The above mentioned utility application of Cowans et al discloses a system and method of temperature control in which the temperature of a load is varied by thermal exchange with a saturated fluid directly, without requiring an intervening heat transfer fluid. Typically the saturated fluid is a refrigerant used in pure gas phase, or pure liquid phase, or more often in a mixed or saturated phase. In accordance with the invention, the vaporizable refrigerant is processed through substantially conventional compression and condensation steps as provided by commercially available equipment. However, compressed but not condensed refrigerant from the compressor is separately controlled, later to be mixed with condensed and selectively expanded refrigerant. The saturated refrigerant after mixing is at a pressure which determines its temperature, and its thermal energy is transferred directly with the thermal load which is to be controlled in temperature. Used in this way, the saturated fluid can provide a wide range of temperatures at the thermal load. However this range can be extended, because at one extreme the thermal load can be heated by using the hot gas phase alone, and at the other extreme the load can be chilled using only refrigerant on the condensed phase, after expansion. In this direct transfer system, temperature changes can be rapid and set points can be controlled very precisely. Equipment costs are substantially reduced because the system does not require use of an intermediate thermal transfer fluid, pumps, or a heat exchanger for thermal transfer fluid.
The system and method present unique challenges, as well as possibilities. Processor components in a refrigeration system must operate satisfactorily through all phases in the compression and heat exchange cycle, so that the refrigerant must be at proper temperatures and pressures so that different functions can be performed. For example, the input to a compressor system should be free of liquid, and in a particular pressure range, or efficiency will be lost or the compressor damaged, or both. Maintaining efficiency throughout can present other problems that require solutions consistent with overall system requirements. For example, if the fluid is in a saturated state, the compressed gas component contributes relatively very little to chilling the heat load during thermal transfer. Thus when the load temperature is to be dropped to a minimum, the presence of the gas limits heat exchange efficiency. Another factor affecting efficiency occurs in a different temperature range, resulting from limitations on the energy of compression that can be applied to the refrigerant. When the refrigerant is to be used for heating, the compressor brings the hot gas to a given level, such as 120° C. However, if substantial heating energy is needed at the load, a much higher temperature level must be reached. The return flow, after heat exchange with the load, cannot however be at levels that disrupt the pressure/temperature/enthalpy balance needed with a vaporizable refrigerant. It is highly desirable to eliminate such problems without introducing thermodynamic conditions which affect the integrity of the refrigeration cycle.
The response capabilities of systems in accordance with the invention can be employed to meet the operative requirements of many different temperature control combinations. Where time is of the essence in bringing a thermal load to a target temperature, anticipatory manipulation of the controller can be useful.
In a transfer direct saturated fluid (TDSF) thermal control system, a number of local variations in control loops and components improve efficiency and stability across a range of load temperatures. Cooling efficiency, at very low temperatures, for example, is markedly improved at the load by extracting at least part of the vapor components in the condensed fluid after expansion before mixing with compressed gas. The lowered mass flow through the line then returning from the load to the compressor reduces the pressure drop in said return line. To this end, a vapor separator is disposed in the line transporting liquid/vapor product before the mixing junction, and the extracted vapor is fed back into the refrigerant returning from the load to compressor while a higher proportion of liquid is fed to the load. Thus heat transfer is more efficient without affecting the temperature of the mix.
Other aspects of the invention are concerned with maintenance of efficiency and improvement of temperature limits when using the high temperature capability of the saturated fluid system. A counter-current heat exchanger may be positioned in the flow path to the load to interchange thermal energy between the incoming input, and the out-going refrigerant passing from the load back to the suction input of the compressor. This energy interchange both increases the temperature level of the input to the load and reduces the temperature of the return fluid. The return fluid may thereafter be brought to a level compatible with the demands of compressor operation. For further heating the input to the load can be passed through a heater operated by the controller and included in the input stream to the load to thereby raise the temperature well above the compressor capability if desired.
A further feature of the system is the incorporation of a computer controlled solenoid bypass between the hot gas shunt that leads to the mixing circuit, and the return line from the load to the suction input of the compressor. This bypass is operated to remove some of the flow from the hot gas line when full hot gas flow might tend to make the loop gain of the servo system unstable and/or reduce the amount of cooling available at temperatures within the desired range. The result introduces a time delay in cooling the load to enable closer control of temperature.
Control circuit adaptations may be introduced to realize further benefits from the concept. Where fast reaction to commands requiring fast temperature changes are needed, temporary and short term commands can be utilized to shorten response times. If, for example, the active part of a thermal load comprises the surface of a wafer holding chuck in a semiconductor processing system, and the heat exchange region is physically spaced apart from the upper surface of the chuck, some time may be needed to bring the chuck surface to a specified temperature. By introducing control algorithms which bypass the need for accumulation of tracking data, the wafer can be much more rapidly stabilized at a target temperature, increasing yield rates and lowering costs.
A better understanding of the invention may be had by reference to the following description taken in conjunction with the accompanying drawings, in which:
Referring now specifically to
In
The output flow from the mixing circuit 26 then cools or heats the thermal load 28, such as a semiconductor tool, after which the refrigerant is transferred on a return line 30 back to the suction input to the compressor 10. The return line 30 includes a serial accumulator chamber 32, in which a heater 34 operated by the controller 20 restores the temperature level, as and if necessary.
Operation of the system has, among other things, the advantage of providing a very wide potential temperature control range from hot to cold (e.g. from ±120° C. to −60° C.), extremely fast temperature adjustments, and also high precision (e.g. ±1° C.). In addition, since no intermediate heat transfer system or medium is needed, these unique capabilities can be provided with substantial cost savings.
However, the use of a saturated fluid in different phases (liquid, vapor, and saturated liquid/vapor phase), introduces a number of operative problems or conditions that should be accounted for to realize system potential more fully. In some applications it is desirable to effect rapid changes between operating modes at different temperature levels. For abrupt cessation of flow in the hot gas line 14, a shutoff valve 40 is disposed in series with the proportional valve 22. For virtually immediate or assured full flow of hot gas, the shutoff valve 40 is bypassed by a shunt valve 46 which is in parallel with it. For rapid control of the condensed refrigerant flow, the condensed refrigerant line 16 includes a shutoff valve 42 and a shunt valve 44, which bypasses the TXV 24, all valves being operated by the controller 20. The condenser system includes a condenser heat exchanger 50 which is cooled by water from a conventional source 52, although other cooling fluids may be used. In a configuration known in the prior art, the water flow rate is governed by a flow control system 54, so as to maintain the output pressure from the compressor 10. To facilitate maximum cooling, a bypass valve 56 is disposed in parallel with the coolant flow control.
Expedients are also used to improve system response and reliability in terms of thermodynamic efficiency. A subcooler heat exchanger 60 is disposed in the return line 30 leading to the suction input to the compressor 10. The subcooler heat exchanger 60 operates as a counterflow device, cooling the outgoing flow from the condenser 12 with returning fluid, which in most modes will be expanded and cooled gases, directed back to the compressor 10. In accordance with the W. W. Cowans Pat. No. 6,446,446 referenced in the predecessor parent application, shunt loop 62 about the subcooler heat exchanger 60 includes a desuperheater valve 64 responsive to a temperature sensor 66 at the suction input to the compressor 10. If the input pressure to the compressor 10 falls too low the flow is augmented by opening the desuperheater valve 64. In the shunt loop 62, these flows are derived from a T-junction 68 at the condenser 12 output.
In order to preserve pressure and temperature balance in the closed loop compression/heat exchange system, the return line from the load 28 is passed through an accumulator 37 which includes a heater 34 operated by the controller 20. The system can thus act in response to temperature signals provided from a temperature sensor 78 associated with the load 28 to restore or equalize the temperature of the fluid in the return line. Also, a conduit to the TXV 24 from sensor bulb 74 in communication with the return line 30 is used for external equalization of the TXV 24.
Another feature cooperates with these elements and relationships to overcome different potential problems. If the pressure in the return suction line to the compressor 10 becomes too high, it is automatically lowered by an included crankcase pressure regulator valve, also known as a “close on rise” (COR) valve 76.
Flows at different points in the circulating loop must often be brought into predetermined pressure and temperature ranges for components to work properly. For example, the compressor 10 input must be maintained above a selected pressure range. This is accomplished by a hot gas bypass valve 82 responsive to a pressure sensor 80 at the input to the compressor 10. The hot gas bypass valve 82 feeds back a portion of the compressor 10 output flow to the suction input in the event the input pressure is too low.
The system as thus far described operates as described and in practice validates the concept and its advantages, but it also possesses certain advantages and potentials not immediately evident. For example, in the high temperature mode, the system can be operated with the proportional valve 22 alone providing temperature modulation, and with the refrigeration line 16 being shut off by the valve 42. The input to the load 12 is then solely the high temperature gaseous flow, but the temperature of the input to the load 28 can be further raised to an even higher level, suitably compensating for anticipated major heat losses at the load 28 at these temperatures. For this purpose, a counterflow heat exchanger 86 and a serially coupled electrical heater 88 are disposed between the mixing circuit 26 and the load 28. The input temperature to the load 28 is detected by a sensor 90, so that actuating signals can be applied from the controller 20 to the heater 88 subsequent to the mixing circuit 26. Separately, a heater 92 is provided in the hot gas line 14 prior to the mixing circuit 26, to be energized by the controller 20 to provide further heating. Reverse flow back toward the control valves is blocked by a suitably placed check valve 94. The counterflow heat exchanger 86 keeps the ? temperature level down to a predetermined range in the suction line to the compressor 10. The sequence of temperature changes in this mode is shown graphically in
At the opposite (cold) end of the operable temperature range, there are limitations on the low range of temperature possible, depending on the proportion of liquid in the refrigerant mix that is fed to the load. The presence of gas in the saturated mix employed on cooling adversely affects performance by increasing the pressure drop between load 28 and input to compressor 10. The temperature of a mix of liquid and vapor at any point is equal to the saturation temperature of the liquid at the pressure experienced by the mix at that particular point. In these systems, with respect to flow in the return line from the load 28 to the compressor 10 input, the pressure drop is proportional to the square of the mass flow of the refrigerant. Since the cooling output power of a vapor cycle system is proportional to the compressor input pressure, it is advantageous to reduce the mass flow return to the compressor. Specifically, cutting the mass flow in half reduces the pressure drop four-fold, since pressure drop in a flowing gas is about proportional to the square of the mass of the gas flow.
With these factors in mind, the condensed refrigerant line 16 includes, subsequent to the TXV 24, a check valve 98 and a vapor separator 100, an example of which is seen in more detail in
When liquid only is fed to the mixing tee 22 to combine with hot gas regulated in flow by proportional valve 22 the combined mixture flowing from mixing tee 26 will simply have less gas than if the separator 100 were not present. When the maximum amount of cooling is demanded at the lowest possible load temperature a condition is encountered that should be noted. Proportional valve 22 would be shut in this mode and the flow through the system shown in
The basic TDSF system enables providing useful heat to maintain the load in the range of 90° C. to 120° C. by delivering high pressure gas to the load at temperatures that are sometimes well in excess of the required load temperature level. Thus, for example, to provide 5 KW of heat to a load which is to be heated to 120° C. with a flow of 200 grams/second of R507 gas requires that the gas be heated to about 28.5° C. or more above 120° C. In giving up heat to the load by cooling 28.5° C. this gas flow will bring the load to the target temperature. Somewhat more than this amount is needed to provide drive for the needed transfer of heat across whatever heat exchanger is used. A temperature of 120° C. is as high as a typical commercial compressor readily withstands, whereas the improvement of
Basically, this is achieved by using the counter-current HEX 86 together with the extra electrical heater 88 in the input path to the load 28, after the mixer 26. During operation, when the system is supplying temperatures less than about 60° C. the system functions substantially the same as does the prior system. When temperatures above this level are required the hot gas from the compressor 10 first provides its maximum level [(A) in
The system includes a further improvement providing adequate control during times when the TDSF system is closely controlling the temperature of an object that is being temperature controlled by the TDSF. A full flow of gas from proportional valve 22 overwhelms the controller function if the entire flow is mixed with the flow from TXV 24. This condition is illustrated by the graph of
The solution used is to employ a bypass line 103 including a hot gas bypass (solenoid) valve 104 as shown in
These expedients all contribute in a highly integrated fashion to assuring greater reliability and extended range for TDSF systems. Practical applications of this concept can use the potential for fast response and precise control afforded by the system to achieve superior results for particular situations. Some testing and instrumentation systems, for example, test a multiplicity of parts or products sequentially at a series of different temperatures, which may vary widely. The capability of a TDSF system for changing rapidly between temperature levels can save much time and money and increase throughout in these inspection applications.
It has been found that TDSF systems can respond to needed temperature changes even faster than the electronic controllers, when the controllers have to store a series of readings before establishing reaching a steady state condition. In a typical controller using proportional and derivative functions, for example, the entry of a new set point can initiate a time consuming sequence in which, while transitioning to a new target value, a succession of readings are required. Where a TDSF system has a faster response it has been found useful to enter an artificial and temporary temperature reading into the controller. A new sequence of readings is not needed because previously taken temperature measurements are retained and the controller operates without interrupting the prior sequence. This enables final temperature adjustment of the saturated fluid much more rapidly. In a specific example, the artificial temperature input is used to compensate for thermal delays that are inherent in the design of a tool. For the semiconductor application, there is a physical distance between the top of a chuck, on which the semiconductor wafer rests, and base region where thermal transfer with the refrigerant takes place. By altering the input temperature artificially in step-wise fashion before starting application of power, control of the chuck temperature is both more rapid and precise. Other empirically derived artificial inputs may be used in other situations, for start-up or shut-down sequences.
While a number of forms and alternatives have been described above, it will be appreciated that the invention is not limited thereto but includes all variants and alternatives within the scope of the appended claims.
This invention relies for priority on previously filed application Ser. No. 11/057,383 of Kenneth W. Cowans et al, filed Feb. 15, 2005 and entitled “Thermal Control System and Method”, and on provisional application 60/733,078 filed Nov. 4, 2005 by Kenneth W. Cowans et al and entitled “Thermal Control System and Method”.
Number | Date | Country | |
---|---|---|---|
60733078 | Nov 2005 | US |