1. Technical Field
This disclosure relates generally to fire prevention sprinkler systems, and more particularly to a fire prevention sprinkler system that can prevent freezing of the system even during cold weather. It further relates to a fluid-distribution system to supply a fluid to a system of fire-prevention sprinklers to prevent freezing thereof.
2. Description of Related Art
Freezing weather is a danger to fire prevention sprinklers, as to other plumbing systems, if water is present in the sprinklers or associated piping and is allowed to freeze. When the sprinklers and associated piping are located in premises that are kept above freezing temperature at all times, this is not a problem.
Where the sprinklers must provide protection for unheated premises, such as some warehouses, loading docks, concealed spaces, or attics, it is not economical to heat the premises just to protect the sprinkler system. One common approach to solving that problem is to retain the water in a portion of the piping system that is in a heated area, and to maintain the sprinklers themselves dry except when in actual operation applying water. These “dry” sprinklers are expensive, and the water in the system piping must remain above freezing temperatures.
Another method for sprinkler protection in freezing conditions is to use a dry pipe sprinkler system. This system uses an air compressor or nitrogen to fill the sprinkler system piping. The sprinklers must be of the dry type. When a sprinkler operates, a control valve opens and allows water to flow into the piping system and discharge from the now-open sprinkler or sprinklers. There is a time delay in providing water application to the fire, which must be determined and taken into account to provide proper fire protection. Such a system requires special installation to prevent trapping of water in the piping system and the equipment, and dry sprinklers are very expensive in comparison to a standard wet pipe sprinkler system.
Another method is to fill the sprinkler system piping with a mixture of water and an antifreeze solution. Recent studies have shown, however, that high percentages of antifreeze can cause actually be dangerous to occupants in the fire area. This is also a relatively expensive method of providing freeze protection due to the cost of materials, and inspection and maintenance requirements.
All of these methods are impractical for certain types of premises, and they each add a significant cost to provide freeze protection to a fire sprinkler system.
It is desired to provide a fire prevention sprinkler piping system that can prevent freezing even when used at low temperatures. It is also desired to provide a fluid-distribution system that can distribute a heated fluid to a fire prevention sprinkler system to prevent freezing.
Some embodiments disclosed herein may utilize an active heat source or generator to provide heat to warm the warming medium fluid. In particular, some embodiments may utilize a radiant heating system to heat the warming medium.
Other sources of heat to warm the medium can be used, examples including water heaters, geo-thermal devices, boilers, and other heat transfer equipment.
A passive heating system may be used in some embodiments.
As shown in
Preferably, a thermostatic control 26 is located in the protected premises, and is coupled to actuate the heat source 18 and pump 22 as needed. It is particularly contemplated to actuate the pump 22 and heat source 18 to cause them to heat and distribute the warming medium 20 whenever the temperature in the premises falls to a certain level. For example, that level may be 50° F. (10° C.). In the illustrated example, when the temperature in the premises is measured as being below that value, the heat source 18 and pump 22 are actuated, and the warming medium 20—in this case, water—is heated to a higher temperature, such as 60° F. (about 15° C.), and circulated through the system to maintain the sprinklers 12 above freezing temperature.
The circulated warming medium 20 also warms the pipes 14 that supply water to the sprinklers 12, to ensure that those pipes 14 also do not freeze.
The thermostatic control 26 may utilize a thermometer 28 or equivalent device (see
In another approach, illustrated in
A higher or lower value for the premises temperature can be used to determine when the system is to be activated, and could in principle be any desired temperature that is sufficiently above 40° F. (about 4° C.) to provide certainty that the sprinklers 12 and the pipes 14 that supply them will not freeze. Similarly, the temperature to which the warming medium 20 is heated need not be 60° F., although it is believed that this temperature is a favorable one in terms of ensuring that the sprinkler system will not freeze, while not requiring excessive energy or cost to heat the medium beyond what is necessary.
As mentioned, radiant heating is preferred as the active heat source 18, but other heat sources may be used instead, including water heaters, geo-thermal devices, boilers, and other types of known heat transfer equipment.
As an alternative to an active heat source, it is also contemplated to use a passive system for providing heat to the warming medium. In such a system, illustrated in
The domestic water supply may be the source of water to be used as the warming medium, via check valve 34; this is also the case with the embodiment of
While various example embodiments of the present invention have been described above, it should be understood that they have been presented by way of example, and not limitation. It will be apparent to persons skilled in the relevant art(s) that various changes in form and detail can be made therein. Thus, the present invention should not be limited by any of the above described example embodiments, but should be defined only in accordance with the following claims and their equivalents.
Further, the purpose of the accompanying Abstract is to enable the U.S. Patent and Trademark Office and the public generally, and especially the scientists, engineers and practitioners in the art who are not familiar with patent or legal terms or phraseology, to determine quickly from a cursory inspection the nature and essence of the technical disclosure provided herein. The Abstract is not intended to be limiting as to the scope of the example embodiments presented herein in any way.
This application claims benefit under 35 U.S.C. §119(e) of provisional A.N. 61/563,118, filed Nov. 23, 2011, the entire contents of which are incorporated herein by reference.
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/US12/66456 | 11/23/2012 | WO | 00 | 5/22/2014 |
Number | Date | Country | |
---|---|---|---|
61563118 | Nov 2011 | US |