A fire alarm system typically includes one or more notification appliances that notify the public of an alarm. A Notification Appliance Circuit (NAC) powers the notification appliances that are connected to a fire alarm control panel. A primary power source (such as line power from an AC line) may supply power to the fire alarm control panel. The fire alarm system may also include a backup voltage source that supplies power to the fire alarm control panel. The backup voltage source (such as a battery) is used when the primary power source is unavailable. Abnormal conditions may cause either the primary or backup power supply to operate at a voltage less than nominal. The lowest voltage that will power the NAC is defined as the worst case operating voltage. The NAC may provide power from the control panel to the notification appliances. The notification appliances draw a significant amount of current from the NAC and create a voltage drop across the wires. The voltage drop may reduce the voltage supplied to the notification appliances at the end of the NAC (opposite the control panel) to a level that is below the voltage necessary to power the notification appliance.
Notification Appliances have a specified operating range. During the design of the fire alarm system, a designer estimates whether all the notification appliances will be powered above their specified minimum operating voltage at the worst case operating voltage. To make this estimation, the designer predicts the voltage drop from the fire alarm panel to the last notification device. The voltage drop calculation is based on the electrical characteristics of the NAC as it is configured in the specific installation. The designer then subtracts the predicted voltage drop from the worst case output voltage of the fire alarm panel and compares the result to the minimum operating voltage of the notification appliance. The NAC design is acceptable when the calculated voltage is above the minimum operating voltage of the notification appliance.
However, the installed system may differ from the designed system. For example, the wiring distance of the NAC may differ due to practical considerations in the building, or alternate routings of the wires by the electrical installers. The actual voltage drop on a NAC in the installed system is frequently different than the calculated voltage drop. Therefore, it is important to confirm, after installation, that the NAC has sufficient voltage to operate the notification appliances.
Conventionally, it was difficult to test the voltage drop in an installed system. It was even more difficult to test the voltage drop at or near the lowest suitable voltage on the NAC. The lowest suitable voltage on the NAC is typically the voltage supplied from the control panel when the backup power source, for example, one or more batteries, are at the end of their rated life. The NAC voltage drop is difficult to determine at the lowest suitable voltage because the nominal output voltage of the control panel is significantly higher than the worst case operating voltage.
Notification appliances draw more current at low voltage than they do at higher voltages. If less current is drawn from the NAC, then the voltage drop across the NAC will also be reduced. Measuring the voltage at the control panel and then at the last notification appliance during higher voltage operation (supplied by the primary power source or the backup power source at the beginning of its rated life), will not give an accurate measurement of the voltage drop in the system during the lowest voltage operation (i.e. when the battery is at the end of its rated life).
In a system where the lowest voltage condition occurs when the batteries are nearly discharged, the only way to measure the voltage drop on a NAC during the lowest voltage operation and verify that it is within its designed parameters, is to power the system from batteries for an extended period of time, until the batteries are near their rated end of life and then activate the notification appliances and measure the voltage drop on each NAC. This is generally not practical and is often not done because it is time consuming and potentially damaging to the batteries. In a system where the lowest voltage occurs when the AC power supply is operating under abnormal conditions (for example a fault on the AC line lowers the system voltage), it is difficult to create the abnormal condition. It requires powering the panel from expensive equipment to vary the AC input. This equipment may be practical in a lab environment but very impractical for a field technician to carry. Accordingly, a need exists for testing whether the NAC is capable of operating at a reduced or worst case system voltage that is simple in design and operation.
The present embodiments relate to a diagnostic monitoring system that determines whether a NAC installation is capable of operating at a reduced, nominal, or worst case system voltage. In order to accomplish this, the diagnostic monitoring system may comprise three parts: (1) a device to control the voltage supplied to the NAC; (2) a remote measurement device to measure the voltage of the NAC (such as an end-of-line device); and (3) a communications system between the Fire Alarm and measurement device. The device to control the voltage supplied to the NAC may create the reduced, nominal, or worst case system voltage. For example, in a test mode, the device to control the voltage supplied to the NAC may control the voltage supplied to the NAC to a test amount. For example, the NAC may be supplied a reduced, nominal, or worst case voltage that may simulate if the NAC were powered at least partly by a battery (such as fully powered by a battery) or powered by a faulty AC line. Specifically, the device may output a voltage that is lower than the voltage supplied under nominal conditions (such as outputting a voltage of 19.5 V in a system that is nominally 24V). As another example, the NAC may be supplied an increased voltage that may simulate if the NAC were powered by a higher voltage than the nominal voltage. In this way, the system may create the presence of abnormal power supply conditions by powering the NAC at the worst case operating voltage (such a worst case lower or upper voltage). This includes simulating using a run-down battery to power the NAC without requiring the running-down of the battery or simulating a faulty AC line without requiring expensive equipment to vary the AC line voltage. Thus, the system may be tested for low-power or high-power conditions without creating a power supply fault.
A fire alarm system may include one or more notification appliances connected in a series across a NAC. The first device to control the power to the NAC (the NAC voltage controller) may be disposed on one end of the NAC. The second device to measure the voltage of the NAC (the NAC voltage measurement device) may be disposed on the other end of the NAC. The NAC voltage controller and NAC voltage measurement device may be in communication with a system controller.
The NAC voltage controller and the NAC voltage measurement device may be used to determine whether the NAC may be operated using a minimum voltage (such as using a backup battery). Specifically, the NAC voltage controller may control the voltage output to the NAC, and the NAC voltage measurement device may measure the voltage at the end-of-the-line. Based on the voltage as measured by the NAC voltage measurement device, it may be determined whether the NAC may be operated properly. Specifically, a monitoring system (such as a fire alarm panel) may receive the voltage as measured by the NAC voltage measurement device, and determine if the NAC may be powered using minimum operating voltage (such as using battery backup). If the measured voltage is less than the minimum NAC appliance voltage, the NAC will have insufficient voltage to maintain functionality of the Notification appliances during low voltage operation. Likewise, if the measured voltage is greater than or equal to the minimum Notification appliance voltage, the NAC will have sufficient voltage to maintain functionality of the notification appliances.
Other systems, methods, features and advantages will be, or will become, apparent to one with skill in the art upon examination of the following figures and detailed description. It is intended that all such additional systems, methods, features and advantages be included within this description, be within the scope of the invention, and be protected by the following claims.
The monitoring system 1 may include a control panel 15 that includes a system controller 2 and the NAC controller 30. The system controller 2 may communicate with the NAC controller 2 in order to activate one or more of the notification appliances 6 in the NAC 5.
As discussed in more detail in
The monitoring system 1 may further include a primary power supply PWR that supplies power to the monitoring system 1.
A backup voltage source BVS may supply power to the monitoring system 1.
The control panel 15 may operate using the power supplied from the primary power supply PWR or the backup voltage source BVS. As discussed above, the primary power supply PWR and the backup voltage source BVS may supply power to the notification appliances 6 via the NAC 5. The system controller 2 or the NAC controller 30 may draw current from the power supplied and create a voltage drop before the power is supplied to the NAC 5. For example, the voltage supplied to the NAC 5 may be less than the voltage supplied to the system controller 2.
As discussed in more detail below, the monitoring system 1 may operate in a normal operational mode and in a test mode. When in the test mode (which may be initiated by operator input to the monitoring system 1), the monitoring system 1 may produce or create an operating voltage (such as a lower or minimum voltage or an upper or maximum voltage) for the NAC using the NAC output controller 10. The lower or minimum operating voltage may be used for systems where low battery operation is the worst case (or lowest) system voltage, so that the production of the lower or minimum operating voltage may simulate that the batteries are being depleted. Or, the lower or minimum operating voltage may be used for systems where the AC power is faulty, so that production of the lower or minimum operating voltage may simulate the fault on the AC power line. The fault on the AC power line may result in a lower AC voltage being input. The upper or maximum voltage may likewise simulate a fault in the system. One configuration of the control panel 15 may include a voltage regulator that outputs a regulated voltage. When there is a fault on the AC power line, the voltage regulator may output a reduced regulated voltage, such as the nominal voltage, or may output an upper voltage. The measurement of the voltage of the end-of-line for the NAC may then be measured using NAC voltage measurement device 7.
As shown in
Though
The notification appliances 6 may be constant power consumption devices. When an alarm condition is sensed by a detection device, the system controller 2 may signal the alarm to the notification appliances 6 through the NAC 5. Notification appliances may include, for example, a visual alarm (strobe), an audible alarm (horn), a speaker, or a combination thereof. Though only one NAC 5 is shown in
As discussed above, the monitoring system 1 may also include a NAC voltage measurement device 7. One or more NAC voltage measurement devices 7 may be coupled to the NAC 5. As shown in
The voltage measurement circuit 20 may measure a voltage on any portion of the NAC 5. For example, the voltage measurement circuit 20 may measure a voltage on the wires 3 and 4 across any of the notification appliances 6. As shown in
The voltage may be measured on a part of the NAC (such as at the end of the NAC 5), as shown at block 604. As discussed above, the NAC voltage measurement device 7 may measure the voltage and may then communicate the measured voltage to the control panel 15. The measured voltage may then be compared with a predetermined voltage (such as a minimum operating voltage) to determine whether the measured voltage is greater than the predetermined voltage, as shown at block 606. Alternatively, instead of being performed by the system controller 2, the voltage comparison may be performed by the NAC voltage measurement device 7 and/or the NAC controller 30.
Whether the measured voltage is greater or less than the predetermined voltage may determine whether the NAC 5 may operate or may not operate sufficiently at the worst case operating voltage (such as nearly depleted batteries or with a faulty AC power line). In particular, if the measured voltage is greater than the predetermined minimum operating voltage, it is determined that the NAC 5 has been setup and configured properly and may operate satisfactorily when operated at the worst case operating voltage, as shown at block 608. Conversely, if the measured voltage is less than the predetermined minimum operating voltage, it is determined that there are too many notification appliances on the NAC 5 and/or there is a problem with the wiring, as shown at block 610. Specifically, a part of the NAC 5 (such as one or more notification appliances 6) may potentially fail when the panel is operated at a supply voltage that is equal to or less than nominal. For example, if the minimum operating voltage for a NAC appliance 6 is 16 V and the measured voltage is 17 V, then it is determined that the measured voltage is greater and that the NAC 5 may operate satisfactorily using battery power.
Alternatively, instead of modifying the voltage at NAC output terminals 3 and 4 using control panel 15 (via the NAC Controller 30), a device separate from the control panel 15 may be used. For example, the wiring to output terminals 3 and 4 may be disconnected from the control panel 15 for the test and connected to a separate diagnostic device, such as a handheld diagnostic tool that powers the NAC 5 and simulates power to the NAC 5 at low voltage. The handheld diagnostic tool may include a separate power supply (or access to a separate power supply) to provide the power to simulate the low voltage. The NAC voltage measurement device 7 may still be used to measure the voltage at the end of the line.
The test sequence may be as follows: (1) disconnect NAC wiring from the control panel (such as disconnect wiring at output terminals 3 and 4); (2) connect NAC wiring to handheld diagnostic tool; (3) run the test software on the diagnostic tool (including reducing the voltage to the NAC); and (4) analyzing the signal from the NAC voltage measurement device 7 to determined whether the system passes or fails (the analysis, including the comparison of the voltage measured by the NAC voltage measurement device 7 with a predetermined voltage, may be performed at the NAC voltage measurement device 7; alternatively, the measured voltage may be transmitted to the handheld diagnostic tool for the handheld diagnostic tool to perform the comparison).
While the invention has been described with reference to various embodiments, it should be understood that many changes and modifications can be made without departing from the scope of the invention. It is therefore intended that the foregoing detailed description be regarded as illustrative rather than limiting, and that it be understood that it is the following claims, including all equivalents, that are intended to define the spirit and scope of this invention.
Number | Name | Date | Kind |
---|---|---|---|
3641570 | Thompson | Feb 1972 | A |
3665461 | Gnagi et al. | May 1972 | A |
4274087 | Swanson et al. | Jun 1981 | A |
4470047 | Vogt et al. | Sep 1984 | A |
4777473 | Weston et al. | Oct 1988 | A |
5705979 | Fierro et al. | Jan 1998 | A |
5754103 | Kanai et al. | May 1998 | A |
6034601 | Barrieau et al. | Mar 2000 | A |
6040769 | Payne | Mar 2000 | A |
6104286 | Luquette | Aug 2000 | A |
6281789 | Furtado et al. | Aug 2001 | B1 |
6313744 | Capowski et al. | Nov 2001 | B1 |
6426697 | Capowski et al. | Jul 2002 | B1 |
6502044 | Lane et al. | Dec 2002 | B1 |
6567001 | Barrieau et al. | May 2003 | B1 |
6693532 | Capowski et al. | Feb 2004 | B2 |
7091847 | Capowski et al. | Aug 2006 | B2 |
7333010 | Barrieau et al. | Feb 2008 | B2 |
7382245 | Girouard | Jun 2008 | B2 |
7469204 | Brooks et al. | Dec 2008 | B2 |
20010038336 | Acevedo | Nov 2001 | A1 |
20030080865 | Capowski et al. | May 2003 | A1 |
20040140891 | Capowski et al. | Jul 2004 | A1 |
20050139682 | Iasso et al. | Jun 2005 | A1 |
20060214811 | Barrieau et al. | Sep 2006 | A1 |
20070001819 | Becker et al. | Jan 2007 | A1 |
20070115111 | Girouard | May 2007 | A1 |
20070179722 | Brooks et al. | Aug 2007 | A1 |
20070188427 | Lys et al. | Aug 2007 | A1 |
20070220907 | Ehlers | Sep 2007 | A1 |
20080266076 | Barrieau et al. | Oct 2008 | A1 |
20080272654 | Lontka | Nov 2008 | A1 |
20090009352 | Savage et al. | Jan 2009 | A1 |
20090167544 | Becker et al. | Jul 2009 | A1 |
20090322526 | Lontka | Dec 2009 | A1 |
20100066552 | Salgueiro et al. | Mar 2010 | A1 |
20100066557 | Henson et al. | Mar 2010 | A1 |
20100073175 | Lontka | Mar 2010 | A1 |
20100127849 | Barrieau et al. | May 2010 | A1 |
Number | Date | Country | |
---|---|---|---|
20100127849 A1 | May 2010 | US |