The present invention relates to the field of valves, particularly valves for fire-fighting systems, but also valves used in the medical domain, for example in systems for injecting and metering drugs, regulating pressure, treating blood, etc.
Fire-fighting systems of the sprinkler type are well known in the prior art. These systems are used as automatic fire-fighting systems. They allow the location at which the fire has broken out to be dowsed quickly by being triggered in response to the sensing of heat. As soon as the temperature has reached a certain value (typically of the order of 68° C.) the sprinkler head ruptures and water is sprinkled onto the location concerned. The effectiveness of such systems is recognized and they are in very widespread use.
There are three main types of sprinkler system and these are as follows:
One conventional type of dry sprinkler system is depicted schematically in
Current safety standards demand that the sprinklers 3 be grouped together (with a maximum Surface area of 5000 m2 per group) so that the location of the incident can be determined with precision. The only method known to date is to use a different hydro-pneumatic combination for each group of sprinklers 3′, 3″, 3″′. If the location in which a fire-fighting system is fitted covers several storeys, it is also necessary to scale up the number of hydro pneumatic combinations accordingly.
The cost of such a unit may be as much as CHF 10,000 and, what is more, depending on the configuration of the building to be protected, numerous pipes are led out in parallel to reach the various points required. Furthermore, the number of combinations also makes the testing that has to be carried out regularly on this kind of system more complicated and increases the sources of potential problems.
In addition, all of the secondary networks 2, 2′, 2″, 2″′ connected to one hydro-pneumatic combination and its check valve 1 have to be completely filled before the pressure reaches its maximum in the sprinkler group concerned, and this causes time to be lost because of the size of such systems, and this delay could prove critical when fire fighting, a situation in which the first minutes or even seconds are of vital importance. For this reason, official standards also define the maximum permissible amount of time that the water can take to reach the group of sprinklers 3′, 3″, 3″′ furthest from the check valve 1.
Another problem faced in dry systems is that of the time it takes for the air to be released from the network when a fire breaks out. Indeed, when the lengths of such networks are taken into consideration, it is necessary to operate on as low a pressure as possible in that part of the network which lies downstream of the check valve 1 in order to minimize this release time. To solve this problem, a kind of air release accelerator in the form of a valve at the end of the network has been added. This valve makes the system more complicated and requires an individual control. In addition, the entire network will none the less fill with water, a situation which from this viewpoint is no improvement over systems which do not have air release accelerators.
Finally, in such networks of pipes which may stretch over several kilometers, with numerous bends and unions, there is always a problem of pressure drops in the part downstream of the check valve 1. To compensate for these drops and to maintain the pressure that keeps the check valve 1 closed, use is made of compressor 4 which injects pressurized air into the network when needed (see
It is an object of the invention to improve the known systems and overcome the abovementioned disadvantages.
More specifically, the invention seeks to propose a dry fire-fighting system which works better than the known systems while at the same time remaining of acceptable cost.
From a more general standpoint, it is an object of the invention to propose a system that can be applied to various technical fields, in addition to the fire-fighting system field, particularly the medical field.
One idea of the invention is to subdivide the network downstream of the water check valve into several sub-networks, each sub-network being isolated by an individual valve, thus making it possible to prevent water from entering the parts of the network where it is not needed, hence improving performance.
Another idea of the invention is to propose such an intermediate valve which is capable both of compensating for the pressure drops in the network and also of opening fully when a fire is detected.
The invention is described in greater detail hereinafter using examples illustrated by the figures attached to this application.
In order to compensate for the pressure drops between the check valve 1 and the valves 6′, 6″, 6″' use is made of the compressor 4, in the conventional way. By contrast, in the pipes of the secondary networks 2′, 2″, 2″′ there is no special compressor for doing this, because it would be too expensive. Hence, the valve according to the invention is capable of compensating for the pressure drops which occur in the branches 2′, 2″, 2″′ of the network between the valves 6, 6′, 6″ and the groups of sprinklers 3′, 3″, 3′″.
The pressure maintained between the valves 6, 6′, 6″ and the groups of sprinklers 3′, 3″, 3′″ is typically of the order of 0.5 to 3 bar. By contrast, the pressure maintained between the check valve 1 and the valves 6, 6′, 6″ is typically of the order of 1.5 to 4 bar, therefore 1 bar higher than the pressure indicated above.
The operation of the valves 6′, 6″, 6″′, which are identical, and the way their controls work is explained in more detail in relation to
In
This mechanism comprises in particular a three-way valve 7 with three positions A, B and C, which is connected on one side to the pipe 2′and on the other side to a cylinder 8 through a restrictor 9. The cylinder comprises a piston 10 actuating the valve 6 (thus allowing it to be opened or closed) and a spring 11 driving the piston 10 toward the left-hand side of the figure in the cylinder 8.
The cylinder 8 is additionally connected to the pipe 2′ by a commissioning pipe 12 which comprises a nonreturn element 13 and allows the pressure to be dumped from the piston without delay.
Using this system it is possible to compensate the pressure drops in the downstream pipe 2′ by using the higher pressure present in the upstream pipe 2 in the way explained hereinafter.
Position A of the valve 7 (see
In position B (see
As soon as the piston has moved past the second passage 16 connected to the restrictor 9, it is possible to enter the standard operating mode that allows for compensation and corresponds to position C of the valve 7.
The compensation mode of operation is depicted in
With the valve 6 slightly open, the air which is kept at a pressure higher than about 1 bar upstream of the valve 6, by the compressor 4, will be released into the pipe 2′ through the valve 6. This air, which cannot enter the volume of the cylinder through the passage 15 because of the nonreturn element 13 will, by contrast, pass through the valve 7 and the restrictor 9 to ultimately enter the volume of the cylinder 8 and drive the piston 10 back (to the right in
The restrictor 9 has a delaying effect in that it prevents the system from returning to a state of equilibrium immediately and makes it possible to ensure that the valve 6 is correctly closed by using the volume of the downstream network as a pressure reservoir.
In the event of a fire, the operation is as follows. One sprinkler head, for example 3′, ruptures so that the air present in the pipe 2′ downstream of the valve 6 is released. The pressure in the cylinder decreases, causing the piston to move to the left in
The embodiments given hereinabove are so by way of example and these concepts can be generalized using the elements and the principles of the invention for other applications requiring a similar kind of operation, namely a system in which, in one state, a fluid is kept at an upstream pressure by means of a fluid at a lower downstream given pressure shut off at a check valve and, in another state, the fluid is allowed to pass by enabling the check valve if the pressure downstream drops below a predetermined pressure.
The elements involved in opening and shutting of the main pipe of a sprinkler network, that is to say the check valve, may be as follows:
The compensating of the downstream pressure performed by the system according to the invention may be internal to the opening and shut-off elements or external thereto. Furthermore, the compensation may be achieved with or without delay in opening/closing and may be performed in advance of or otherwise the opening/closing of the regulating control.
The regulating controls for providing compensation or introducing an alarm situation (opening or closing down the system) may be as follows:
For example, it is possible to conceive of an actuator comprising electronic controls using, as its regulating parameters, the upstream and downstream pressures and commanding the opening/closure of the valve on the basis of these values in a way equivalent to that described hereinabove.
By way of trip element, which is a sprinkler in the embodiment described hereinabove, it is possible to imagine other types of sensors that perform the same function. Apart from heat detectors, use may be made of a pressure sensor or of any other type of sensor that may be beneficial to the application in question.
Of course, the system according to the invention can be coupled to the pipework using the following systems:
The system according to the invention needs to transmit an alarm when it is opened and closed. This alarm raised using electrical, pneumatic, mechanical or other contacts.
The open/close command allows action on the main valve of the invention by a system involving an electric motor, a pneumatic actuator, a hydraulic actuator, an oleopneumatic actuator or alternatively a mechanical actuator.
Of course, the elements indicated hereinabove can be selected freely according to the application to be made by applying the principles of the invention.
Number | Date | Country | Kind |
---|---|---|---|
01969/04 | Nov 2004 | CH | national |
Number | Date | Country | |
---|---|---|---|
Parent | 11791479 | May 2007 | US |
Child | 14694947 | US |