The present invention relates to improvements in Ground Fault Circuit Interrupters (GFCIs), and more particularly to interrupters which are capable of providing a combination of surge and heat protection to receptacles.
The use of electrical power, through wiring and related components, had originally been in accordance with many conflicting standards, but New York, around 1881, established electrical codes to regulate installations of lighting. Since 1897, a private, non-profit organization formed by insurance companies—the National Fire Protection Association (NFPA)—began publishing the National Electric Code (NEC). The NEC comprises a consensus of opinions on electrical safety codes, and proposals for changes to be made thereto are considered by code-making panels and in committees consisting of engineers, tradesmen, manufacturer representatives, firefighters, and others. The NEC is updated every three years, with the 2008 version being the latest. The NEC is approved as an American standard by the American National Standards Institute (ANSI), and is formally identified as ANSI/NFPA 70. Although the NEC is not by itself U.S. law, regulations enacted by cities, counties, and states regarding building codes are often taken verbatim from the NEC, or are only slightly modified therefrom.
Article 210.8 of the NEC addresses the use, in branch circuits, of a Ground Fault Circuit Interrupter (GFCI) for the protection of personnel. The article cites nine locations (210.9(A)(1)-(9)) within an occupancy where GFCIs are required for electrical sockets, and generally includes wet areas within bathroom and kitchen areas, as well as certain crawl-space locations, garages, boathouses, and unfinished basements. A GFCI serves to prevent electrical damage to equipment, and severe or fatal electric shocks to persons. Proper deployment of GFCIs within dwellings and commercial buildings would prevent about two-thirds of the roughly 300 accidental electrocutions that occur annually in the United States.
The forerunner of today's GFCI was disclosed by U.S. Pat. No. 3,213,321 to Dalziel for “Miniature Differential Circuit Breaker,” with improvements made thereafter, including U.S. Pat. No. 3,852,642 to Engel for “Sensing Amplifier and Trip Circuit Particularly for Ground Fault Circuit Interrupter,” and U.S. Pat. No. 4,345,289 to Howell for “Ground Fault Circuit Interrupting Device With Improved Thyristor Triggering.”
A GFCI is similar in function to that of circuit breakers and fuses, but whereas a circuit breaker detects a fault condition when the “hot” current exceeds a fixed value for a fixed time, after which it breaks the circuit's continuity, a GFCI will interrupt the current when it detects current “leaking” to ground, either directly or through the resistance of a person. The GFCI senses any loss of current by recognizing an imbalance between the current in the “hot” side, and the current in the “neutral” side, and monitors the balance using a differential current transformer. GFCIs are designed to interrupt current flow within 25-40 milliseconds, which would limit the shock accidentally received to be less than the duration that may normally be needed to drive the victim's heart into ventricular fibrillation, the common cause of death where electric shock has occurred. The NEC requires circuit interruption where the current leakage exceeds a range of 4-6 milliamperes (normally a 5 mA trip setting is used) when protecting people, and it may be as high as 30 mA when protecting equipment.
However, as electrical energy is transported through a circuit—circuitry comprising electrically insulated wires and components—the movement of electrons therein produces a temperature rise in both the conductor and any insulation utilized. While wiring materials typically dictated by NEC to be copper—tend to have very high melting temperatures, being around 1,980 degrees Fahrenheit, the insulation utilized typically melts around 300 degrees Fahrenheit. This phenomenon is exacerbated by voltage surges, against which protection is generally provided by a thermal magnetic circuit breaker, which uses a bimetallic strip responding to less extreme but longer-term over-current conditions. The bimetallic strip utilized is called a varistor. A varistor is specially constructed to exhibit a significant nonlinear current-voltage characteristic, having a high resistance at low voltages and a low resistance at high voltages, with the most common varistor being a metal oxide varistor (MOV). Improvements to the use of a MOV in a GFCI circuit was shown by U.S. Pat. No. 4,345,289 to Howell,
There are some prior art GFCI designs addressing the problem of fires that were believed to be caused by overloaded electrical outlets, overloads that may be caused by a loose connection, a glowing connection and/or a high resistance path. A glowing connection may occur when copper oxide is formed between a copper wire and a steel screw in a small air gap creating carbon which glows. One such invention is shown by U.S. Pat. No. 4,951,025 to Finnegan for “Thermally Monitored Electrical Outlet Receptacle Apparatus.” However, the invention disclosed herein provides a means of thermal protection and current interruption by using sensors to trip the GFCI solenoid, as hereinafter described.
It is an object of the invention to provide a switch feature across a control SCR, which may cause a GFCI solenoid to trip when abnormal temperatures are detected.
It is also an object of the invention to provide a temperature sensing means of GFCI activation for either a plug-in adaptor or a receptacle.
The device comprises of a GFCI receptacle with a thermal cutoff feature. When there is an imbalance in the current sensing transformers, the controller/comparator senses the imbalance, turning on the SCR, which drives the solenoid. By simply switching across the SCR, either by a mechanical thermal switch or an electronic switch, one can turn on the solenoid at a preset temperature. This will disconnect the load from the face as well as downstream, eliminating any possible current draw, and eliminating any possible heating that may have resulted. The device can be made, so that when the temperature falls back below the threshold, the switch will turn back off and the device could operate as normal. It can also be set so that the GFCI is a one shot, in which the thermal sensor does not go back to its original position.
A ground fault circuit interrupter (GFCI) is an electrical device that works to de-energize a circuit upon detection of abnormal current flow, such as current “leaking” to ground—through a direct “ground fault,” or through the resistance of a person. A ground fault condition may exist when there is a current imbalance between the current-carrying phase and neutral, where the imbalance is above a designated threshold specified in the particular electrical code.
A typical GFCI 10 may comprise a housing 15 that provides support for the requisite circuitry, and an installation means for installation of the GFCI within an electrical outlet box. The installation means may comprise flanges 16 protruding out from the housing 15, with a screw being retained in an orifice 17 in each flange 16, thereby making the flanges 16 of GFCI 10 securable to the electrical outlet box (not shown) in the wall of a dwelling or commercial building. The housing 15 of the GFCI 10 may comprise one or more neutral terminals (23, 24), a load terminal 22, and a hot terminal 21, each of which may be in the form of a screw, and have electrical connections according to the schematic circuit diagram of
Many fires are believed to be caused by overloaded electrical outlets, that is, outlets operated with more power transfer than the outlet was designed for. Fires are sometimes caused by a loose connection, a glowing connection, and/or a high resistance path. A glowing connection may occur when copper oxide is formed in a small air gap between a copper wire and a screw creating carbon which may glow. The condition of too much power usage is always accompanied by increased temperature in at least one of the following: the ambient temperature, the receptacle temperature, and the temperature of a prong of an electrical plug inserted into the receptacle. It is also possible that voltage surges may occur regularly, but are of insufficient amplitude to cause a trip, but serve to increase temperatures, which may cause fires. To avoid hazardous condition capable of leading to fires, it is desirable for the GFCI to sense when operating temperatures are excessive, and to cease operation by de-energizing the circuit. Electrical codes also usually mandate a maximum amount of time after which the unit must trip in response to a ground fault.
As seen in
As seen in the circuit schematic of
The circuit of
The interrupter is actuated when the differential transformer or G/N Transformer senses that more current is flowing into the load from the source through the hot conductor than is flowing back to the source through the neutral conductor.
Interruption of circuit continuity may be by a disconnect solenoid coil 60. The hot line (Phase) of the input side (through primary conductor 31), the solenoid coil 60, and a diode bridge rectifier (D2-D5) circuit 70 are connected in series to form the power supply circuit that supplies power to the GFCI control circuit. The GFCI device may be used in a single phase circuit, such as a single phase 120V AC circuit, or in a polyphase circuit, such as 120/240V AC circuit. A comparator may be used to sense current differential in each of the transformers, and where there is a differential, the comparator may trigger the solenoid.
The circuit may further comprise, as seen in
The examples and descriptions provided merely illustrate a preferred embodiment of the present invention. Those skilled in the art and having the benefit of the present disclosure will appreciate that further embodiments may be implemented with various changes within the scope of the present invention. Other modifications, substitutions, omissions and changes may be made in the design, size, materials used or proportions, operating conditions, assembly sequence, or arrangement or positioning of elements and members of the preferred embodiment without departing from the spirit of this invention.
This application claims priority on U.S. Provisional Application Ser. No. 61/401,277 filed on Aug. 10, 2011, the disclosures of which are incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
61401277 | Aug 2010 | US |