All publications and patent applications mentioned in this specification are herein incorporated by reference to the same extent as if each individual publication or patent application was specifically and individually indicated to be incorporated by reference.
Energy consumption in commercial and residential buildings is a very expensive component of the cost of operating and maintaining a building. For example, commercial buildings have expensive air conditioning and heating needs that, over the lifetime of the building(s), often add up to more than double the initial cost for construction. Attempts over the years to reduce energy consumption have resulted in adding substantial increases in construction costs that are often not recouped over the short term.
Buildings represent approximately 40% of the energy used in the United States and are fueled almost entirely with fossil fuels that are expensive and damaging to the environment. Further, there are a number of problems that make building heating, ventilation, and cooling (HVAC) systems inefficient. These problems include: (1) pressure to keep construction costs low by purchasing inexpensive, wasteful HVAC systems; (2) wasting potentially useful energy rejected through chillers, etc. rather than moving it to where it is needed or storing it for later use; (3) high energy movement through walls because of inadequate insulation; (4) constantly reheating and re-cooling the building mass rather than holding it at temperature; (5) overbuilt, inefficient systems that could be made much smaller; (6) the inability to effectively use local energy (e.g. solar, body heat, etc.); (7) heating the building when the heating system is least efficient and likewise cooling the building when the cooling system is least efficient; and (8) the expense of renewable energy sources. The need thus exists for an energy and cost-efficient heating and cooling system.
Further, According to the DoE report “Energy Efficient Buildings (EEB) HUB Intelligent Building Operations (Task 4) Overview” presented at the DOE BTO Sensors and Controls Program and Project Review, May 21, 2013, intelligent building energy operations have not been broadly used largely because of two major problems. First, it is expensive and time consuming to custom design every individual building and then design the control system for the building. Second, once the building and the intelligent control system are designed, there is a costly process for creating and programming the controls then commissioning them in the building. However, if intelligent building energy operations can be applied in a cost-effective and timely manner, market barriers to wide-spread adoption would be significantly reduced. Accordingly, a need exists for intelligent cost-efficient building energy operations.
In general, in one embodiment, a method of designing an optimized heating and cooling system includes: (1) automatically importing data from an energy model into an optimization model; (2) simulating energy use of a virtual heating and cooling system operating a thermal source or sink with the optimization model based upon the data from the energy model to obtain an optimized system design; (3) developing controls for an actual heating and cooling system based upon the optimized system design; and (4) automatically exporting the controls directly to a controller for the actual heating and cooling system.
This and other embodiments can include one or more of the following features. The data from the energy model can include predicted thermal loads for the system design. The data from the energy model can include weather data for the system design. Simulating energy use to obtain an optimized system design can include calculating an amount of energy required to operate the system, determining a size of the system, or determining a cost of operating the system. Simulating the energy use can include using desired outcome parameters to determine the optimized system design. The desired outcome parameters can include lowest energy cost, lowest construction cost, or lowest life cycle cost.
In general, in one embodiment, a method of implementing an optimized heating and cooling system includes: (1) simulating energy use of a virtual heating and cooling system operating a thermal source or sink to obtain an optimized system design; (2) developing controls for an actual heating and cooling system based upon the optimized system design; (3) exporting the controls to a controller for the actual heating and cooling system; (4) operating the actual heating and cooling system; (5) tracking a thermal load on the system; (6) comparing the tracked thermal load to an expected thermal load; and (7) indicating a failure in the actual heating and cooling system if the tracked thermal load is a predetermined amount different than the expected thermal load.
This and other embodiments can include one or more of the following features. The predetermined amount can be a variance in the load of 25% or more. The method can further include obtaining the expected thermal load from an energy model. Indicating a failure can include sounding an alarm. The controls can include runtimes and start times for each of the thermal sources and sinks.
In general, in one embodiment, a method of implementing an optimized heating and cooling system includes: (1) simulating energy use of a virtual heating and cooling system operating a thermal source or sink to obtain an optimized system design; (2) developing controls for an actual heating and cooling system based upon the optimized system design; (3) exporting the controls to a controller for the actual heating and cooling system; (4) operating the actual heating and cooling system; (5) tracking a thermal load on the actual heating and cooling system for a set period of time; and (6) determining whether an additional energy saving strategy would reduce energy use of the actual heating and cooling system.
This and other embodiments can include one or more of the following features. The method can further include simulating energy use of the actual heating and cooling system under the controls prior to the determining step. The energy saving strategy can include separately controlling the pumping rates and times for a plurality of different heat sources or sinks individually. The energy saving strategy can include charging a building component in advance of projected energy needs. The energy saving strategy can include manipulating a temperature difference between a source of thermal energy and a user of energy.
In general, in one embodiment, a method for determining an optimal use of a plurality of geothermal heat exchangers includes: (1) activating a plurality of geothermal heat exchangers under a first set of controls; (2) predicting a thermal loss or gain for each of the plurality of geothermal heat exchangers over a selected period of time under the first set of controls; and (3) activating the plurality of geothermal heat exchangers under a second set of controls based upon the predicted thermal loss or gain such that the runtime and/or flow rate varies from one geothermal heat exchanger to another.
This and other embodiments can include one or more of the following features. The method can further include determining the runtime and/or flow rate for each of the geothermal heat exchangers in the second set of controls by optimizing the runtimes and flow rates. Optimizing the runtime and flow rates can include using particle swarm optimization. Activating the plurality of geothermal heat exchangers under the second set of controls can include running all of the geothermal heat exchangers at a minimum flow rate and then ramping each geothermal heat exchanger to a higher flow rate. The method can further include staggering a start-time for ramping each of the geothermal heat exchangers.
The novel features of the invention are set forth with particularity in the claims that follow. A better understanding of the features and advantages of the present invention will be obtained by reference to the following detailed description that sets forth illustrative embodiments, in which the principles of the invention are utilized, and the accompanying drawings of which:
Described herein is an optimized heating and cooling system (or heating, ventilation, and air-conditioning (HVAC)) system that includes thermal sources and/or thermal sinks and a method for optimization of such a system. The system and method described herein advantageously reduces the amount of energy required to heat and cool a building and the size of the equipment required to do so. The system and method described herein also advantageously produces automated intelligent building controls specifically for an individual building design in order to optimize the performance of the HVAC system, eliminating substantial cost and errors in the process.
The methods described herein can be used with any suitable energy management systems including geothermal HVAC, hybrid geothermal HVAC, hybrid HVAC systems, high efficiency HVAC systems, and HVAC systems that include a thermal storage capability even though aspects of the disclosure are described with specific reference to geothermal or ground-source heat pump HVAC systems. The methods described herein can be used with any of the energy systems described in U.S. Patent Application Publication No. 2011/0272117, titled “Energy Chassis and Energy Exchange Device,” and filed May 5, 2011, and/or in conjunction with the methods described in International Patent Application No. PCT/US2014/020379, filed Mar. 4, 2014 and titled “Energy Management Systems and Methods of Use,” both of which are incorporated by reference herein.
An exemplary heating and cooling system 100 is shown in
In one embodiment, a heating and cooling system, such as the system shown in
Referring still to
At step 215, the system can be tested and implemented using the controls developed at step 211. That is, the thermal load can be tracked immediately (such as by measuring the water flow at a geothermal heat exchanger and the temperature difference across it). If there is a difference in the thermal load relative to expected based upon the energy model (from steps 201 and 203), the system can flag an error and/or sound an alarm. A large difference, such as a consistent variance of 25% or more, can be used to indicate equipment failure or other problem with the system. Thus, for the initial system commissioning process, this “model-based” performance information provides a metric for comparison to actual thermal loads and equipment performance, reducing the commissioning time and identifying system issues very rapidly. When applied, this technology can identify, during the start-up and commissioning phase of a building, if the heating/cooling loads are significantly different from the anticipated loads identified in the energy model during the design process, allowing identification and corrective action to be taken immediately instead of in the future when high energy consumption indicates a potential problem. This comparison of design data versus actual performance data allows precise reporting of the actual heating and cooling energy load, the cost of meeting that load, and the availability of alternative sources of supply for meeting that load when applied to a limited thermal source or sink, such as a ground-source deep earth heat exchanger. This allows performance feedback reporting that measures the building's actual performance against the original design. In some embodiments, the optimized intelligent control software stores the original HVAC system design and energy model for the design so that the actual performance of the system can be compared to the energy projections made at the time the system was designed.
Further, once the system is implemented, performance parameters can be automatically tracked at step 217. Based upon those parameters, a simulation can be executed at step 219 (such as an 8760 simulation) to forecast future performance based upon the tracked parameters. If the determined future performance indicates an undesireable outcome at step 221 (such as an energy use that is too high, a lifecycle cost that is too high), then new optimized control algorithms can be developed and implemented at step 223. The tracking, simulation, and generating steps (217, 219, 221, 223) can then be repeated, such as every 5-7 days.
In some embodiments, the environmental, occupancy, and other factors used in the original energy model can be updated to provide a performance baseline for the comparison of actual versus predicted performance to provide system and energy performance feedback to the building owner/operator. The system can process information from the HVAC control system sensors typically applied in order to determine actual thermal energy flows to calculate the performance metrics.
A more detailed method 300 of developing the controls for an HVAC system is shown in
Thus, once the design profile is captured, the appropriate HVAC system components can be sized and configured using virtual models (computer code) of their performance to simulate the optimum operation of that equipment. The HVAC system equipment performance can be defined using a series of mathematical expressions that take into account typical operating parameters, loading, etc. From the sizing, the engineer can prepare the specifications for construction. Typically, mechanical engineers configure the HVAC system design and then use an energy model to simulate operation of the system using occupancy and use assumptions from the owner with typical weather data for the location to simulate operation of the building for a year. The peak heating and cooling loads of the system tell the engineer how large the heating and cooling components have to be. The system and process described with respect to method 300 can still include running the design in a simulation for a year, but the optimization software can be used to operate the system. In this simulation, the optimization engine reduces the use of energy, which lowers the peak equipment loads, which in turn may reduce the size of equipment or system components, such as geothermal deep earth heat exchangers and cooling towers. This advantageously creates a smaller system that both costs less to buy and reduces the energy used by the system.
A functional example of the use of the method 300 is the application of a ground-source heat pump HVAC system for a new building. One approach is to install a ground heat exchanger (GHX) that is sufficiently large to provide all heating and cooling for the facility. However, if the annual cooling load requirements are much greater than the annual heating load requirements, the GHX will need to be sized for the cooling load and will have excess capacity during the heating season. This may create a high first cost penalty, which might eliminate the consideration of a ground-source heat pump system. In lieu of this approach, if the above intelligent design optimization software is used and combined with intelligent controls to pre-condition a smaller (and less expensive) GHX using a closed-circuit cooling tower operating in the winter (heating) season, the first (construction) cost will be much lower (potentially 50 to 70%), and the energy consumption may also be lower due to more optimum entering water temperatures provided to the heat pumps.
Advantageously, the method descried with respect to
Referring to
Referring to step 411, various energy saving strategies can be used to potentially improve the efficiency of the building HVAC system after the initial controls have been implemented. These energy saving strategies can be used individually, but also in synergistic groups that make the performance of each piece of equipment more efficient and make the performance of the entire network of energy devices, including waste energy recycling and the capture of environmental energy, operate more efficient as a total system. This process continuously adapts key control algorithms to account for changing building HVAC load profiles, changing utility rate structures, changing weather, etc. In performing monitoring-based system optimization, various energy saving strategies can be implemented as algorithms in software designed to be expanded with new strategies over time.
One exemplary energy savings strategy includes determining the optimum pumping (flow) rate for a given piece of equipment in a HVAC system in order to determine how long and at what rate to operate one or more different pumps in order to minimize the amount of energy used by the entire system. For example, changing the runtime and/or flow of a plurality of different ground heat exchangers (GHX) can advantageously decrease the overall power consumption of the system.
In one exemplary study of a system that included five ground heat exchangers, in order to quantify the optimal efficiency of the GHX, the efficiency metric used (EER, or energy efficiency ratio) was defined for the GHX as the ratio of the total heat absorbed or rejected by the GHX to the power consumed by the GHX pump (nominally BTU/W-hr). Then each GHX model was run through a series of cases of varying water inlet temperature and flow rate. The results are shown in
As a result of the EER study, it was determined that in the interest of preserving minimum pump speed, and thus minimum power consumption and maximum GHX EER, a GHX staging control was desired such that at stage 1, increasing building entering water temperature would command successive GHX pumps to start at minimum flow. If building entering water temperature continued to increase (assuming the fluid loop was rejecting heat to the ground), and once all GHX pumps were running at minimum flow, each GHX pump would then be allow to speed up in sequence until such time as all GHX pumps were running at full flow (speed). The baseline model was again run through an annual, hourly simulation using pump staging control as shown in
In order to model the use of various runtimes for pumps to determine how to control the pumps (and to determine whether any energy savings would result from doing so), various modeling techniques, such as genetic algorithm optimization or particle swarm optimization, can be used. In one embodiment, particle swarm optimization is used.
Particle swarm optimization considers a random set of “particles,” each of which is a possible solution to the optimization problem (objective function), and are allowed to “fly” or move as a swarm through the solution space. In a two-variable optimization function, the solution space would be two dimensions, with each dimension corresponding to an objective function variable. A random set of particles defines the first swarm. These particles are each given a position in the solution space as well as a velocity vector. Each particle thus knows where it is and where it is going. Each particle is evaluated for its fitness to the solution, and then using this knowledge, successive new generations of particles are produced. Each particle is evaluated for both its personal best fit and its global fit. Each particle, at each generation (or position in the solution space), is evaluated to determine if it is a better fit than it was any other prior position. If not, it is left behind in the swarm. If it is better, then its fitness is compared to the rest of the swarm. If its own fitness is better than any other particle in the swarm (a global best), it is allowed to continue to the next generation. If not, it is moving away from the optimal swarm in the solution space, and so it is left behind in the swarm and not allowed to continue to the next generation. Each new population is therefore moving closer to the optimal solution in the solution space. Once the value of the global best solution remains steady from generation to generation, the global optimum has been reached.
An individual GHX can be cooled by allowing it to “rest” and dissipate its heat to the surrounding soil. Assuming that this temperature decay is exponential, the fully integrated system model (ISM) was run through a five-year simulation, and then all five borefields were “turned off” so that their decay might be predicted as shown in
Knowing that the GHX can recover on its own under zero flow conditions, each GHX can be “rested” while the others provide the heat sink for the loop. For the next run, each GHX was allowed to rest for 4000 hours in sequence over a five-year simulation as shown in
In this study, each GHX was either “on” or “off” (no variable flow), and in the interest of preserving GHX EER, each GHX that was “on” was randomly limited to 70% of maximum flow. The associated GHX temperatures are shown in
The next study was using a sequential rotating schedule for the five GHXs, but the rotation occurred every 1000 hours instead of 4000. It was deduced then that the individual GHXs would not fully recover after only resting for 1000 hours, but it was assumed that they would reach steady-state, so the question was at what soil temperature would they reach steady-state and at what EER penalty would that occur. The resulting soil temperatures are as shown in
In summary, study results suggested that: (1) the as-designed GHX pump staging flow control, when executed in the ISM, produced a near-zero creep for each GHX, but the heat pump entering water temperature varied greatly over the annual run, suggesting a varying effect on the plant EER; (2) the ISM, when executed with all GHX pumps running at 100% duty for the entire year, produced a larger annual GHX creep with no appreciable change of heat pump entering water temperature; (3) maximum GHX EER occurred at minimum GHX pump flow in both heating and cooling modes, suggesting that a pump staging control that favored all pumps running at minimum flow prior to ramping individual pumps to maximum flow may have a positive effect on GHX EER maximization; (4) the ISM was executed through an annual run with a pump staging control and the total GHX power consumption was demonstrated to be 30% less than the baseline (as-designed) configuration; and (5) particle swarm optimization of GHX pump control schedules for minimum plant power consumption demonstrated a trade-off between GHX creep and plant EER.
In one embodiment, the energy saving algorithm can thus include individually controlling each GHX pump in a system. The algorithm can employ the use of a moving horizon, such that: (1) At initial start, the GHX pumps are controlled according to the hourly run schedule calculated from the PSO process. These initial (design) run schedules are arrays of 8760 points representing hourly run information for one year. (2) After one week of continuous run, the algorithm examines actual performance to date and uses this observed performance to predict system behavior for another year. This predicted behavior is then run as an input to the ISM and, running the PSO routine again, a new 8760 runtime schedule is generated for each GHX pump; and (3) This process is repeated for the duration of the equipment operation, so that once per week, the entire year-long simulation is conducted along with the PSO algorithm to re-optimize the GHX operating schedules. In this manner, weekly optimizations are performed continuously so as to account for system operation outside design parameters.
Thus, by tracking heat transfer, pumping energy, and entering water temperature to heating or cooling equipment, an overall plant efficiency, such as an EER, can be determined. System variables, such as flow rate, can then be changed automatically to determine if additional efficiency is possible. By measuring and analyzing actual outcomes, better control algorithms can be determined instead of solely being based on theoretical information. Some thermally massive heat storage systems, such as ground-source heat exchangers can provide additional thermal capacity at lower flow rates, which is counter-intuitive to standard engineering assumed performance.
Another exemplary energy saving strategy includes charging a building component, material or system with thermal energy (or cooling that material) in advance of energy need in order to time shift available energy or time shift the discharge of the thermal energy to improve the efficiency of the system. This process includes measuring the rate of thermal decay of a given material (e.g., the fabric of a building, ice, phase-change material or water storage, the mean earth temperature of a geothermal borefield, etc.) and then using that loss rate (i.e., the thermal decay rate) to determine a temperature decay rate for the material that can be projected in order to analyze the energy efficiency of storing, or discharging a given amount of energy at a given time under given conditions. An algorithm can then be used to determine how much thermal energy can be successfully stored or dissipated over a particular period of time in that material under the given conditions in order to determine how much energy can be effectively and efficiently added to the material (net of the thermal decay rate) in order to time shift that energy to when it may be more efficiently used or discharged into the environment.
Another exemplary energy saving strategy includes using multiple variables to determine the best method for an HVAC system or sub-systems to use to meet building energy demands over a given time period with the user defining the best outcome based on the selection of one, or more criteria. This may entail activating various thermal sources and sinks based upon actual thermal loads of the building, availability of the source or sink to address the load and the relative cost of the energy from the source or sink. For example, if 58° F. chilled water is needed for radiant cooling, it might be available from an air-cooled chiller (relatively high energy cost), closed-circuit evaporative cooling tower (lower energy cost), or directly from a ground-source earth heat exchanger (lowest energy cost).
Another exemplary energy saving strategy includes directly manipulating the temperature difference between the source of thermal energy and the use of that energy in order to increase the efficiency of the energy transfer (i.e. the ΔT). The application of monitoring-based control algorithm optimization allows the software to automatically track energy transfer per unit of input energy, then optimize the flow rate, etc. to provide optimum heat transfer at lowest input energy consumption.
Other exemplary energy saving strategies include: (1) determining the optimal size of each component in a hybrid HVAC system for the highest return on investment, highest energy efficiency, or other factors; (2) determining the optimal setpoints; (3) automated fault detection and diagnostics; (4) optimal maintenance scheduling; (5) increased occupant awareness via performance feedback reports; and (6) determining the most efficient source of energy to use, when and for how long to achieve a target level of energy availability from a hybrid HVAC system that has multiple methods to provide the needed heating and cooling source thermal energy.
Additional details pertinent to the present invention, including materials and manufacturing techniques, may be employed as within the level of those with skill in the relevant art. The same may hold true with respect to method-based aspects of the invention in terms of additional acts commonly or logically employed. Also, it is contemplated that any optional feature of the inventive variations described may be set forth and claimed independently, or in combination with any one or more of the features described herein. Likewise, reference to a singular item, includes the possibility that there are a plurality of the same items present. More specifically, as used herein and in the appended claims, the singular forms “a,” “and,” “said,” and “the” include plural referents unless the context clearly dictates otherwise. It is further noted that the claims may be drafted to exclude any optional element. As such, this statement is intended to serve as antecedent basis for use of such exclusive terminology as “solely,” “only” and the like in connection with the recitation of claim elements, or use of a “negative” limitation. Unless defined otherwise herein, all technical and scientific terms used herein have the same meaning as commonly understood by one of ordinary skill in the art to which this invention belongs. The breadth of the present invention is not to be limited by the subject specification, but rather only by the plain meaning of the claim terms employed.
This application claims priority to U.S. Provisional Application No. 61/874,297, filed Sep. 5, 2013 and titled “SYSTEM FOR OPTIMIZATION OF BUILDING HEATING AND COOLING SYSTEMS,” the entire contents of which are herein incorporated by reference.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/US2014/054402 | 9/5/2014 | WO | 00 |
Publishing Document | Publishing Date | Country | Kind |
---|---|---|---|
WO2015/035241 | 3/12/2015 | WO | A |
Number | Name | Date | Kind |
---|---|---|---|
2154263 | Carrier | Apr 1939 | A |
3729051 | Mannion | Apr 1973 | A |
4304294 | Reisman | Dec 1981 | A |
4360056 | O'Connell | Nov 1982 | A |
4375806 | Nishman | Mar 1983 | A |
4909312 | Biedenbach et al. | Mar 1990 | A |
5224357 | Galiyano et al. | Jul 1993 | A |
5244037 | Warnke | Sep 1993 | A |
5274571 | Hesse et al. | Dec 1993 | A |
5323843 | Olszewski et al. | Jun 1994 | A |
5467265 | Yamada et al. | Nov 1995 | A |
5479358 | Shimoda et al. | Dec 1995 | A |
5564282 | Kaye | Oct 1996 | A |
5671608 | Wiggs et al. | Sep 1997 | A |
5706888 | Ambs et al. | Jan 1998 | A |
5778683 | Drees et al. | Jul 1998 | A |
5934369 | Dosani et al. | Aug 1999 | A |
5937665 | Kiessel et al. | Aug 1999 | A |
5992507 | Peterson et al. | Nov 1999 | A |
6250371 | Amerman et al. | Jun 2001 | B1 |
6250560 | Kline et al. | Jun 2001 | B1 |
6276438 | Amerman et al. | Aug 2001 | B1 |
6959520 | Hartman | Nov 2005 | B2 |
7228696 | Ambs et al. | Jun 2007 | B2 |
7407003 | Ross | Aug 2008 | B2 |
7647773 | Koenig | Jan 2010 | B1 |
7894943 | Sloup et al. | Feb 2011 | B2 |
8219250 | Dempster et al. | Jul 2012 | B2 |
8291720 | Hartman | Oct 2012 | B2 |
8346398 | Ahmed et al. | Jan 2013 | B2 |
8378280 | Mills et al. | Feb 2013 | B2 |
8571832 | Raman et al. | Oct 2013 | B2 |
8851066 | Kapteyn | Oct 2014 | B1 |
9080789 | Hamstra et al. | Jul 2015 | B2 |
9360236 | Stewart et al. | Jun 2016 | B2 |
9709337 | Pilebro et al. | Jul 2017 | B2 |
20040206085 | Koenig et al. | Oct 2004 | A1 |
20040267408 | Kramer | Dec 2004 | A1 |
20060048770 | Meksvanh et al. | Mar 2006 | A1 |
20070017667 | Weng | Jan 2007 | A1 |
20070179917 | Patel et al. | Aug 2007 | A1 |
20070192078 | Nasle et al. | Aug 2007 | A1 |
20070235179 | Phillips | Oct 2007 | A1 |
20070295477 | Mueller et al. | Dec 2007 | A1 |
20080230205 | Seguin et al. | Sep 2008 | A1 |
20090019876 | Guglietti et al. | Jan 2009 | A1 |
20090095477 | Nguyen et al. | Apr 2009 | A1 |
20090194257 | Niu et al. | Aug 2009 | A1 |
20090287355 | Milder et al. | Nov 2009 | A1 |
20090307636 | Cases et al. | Dec 2009 | A1 |
20100200191 | Livingston | Aug 2010 | A1 |
20100223171 | Baller | Sep 2010 | A1 |
20110125451 | Cheifetz et al. | May 2011 | A1 |
20110153103 | Brown | Jun 2011 | A1 |
20110220320 | Kidwell | Sep 2011 | A1 |
20120072181 | Imani | Mar 2012 | A1 |
20120232701 | Carty et al. | Sep 2012 | A1 |
20120271462 | Dempster et al. | Oct 2012 | A1 |
20130013121 | Henze et al. | Jan 2013 | A1 |
20130048114 | Rothman et al. | Feb 2013 | A1 |
20130125565 | Erpelding et al. | May 2013 | A1 |
20130179373 | Mutchnik et al. | Jul 2013 | A1 |
20140133519 | Freitag | May 2014 | A1 |
20150248511 | Suryanarayana et al. | Sep 2015 | A1 |
20150316295 | Hamstra et al. | Nov 2015 | A1 |
20160018125 | Hamstra et al. | Jan 2016 | A1 |
Number | Date | Country |
---|---|---|
2783217 | May 2006 | CN |
101004331 | Jul 2007 | CN |
201066246 | May 2008 | CN |
102008039105 | Feb 2010 | DE |
102012002028 | Aug 2013 | DE |
S60-251336 | Dec 1985 | JP |
2000-212733 | Aug 2000 | JP |
2003-130494 | May 2003 | JP |
2003-214722 | Jul 2003 | JP |
2006-234376 | Sep 2006 | JP |
200890514 | Apr 2008 | JP |
2009-250454 | Oct 2009 | JP |
4948079 | Jun 2012 | JP |
WO2009007684 | Jan 2009 | WO |
WO2009042581 | Apr 2009 | WO |
Entry |
---|
Berke et al.; Application of artificial neural networks to the design optimization of aerospace structural components; NASA Tech. Memo; retrieved for the internet (https://ntrs.nasa.gov/archive/nasa/casi.ntrs.nasa.gov/19930012642.pdf); 12 pgs.; Mar. 1993. |
LeCroy et al.; Application of neural networks and stimulation modeling in manufacturing system design; SOUTHCON/96 (Conference); Orlando, FL, USA; pp. 322-326; Jun. 25-27, 1996. |
Hackel, Scott P.; Development of Design Guidelines for Hybrid Ground-Coupled Heat Pump Systems; Master of Science thesis submitted at the University of Wisconsin—Madison; May 2008. |
Kecebas et al.; Artificial neural network modeling of geothermal district system thought exergy analysis; Energy Conversion and Management; 64; pp. 206-212; Dec. 2012. |
Hamstra et al., U.S. Appl. No. 16/247,446 entitled “Energy chassis and energy exchange device,” filed Jan. 14, 2019. |
Number | Date | Country | |
---|---|---|---|
20160195288 A1 | Jul 2016 | US |
Number | Date | Country | |
---|---|---|---|
61874297 | Sep 2013 | US |