This disclosure relates generally to electrical generator systems and especially to electrical generators utilizing hydrogen gas to cool the generator.
Modern electrical power plants often utilize turbine generators to produce electricity. During operation, these generators produce large amounts of heat which must be dissipated in order for the generators to operate at maximum efficiency. Traditionally, air was used as a cooling medium to help dissipate the heat. However, as generator capacity and size increased, hydrogen replaced air due to its high heat capacity and low density. Additionally, the use of hydrogen reduces the windage or friction losses over comparably sized air cooled units.
Due to the loss in efficiency from windage, it is desirable to maintain as high a purity level of the hydrogen in the generator. As shown in
While the generator is in operation, hydrogen is continuously lost due to leaks in seals. Traditionally, to maintain the appropriate level of pressure and purity in the generator, the power plant operator would purchase hydrogen gas in bulk from gas producers who delivered the gas in cylinders or by tanker truck. The operator would periodically check the purity level and add hydrogen from the hydrogen gas cylinders as needed.
As an alternative to using bulk purchased hydrogen gas, power plant operators have also used electrolysis gas generators which allow the operator to produce hydrogen gas on-site. The electrolysis generators use electricity to split water into hydrogen and oxygen gas. The use of electrolysis typically reduced the cost of using hydrogen and also reduced the security concerns of the power plants in having to receive and store large quantities of a flammable gas. Typically, however, the electrolysis generators which are economically viable for providing makeup gas for the electrical generator lacked the capacity to produce sufficient volumes of hydrogen to quickly purge or fill the electrical generator after it had been shut down for maintenance. Also, plant operators still relied on manual filling of the generators which did not allow for optimal efficiencies.
Accordingly, what is needed in the art is a system for maintaining high purity levels of hydrogen in an electrical power generator and for providing a means for utilizing an on-site hydrogen generator to produce sufficient hydrogen to purge or fill the electrical power generator.
A method and apparatus is provided for an a system for maintaining hydrogen purity in an electrical power generator. The purity system includes: a generator, a hydrogen generator configured to provide hydrogen gas to the generator, a purity monitor for detecting the level of hydrogen purity in the generator and providing a signal when the purity drops below a predetermined threshold. The system automatically compensates for gas loss or contamination to maintain the desired level of efficiency in the electrical generator.
The above discussed and other features will be appreciated and understood by those skilled in the art from the following detailed description and drawings.
Referring now to the drawings, which are meant to be exemplary and not limiting, and wherein like elements are numbered alike:
As the demand for power by consumers has increased, electrical power producers have increasingly turned to larger generators to fulfill the needs of society. As the size of the generators increased, it became increasingly more difficult to maintain the generator at an appropriate operating temperature to prevent damage to the generator components. Smaller generators relied on air cooling to dissipate heat from the generator rotor windings. To improve heat transfer, generator manufacturers began to utilize hydrogen gas as a transfer agent since the thermal conductivity of hydrogen is seven times that of air.
The switch to hydrogen also yielded side benefits by reducing the windage losses in the generator due to hydrogen's lower density. As shown in
In addition to contamination, operators must cope with hydrogen leaks which typically occur at the generators seals. As hydrogen escapes, the operator must add make-up hydrogen gas to the generator in order to maintain the heat transfer and low windage benefits. In a typical generator such as a GE Frame-7 generator, the loss of hydrogen and the amount of hydrogen can reach up to 20-40 cubic feet of hydrogen per hour.
An exemplary embodiment of the present invention is shown in
The generator 12 also includes a vent line 19 which connects to a solenoid valve 20. The outlet of the valve 20 leads to a vent which allows the hydrogen gas to be properly dissipated into the atmosphere. As will be described in more detail herein, a communications link 17 connects the purity monitor 18 with the solenoid valve 20. A hydrogen generator 24 provides hydrogen gas to the generator 12 through conduit 26. Alternatively, a controller (not shown) in the generator 12 controls the solenoid valve 20 to vent the hydrogen gas.
In the preferred embodiment, the hydrogen generator will include a water-fed electrochemical cell which is capable of disassociating reactant water into hydrogen and oxygen gas. Suitable reactant water is deionized, distilled water, which is continuously supplied from a water source 28. The electrochemical cell will preferably be of a polymer electrode membrane (PEM) type. The electrochemical cell may also be any other suitable electrochemical cell such as, but not limited to, alkaline, phosphoric acid, or solid oxide based cells. The hydrogen generator 24 may also be any non-electrochemical system capable of producing hydrogen gas such as, but not limited to, a steam methane, or natural gas reformation.
An output sensor 30 is incorporated into the hydrogen generator 24 to sense the differential pressure between the hydrogen generator 24 and the conduit 26. The output sensor 30 may be a pressure transducer that converts gas pressure within the conduit 26 to a voltage or current level indicative of the gas pressure. Output sensor 30 may also be any other sensor suitable for sensing a qualitative or quantitative parameter of the gas and provide an electrical signal indicative of that parameter as an output. Such other sensors include, but are not limited to, a flow rate sensor, a mass flow sensor, and a differential pressure sensor. Optionally, a feedback signal 29 may be provided from the pressure monitor 16 to the hydrogen generator 24
Output sensor 30 interfaces with a controller (not shown) that is capable of converting the analog voltage or current level provided by the sensor 30 into a digital signal indicative of the sensed hydrogen pressure. The controller compares the sensed hydrogen pressure to a predetermined parameter for controlling the output of the hydrogen generator 24 as will be described in more detail herein.
An alternate embodiment of the electrical power generating system 10 is shown in
Electrical power generators hold a large volume of hydrogen gas, typically at least 7,500 cubic feet. Consequently, at an event where the generator needs to be purged and filled with hydrogen gas, such as at startup, or after maintenance, the operator will need access to a large volume of hydrogen gas. Events such as startup or maintenance purging typically occur on an annual basis. Since a hydrogen generator capable of generating this volume of hydrogen in a short period of time would be greatly over-sized for daily operation. Accordingly, it is desirable to have a means for storing excess hydrogen gas generated by the hydrogen generator 24. In the embodiment shown in
Referring to
If the answer to the query of block 66 is affirmative, either in the first instance or after one or more negative answers, the method 60 proceeds to block 68 where a control signal is passed from purity monitor 18 to the valve 20 causing the valve 20 to open. The opening of the valve 20 allows gas from the generator 12 to be vented to the atmosphere.
The method 60 then proceeds on to block 70 to produce hydrogen gas. Generally, the hydrogen generator 24 will detect the pressure drop at sensor 30 that results from the venting of the generator 12 which occurred in block 68. Typically, upon detection of this drop in pressure below the desired pressure Pdes the hydrogen generator 24 will initiate production of hydrogen gas which is transferred to the generator 12.
The method 60 then continues on to block 72 where the gas from the generator 12 is sampled and the hydrogen purity measured. Method 60 then proceeds on to query block 74 where the Hpure is compared with a desired level Hpref. If the query answers affirmative, the method 60 loops back to block 72 and continues to monitor the hydrogen purity Hpure in the generator 12. This loop continues generally until method 60 is externally terminated or paused, or until the query of block 74 is answered negatively.
If the answer to the query in block 74 is negative, this is indicative that the purity level of the hydrogen gas in the generator has reached a level desired by the operator. The method 60 then proceeds on to block 76 where a control signal is passed from the purity monitor 18 to the valve 20. The valve 20 closes and the venting of gas from the generator 12 stops. Method 60 then proceeds on to block 78 where hydrogen production ceases. In the preferred embodiment, when the valve 20 is closed, the pressure will rise in the generator. This pressure rise will be detected in the sensor 30, and when the pressure in the generator reaches the desired pressure Pdes the hydrogen generator 24 stops production of hydrogen gas. Typically, the desired pressure Pdes is between 30 psi and 75 psi. Method 60 then continues back to block 64 to start the process again. It will be appreciated that method 60 is performed repetitively during the operation of the system 10.
Referring to
If the query block 86 returns an affirmative response, the method 80 continues on to block 88. In block 90, purity monitor 18 sends a control signal to the hydrogen generator 24 which causes the hydrogen generator 24 to initiate hydrogen production at a predetermined flow rate and pressure Pdes. Typically, the desired pressure Pdes is between 30 psi and 75 psi, with a preferred pressure of 45 psi. In the preferred embodiment, the desired pressure Pdes is greater than the relief pressure Prelief of valve 20.
After hydrogen gas production is initiated, the method 80 continues on to query block 91 where Prelief and Pgen are introduced into the following query:
Is Pgen>Prelief?
Here, the parameter Pgen represents the pressure inside the generator 12 and the parameter Prelief represents the pressure setting at which the valve 20 will open allowing the gas from the generator 12 to vent to the atmosphere. If the query in box 91 returns a negative, the method 80 loops back to box 90 and hydrogen continues to be generated and provided to the generator 12. The method 80 continues until terminated or paused by the operator.
If the query in box 91 returns an affirmative response, indicating that the pressure inside the generator has reaches a value greater than the relief setting on the valve 20, the method 80 continues on to box 92 and the valve 20 is opened. The method continues on to monitor the hydrogen purity level Hpure in box 93 and compare the measured level with the desired purity level in box 94 in a similar manner as has been described herein above.
Once the purity of the hydrogen gas in the generator achieves the desired purity level, the method 80 continues on to block 96 where the purity monitor 18 transmits a control signal to the hydrogen generator 24 causing the hydrogen generator to cease production of hydrogen gas. Once the hydrogen generator stops producing gas, the method 80 continues on to box 98 where the valve 20 will close once the pressure in the generator drops below the predetermined threshold.
Method 80 then continues back to block 84 to start the process again. It will be appreciated that method 80 is performed repetitively during the operation of the system 10.
Referring to
While the tank 40 is filling, the method 100 monitors the pressure Ptank in the tank 40. The tank 40 will also have a maximum working pressure rating Pmax. Typically, the tank 40 will have a maximum pressure rating between 2000 psi and 10,000 psi, with a preferred rating of 2,400 psi. Method 100 proceeds to block 114 where Ptank and Pmax are introduced into the following query:
IS Ptank<Pmax?
If the query block 114 responds affirmatively, the method 100 proceeds query box 118 where the hydrogen purity level is compared to the desired level. If the query block 118 returns an negative response, which would indicate that the generator required replenishment of pure hydrogen gas., the method 100 returns to block 112 in order to continue filling the tank with hydrogen. If the query in block 118 returns an affirmative response, the method 100 then proceeds on to block 120 where the valve 36 is closed and then onto block 122 where the vent valve 20 is opened and gas from the generator 12 is vented to the atmosphere. Method 100 then proceeds through blocks 126-134 to replenish the generator with hydrogen gas to the appropriate purity level in the same manner as was described herein above with respect to method 60 and blocks 72-78.
It should be appreciated that the process steps in blocks 128-134 may also be accomplished using the alternate method described with respect method 80. In addition, in applications where the hydrogen generator 24 is continuously producing gas for the generator 12, it is within the contemplation of this invention that the hydrogen generator 24 provides hydrogen gas to both the tank 40 and the generator 12 simultaneously with preference being given to supplying the generator 12.
While the invention has been described with reference to a preferred embodiment, it will be understood by those skilled in the art that various changes may be made and equivalents may be substituted for elements thereof without departing from the scope of the invention. In addition, may modifications may be made to adapt a particular situation or material to the teachings of the invention without departing from the essential scope thereof. Therefore, it is intended that the invention not be limited to the particular embodiment disclosed as the best mode contemplated for carrying out this invention.
The present application is a continuation of U.S. patent application Ser. No. 10/711,395 entitled “System for Maintaining Hydrogen Purity in Electrical Generators and Method Thereof” filed on Sep. 16, 2004, which is incorporated herein by reference in its entirety.
Number | Date | Country | |
---|---|---|---|
Parent | 10711395 | Sep 2004 | US |
Child | 12463105 | US |