be performed in any suitable order unless otherwise indicated herein or otherwise clearly contradicted by context. The use of any and all examples, or exemplary language (e.g., “such as”) provided herein, is intended merely to better illuminate the invention and does not pose a limitation on the scope of the invention unless otherwise claimed. No language in the specification should be construed as indicating any non-claimed element as essential to the practice of the invention.
Preferred embodiments of this invention are described herein, including the best mode known to the inventors for carrying out the invention. Variations of those preferred embodiments may become apparent to those of ordinary skill in the art upon reading the foregoing description. The inventors expect skilled artisans to employ such variations as appropriate, and the inventors intend for the invention to be practiced otherwise than as specifically described herein. Accordingly, this invention includes all modifications and equivalents of the subject matter recited in the claims appended hereto as permitted by applicable law. Moreover, any combination of the above-described elements in all possible variations thereof is encompassed by the invention unless otherwise indicated herein or otherwise clearly contradicted by context.
Number | Name | Date | Kind |
---|---|---|---|
1813395 | Fraser | Jul 1931 | A |
1842337 | Te Pas | Jan 1932 | A |
1968319 | Shively | Jul 1934 | A |
1991557 | Johnson | Feb 1935 | A |
2112554 | Beam | Mar 1938 | A |
2953198 | Hajny | Sep 1960 | A |
3166248 | Fleer | Jan 1965 | A |
3405999 | Riehl | Oct 1968 | A |
4076171 | Swenson | Feb 1978 | A |
4131413 | Ryno | Dec 1978 | A |
4164936 | Dottore, Jr. | Aug 1979 | A |
4182483 | Swenson | Jan 1980 | A |
4192310 | Brodin | Mar 1980 | A |
4204833 | Kmetz et al. | May 1980 | A |
4225080 | Barth | Sep 1980 | A |
4264296 | Folkerts | Apr 1981 | A |
4266929 | Swenson | May 1981 | A |
4289271 | Barth | Sep 1981 | A |
RE30936 | Kmetz et al. | May 1982 | E |
4386731 | Barth | Jun 1983 | A |
4408567 | Morton | Oct 1983 | A |
4413975 | Turner et al. | Nov 1983 | A |
4545009 | Muraki et al. | Oct 1985 | A |
4770160 | Schimmeyer | Sep 1988 | A |
4778378 | Dolnick et al. | Oct 1988 | A |
5039006 | Habegger | Aug 1991 | A |
5239947 | Schimmeyer | Aug 1993 | A |
5393221 | McNally | Feb 1995 | A |
5447125 | McNally et al. | Sep 1995 | A |
5511971 | Benz et al. | Apr 1996 | A |
5682841 | Schimmeyer et al. | Nov 1997 | A |
5732692 | Schimmeyer | Mar 1998 | A |
5911217 | Dameworth | Jun 1999 | A |
6418883 | Bourke et al. | Jul 2002 | B2 |
6546897 | Edds et al. | Apr 2003 | B1 |
6584940 | Khadkikar et al. | Jul 2003 | B1 |
7311064 | Schimmeyer | Dec 2007 | B2 |
7818095 | Hotton et al. | Oct 2010 | B2 |
20050066958 | Guzorek | Mar 2005 | A1 |
Number | Date | Country |
---|---|---|
2409271 | Apr 2003 | CA |
2426723 | Jul 2003 | CA |
2482509 | Mar 2005 | CA |
0019671 | May 1979 | EP |
528827 | Nov 1940 | GB |
942650 | Nov 1963 | GB |
953982 | Apr 1964 | GB |
1 475 133 | Jun 1977 | GB |
56119420 | Sep 1981 | JP |
57188950 | Nov 1982 | JP |
58033050 | Feb 1983 | JP |
59157422 | Sep 1984 | JP |
60-226623 | Nov 1985 | JP |
62063140 | Mar 1987 | JP |
63021404 | Jan 1988 | JP |
4045320 | Feb 1992 | JP |
2007232262 | Sep 2007 | JP |
WO 9517631 | Jun 1995 | WO |
WO 0040906 | Jul 2000 | WO |
WO 2006135319 | Dec 2006 | WO |
Number | Date | Country | |
---|---|---|---|
20100012048 A1 | Jan 2010 | US |