The present invention relates generally to managing energy usage in a facility. More specifically, the present invention relates to an electrical utility managing electricity usage in one or more facilities.
Most electric utilities in North America generate electrical energy using power plants that operate by burning fossil fuels, such as coal, or through nuclear fission. Such power plants are able to generate power on a continuous basis for extended periods of time, but have the disadvantage that their power output cannot be quickly increased or decreased. Furthermore, any excess power generated using coal or nuclear power plants generally cannot be economically stored by a utility for later use by the utility's customers. Consequently, if not used by the utility's own customers, such excess power must be sold on the open market, often at a very low price. It is essential that generation and load (including export sales or purchases) are in balance at all times.
Electrical utilities adjust generation to match demand on a continuous basis. The electrical load that the electric utility supplies typically fluctuates throughout the day, with the lowest demand occurring at night, and the highest demand occurring in the late afternoon and early evening. Generating facilities that can change output rapidly are either relatively scarce (hydroelectric—8% of US total capacity), or are inefficient and expensive to operate (simple gas turbine generators). During times of low demand, because most utilities in North America have excess power available as a result of their relying on coal or nuclear power plants, the cost of electricity is relatively low and selling excess power is uneconomical. During times of high demand, because additional capacity cannot quickly be brought online or may be available only by using high cost generating facilities, the marginal cost of electricity is relatively high and buying additional power to meet demand can be very expensive. While a utility can generate additional electricity during periods of high demand to meet marginal demand in excess of normal generation capacity, such generation is usually done using inefficient gas turbine equipment, and the power that results is therefore usually relatively expensive. Electric utilities consequently have an incentive to generate a constant level of power that is sufficient to meet their customers' power needs during periods of high demand so as to avoid having to purchase or generate expensive power, but at the same time have a disincentive to avoid overgeneration because excess power cannot be stored or sold economically during periods of low demand. In other words, electric utilities have great incentive to minimize the difference between the power consumed during periods of high demand versus the power consumed during periods of low demand.
The utility, in fact, must meet two requirements:
Both of these methods of control are known in the art. An example of a load shedding system involves a utility manually calling consumers during periods of high demand and asking them to shut off certain loads for a period of time. This method is disadvantageous in that it relies on human interaction and is therefore slow and prone to error, and in that it requires a load that can either be shut off during periods of high demand or powered with an alternative energy source. Peak shaving generally is disadvantageous in that customers may not have loads that can easily be powered using alternative energy sources or shut off during periods of high demand. Furthermore, utilities typically pay their consumers to participate in peak shaving programs, at a cost that is often in excess of $0.15/kWh saved.
With the specific exception of load shedding, all utility controls have generally relied on controlling generation rather than load. As the utilities have grown, this method has become more and more difficult. In recent times, the utilities have focused some attention on the use of Load Based Regulation (LBR) systems. Almost all of these systems have used either a form of energy storage, or a load that can be controlled to provide the utility with the capacity to do the short term AGC control.
Accordingly, it would be advantageous to develop at least one of a new system, method, or memory that allows electric utilities to better regulate the demand for electricity.
According to one aspect of the invention, there is provided a method of managing energy supplied by an electric utility to a customer facility that is heatable by electrical and non-electrical heating means, comprising: determining a desired cumulative instantaneous electrical load of the utility (“target load”); determining a total instantaneous electrical load on the utility imposed by the facility (“current load”); determining a requested load from the utility as the difference between the target load and current load; when the requested load is positive, increasing heating of the facility by the electrical heating means to meet at least part of the requested load and decreasing heating of the facility by the non-electrical heating means; and when the requested load is negative, decreasing heating of the facility by the electrical heating means to reduce at least part of a requested load deficit and increasing heating of the facility by the non-electrical heating means. The desired target load can be set equal to a peak load on the utility imposed by the facility in a selected time period.
The method can further comprise determining a marginal cost of heating the facility by the electrical heating means and a marginal cost of heating the facility by the non-electrical heating means, and increasing the heating of the facility by the electrical heating means only when the marginal cost of heating by the non-electrical heating means is greater than the marginal cost of heating by the electrical heating means. The method can further comprise determining a peak billed demand threshold of the facility in a selected billing period and a total electrical demand of the facility and increasing the heating of the facility by electrical heating means only when the total electrical demand of the facility is less than the peak billed demand threshold of the facility. All electrical consumption by the facility can contribute to determination of the peak billed demand threshold of the facility. Alternatively, only electrical consumption by the facility for non-heating purposes can contribute to determination of the peak billed demand threshold.
Increasing heating of the facility by the electrical heating means increases a current heating electrical load of the facility, and decreasing heating of the facility by the non-electrical heating means decreases a current heating non-electrical load of the facility. When the requested load is greater than the current heating non-electrical load, the method may further include increasing heating of the facility by the electrical heating means thereby increasing the current heating electrical load of the facility by the current heating non-electrical load; and decreasing heating of the facility by non-electrical heating means thereby decreasing the current heating non-electrical load to zero. Additionally, when the requested load is not greater than the current heating non electrical load, the method may further include increasing heating of the facility by the electrical heating means thereby increasing the current heating electrical load by the requested load; and decreasing heating of the facility by the non-electrical heating means thereby decreasing the current heating non-electrical load by the requested load.
The method may also include determining whether the requested load of the electricity vendor is greater than the current heating non-electrical load of the facility only when the difference between the peak billed demand threshold and the facility total electrical demand is greater than the current heating non-electrical load.
The method may also include determining whether the requested load is greater than a difference between the peak billed demand threshold and the current heating electrical load if the difference between the peak billed demand threshold and the facility total electrical demand is not greater than the current heating non-electrical load; and then when the requested load is greater than the difference between the peak billed demand threshold and the current heating electrical load: increasing heating of the facility by electrical heating means thereby increasing the current heating electrical load to the peak billed demand threshold; and decreasing heating of the facility by non-electrical heating means thereby decreasing the current heating non-electrical load by the difference between the peak billed demand threshold and the current heating electrical load.
When the requested load is not greater than the difference between the peak billed demand threshold and the current heating electrical load, the method may include increasing heating of the facility by electrical heating means thereby increasing the current heating electrical load by the requested load; and decreasing heating of the facility by non-electrical heating means thereby decreasing the current heating non-electrical load by the requested load.
The method may also include determining whether the difference between the peak billed demand threshold and the facility total electrical demand is greater than the current heating non-electrical load only when the peak billed demand threshold is greater than the facility total electrical demand. Additionally, the method may also include determining whether the peak billed demand threshold is greater than the facility total electrical demand only when a marginal cost of electricity is less than a marginal cost of fuel.
According to a further aspect of the invention, there is provided a computer readable medium having encoded thereon steps and instructions for execution on a processor to manage energy supplied to a facility, the steps and instructions including the method as described above.
According to another aspect of the invention, there is provided a system for managing energy supplied by an electric utility to a customer facility. The system comprises a server having inputs communicative with the facility to receive a total instantaneous electrical demand of the facility, and communicative with the utility to receive a desired cumulative electrical load of the utility. The system also comprises a processor communicative with the inputs and having a memory having recorded thereon statements and instructions for execution by the processor to perform a method as described above. The system also comprises outputs communicative with the facility to control heating of the facility by non-electrical means and electrical means.
The utility can include an automatic generation control system, in which case the server inputs are communicative with the utility to receive an area control error from the automatic generation control system, and the processor is programmed to determine a target load of the utility from the area control error and perform the method as described above to control the heating of the facility by electrical means to meet any additional generation required by the automatic generation control system.
According to another aspect of the invention, there is provided a method of providing a spinning reserve to an electric utility having a customer facility that is heatable by electrical and non-electrical heating means. The method comprises: heating the facility by electrical heating means using electricity from the utility at a current heating electrical load that is at least as high as a maximum selected spinning reserve; receiving a spinning reserve request from the utility; then decreasing heating of the facility by the electrical heating means until the current heating electrical load is decreased by the requested spinning reserve, and increasing heating of the facility by the non-electrical heating means.
There are three general areas where a vendor (electric utility or Independent System Operator (ISO)) may benefit. The system may be used as a dispatchable load, increasing system load during off peak periods when surplus electricity is likely to be sold to other utilities at a very low price. It may also be used to provide Regulation Services, allowing the utility to use a fast responding load for AGC Control, instead of a generator, reducing system costs. Finally, it may also be used as a “Spinning Reserve” source, allowing the utility to reduce load rapidly, without disturbing customers, in the event of a system disturbance when generation has been lost.
One benefit of the invention is that, as opposed to peak shaving wherein the vendor must pay consumers to reduce electrical load, the vendor can make money according to the present invention by selling electricity to its own consumers in excess of the price the electricity would otherwise fetch on the open market during a period of low demand.
An additional benefit of the invention is that it allows the vendor to increase the base electrical load it has to satisfy. This is beneficial in that the vendor can satisfy an increased base electrical load through relatively non-polluting and inexpensive means of electricity generation, such as nuclear power, as opposed to being forced to satisfy large periodic spikes in electrical load using expensive, relatively polluting forms of generation such as generating power using gas turbines.
An additional benefit of the present invention is that it can make unpredictable, variable output sources of electricity, such as wind power, economically viable. If the vendor can quickly increase and decrease electrical load as desired, any sudden increases or decreases in electricity generation that result from wind power, for example, can be sold to the vendor's customers.
A benefit of the aspects of the present invention that utilize electrical means to affect the current heating electrical load of the facility is that such electrical means can be relatively inexpensive and consequently can be easily adopted and installed into the facility. For example, a relatively inexpensive electric boiler can be purchased as an electrical means that is used to affect the current heating electrical load of the facility, with the added benefit that use of the electric boiler can offset use of non-electrical heating means such as a fuel boiler, thereby reducing fossil fuel usage.
A benefit of the aspects of the invention that utilize electrical and non-electrical means to affect the current heating electrical and non-electrical loads of the facility, respectively, is that the facility total heating load can remain constant regardless of how facility heating is apportioned between the electrical and non-electrical means. Consequently, a change in the current heating electrical load does not negatively affect the total heating provided to the facility.
a) is an exemplary graph of electrical energy that is supplied by the utility to various facilities over a given time period;
b) is an exemplary graph of electrical energy that is supplied by the utility to various facilities over a given time period, according to the first embodiment of the invention;
c) is an exemplary graph of electrical energy consumption by any given facility over a given time period;
d) is an exemplary graph of electrical energy consumption by any given facility over a given time period, according to the first embodiment of the invention;
In contrast to “peak shaving,” an alternative method of regulating demand such that the difference between power usage during periods of high and low demand is reduced is “valley filling”. Valley filling in the context of an electrical utility relates to increasing the electrical load demanded by the utility's customers during off-peak periods such that the difference between the “peak electrical load” (the maximum amount of power that is utilized by the utility's customers at any given time over a given time period) and the “base electrical load” (the minimum amount of power that is consistently utilized by the utility's customers over the time period) is reduced. In one embodiment, such valley filling involves utilizing the electricity that is generated by the utility but not consumed by the utility's customers. Some utilities must sell this excess electricity on the open market at a discounted price (which is often below the marginal cost of generating this excess electricity) because their generation technology cannot economically adjust electrical output to follow the load demanded by its customers. Therefore, the utility generates electricity at a relatively steady state, and “valleys” below the steady state output are created because of the fluctuating demand from the customers. The embodiments described herein can be used, for example, to utilize this excess electricity, i.e. “filling in the valley”, to heat the space or water of customer facilities instead of or in conjunction with heating by fossil fuels.
In some embodiments, electric heaters such as electric boilers or furnaces are installed in each facility to complement existing non-electric heaters, such as gas boilers or furnaces, and the electric furnaces can be operated to produce space heating and the electric boilers are operated to produce space heating and/or domestic hot water.
In the embodiments that will be described below, there is provided an algorithm, stored on a memory and executable by a processor, for managing energy supplied by an electric utility to a customer facility that is heatable by electrical and non-electrical heating means, and in particular, to operate the electrical and non-electrical heating means in a manner that is economic for the utility, and also preferably economic for the facility. This algorithm is hereinafter referred to as the “utility valley filling algorithm”.
Referring to
The facility B in this embodiment is a building that requires heat and electricity. The facility B is supplied electricity from the utility A via power lines 39 to power electrically-powered fixtures and devices (not shown) found within the facility B. Installed at, in or near the facility B are components which use electricity and fuel to heat the facility B, as depicted in
The electrical heating assembly 14 is comprised of an electrical heating element 22 and an electrical heat storage device 24. The heating element 22 can be one or more electric furnaces to heat air and/or one or more electric boilers to heat water. Instead or in addition to the electric furnace, the electric boiler can be coupled to a heat exchanger to heat air. The electrical heat storage device 24 can be a container for storing heated water, such as the boiler's water tank. Similarly, the fuel heating assembly 16 is comprised of a fuel heating element 26 and a fuel heat storage device 28, wherein the fuel heating element 26 can be one or more fuel furnaces and/or fuel boilers, and the fuel heat storage device 28 can be a heated water storage container. One or more components of the electrical and fuel heating assemblies 14, 16 can pre-exist in the facility B, in which case the server 200 can instruct the facility B to use such components to manage electricity and fuel used by the facility B. Alternatively, one or more of these components can be installed if not already in the facility B for use by the server 200. Each of the electrical and fuel heating assemblies 14, 16 can have an SCR controller to allow continuous adjustment over the entire operating range of the heating assemblies 14, 16, and each of the heating assemblies 14, 16 can also have a revenue certified meter, or “smart meter”, that provides readings such as current kW, kVAR, voltage and system frequency.
The utility A supplies electricity via the power line 39 to the electric heating element 22 of the electric heating assembly 14. The facility B has a fuel storage tank 29 for storing fuel for use by the fuel heating assembly 16. The fuel can be natural gas, butane, propane, heating oil or any other heating fuel as is known in the art. Fuel is purchased from a fuel vendor (not shown) who sends a tanker (not shown) to replenish the tank 14 from time to time. Alternatively, the facility B can be coupled to a fuel line (not shown) and the fuel vendor can supply fuel directly to the facility B via the fuel line.
The utility A supplies electricity to the facility B and can be, for example, an electricity vendor such as the British Columbia Hydro and Power Authority (“BC Hydro”). “Utility” as used in this description also includes utility operators. The facility B, while diagrammed as a single facility, in practice typically represents a plurality of facilities B that can all be simultaneously supplied with power from the utility A. The server 200 can communicate with the utility A and facility B using, for example, electrical power lines as a medium or via any other suitable type of network, including a packet-switched network such as the Internet. Optionally, installed at the facility B can be a facility energy management system that is able to alternate between electrical and non-electrical (i.e.: fuel) sources of energy to provide heating to the facility B.
The facility B has a variety of heating and electrical loads, which can be summarized as follows:
Referring particularly to
The server 200 outputs the following signals to the facility B:
The server 200 accepts as an input the following signal from the utility A:
The server 200 outputs the following signals to the utility A:
In one embodiment, the server 200 communicates with a controller (not shown) at the facility B. The controller communicates with sensors (not shown) that measure the various electrical (both heating and non-heating) and fuel loads of the facility B. The controller also communicates with and can control the electrical and fuel heating assemblies 14, 16 such that the amount of electricity and fuel consumed by the electrical and fuel heating assemblies 14, 16, respectively, can be adjusted in accordance with the signals received from the server 200. In the embodiments considered herein, the controller at the facility B can set the consumption of the electrical heating assembly 14 to be equal to the target electric heater load 216, and accordingly set the consumption of the fuel heating assembly 16 to be the difference between the facility total heating load 20 and the target electric heater load 216. In an alternative embodiment, no controller has to be physically present at the facility B, and the electrical and fuel heating assemblies 14, 16 can be controlled remotely, such as directly using the server 200.
Graphically, “utility valley filling” can be understood through reference to
a) is an exemplary curve of cumulative electrical load of the facilities B prior to implementation of the utility valley filling algorithm. As can be seen in
b) is an exemplary curve of cumulative electrical load of the facilities B following execution of the utility valley filling algorithm. The utility valley filling algorithm, using methods such as those described below in relation to
c) and 2(d) graphically represent the demand of any given facility B for a given period of time. The vertical axis 43 represents electrical load, in kW, that the facility B places on the utility A, while the horizontal axis 44 represents the time of the day in hours, beginning at midnight and ending 24 hours later. The curve 47 represents the cumulative electrical load of the facility B in kW, and the area 49 below the curve 47 represents the energy, in kWH, consumed by the facility B.
c) is an exemplary curve of demand of any given facility B prior to implementation of the utility valley filling algorithm. In
d) is an exemplary curve of demand of any given facility B following execution of the utility valley filling algorithm. In the embodiment depicted in
Referring now to
Assuming the marginal cost of electricity is less than the marginal cost of fuel for the subject facility B, the server 200 then determines whether the facility B is currently consuming electricity at its peak demand 209 (block 302). Again, if the facility B is consuming electricity at its peak demand 209, then, from the perspective of the facility B, additional electricity cannot be used economically, and the server 200 should proceed to querying whether other facilities (block 312) can satisfy the demand request from the utility A.
In an alternative embodiment (not depicted), a maximum economic electrical load can be determined for each facility. The maximum economic electrical load is not greater than the peak demand 209 of all the facilities B that are customers of the utility A and can be set to equal the peak demand 209. However, the maximum economic electrical load can also be set to a level below the peak demand 209 so that if the facility B requires additional electrical power, that power can be supplied without the facility total electrical demand exceeding the peak demand 209.
If facility total electrical demand is less than peak demand 209 of the subject facility B, then the server 200 determines whether the difference between peak demand 209 and the facility total electrical demand is greater than the current heating non-electrical load (block 304). This means that at least some of the heating being provided by the fuel heating assembly 16 (e.g. a fuel boiler or furnace) can be replaced by heating from the electrical heating assembly 14, such as an electrical boiler or furnace, so long as the total electrical demand stays below the peak demand 209, i.e. avoids incurring a higher peak demand charge. If this difference is greater than the current heating non-electrical load, then the current heating non-electrical load could be reduced to zero (e.g. by shutting off the gas boiler or furnace), if necessary, with the current heating electrical load economically increasing by a corresponding amount, and the server 200 proceeds to block 306.
At block 306, the server 200 determines whether the “requested load” by the utility A is greater than the current heating non-electrical load of the facility B. The “requested load” is the difference between the target load 218 of the utility A and the current load 220 representing the load of all of the facilities B; the requested load (when greater than zero) therefore represents the excess produced electricity which the utility A desires to sell to its customers to heat or otherwise be used by the facilities B. If the requested load is greater than the current heating non-electrical load, then heating provided by the fuel heating assembly 16 can instead be performed by the electric heating assembly 14, which is executed by: increasing the current heating electrical load by the current heating non-electrical load; and decreasing the current heating non-electrical load to zero. Consequently, the current load 220 will increase by the current heating non-electrical load (block 308). In other words, the server 200 causes the subject facility B to heat itself by electricity instead of fuel to the extent that it is economical for the facility B to do so, thereby consuming some of the excess produced electricity and lowering the utility's requested load. If there is still excess produced electricity, there remains a requested load by the utility A, and the server 200 proceeds to a subsequent facility B (block 310) in an attempt to further meet the requested load.
If the requested load is less than the current heating non-electrical load, then the current facility B can meet the entire requested load by operating its electric heating assembly 14. The server 200 increases the current heating electrical load by the requested load, decreasing the current heating non-electrical load by the requested load. As a consequence, the requested load goes to zero and the current load 220 rises to equal target load 218. In other words, the requested load is satisfied entirely by the present facility B, and the process can therefore subsequently end (block 320).
Returning to block 304, for the subject facility B, if the difference between peak demand 209 and the facility total electrical demand is not greater than the current heating non-electrical load, then the server 200 proceeds to block 316. At block 316, the server 200 determines whether the utility's requested load is greater than the difference between peak demand and the facility total electrical demand of the subject facility B. If the requested load is not greater, then the server 200 progresses to block 318 and adjusts current heating electrical and non-electrical loads and the current load 220 as described above. If the requested load is greater, then the server 200 proceeds to block 314 and sets the current heating electrical load of the subject facility B to its peak demand 209; decreases the subject facility's current heating non-electrical load by the difference between peak demand 209 and the facility total electrical demand; and increases the utility's target load 218 by the difference between peak demand 209 and the facility total electrical demand. As block 314 does not result in the requested load being decreased to zero (i.e.: the current load 220 is not set equal to the target load 218), the server 200 proceeds to block 312 and proceeds to another facility B in an attempt to further increase demand.
Referring now to
If the utility's requested utility current load decrease is greater than the current heating electrical load of the subject facility B, then assuming that the capacity of the fuel heating assembly 16 of the subject facility B is sufficiently high, the entirety of the current heating electrical load can be transferred from the electric heating assembly 14 to the fuel heating assembly 16. Consequently, at block 404, the current heating non-electrical load is increased by the current heating electrical load by activating or increasing output of the fuel heating assembly 16; and the current heating electrical load is decreased to zero by de-activating the electric heating assembly 14. Consequently, the utility's current load 220 is also decreased by the facility's current heating electrical load. As the utility's requested current load decrease will still be non-zero, the utility will require other facilities to shut down or reduce output from their electric heating assemblies 14, and thus the server 200 then proceeds to another facility B (block 406) in an attempt to decrease the current load.
If the utility's requested current load decrease is not greater than the facility's current heating electrical load, then (at block 408) the facility's current heating non-electrical load is increased by the requested load decrease by activating or increasing output from the fuel heating assembly 16; the current heating electrical load is decreased by the requested load decrease by de-activating or reducing output from the electric heating assembly 14. Consequently, the current load 220 will decrease by the requested load decrease. As the requested load decrease is zero after block 408, the process can end (block 410).
Referring now to
At block 500, the server 200 will determine whether the requested load from the utility A is greater than the current heating non-electrical load of the facility B. When the requested load is greater than the current heating non-electrical load, only some of the current load can be met by the electric heating assembly 14 of the subject facility B and the server 200 proceeds to block 502; otherwise, the server 200 proceeds to block 506.
If the requested load is greater than the current heating non-electrical load, then assuming that the capacity of the electric heating assembly 14 is sufficiently high, the entirety of the current heating non-electrical load can be transferred from the fuel heating assembly 16 to the electric heating assembly 14. Consequently, at block 502, the current heating electrical load is increased by the current heating non-electrical load by activating or increasing output of the electric heating assembly 14; and the current heating non-electrical load is decreased to zero by deactivating the fuel heating assembly 16. Consequently, the current load 220 is also decreased by the current heating non-electrical load. As the requested load will still be non-zero, the server 200 then proceeds to another facility B (block 504) in an attempt to increase electrical demand from the facility B to meet the utility's requested load.
If the requested load is not greater than the current heating non-electrical load, then the electricity consumption of the electrical heating assembly 14 can be increased to meet all of the requested load, and (at block 506) the current heating electrical load is increased by the requested load by increasing the electrical output of the heating assembly 14; and the current heating non-electrical load is decreased by the requested load by deactivating or reducing output of the fuel heating assembly 16. Consequently, the utility's current load 220 is increased by the requested load. As the requested load is zero after block 506, the process can end (block 510). Of note, the server 200 does not factor whether adjusting the electrical and fuel usage of the facilities is economical to the facilities, and only bases its decisions on carrying out the most economical course of action from the perspective of the utility A.
Optionally, any increase (or decrease) in the target load can be apportioned equally between a plurality of facilities B to which the server 200 and the utility A are coupled. Alternatively, if any particular one of the facilities B is incapable of accepting the entirety of its portion of a load increase, the load for that particular facility may be increased to the greatest extent possible, with any excess load assigned to one of or apportioned amongst the remaining facilities.
The server 200 may execute the utility valley filling algorithm from time to time, such as every few seconds, refreshing the values of the various signals used in executing the algorithm each time in order to ensure that the algorithm is consistently being implemented using up-to-date and accurate values.
According to a further embodiment, there is provided a computer readable medium, such as random access and read only memories and various disc-based media, each having encoded thereon the aforedescribed steps and instructions. This medium is accessed by a server or other computing device which is communicative with the utility A and its facilities B and can control the operation of the electric and fuel heaters in the facilities B. The medium can be installed on the computing device directly, or be located remotely from the computing device in a separate computer and communicative with the computing device by known networking means.
According to yet another embodiment, the server 200 is programmed to execute the valley filling algorithm such that the facility B is operated to provide a spinning reserve to the utility A. A spinning reserve is any back-up energy production capacity which is made available to a utility within short notice e.g. 10 minutes, and can be operated continuously for a defined length of time, e.g. at least two hours. The server has an additional input (not shown) communicative with the utility A which receives a request from the utility A for spinning reserve. The utility valley filling algorithm stored on the memory of the server and executed by the processor of the server is modified so that when a request for spinning reserve is received from the utility A, the server 200 sends a control signal to the electrical heating assembly 14 to reduce the current heating electrical load by the requested spinning reserve, and sends another signal to the non-electrical heating assembly 16 to increase the current heating non-electrical load by the same amount. To ensure that the there is sufficient capacity to meet the maximum contracted spinning reserve of the utility A, the utility valley filling algorithm can be modified so that electrical heating assembly 14 is operate at a current heating electrical load that is always at least as high as the contracted spinning reserve.
One practical effect of the above is that the utility A is able to “dispatch demand” as it is able to “dispatch generation”. Utilities A dispatch generation by increasing and decreasing power generation as required in response to demand. “Dispatching demand” is akin to dispatching generation in reverse. If the utility A must satisfy more demand than it has supply, in addition or as an alternative to “dispatching generation”, the utility A could “dispatch demand” by reducing demand according to the algorithm discussed in relation to
In contrast to peak shaving, one benefit of utility valley filling is ease of application, in that consumers can relatively inexpensively buy an electric boiler, for example, for use during periods of low demand. When utility valley filling results in an increase in demand for electricity during periods of otherwise low demand, greenhouse gas emissions from the facility will be reduced as fossil fuel usage will be displaced by increased electricity usage.
A second benefit of utility valley filling is that, as opposed to peak shaving wherein a utility must pay consumers, a utility can make money using utility valley filling, as it can sell power to its own consumers in excess of the price the power would otherwise fetch on the open market during a period of low demand. A third benefit of utility valley filling is that consistent utility valley filling can result in an increased “base electrical load”, or minimum amount of power that is consistently utilized by facilities. Instead of using inefficient means of power generation, such as expensive gas turbine equipment, to satisfy periodic spikes in load, a utility that has to satisfy a significantly increased base electrical load can instead use cleaner (i.e.: reduced greenhouse gas emissions) and less expensive means of electricity generation, such as nuclear or wind power. One result of this is that when base electrical load is increased, fossil fuel usage by the facility is decreased, and an overall drop in greenhouse gas emissions results. An overall drop in greenhouse gas emissions results because not only does the facility reduce its fossil fuel consumption, but such reduction in fossil fuel use is offset by increased electricity consumption that is produced using a relatively clean form of generation.
A fourth benefit of utility valley filling is that it can make unpredictable, variable output sources of electricity, such as wind power, economically viable. A wind turbine, for example, may generate a great deal of power when the demand for electricity and the price a utility can charge for electricity are low, and also may generate hardly any power when the demand for and price of electricity are high. Consequently, such variable output sources are often not attractive to utilities. A utility that can increase or reduce the demand it must satisfy as desired would be able to increase demand for electricity during periods of otherwise low demand and decrease demand for electricity during periods of otherwise high demand, thereby making economical such unpredictable, variable output sources of electricity.
A fifth benefit of utility valley filling wherein the electrical heating assembly 14 and the fuel heating assembly 16 are used to heat the facility B is that regardless of changes in how the heating load is apportioned between the electrical heating assembly 14 and the fuel heating assembly 16, the facility total heating load 20 can remain constant. Consequently, from the facility B's point of view, a change in the electrical consumption of the electrical heating assembly 14 because of a change in the needs of the utility A does not negatively affect the total amount of heating provided to the facility B, since the fuel heating assembly 16 is able to compensate for changes in the heating output of the electrical heating assembly 14. In prior art methods such as “peak shaving”, referenced above, reducing the electrical load of the facility B means that certain electrical devices or services must be shut down and that operations at the facility B suffer as a result, as no alternative energy source is available to compensate for the decrease in electricity from the utility A. According to the present embodiments, not only can the fuel heating assembly 16 compensate for changes in output of the electrical heating assembly 14, but the fuel heating assembly 16 is able to respond quickly enough such that users do not notice any change in electrical load at all.
As mentioned above, one use of the aforedescribed embodiments is to “dispatch demand” instead of “dispatch generation”. Conventionally, one scenario in which the utility A has been forced to “dispatch generation” is when the power output of electric generators within a jurisdiction (“Jurisdiction”) deviates from the amount of load in the Jurisdiction. For example, in Ontario, Canada, the Independent Electric System Operator (“IESO”) is responsible for calculating the market price of electricity and for overseeing the purchase and sale of electricity within Ontario. Every five minutes, the IESO calculates a new market price for electricity by balancing the supply of electricity with the projected demand for electricity over the following five minute interval. As supply is balanced against projected demand, there are necessarily deviations between the supply of electricity and the actual demand in the five minute interval; these deviations are collectively referred to as “Area Control Error”. An Automatic Generation Control System (“AGC System”) monitors the Area Control Error and accordingly dispatches generation in response to it. If supply exceeds load, generation is reduced; conversely, if supply is less than load, generation is increased. Matching supply and load is important because if supply drops below load, relatively expensive electricity will flow into the Jurisdiction via “tie lines”, which electrically couple the Jurisdiction to neighbouring jurisdictions, and because the system frequency within the Jurisdiction will fall below a preset threshold (60 Hz in Ontario). Conversely, if supply exceeds load, electricity will flow out of the Jurisdiction via the tie lines at a loss, and system frequency will exceed the preset threshold.
In order to be able to increase and decrease generation as required, the utility A can contract to have generated for it a specific amount of power (“AGC Additional Generation”). In Ontario, for example, the IESO contracts with various electricity suppliers to generate for it up to 150 MW of AGC Additional Generation. In order to be able to increase and decrease supply as required, the AGC System may be configured to consistently use 75 MW of this power, such that generation can be increased (in which case some of the electricity supplier's remaining generation capacity is utilized) or decreased (in which case the electricity suppliers are instructed to generate less power) by as much as 75 MW.
As discussed above, generating the AGC Additional Generation is typically expensive and may be done with relatively heavily polluting forms of generation (e.g.: gas turbines). Electricity generated in this fashion can easily cost at least $0.10-$0.15/kWh. This is in contrast to what is a typical average price of electricity in the Jurisdiction; in Ontario, for example, the typical average price of electricity can be approximately $0.054/kWh.
Instead of the utility A contracting to have expensive electricity generated such that it can “dispatch generation”, the aforedescribed embodiments can be used to control the load of the facilities B within the Jurisdiction, i.e. to “dispatch demand” to the facilities B, thereby resulting in a much more inexpensive and less polluting way of ensuring that generation matches load. Notably, such an application of “dispatchable demand” differs from increasing the base electrical load such that the difference between the base electrical load and the peak electrical load is reduced. The AGC System can “dispatch demand” to help ensure that supply meets load and to reduce Area Control Error regardless of the difference between the base electrical load and the peak electrical load.
Referring now to
In
Assuming that each facility B utilizes the electrical and fuel heating assemblies 14, 16 to heat DHW, then from the facility B's point of view it can be shown that replacing a single fuel boiler with the pair of electrical and fuel heating assemblies 14, 16 coupled to the server 200 executing the utility valley filling algorithm is an economically wise choice. For example, presume that natural gas is the fuel used by the fuel heating assembly 16 and that the price of fuel is approximately $10/GJ. Also presume that the facility B purchases electricity at a cost of approximately $0.02/kWh (or roughly $5.60/GJ). Then, as indicated in Table 1 below, for a 300 kW electric heating assembly 14 the facility B will have recouped its installation costs in 5 years:
As mentioned above, a typical average price of the electricity used to meet the base electrical load within the Jurisdiction is $0.054/kWh. The utility A can purchase electricity at this price in sufficient quantities to satisfy 75 MW in load of the electrical heating assemblies 16 of the facilities B and then resell it to the facilities B at the price of $0.02/kWh, as noted above. Consequently, the net cost to the utility A for the electricity is $0.034/kWh, which is significantly cheaper than the $0.10-$0.15/kWh that is typically paid for AGC Additional Generation.
In a conventional system wherein AGC Additional Generation is used in order to equate generation and load, generation is increased when load increases and generation is decreased when load decreases. In a system wherein as much as 150 MW of AGC Additional Generation is available, typically 75 MW of baseline AGC Additional Generation is purchased at $0.10-$0.15/kWh. If load in the electrical grid rises and more generation is needed, additional AGC Additional Generation can be purchased at this price; if load in the electrical grid falls and less generation is needed, less than 75 MW of the AGC Additional Generation can be used, at a savings of $0.10-$0.15/kWh.
In contrast, when using the server 200 to “dispatch demand” to the facilities B according to the present embodiment, the utility A can purchase 75 MW at a net price of $0.034/kWh. If load in the electrical grid rises, the server 200 can instruct the electrical heating assemblies 14 of the facilities B to decrease their electricity usage by the amount load has risen in the rest of the electrical grid. In this way, this additional load can be satisfied from the electricity that would otherwise have been used by the facilities B for heating. If, for example, the current load 220 on the utility A has just risen by 15 MW, the target load 218 of the utility A will decrease by 15 MW, as the utility A will want to decrease electricity usage of the electrical heating assemblies 14 of the facilities B so as to be able to satisfy the sudden increase in load placed on the electrical grid by other users in the Jurisdiction. The “requested load decrease” can then be set to 15 MW, as discussed in respect of
Practically, in order to provide redundancy and to increase reliability, multiple servers 200 can be used to control various groups of facilities. Electric heating assemblies 14 can be installed having typical capacities of 300 kW to 2 MW.
While particular embodiments have been described in the foregoing, it is to be understood that other embodiments are possible within the scope of the invention and are intended to be included herein. It will be clear to any person skilled in the art that modifications of and adjustments to this invention, not shown, are possible without departing from the spirit of the invention as demonstrated through the exemplary embodiment.
Number | Date | Country | Kind |
---|---|---|---|
61/100.908 | Sep 2008 | US | national |
61/156359 | Feb 2009 | US | national |
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/CA09/01374 | 9/29/2009 | WO | 00 | 3/29/2011 |