This disclosure relates generally to electrical generator systems and especially to electrical generators utilizing hydrogen gas to cool the generator.
Modern electrical power plants often utilize turbine generators to produce electricity. During operation, these generators produce large amounts of heat which must be dissipated in order for the generators to operate at maximum efficiency. Traditionally, air was used as a cooling medium to help dissipate the heat. However, as generator capacity and size increased, hydrogen replaced air due to its high heat capacity and low density. Additionally, the use of hydrogen reduces the windage or friction losses over comparably sized air cooled units.
Due to the loss in efficiency from windage, it is desirable to maintain as high a purity level of the hydrogen in the generator. As shown in
While the generator is in operation, hydrogen is continuously lost due to leaks in seals. Traditionally, to maintain the appropriate level of pressure and purity in the generator, the power plant operator would purchase hydrogen gas in bulk from gas producers who delivered the gas in cylinders or by tanker truck. The operator would periodically check the purity level and add hydrogen from the hydrogen gas cylinders as needed.
As an alternative to using bulk purchased hydrogen gas, power plant operators have also used electrolysis gas generators which allow the operator to produce hydrogen gas on-site. The electrolysis generators use electricity to split water into hydrogen and oxygen gas. The use of electrolysis typically reduced the cost of using hydrogen and also reduced the security concerns of the power plants in having to receive and store large quantities of a flammable gas. Typically, however, the electrolysis generators which are economically viable for providing makeup gas for the electrical generator lacked the capacity to produce sufficient volumes of hydrogen to quickly purge or fill the electrical generator after it had been shut down for maintenance. Also, plant operators still relied on manual filling of the generators which did not allow for optimal efficiencies.
Accordingly, what is needed in the art is a system for maintaining high purity levels of hydrogen in an electrical power generator and for providing a means for utilizing an on-site hydrogen generator to produce sufficient hydrogen to purge or fill the electrical power generator.
A method and apparatus is provided for a system for maintaining hydrogen purity in an electrical power generator. The method and apparatus are also provided for determining when preventative maintenance is required or if a major leak is formed in the electrical power generator. The purity system includes: a generator, a hydrogen generator configured to provide hydrogen gas to the generator, a purity monitor for detecting the level of hydrogen purity in the generator and providing a signal when the purity drops below a predetermined threshold. The system automatically compensates for gas loss or contamination to maintain the desired level of efficiency in the electrical generator.
A method for determining a hydrogen leak in an electrical generator is also provided by first measuring a first hydrogen flow rate. The method then measures a second hydrogen flow rate and determines a first rate of change of hydrogen flow from the first and second hydrogen flow rates. In response to the first rate of change of hydrogen flow exceeding a predetermined value the method will generate an alarm signal.
A method for determining a preventative maintenance schedule in an electrical generator is also provided. This method measures a first hydrogen flow rate and a second hydrogen flow rate. A first rate of change of hydrogen flow is determined from the first and second hydrogen flow rates. A first time value is then determined where the first time value represents the amount of time remaining until preventative maintenance is required.
In another alternate embodiment, a computer readable medium having computer executable instructions for performing a method for monitoring the operation of a hydrogen cooled electrical generator is provided. The method receives a first signal representative of the rate of hydrogen gas flow to an electrical generator. A rate of change of hydrogen gas flow from said first signal is determined and a second signal is generated if the rate of change of hydrogen gas flow exceeds a predetermined value. Also, a third signal representing operating time remaining until preventative maintenance is required may be generated.
The above discussed and other features will be appreciated and understood by those skilled in the art from the following detailed description and drawings.
Referring now to the drawings, which are meant to be exemplary and not limiting, and wherein like elements are numbered alike:
As the demand for power by consumers has increased, electrical power producers have increasingly turned to larger generators to fulfill the needs of society. As the size of the generators increased, it became increasingly more difficult to maintain the generator at an appropriate operating temperature to prevent damage to the generator components. Smaller generators relied on air cooling to dissipate heat from the generator rotor windings. To improve heat transfer, generator manufacturers began to utilitize hydrogen gas as a transfer agent since the thermal conductivity of hydrogen is seven times that of air.
The switch to hydrogen also yielded side benefits by reducing the windage losses in the generator due to hydrogen's lower density. As shown in
In addition to contamination, operators must cope with hydrogen leaks which typically occur at the generators seals. As hydrogen escapes, the operator must add make-up hydrogen gas to the generator in order to maintain the heat transfer and low windage benefits. In a typical generator such as a GE Frame-7 generator, the loss of hydrogen and the amount of hydrogen can reach up to 20-40 cubic feet of hydrogen per hour.
An exemplary embodiment of the present invention is shown in
The generator 12 also includes a vent line 19 which connects to a solenoid valve 20. The outlet of the valve 20 leads to a vent which allows the hydrogen gas to be properly dissipated into the atmosphere. As will be described in more detail herein, a communications link 17 connects the purity monitor 18 with the solenoid valve 20. A hydrogen generator 24 provides hydrogen gas to the generator 12 through conduit 26. Alternatively, the a controller (not shown) in the generator 12 controls the solenoid valve 20 to vent the hydrogen gas.
In the preferred embodiment, the hydrogen generator will include a water-fed electrochemical cell which is capable of disassociating reactant water into hydrogen and oxygen gas. Suitable reactant water is de-ionized, distilled water, which is continuously supplied from a water source 28. The electrochemical cell will preferably be of a polymer electrode membrane (PEM) type. The electrochemical cell may also be any other suitable electrochemical cell such as, but not limited to, alkaline, phosphoric acid, or solid oxide based cells. The hydrogen generator 24 may also be any non-electrochemical system capable of producing hydrogen gas such as, but not limited, a steam methane, or natural gas reformation.
An output sensor 30 is incorporated into the hydrogen generator 24 to sense the differential pressure between the downstream in the conduit 26. The output sensor 30 may be a pressure transducer that converts gas pressure within the conduit 26 to a voltage or current level indicative of the gas pressure. Output sensor may also be any other sensor suitable for sensing a qualitative or quantitative parameter of the gas and provide an electrical signal indicative of that parameter as an output. Such other sensors include, but are not limited to, a flow rate sensor, a mass flow sensor, and a differential pressure sensor. Optionally, a feedback signal 29 may be provided from the pressure monitor 18 to the hydrogen generator 24
Output sensor 30 interfaces with a controller (not shown) that is capable of converting the analog voltage or current level provided by the sensor 30 into a digital signal indicative of the sensed hydrogen pressure. The controller compares the sensed hydrogen pressure to a predetermined parameter for controlling the output of the hydrogen generator 24 as will be described in more detail herein.
An alternate embodiment of the electrical power generating system 10 is shown in
Electrical power generators hold a large volume of hydrogen gas, typically at least 7,500 cubic feet. Consequently, at an event where the generator needs to be purged and filled with hydrogen gas, such as at startup, or after maintenance, the operator will need access to a large volume of hydrogen gas. Events such as startup or maintenance purging typically occur on an annual basis. Since a hydrogen generator capable of generating this volume of hydrogen in a short period of time would be greatly over-sized for daily operation. Accordingly, it is desirable to have a means for storing excess hydrogen gas generated by the hydrogen generator 24. In the embodiment shown in
As discussed above, electrical power generators are large apparatus' which hold a large volume gas. In prior art systems which utilized cylinder or tube trailer delivered hydrogen gas containers, a manual shut-off valve was placed between the gas cylinders. This valve prevented the flow of hydrogen into the generator and preventing the discharging of gas into the facility in the event that a major leak occurred in the generator. Accordingly, as described above the hydrogen purity level in prior art systems would continue to drop until the operator manually opened the shut-off valve to refill the generator.
The system 10 will also have a maximum hydrogen flow Fmax 138 which corresponds to the maximum hydrogen flow the hydrogen generator 24 may produce. In the preferred embodiment, the maximum hydrogen flow Fmax 138 will be determined by the ventilation system in the facility where the generator system 10 is located. By providing adequate ventilation, even if the maximum hydrogen flow Fmax 138 is released into the facility, appropriate operating conditions will still exist. This allow the elimination of the need for the manual shut-off valve used in the prior art discussed above and allows the hydrogen generator 24 to be continuous operating and connected to the generator 12.
Trending the hydrogen flow F also provides additional advantages in maintaining safe operation of the generator system 10 as shown in
As will be described in more detail below, by trending the hydrogen flow, the component failure resulting in the hydrogen leakage may be detected and the system may take a predetermined action, such as but not limited to sounding an alarm or disabling the system. Alternatively, by being immediately notified of a potential component failure, the operator will have more time to investigate the cause of the increase hydrogen flow and adjust the operation of the generator system 10 as appropriate.
Referring to
If the answer to the query of block 66 is affirmative, either in the first instance or after one or more negative answers, the method 60 proceeds to block 68 where a control signal is passed from purity monitor 18 to the valve 20 causing the valve 20 to open. The opening of the valve 20 allows gas from the generator 12 to be vented to the atmosphere.
The method 60 then proceeds on to block 70 to produce hydrogen gas. Generally, the hydrogen generator 24 will detect the pressure drop at sensor 30 that results from the venting of the generator 12 which occurred in block 68. Typically, upon detection of this drop in pressure below the desired pressure Pdes the hydrogen generator 24 will initiate production of hydrogen gas which is transferred to the generator 12.
The method 60 then continues on to block 72 where the gas from the generator 12 is sampled and the hydrogen purity measured. Method 60 then proceeds on to query block 74 where the Hpure is compared with a desired level Hpref. If the query answers affirmative, the method 60 loops back to block 72 and continue to monitor the hydrogen purity Hpure in the generator 12. This loop continues generally until method 60 is externally terminated or paused, or until the query of block 66 is answered affirmatively.
If the answer to the query in block 74 is negative, this is indicative that the purity level of the hydrogen gas in the generator has reached a level desired by the operator. The method 60 then proceeds on to block 76 where a control signal is passed from the purity monitor 18 to the valve 20. The valve 20 closes and the venting of gas from the generator 12 stops. Method 60 then proceeds on to block 78 where hydrogen production ceases. In the preferred embodiment, when the valve 20 is closed, the pressure will rise in the generator. This pressure rise will be detected in the sensor 30, and when the pressure in the generator reaches the desired pressure Pdes the hydrogen generator 24 stops production of hydrogen gas. Typically, the desired pressure Pdes is between 30 psi and 75 psi. Method 60 then continues back to block 64 to start the process again. It will be appreciated that method 60 is performed repetitively during the operation of the system 10.
Referring to
If the query block 86 returns an affirmative response, the method 80 continues on to block 88. In block 86, purity monitor 18 sends a control signal to the hydrogen generator 24 which causes the hydrogen generator 24 to initiate hydrogen production at a predetermined flow rate and pressure Pdes. Typically, the desired pressure Pdes is between 30 psi and 75 psi, with a preferred pressure of 45 psi. In the preferred embodiment, the desired pressure Pdes is greater than the relief pressure Prelief of valve 20.
After hydrogen gas production is initiated, the method 80 continues on to query block 91 where Prelief and Pgen are introduced into the following query:
Here, the parameter Pgen represents the pressure inside the generator 12 and the parameter Prelief represents the pressure setting at which the valve 20 will open allowing the gas from the generator 12 to vent to the atmosphere. If the query in box 86 returns a negative, the method 80 loops back to box 90 and hydrogen continues to be generated and provided to the generator 12. The method 80 continues until terminated or paused by the operator.
If the query in box 91 returns an affirmative response, indicating that the pressure inside the generator has reaches a value greater than the relief setting on the valve 20, the method 80 continues on to box 92 and the valve 20 is opened. The method continues on to monitor the hydrogen purity level Hpure in box 93 and compare with the desired purity level in box 94 in a similar manner as has been described herein above.
Once the purity of the hydrogen gas in the generator achieves the desired purity level, the method 80 continues on to block 96 where the purity monitor 18 transmits a control signal to the hydrogen generator 24 causing the hydrogen generator to cease production of hydrogen gas. Once the hydrogen generator stops producing gas, the method 80 continues on to box 98 where the valve 20 will close once the pressure in the generator drops below the predetermined threshold.
Method 80 then continues back to block 84 to start the process again. It will be appreciated that method 80 is performed repetitively during the operation of the system 10.
Referring to
While the tank 40 is filling, the method 100 monitors the pressure Ptank in the tank 40. The tank 40 will also have a maximum working pressure rating Pmax. Typically, the tank 40 will have a maximum pressure rating between 2000 psi and 10,000 psi, with a preferred rating of 2,400 psi. Method 100 proceeds to block 114 where Ptank and Pmax are introduced into the following query:
If the query responds affirmatively, the method 100 proceeds query box 118 where the hydrogen purity level is compared to the desired level. If the query returns an affirmative response, which would indicate that the generator required replenishment of pure hydrogen gas. The method 100 then proceeds on to block 120 where the valve 36 is closed and then onto block 122 where the vent valve 20 is opened and gas from the generator 12 is vented to the atmosphere. Method 100 then proceeds through blocks 128-134 to replenish the generator with hydrogen gas to the appropriate purity level in the same manner as was described herein above with respect to method 60 and blocks 72-78.
It should be appreciated that the process steps in blocks 128-134 may also be accomplished using the alternate method described with respect method 80. In addition, in applications where the hydrogen generator 24 is continuously producing gas for the generator 12, it is within the contemplation of this invention that the hydrogen generator 24 provides hydrogen gas to both the tank 40 and the generator 12 simultaneously with preference being given to supplying the generator 12.
Referring to
If decision block 166 returns an affirmative response, meaning the hydrogen flow rate is greater than the parameter Z, the process transfers to block 168 as will be described with respect to
If decision block 166 indicates that the rate of change of hydrogen flow dF/dt is greater than a predetermined threshold Z, the process 153 proceeds to block 168 which transfers to process 177 shown
If decision block 184 indicates a positive, meaning that the hydrogen flow Ft=1 is less than or equal to Fmax, the process proceeds to block 185 were an alarm signal is generated alerting the operator to the condition. Process 177 then proceeds on to blocks 186 where a timer is started at tt=2, and the hydrogen flow Ft=2 is measured in block 188. The process pauses until ttt=3 in block 190 and the hydrogen flow Ft=3 is measured in block 192. Process 177 then proceeds on to block 194 where the parameters Ft=2, Ft=3 are used to calculate a new rate of change of hydrogen flow dF/dt. The process 177 then loops back to Start block 178.
If decision block 184 indicates a negative, meaning that Ft=1 is greater than Fmax, then process 177 proceeds to decision block 196 where the hydrogen flow parameter Ft=1 is compared with the ventilation flow Fvent for the facility or enclosure that the generator system 10 is housed. The parameter Fvent represents the ventilation flow through the room that is required to maintain a desirable operating point for the mixture of hydrogen with the air in the room where the generator system 10 is located. Typically, a sufficient flow is desired to maintain the hydrogen levels in the room at less than 50% of the lower flame limit (LEL) of hydrogen in air. It should be appreciated that the parameter Fvent may be a predetermined fixed value based on the design of the facility, or the process 177 may communicate with a facility control system which monitors the operation of the heating and ventilation controls (“HVAC”). If communication between the HVAC monitoring system and process 177 is enabled, process 177 can adjust the hydrogen output of hydrogen generator 24 to maintain a desired operating environment.
If decision block 196 indicates a positive and Ft=1 is less than or equal to Fvent, process 177 proceeds to block 198 which generates an alert signal. Process 177 the loops back to Start block 178.
If decision block 196 indicates a negative, the process proceeds to decision block 200 which determines if Fvent is equal to zero. Under this condition, there would be no ventilation in the facility housing the generator system 10 which may allow undesirable levels of hydrogen to build up in the facility due to the lack of ventilation. If decision block 200 indicates that the required ventilation is absent, the process proceeds to block 202 where hydrogen production in the hydrogen generator 24 is terminated and the process 177 is stopped in block 204.
If decision block 200 confirms that ventilation in the facility is operating, then the process 177 proceeds to block 206 where the hydrogen output of the hydrogen generator 24 is reduced until the hydrogen flow F is less than Fvent. An alert signal is generated in block 208 and process 177 loops back to Start block 178,
While the invention has been described with reference to a preferred embodiment, it will be understood by those skilled in the art that various changes may be made and equivalents may be substituted for elements thereof without departing from the scope of the invention. In addition, may modifications may be made to adapt a particular situation or material to the teachings of the invention without departing from the essential scope thereof. Therefore, it is intended that the invention not be limited to the particular embodiment disclosed as the best mode contemplated for carrying out this invention.
This application is a continuation application of U.S. patent application Ser. No. 10/994,772 filed Nov. 22, 2004, which was abandoned and is a continuation-in-part application of U.S. patent application Ser. No. 10/711,395 filed Sep. 16, 2004, which is now U.S. Pat. No. 7,550,113, both of which are incorporated herein by reference in their entirety.
Number | Name | Date | Kind |
---|---|---|---|
4029951 | Berry et al. | Jun 1977 | A |
4531070 | Kuhn | Jul 1985 | A |
4891629 | Gajjar et al. | Jan 1990 | A |
5088315 | Johnson | Feb 1992 | A |
5510201 | Werth | Apr 1996 | A |
5929324 | Hu et al. | Jul 1999 | A |
6305442 | Ovshinsky et al. | Oct 2001 | B1 |
6524464 | Dubey, Jr. | Feb 2003 | B2 |
6841046 | Puthawala et al. | Jan 2005 | B2 |
6893755 | Leboe | May 2005 | B2 |
20030009164 | Woloszko et al. | Jan 2003 | A1 |
20030090164 | Brosnihan et al. | May 2003 | A1 |
20030141200 | Harada | Jul 2003 | A1 |
20090211920 | Speranza et al. | Aug 2009 | A1 |
Number | Date | Country |
---|---|---|
0229719 | Jul 1987 | EP |
270315 | Jul 1928 | GB |
59216441 | Dec 1984 | JP |
60145408 | Jul 1985 | JP |
61231849 | Oct 1986 | JP |
1995231610 | Aug 1995 | JP |
Number | Date | Country | |
---|---|---|---|
20070244601 A1 | Oct 2007 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 10994772 | Nov 2004 | US |
Child | 11764882 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 10711395 | Sep 2004 | US |
Child | 10994772 | US |