1. Field of the Invention
The invention relates in general to methods of performing thermodynamic cycles for generating mechanical and electrical power, and for heating, or cooling.
2. Description of the Related Art
The prior art includes combustors and combustion systems that use diluents to cool combustion, but which provide with relatively poor control over the peak fluid temperature and little spatial control over the transverse fluid temperature profile (or distribution). Cooling of the combustion products has commonly been done with excess air. Pressurizing or compressing this excess air commonly consumes 40% to 85% (from large turbines to microturbines) of the gross turbine power recovered resulting in low net specific power. I.e., the gross power less compressor and pump power produced per mass flow through the compressor(s) or turbine(s).
Conventional applications of diluent have particularly focused on controlling emissions, flame stability and flame quenching, especially when using ultra-lean mixtures and operating near a combustion limit. (E.g., see Lefebvre, A., “Gas Turbine Combustion”, Hemisphere Publishing, 2nd ed. (1998) ISBN 0-89116896-6, section 5-7-3; Bathie, William W., “Section 5.8 Evaporative—Regenerative Gas Turbine Cycles”, 2nd ed., ISBN 0-471-31122-7 (1996), John Wiley & Sons, p 139; Boyce, Meherwan P., “Gas Turbine Engineering Handbook”, 2nd ed., ISBN 0-88415-732-6 (2002), Gulf Publishing Company, p 62; Lindquist, Torbjorn, “Evaluation Experience and Potential of Gas Turbine Based Cycles With Humidification”, Doctoral Thesis, Division: Thermal Power Engineering, Department: Heat and Power Engineering, Lund University, Sweden (2002), p 85). Other efforts to reduce the use of excess air as diluent have employed forms of thermal diluent with higher heat capacity than air, such as steam and CO2, that can remove more heat with less compression work (e.g., Ginter, U.S. Pat. Nos. 3,651,641, 5,627,719, 5,743,080, and 6,289,666 mentioned above, Ginter U.S. Pat. No. 5,271,215, and Cheng U.S. Pat. No. 6,370,862).
Temperature control in multiple locations in the thermodynamic cycle is important for efficient operation. Controlling the peak temperature and profile of the energetic fluid delivered to an expander results in better efficiencies of the cycle (Gravonvski, A. V., et al., “Simulation of Temperature Field Redistribution Through Multi-Stage Cooled Turbines”, 2001-GT-0576, ASME Turbo Expo, 2001, New Orleans). It is difficult, however, to control the temperature profile using excess air or steam as customarily employed to cool cycle components and special mixing devices. The irregularities in the spatial and temporal temperature distribution of flows require greater design margins than preferred to compensate for the large uncertainties in the temperature profiles. (E.g., Malecki, Robert E., et al, “Application of and Advanced CFD-Based Analysis System to the PW600 Combustor to Optimize Exit Temperature Distribution—Part 1”, Proc., ASME, Turbo Expo, 2001). The problem of temperature irregularities is heightened by changes in work load or variations in ambient conditions.
Various thermodynamic cycles have been proposed to improve heat recovery and system efficiency. The conventional Combined Cycle (CC) utilizes a Heat Recovery Steam Generator (HRSG) to generate steam by heat exchange with expanded fluid formed by expanding energetic fluid through a first turbine. The generated steam is expanded through a second (steam) turbine. This results in high capital costs from two turbines. Consequently combined cycles are designed to mostly be used in base load applications. However, deregulation is requiring increasing cyclic power generation. In the Steam Injected Gas Turbine (STIG) cycle, steam is generated in a similar HRSG and is injected upstream of the expander. This uses the same gas turbine with a higher energy per unit mass flow. By only delivering steam, the STIG cycle is limited in its ability to recover lower temperature heat. High water treatment costs and water availability are often stated as a major objections to more widespread use of the STIG. The CHENG cycle is similar to the STIG cycle and with similar objections.
The Recuperated Water Injection (RWI) cycle utilizes a recuperator to recover heat from expanded fluid into incoming compressed air. It may water injection on the intake of the recuperator to improve heat recovery. This is typically limited by an air saturation limit. The Humidified Air Turbine (HAT) cycle humidified intake air through a saturator. The Evaporated Gas Turbine (EvGT) is a similar cycle. While utilizing lower quality water, the HAT and EvGT cycles are limited in the amount of deliverable diluent by one or more air saturation limits. An EvGT cycle has been demonstrated at LUND University in Sweden. Otherwise these RWI, HAT, and EvGT cycles have been little used, possibly because of relatively high capital costs. The HAWIT cycle has been proposed to reduce capital costs. It utilizes direct contact heat exchangers to reduce the cost of surface heat exchangers used in the HAT cycle. It has lower costs but lower efficiency than the HAT cycle. The relative efficiency and internal rate of return for these cycles were compared by Traverso, Alberto, “Thermoeconomic Analysis of STIG RWI and HAT Cycles With Carbon Dioxide (CO2) Emissions Penalty”, Tesi di Laurea, Università di Genova (DIMSET), 2000.
Conventional heat recovery methods have particular difficulty in recovering useful heat below the temperature of steam recovered by heat exchange with the expanded fluid with sufficient pressure to reinject upstream of an expander, or within a steam expander. Much heat energy continues to be lost as the expanded fluid is exhausted. Conventional methods of recovering heat from the expanded fluid (after the hot energetic fluid has been expanded to extract mechanical energy) often seek to use high temperature recuperators to heat the large volume of excess cooling air. E.g., air to air recuperators approaching 700° C. These result in high cost and expensive maintenance, where the recuperator alone may exceed 30% of system costs and 80% of the maintenance in micro-turbines.
Using diluents other than air have resulted in further expenses in diluent supply and recovery in relevant cycles for power generation such as “wet” or humid cycles like STIG and HAT. Conventional cycles with typical heat and/or diluent recovery systems need to add “make-up” diluent to compensate for inefficiencies of the system and to reduce operation costs.
Thermodynamic cycles that use a diluent beyond the oxidant containing fluid often need to recover that thermal diluent for pollution and/or economic reasons, as for example, in Italian Patent TO92A000603 to Poggio and Ågren, N., “Advanced Gas Turbine Cycles with Water-Air Mixtures as Working Fluid”, Doctoral Thesis, KTH, Stockholm, Sweden, 2000). Such processes have been expensive. Make-up diluent is commonly needed because of inefficiencies in the recovery process (Blanco, G. and Ambs, L., “Water Recovery Systems for Steam Injected Gas Turbines: an Economic Analysis”, Proc. 15, Int'l. Conference on Efficiency, Costs, Optimization, Simulation and Environmental Impact of Energy Systems, Berlin, 2002).
In the addition of a thermal diluent, fluid filtering and cleanup has been required to prepare the diluent to be delivered to the thermodynamic cycle system (Ågren, N., op. Cit. (2000); SPE Mashproekt, “Aquarius Cycle”, Nikolaev, Ukraine (http://www.mashproekt.nikolaev.ua). Such conventional methods add substantial expenses.
Pollutants are becoming a common concern throughout the world and their control is becoming more important. Relevant art methods of adding water often exacerbate formation of some pollutants, such as CO, while decreasing others, such as NOx. (E.g., See Lefebvre, 1998, p 337 on CO vs NOx). Control of pollutants to stringent legislated methods has often required additional components at substantial further capital and maintenance costs. Many of these pollutant control devices have short lives compared to the overall plant life resulting in further maintenance expenses. Major firms appear to have made a concerted effort to shift to dry excess air to achieve low NOx emissions and to avoid the use of steam as diluent.
Conventional wisdom discourages water injection into turbine power systems (e.g., Lefebvre op. Cit. 1998, p 337). The cost of providing and treating water is frequently claimed to be a substantial hindrance. Commentators expect efficiencies to drop as more water or steam is added to the cycle (e.g., Pavri, Roointon and Moore, Gerald, “Gas Turbine Emissions and Control,” GE Technical Document No. GER4211, 2001, p 18, www.gepower.com).
Thermodynamic cycles are sometimes used for both mechanical power and heating. The heat produced by the combustion process may be used for heat in assorted applications from steam production to district heating. These “combined heat and power” (CHP) applications have been limited by the design of the CHP device. If the demand for heat or power deviates from the design of the CHP system, the efficiencies may be greatly reduced, especially when providing hot water.
Thus, a need clearly exists for improved energy conversion systems and thermodynamic cycles, which provided reduced system life cycle costs and emissions and improved performance and reliability. There is similar need for improving the thermodynamic efficiency and reducing expenses while maintaining or improving limitations imposed by equipment, environment, including turbine blade life, and pollutant emissions. The present invention seeks to meet these needs.
According to one aspect of this invention, a new thermodynamic power cycle with a heat and mass transfer system is provided that more effectively recovers heat from expanded energetic fluid. In such an embodiment, users preferably configure an energy conversion system to operate on an enhanced VAST Cycle to utilize a diluent comprising a vaporizable component (e.g., water) to provide effective heat recovery from an expanded energetic fluid downstream of an expander. In one embodiment, a VAST water cycle (VAST-W) recovers heat from the expanded fluid by heating liquid diluent, e.g. water. In another embodiment, a VAST Steam Cycle (VAST-WS) recovers that heat by heating, evaporating, and preferably superheating liquid diluent, e.g. with water and steam.
In other embodiments, a VAST Recuperated Water-Steam Cycle (VAST-WSR) cycle is configured to recover heat from a portion of the expanded fluid to incoming oxidant containing fluid using a recuperator, together with the respective VAST-W and VAST-WS components. Each cycle includes a combustor preferably operable to deliver, mix, and combust oxidant containing fluid, fuel containing fluid, liquid and/or vaporized diluent.
According to another aspect of the invention, heat is recovered from heat generating components and from cooling heated components. In one such embodiment, users preferably distribute diluent to recover heat from one or more of heated components and heat generating components such as one or more turbines, combustors, generators, drives and motors. They preferably configure a controller operable to manage the diluent distribution to cool multiple fluids and components and to deliver heated diluent to a combustor.
According to another aspect of the invention, VAST combustors are preferably provided and configured operable to control VAST Cycles under near stoichiometric conditions while keeping pollutants low, such as described in the above-mentioned Ginter, patents, and Hagen et al., patent applications. They are preferably configured to accommodate all the liquid and/or vapor diluent desired upstream of the expander by replacing at least some excess diluent air. More preferably, the diluent delivery is operable to displace some to all excess air from the Brayton cycle to near stoichiometric conditions, e.g., by adding diluent (e.g., water and/or steam) sufficient to exceed one or more of the air saturation limit, a steam generation limit, a premixed combustibility and/or flame stability limit, and a small droplet combustion quench limit. Compressors are preferably resized relative to turbines to accommodate the lower oxidant containing fluid flows, providing major cost savings.
In another aspect of the invention, the cost of providing and treating diluent within the cycle is reduced. Here, the expanded fluid is preferably cooled with a condenser, and diluent condensed and recovered. A direct contact condenser using cooled diluent (e.g., water) is preferred to improve recovery efficiency and reduce pollutants exhausted. Water is preferably recovered at a rate greater than the rate of water formed in combustion and/or the water delivered as moisture (humidity) in the intake air. More preferably, water is recovered at more than the rate of diluent being delivered upstream of the expander outlet, thus making the thermodynamic energy conversion cycle self sufficient in water. Recovering excess diluent assists in removing fluid contaminants by removing or discharging recovered diluent in excess of the amount delivered upstream of the expander outlet. Excess intake oxidant containing fluid flow is preferably reduced and its diluent effect replaced with diluent, resulting in corresponding reductions in intake contaminants entrained into the system. With cleaning fuel or by using clean fuel, and/or with intake spray cleaning, contaminant levels may be controlled by diluent discharge. The cycles preferably treat and recycle diluent, reducing treatment costs.
In another aspect of the invention, heat conversion to mechanical power can be increased. Here, the pressure ratio of the compressors is increased, particularly with liquid diluent delivery. Users preferably configure a recompressor downstream of the expander and condenser. The combustor may be configured for lower pressure drop. A direct contact condenser may be used to reduce the pressure loss in the condenser. The pressure ratio of the intake compressors, the recompressor, the combustor pressure loss, and the direct contact pressure loss are configured to achieve desired net expansion ratio across the turbine. With increased expansion, the heat recovery system is preferably configured for a lower exhaust temperature.
In another aspect of the invention, an object is to increase the hot energetic (“working”) mean fluid temperature, (e.g., Turbine Inlet Temperature—TIT) and system efficiency are increased. Here, a Trifluid VAST combustor preferably operable to control the transverse temperature distribution entering the expander and precisely controlling fluid flows is preferably used. This is preferably operable to provide higher mean fluid temperatures with the same fluid peak temperature and/or maximum control temperature at a control location, preferably while controlling pollutant levels. Diluent (e.g., water, steam, and/or CO2) is preferably used (instead of air cooling) to cool combustor and/or expander hot sections. The heated diluent is preferably recycled upstream into the combustor, thus avoiding diluent cooling of the energetic (working) fluid and further reducing compressor size and cost.
According to another aspect of the invention, the cost and energy to treat the intake oxidant containing fluid is reduced. Here, direct contactors are preferably used to spray filter the intake oxidant fluid using excess liquid diluent. Intake diffusers, and filters are preferably resized for the lower oxidant flows. Cold diluent may be used to increase intake oxidant fluid density.
According to a further aspect of the invention, the power and equipment traditionally required in ultra-lean combustion to compress gaseous oxidant containing fluid relative to the power generated are reduced, thereby increasing the net specific power of compressors and turbines as well as reduced system costs, (i.e., the gross turbine power less pumping power, divided by the respective mass flow.) Here, at least some vaporizable diluent is preferably used to reduce the excess gaseous oxidant containing fluid commonly used as diluent, and to displace gas pumping with liquid pumping work. Vaporizable diluent is preferably used to provide more heat per unit mass flow, (and usually more enthalpy per volume of energetic fluid) flowing through the expander than in a Brayton cycle. E.g., using a diluent/fuel mass ratio omega about more than 1 and an relative oxidant/fuel ratio Lambda greater than 1.
In still a further aspect of the invention, the cycles preferably configure the compressors to cool the oxidant containing fluid while using diluent to recover that heat of compression. The cycles preferably use direct fluid contactors, such as taught in the Hagen et al., '191 patent application mentioned above, to improve spatial distribution of diluent delivery in compressor precoolers, inter-coolers, and/or intra-coolers. Surface heat exchangers using cool diluent may be used with the resultant heated diluent being recycled into heat exchange system or into the combustor.
In still another aspect of the invention, an object is to control major pollutant levels below desired limits while operating with less excess oxidant than a Brayton cycle, preferably near stoichiometric conditions. VAST combustors capable of controlling transverse distribution of fluid delivery are preferably utilized, being operable to provide transverse distributions of lower relative oxidant (or relative air) than Brayton cycles, preferably near stoichiometric conditions and at a prescribed fluid temperature, while achieving low pollutant emissions. (The relative oxidant/fuel ratio is the actual oxidant/fuel ratio divided by the stoichiometric oxidant/fuel ratio.) In such an embodiment, by using a combustor operable to constrain peak combustion temperatures while using low excess oxidant, the emissions of a combustion byproduct (such as oxides of nitrogen NOx) are preferably reduced and more preferably controlled below an upper NOx concentration limit. More preferably the rate of byproduct emissions is maintained below a prescribed emissions rate (mass per time, or mass per energy kg/MWh). By using a combustor operable to control transverse temperature distributions and fluid composition distributions, good fuel oxidation may be readily achieved sufficient to maintain a concentration of partially oxidized fuel component less than a prescribed concentration of partially oxidized fuel. More preferably, emission rate of one of carbon monoxide, and/or a partially oxidized or residual fuel component below a prescribed emissions rate (mass per time or mass per energy kg/MWh)
In still a further aspect of the invention, an object is to configure a VAST cycle operable to provide one or more of shaft power and/or hot water, saturated steam, and superheated steam, in a Combined Heat and Power (CHP) system as desired for particular applications. Here, such an embodiment, the heat and mass transfer system is preferably configured with one or more locations from which to extract such heated fluids together with mechanical (or electrical) power. Diluent delivery, heat recovery, and the combustor are preferably configured and controllable to provide flexible control over the delivery of heated diluent, vaporized diluent, and/or superheated diluent, total heat Q, and mechanical and/or electrical power. (e.g., rates of delivering water, steam, and/or superheated steam, shaft power and/or electricity.)
It should be noted that several aspects of the invention have been described above along with the advantages achieved over the prior art. Of course, it is to be understood that not necessarily all such objects or advantages may be achieved in accordance with any particular embodiment of the invention. Thus, for example, those skilled in the art will recognize that the invention may be embodied or carried out in a manner that achieves or increases one advantage or group of advantages as taught herein without necessarily achieving other objects or advantages as may be taught or suggested herein.
Having thus summarized the general nature of the invention and some of its features and advantages, certain preferred embodiments and modifications thereof will become apparent to those skilled in the art from the detailed description herein having reference to the figures that follow, each having features and advantages in accordance with one embodiment of the invention, of which:
Ginter VAST Cycle
U.S. Pat. Nos. 3,651,641, 5,617,719, 5,743,080 and 6,289,666 to Ginter teach VAST thermodynamic power cycles that primarily pump liquid thermal diluent (such as water) into a thermodynamic cycle to cool the combustion, reducing the use of excess dilution air. This VAST (“Value Added Steam Technology”) cycle is a hybrid between the Brayton and Rankine cycles. It preferably uses fluid water as diluent. It preferably uses an energetic fluid formed in a VAST direct contact fluid combustor, containing both hot products of combustion and superheated steam. This hot energetic fluid is preferably expanded through an expander to generate shaft and/or electrical power. E.g., via a turbine or reciprocating engine. It may also provide Combined Heat and Power (CHP).
With reference to
A Heat and Mass Transfer System 6000 is used to distribute diluent about the system. It preferably recovers heat from one or more hot fluids, thereby forming cooled fluids. E.g., cooling expanded fluid, thereby forming a cooled expanded fluid. It preferably cools components heated by products of combustion, energetic fluid and/or expanded fluid, such as the combustion system and expansion system. It preferably cools self heated components, such as motors, pumps, bearings, electromagnetic converters (such as power converters, transformers, and capacitors), and electromagnetic controllers. (I.e., heat generating components other than the combustor.) It receives Work Input, such as for motors, pumps, and bearings. It preferably delivers diluent to one or more hot systems or components to exchange heat with and cool those components. e.g., one or more components of the combustion system, expansion system, fuel delivery system, and/or oxidant delivery system. The Heat and Mass Transfer system preferably recovers heat using diluent containing fluid, oxidant containing fluid, fuel containing fluid, and/or a coolant fluid, thereby forming a respective heated fluid. It may exhaust expanded cooled fluid. It may provide hot or cold fluid for heating, and/or refrigeration.
The Heat and Mass Transfer System 6000 preferably delivers to a outlet port connectable to a utilization device one or more of diluent, water and/or carbon dioxide formed by combustion in some configurations. In some configurations, heated fluid is preferably delivered to a thermal utilization device comprising a thermal device selected to provide a thermal use. E.g., and/or a heat using heated fluid such as heated diluent, heated oxidant, fluid comprising products of combustion delivered to a heat exchanger for district heating, steam heating for chemical or refinery applications, or an absorptive cooler for absorptive cooling. A mechanical utilization device may be selected for this utilization device. E.g., a gas turbine, a steam turbine, an hydraulic piston, or a pneumatic piston. In some embodiments, the utilization device more preferably comprises both thermal and mechanical utilization devices. E.g., combined heat and power (CHP) applications. Some utilization devices may provide control over the distribution of heated fluid between thermal and mechanical applications. With reference to
A Fuel Delivery System 3000 is provided to receive fuel-containing fluid and preferably deliver it through the Heat and Mass transfer System 6000 to the Combustion System 4000. It may also delivery fuel directly to the Heat and Mass Transfer System 6000. It requires Work Input for pumps and fluid treatment. The Fuel Delivery System 3000 may heat and/or treat the fuel-containing fluid in the Heat and Mass Transfer System 6000. An Oxidant Delivery System 1000 delivers an oxidant-containing fluid (termed “oxidant”) to one or more of the Combustion System 4000, the Heat and Mass Transfer System 6000, and the Expansion System 5000. It requires Work Input for the compressing or pressurizing device (e.g., a pump or compressor,) for fluid compression and/or pumping to pressurize gaseous and/or liquid oxidant containing fluid to form a compressed or pressurized oxidant. The oxidant containing fluid may require fluid treatment. E.g., filtering air upstream of a compressor. A Diluent Delivery System 2000 preferably receives recovered diluent and delivers diluent to the Heat and Mass Transfer System 6000. The Diluent Delivery System 2000 may treat diluent before delivery. It preferably pressurizes diluent to be delivered through the Heat and Mass Transfer system 6000 to one or more of the Fuel Delivery System 3000, the Oxidant Delivery System 1000, the Combustion System 4000, and/or the Expansion System 5000. It may deliver diluent directly to one or more of those systems. It requires Work Input for pumps and energy for fluid treatment.
The VAST cycle preferably pumps liquid water in to form steam by direct contact of water delivered upstream of the expander 5100, particularly in contact with the combusting fluids or energetic fluid in the combustor between the compressor and the expander. This preferably forms steam at the highest possible temperatures useable in turbines 5100 with cooled blades, (or for uncooled blades). The VAST system preferably uses an insulted pressure vessel that is kept relatively cool, enabling use of inexpensive pressure vessel materials and construction. This approach avoids conventional metallurgical limits where the combustion heat must be transferred through a surface heat exchanger. Thus it avoids the primary constraints on the temperature of conventional steam power systems and the corresponding limits on the working fluid temperature and system efficiency.
By Carnot's law, thermodynamic efficiency increases as the difference between high temperature of the energetic (working fluid) at the inlet to the expander and the low temperature at the outlet of the expander divided by the high absolute temperature. Gas turbines utilizing a VAST cycle can operate with mean Turbine Inlet Temperatures (TIT) of about 1773 K (1500° C.) compared to high temperature metallurgical limits of about 1373K (1100° C.) with current materials. VAST cycles will operate at higher temperatures as such materials are developed. E.g., to 1973 K (1700° C.) or higher. The VAST cycle preferably uses an embodiment of the Trifluid combustor taught in the related Trifluid patent application incorporated herein by reference. The Trifluid combustor enables operators to very precisely and accurately control or limit the temperature of the energetic fluid F405 exiting the combustor at one or more locations to a desired design or allowable peak operating temperatures given the tolerable material temperature and stress of the turbine blades, with the associated blade cooling provided. It preferably enables control of a plurality of temperatures transverse to the flow, across multiple fluid streamlines. It more preferably enables controlling the spatial temperature distribution of the energetic fluid F405 exiting the combustor into the expander.
With such precise peak temperature control, users preferably increase the mean temperature in the energetic fluid F405 by adjusting the spatial fluid temperature control to about match the turbine blade temperature to near the desired temperature profile for the turbine blades, given the available blade cooling. Using thermal diluent to cool a combustor liner (or combustion chamber wall) reduces or replaces the gaseous thermal diluent (e.g., air) conventionally used to cool the liner. The heated diluent is then delivered into the fluid flow upstream of the expander outlet. E.g., into the combustor or compressor or hot section of the expander. This recycles the heat transfer through the liner back into a combustion chamber 4100 within the combustion system 4000, avoiding most of the related heat loss and reduction in temperature in the energetic fluid F405 in the relevant art.
Embodiments preferably using one or more of these methods to increase the useable mean (high) temperature of the energetic fluid F405 (the Turbine Inlet Temperature TIT) and correspondingly increase the Carnot thermal efficiency relative to conventional technologies while controlling to not exceed the peak component temperatures in the downstream expander 5100. By preferably reducing or displacing the commonly used excess oxidant cooling flows through the liner, users improve the spatial control and preferably uniformity of the static pressure distribution and the velocity distribution of the energetic fluid F405 across the combustor exit. Improving these parameter distributions in the energetic fluid F405 substantially improves the flow patterns within the turbine 5100, closer to limiting flows, and increases the turbine efficiency.
The VAST cycle preferably uses a direct contact heat exchanger 7500 to cool the flow the expanded fluid downstream of the expander and condense the diluent. By using a distributed direct contact fluid condensor 7500, users improve the heat transfer resulting in a closer approach temperature compared to conventional art surface heat exchangers. They increase the effective flow area and reduce the effective pressure drop and energy losses across the condensor 7500. Embodiments using one or both of these methods lower the effective cold temperature in the Carnot efficiency, thereby increasing the Carnot efficiency.
By delivering liquid thermal diluent (e.g., water) to displace some to most of the excess oxidant containing fluid (e.g., air), some embodiments preferably reduce compression work and the parasitic pumping losses in the oxidant fluid compressor 1300 and thermal diluent pump. Using a spray direct contact filter reduces the parasitic intake fluid pressure loss. Such filters reduce the drop in efficiency from dirt buildup within the compressor 1300. Such direct contact filter cleaning reduces the amount of material carried over into the fluid condensed after the turbine. This reduces the filtration and pH balancing and corresponding parasitic pumping required to recycle the condensed fluid. By reducing one or more of these parasitic pumping losses, the various embodiments described significantly increase the net system efficiency.
The net specific power and efficiency (per fluid mass flow and/or per volumetric flow) of the VAST thermodynamic cycles are substantially improved by using one or more embodiments of the Trifluid combustor, direct contact condenser 7500, and direct contact filter as described herein and in the Contactor (“191”) patent application and the Trifluid patent application.
Heat and Mass Transfer System
Economizer
With reference
In some configurations, users preferably direct only part of the total recycled thermal diluent through the economizer 6500. E.g., With further reference to
Similarly, users may provide one or more direct contactors as spray intercoolers between one or more lower pressure compressors 1310 and higher pressure compressors 1350 or compressor stages to cool one or more compressor components. E.g., such as taught in the Contactor (“191”) patent application. They may similarly provide diluent to cool the pressure vessel surrounding the combustion chamber 4100 in the combustor 4000 as taught in the Trifluid patent application. In the VAST-WS Cycle configuration results shown in
In modified configurations, users preferably provide a variable flow splitter 6320 after the diluent recovery system 6010 (e.g., a surface condensor 7400) to direct part or all of the thermal diluent to the downstream Preheater 7100 to recover heat from an expanded fluid F421 being exhausted to the Diffuser 5900 (or exhaust, or stack) that exhausts the expanded fluid F475 to ambient conditions. This splitter 6320 permits adjusting the amount of the thermal diluent flow through the preheater 7100 and thus directly affecting the temperature of the thermal diluent flow F270 exiting the preheater. This also affects the amount of diluent flow F249 through the economizer and thus the temperature of the thermal diluent flow F275 exiting the Economizer 6500.
*& Condensor, or Condensor & Recompressor; Cost equations per Traverso 2003
In some configurations, users preferably operate the energy conversion system with an economizer in the “VAST Water Economizer Cycle” (VAST-W). They preferably pressurize the thermal diluent (e.g., water) to sufficient pressure to deliver the heated diluent F275 downstream of the economizer 6500 to the Combustion System 4000 without vaporizing. E.g., they may use a pump 7800 to pressurize a water diluent flow F248 and deliver a pressurized water flow F249 to the economizer 6500 and consequently form and deliver a pressurized hot water flow F275 to the Combustion System 4000 generally without the water evaporating to steam before delivery to the combustor. By using a high expansion ratio through the expander 5100 and condensing the expanded fluid F420 users achieve a substantially greater power generated by the expander (turbine) per mass flow compared to conventional cycles. It gives lower Turbine Exit Temperature in the expanded fluid F420 exiting the expander into the Economizer 6500 than in the relevant art.
With the VAST Water (Economizer) Cycle, users preferably operate near stoichiometric conditions by using a suitable combustor, and by configuring the oxidant delivery system relative to the expander to accommodate the thermal diluent delivered to the combustor without causing surge etc. As shown in
The relative installed capital costs shown in
With reference to
Further referring to
Evaporator (Boiler, or Steam Generator)
VAST Steam Cycle (VAST-WS)
With reference to
Superheater (Gas-Gas Heat Exchanger)
In modified embodiments, users preferably configure a heat exchanger operable to form superheated diluent while recovering heat from expanded fluid exiting the expander 5100. For example, referring to
With further reference to
In some configurations, users preferably deliver only part of the thermal diluent heated by the Economizer 6500 through the Evaporator 6600. With further reference to
With reference to
Once Through Steam Generator (Heat Exchanger)
In some embodiments, a Once Through Steam Generator (OTSG) is preferably used to recover heat from the expanded fluid. This may form hot liquid, vaporized, or superheated diluent. E.g., hot water, steam, or superheated steam. This may be used in one or more VAST-W and/or VAST-WS cycles. Multiple once through heat exchangers may be used to provide combinations of hot water, steam, and/or superheated steam as needed. An OTSG provides the benefit of more rapid startup, and greater safety from much a smaller mass of hot pressurized diluent in the system.
Heated Diluent to User Applications
With reference to
With reference to
With reference to
With further reference to
Such control measures permit users to utilize some or all of the heat recoverable from the expanded fluid. The flow of diluent into the combustor is adjusted accordingly to account for the variation or difference between a diluent temperature and the desired control temperature. E.g., at the combustor outlet. Users preferably use this in conjunction with a VAST combustor operable to accommodate diluent temperatures from very hot to cold according to heat provided to the outlet port connectable to one or more utilization devices.
One or more desuperheaters with or without attemperators may be employed to reduce at least one parameter of pressure or temperature where downstream users (e.g., District Heating) desire or require reduced pressure or temperature or both. Thermal diluent from within the Cycle and external sources (e.g., returned fluid from District Heating) can be used as the source of attemperating water.
Recuperator (Gas-Gas Heat Exchanger)
With reference to
With further reference to
In some embodiments, a substantial portion of one or more diluent flows are preferably delivered upstream of the Recuperator 6800 to further cool the oxidant containing fluid upstream of the Recuperator 6800. In some embodiments, users provide direct contactors to deliver thermal diluent into the compressed oxidant containing fluid being delivered into a recuperator to assist recovery of heat from the expanded fluid downstream of the turbine expander. Users preferably provide one or more direct contactor fluid mixers to deliver liquid diluent into the pressurized oxidant fluid stream to increase the specific heat capacity of the pressurized oxidant fluid in and/or upstream of the recuperator 6800. This beneficially improves surface heat transfer, and reduces the size and cost of the recuperator 6800. E.g., with further reference to
With further reference to
With reference to
Preheater
In some embodiments, users may utilize a preheater 7100 to preheat the thermal diluent to moderate temperatures (e.g., water) from lower temperature diluent and recover heat from the cooled expanded fluid (or “flue gas”) that is heated by the recompressor 5300 before it is discharged to ambient conditions. (See, for example,
In modified configurations, users preferably direct only part of the total recovered diluent through the preheater 7100. They preferably duct some or all of the balance of the recovered thermal diluent to parts of the system requiring or desiring lower temperature fluids to cool flows or equipment and to improve efficiency. (See, for example,
For example, users preferably direct a portion of the cooler flows to a spray entrainer into the compressor, or a spray intercooler between the low and high pressure compressor and/or to cool pressure vessel. In some configurations, directing part of the flow through the preheater provided higher thermoeconomic benefits than directing all of the thermal diluent through the preheater to heat it. Thus, users preferably provide lower temperature thermal diluent F248 to the economizer 6500 than to flows F270 to intercool the compressor to improve the cycle efficiency.
In other configurations, users preferably replace the recuperator in a heating or power system by an economizer in some configurations. They preferably include the recompressor. One or both of these measures substantially reduces the temperature of the expanded fluid exiting the expander. These measures very substantially reduce the operating temperatures of the heat recovery equipment and the associated costs. In some configurations, users preferably include the evaporator and/or the superheater.
One or more of these measures significantly increase the thermodynamic efficiency of the power generation or combined heat and power generation system (CHP). For example, in relevant art microturbines, recuperators are often provided to increase the system efficiency from about 23% for a simple cycle to about 30% to 31% for a recuperated microturbine at about 80 kW to about 100 kW. A VAST-W Cycle may improve the cycle efficiency by about three percentage points or about 10% to about 33% assuming an 80% combined efficiency for generator, power converter, and bearings at low pressure ratio beta.
Similarly, with improved power electronics, the VAST-W Economizer and VAST-WS Steam cycles improve system efficiency by about 3 to 4 percentage points or about 10% improvement in efficiency. This assumes a generator efficiency of about 98%, a variable frequency power conversion electronics efficiency of about 95%, and about 93%-95% efficiency for bearings and other components. E.g., these give about 32.5% to about 35.7% efficiency (LHV) for the VAST Water (or Economizer) and VAST Steam cycles (VAST-W and VAST-WS) at about 100 kW with similar moderate efficiency turbomachinery and TIT.
Improved turbomachinery efficiencies and/or Turbine Inlet Temperatures would further improve these efficiencies. E.g., for a 100 kW VAST-W microturbine system with only an economizer, is expected to show efficiencies of about 32.5% at 950° C. these rise with Turbine Inlet Temperature to about 33.8% at 1000° C., about 36.1% at 1200° C. and about 36.9% at 1200° C.
These configurations of heat recovery methods similarly reduce the costs of a thermodynamic conversion system. For example, in microturbine systems, the recuperator alone often costs about as much or more than the compressor and turbine combined e.g., at about 200 kW and smaller. Furthermore, high temperature recuperators cause a major portion of the repairs and maintenance (reportedly about 80% in some systems.) By preferably replacing the recuperator with an evaporator, using higher pressures and expansion, users reduce the costs of the micro-turbine power system by about 20% to about 25%.
Such combinations of improving efficiency and/or reducing costs significantly improve the capital cost per power ($/kW). They preferably provide one or more of reduced operating costs and lower environmental costs.
The expanded cooled fluid F460 is preferably directed through the condensor to exchange heat with cool thermal diluent. Both the condensed diluent-containing fluid and the liquid diluent-containing fluid used to cool and condensed diluent-containing fluid from the cooled expanded fluid are preferably recovered.
With reference to
In recompressor embodiments, the condensed diluent is preferably pumped up from the low pressure of the expanded cooled fluid in the condensor to the desired return pressure. A barometric leg is preferably added and the diluent pump placed at the bottom of the leg to reduce or avoid cavitation.
The hottest portion of condensate from the condensor is preferably recycled to the heat and mass transfer system with a flow about equal to the amount of diluent-containing fluid delivered upstream of the exit of the expander and directed from the heat exchangers to various user heat applications. This warm diluent flow is preferably treated and redirected back towards one or more of the compressor 1300, combustor 4000, and expander 5100, through one or more of the heat exchangers to again recover heat as desired. Sufficient warm diluent or coolant fluid is preferably collected from the coolest part of the surface heat exchanger 7400 and circulated around the cooling cycle.
Combustion with oxygen or oxygen enriched air eliminates some or substantially all nitrogen and other non-condensable gaseous thermal diluents in some embodiments. Reducing or removing nitrogen and other diluents in air in some embodiments similarly reduces the energy, equipment, and costs of separating out the carbon dioxide formed by combustion from the cooled expanded fluid.
With reference to
Users more preferably use direct contactors in forming the direct contact condensers as taught in the Hagen et al., '191 patent application, with particular reference to
These cooling methods condense a major portion of the steam and water vapor in the expanded and cooled energetic fluid. This leaves nitrogen and carbon dioxide and a small portion of oxygen and water vapor in the condensed expanded fluid. By eliminating almost all excess air in combustion, and then condensing and removing the water formed and injected, these embodiments probably create the highest concentration of carbon dioxide in the cooled exhaust gas of all conventional technology that does not use oxygen enriched air or oxygen for combustion. (See, for example, Table 3.)
For example, combusting diesel fuel with 110% of stoichiometric oxidant in the oxidant containing fluid, (e.g., oxygen in compressed air) the resulting carbon dioxide (CO2) forms about 13.34% of the non-condensables by volume in the condensed expanded fluid (dry basis excluding water vapor, assuming Diesel#2 can be represented by C12H26)—or 19.42% by mass. This compares with about 4.26% carbon dioxide by volume (6.40% by mass) using lean combustion with intake air at about 334% of stoichiometric air, where oxygen forms about 15% by volume of the residual non-condensable gases on a dry basis (about 16.39% by mass.)
In some embodiments, users then compress and separate the remaining carbon dioxide. The higher concentration of carbon dioxide in the cooled expanded fluid results in significantly lower energy use and costs to separate out the carbon dioxide compared to conventional processes. For example, with the Diesel #2 combustion in about 110% of stoichiometric air, users obtain about 303% of the concentration of carbon dioxide by mass obtained by conventional lean combustion systems operating with about 334% of stoichiometric air. Users thus use about 67% less pumping power etc. in recovering this high carbon dioxide concentration.
Filtering and absorptive processes are preferably used to remove contaminants from the cooled expanded fluid. Some embodiments utilize compression and condensation to separate and recover the carbon dioxide. Other embodiments utilize pressure swing absorption or vacuum pressure swing absorption using absorptive materials and methods preferably configured to recover carbon dioxide. Some applications use chemical absorption processes using amines or other absorptive materials to separate CO2. Other embodiments use physical, electrochemical or conductive membrane separation methods to recover carbon dioxide.
Hot Water—District Heating
In addition to shaft power and/or electricity, users preferably provide equipment to provide heated thermal diluent, thermal diluent vapor, and/or superheated thermal diluent vapor, in some configurations. With reference to
With reference to
With further reference to
When District Heating is desired or required, users may select one of the VAST Water or VAST Steam Cycles according to the amount of steam required. Users preferably configure one or more of the preheater and economizer, and/or control the relative flows thorough those components to adjust the temperature and flow of hot water delivered to District Heating in some configurations. (See, for example,
In District Heating applications using hot water, after the hot water is delivered and cooled, it is preferably returned to the energy conversion system. Some water is commonly lost in the District Heating system. In some embodiments, users recover excess water from the expanded fluid and use this to provide makeup water for the District Heating. This earns an value equivalent to the avoided cost of providing makeup water. In some modified embodiments, a regenerative heat exchanger may be used to recover residual heat from the returned fluid, thereby recovering heat and adding heat to the VAST Cycle, such as in heating the diluent.
Steam for Other Applications
Users preferably use an embodiment of the VAST Steam Cycle (VAST-WS) when low pressure steam is desired or needed. With the VAST Steam Cycle, users preferably configure one or more of the preheater, economizer, evaporator and/or control the relative flows thorough those components to adjust the temperature and/or flow of low pressure steam generated. They may also control the temperature and/or the flow of hot water to the utilization device, such as District Heating in some configurations. (See, for example,
Users preferably use a VAST Steam Cycle (VAST-WS) embodiment when high pressure steam is desired or needed. With the VAST Steam Cycle, users preferably configure one or more of the preheater 7100, economizer 6500, evaporator 6600, and superheater 6700, and/or control the relative flows thorough those components to adjust the temperature and/or amount of high pressure steam delivered as desired or configured. They may also configure the system to provide hot water and/or low pressure steam as desired or needed in some configurations. (See, for example,
Cooling or Refrigeration Systems
In some configurations, users deliver hot fluid to a cooling utilization device to provide one or more cooling systems. E.g., for air conditioning, chilling, and/or refrigeration. E.g., using one or more absorption cooling systems suitable to the desired cool temperature(s). In other configurations, some or all of the power available in the VAST cycle is preferably used to drive one or more mechanical compression/expansion cooling systems instead of or in addition to the absorption cooling systems. These may cool air, chill water, form ice, and/or cool refrigerant.
In other applications, users provide all three of electrical or mechanical power, heat and air conditioning by appropriately configuring VAST Cycles. Such combined power and cooling configurations provide substantial thermo-economic and environmental advantages over conventional relevant art.
Where there are substantial fluctuations in demand for cold services and/or mechanical or electric power, users modify a VAST Cycle configuration to preferably provide thermal storage and deliver to/draw from the cold storage and deliver cooling service as desired. E.g., users preferably operate the cooling equipment during off peak hours to cool a coolant fluid. E.g., cold water, cold air, or refrigerant. The coolant fluid is then preferably used to exchange heat with the cold storage system. E.g., with cold water tanks, slush or ice storage, and/or cold rock storage. In some configurations, users preferably use the cool storage to cool the intake oxidant containing fluid. This helps increase the density of the intake air and compressor capacity, especially on hot days.
Power Boost
Users preferably provide diluent to cool the combustion and/or energetic fluid in the combustor prior to the expander. By such means, they increase the amount of fuel and oxidant that can be combusted and the power capacity of the system. They preferably maintain the temperature of the energetic gases while so doing.
This capability of the VAST Cycles to change or boost power while maintaining temperature provides particular benefits compared to conventional relevant art lean combustion systems using excess air as the thermal diluent. In those systems, combusting additional fuel increases the temperature of the energetic gas exiting the combustor, thereby increasing the damage rate to turbine blades and other hot section components. With VAST Cycles, users preferably control the temperature independently of the fuel flow and power levels.
Under some conditions, users preferably increase temperature of the energetic fluid at the combustor exit to increase the power generation capacity of the turbine and/or the efficiency of the turbine. E.g., under emergency power demand conditions. By the improved temperature control methods described in the Hagen et al. '191 patent applications mentioned above, users preferably precisely control the exit temperature and duration of such temperature increases. These are carefully monitored relative to the degradation rate of the turbine blades.
Given the flexibility of the VAST Cycle, users preferably adjust the cooling flows and coolant temperatures of the steam and/or water coolant flows to the turbine blades to increase blade cooling when and as the temperature of the energetic fluid is increased in some configurations. This cools the turbine blades more than in conventional relevant art, reducing the damage rate of high temperature operation. Users thus reduce blade replacement frequency and improve system life cycle costs compared to conventional relevant art.
Flow Controls
Users preferably provide actuators and controls to adjust the flow ratio in one or more of the preheater, economizer and evaporator splitter valves to adjust these flows as desired or needed in some configurations. Users preferably provide dynamic actuators, controls and sensors to dynamically control the relative portions of hot water, low pressure steam, high pressure steam and power as desired by the application with time or as processes vary etc. e.g., these may use electrical, hydraulic, pneumatic, or mechanical actuators.
In some embodiments, users provide multiple recycled thermal diluent flows and heat these to multiple temperatures by recovering heat from the expanded fluid. For example, users preferably provide cool water to cool liquid fuel-delivery systems to prevent coking. Complementarily, users provide hot water and/or steam into the combustor to control combustion temperature profiles to constrain NOx emissions below a prescribed concentration, while oxidizing most carbon monoxide and other combustible components below prescribed concentrations, and achieve desired Turbine Inlet temperatures. Users preferably deliver fine droplets of heated water and/or steam help extend one or more combustion stability limits. Users preferably deliver liquid diluent so that a substantial portion evaporates after the onset of combustion.
In embodiments wherein the utilization device provides cooling, users preferably control the delivery heated diluent fluid flows to the cooling utilization device. More preferably, the distribution of heated diluent delivery is controlled between upstream of the expander outlet, and to the cooling utilization device to control the distribution between power generation and cooling. More preferably still, the rate of power production and/or the rate of cooling are controlled by controlling fuel delivery, and the distribution of heated diluent flows between upstream of the expander outlet for power generation and heat exchangers providing heated diluent to the cooling utilization device to provide cooling. Most preferably, the oxidant delivery rate is controlled together with the fuel delivery rate and the distribution of diluent flows within the energy conversion system, to control both the rate of power and the rate of cooling delivered by the energy conversion system.
In some embodiments, users produce excess water (or achieve a net positive water balance) with VAST Steam Cycles (VAST-WS), and/or VAST Water (Economizer) Cycles (VAST-W). (See, for example,
For example, with the 50 MW industrial aeroderivative example, with VAST Steam Cycles, user achieved net positive water balance for all air compressor pressure ratios Beta calculated from about 10 to about 50 with about 105% of stoichiometric air flow. They achieve similar net positive water balances for VAST Steam Cycles with no air cooling. These flows amount to about 0.5 to about 1.5 times the flow of the fuel depending on the type of fuel, the air compressor ratio Beta and environmental parameters of relative humidity and the temperature of the ambient cooling fluid. (e.g., from deep sea water at about 7 degrees C. to hot desert air at about 45 degrees C. or higher.)
Configuring the VAST Steam Cycle to improve the Internal Rate of Return and considering the excess water as a revenue stream results in a configuration that condenses and recovers about twice as much water for sale as in some configurations without water sales.
Similarly, users achieved net water balance for VAST Water (Economizer) Cycles for air compressor pressure ratios of about 28 and larger with about a 105% of stoichiometric air flow in this example.
By contrast, all the relevant art humid cycles modeled required very substantial make up water. These make up water flows amounted to about 4 to 9 times the flow rate of fuel. The excess water produced of the VAST Cycles (net positive water balance) compared to the make up water required (negative water balance) of the relevant art cycles CC2L, STIG, RWI, HAT and HAWIT, provide substantial environmental and thermoeconomic advantages.
Such VAST Cycle power systems can be configured with air cooling systems to condense and recover water. Consequently, they can be sited anywhere without any requirements for an ambient water supply other than the quantity of water sufficient to prime the energy conversion system on startup until a positive water balance is obtained.
In VAST Cycle configurations achieving a net positive water balance (excess water), most of the particulates and contaminants in the intake oxidant containing fluid, fuel and thermal diluent are condensed with the thermal diluent in the condensor. The concentration of these components in the excess condensed thermal diluent is usually of a similar magnitude or less than the concentration of these contaminants in the intake fuel. The flow of these contaminants into the expander from the combustor generally corresponds to the intake contaminant flow from the fuel and oxidant flows, plus the flow of contaminant recycled with the thermal diluent (e.g., the water.)
Where the contaminants in these combined flows are less than the desired or required concentrations for the expander at the temperatures considered, users preferably manage the buildup of contaminants by discharging the contaminants from the system in the excess thermal diluent formed, e.g., via the excess water discharged. In such configurations, users achieve substantial reductions in system cost by displacing almost all the water treatment equipment required for conventional relevant art.
Sufficient water storage is preferably provided to contain excess recovered water, and/or to store makeup water from an external source, for use in the VAST Cycle to buffer operations, and/or to facilitate startup to provide water before water recovery commences or is otherwise available. In modified embodiments, a bladder system is used to provide a higher pressure storage than would otherwise be available. One or more Charging Pumps may be employed to provide water to fill the VAST Cycle components or to increase header pressure under predetermined conditions.
Users preferably control the temperature profile of the combustion fluids and/or of the energetic gas leaving the combustor by adding thermal diluent. They preferably pumping it into the thermal system as liquid diluent. User preferably deliver liquid and/or vaporized or superheated thermal diluent through one or more distributed contactors as described herein. Users preferably create water/fuel and air/fuel spatial distributions using the present embodiments that are significantly more controlled, and preferably more controlled and/or uniform than conventional technologies. This results in significant reduction in spatial temperature variations from desired temperature profiles.
In some configurations, users provide additional nozzles about, along, and within the combustor 4000 downstream of the flame to increase the water or steam delivery. Users preferably control the proportions of thermal diluent delivered to fuel delivered to control the temperature of the resultant reacted mixture or energetic fluid. Users preferably account for any excess oxidant and/or gaseous thermal diluent or other reactant, and the temperatures, pressures and heat capacities of each of the fluids that change the temperature of reaction or of the energetic fluids.
For example, Table 4 shows the typical temperatures achieved by delivering water as thermal diluent at various water/fuel ratios when burning #2 Diesel fuel provided at about 350 K (about 77° C. or 171° F.) with about 110% of the stoichiometric ratio of compressed air at a pressure ratio of about 10 (e.g., 10 bar) at about 788 K (about 515° C. or about 959° F.) with about 60% relative humidity in the intake air. The inlet water is provided at ambient conditions of about 300 K (about 27° C. or 81° F.).
For example, at about 110% excess air, users preferably provide about 7:1 water/fuel m/m with Diesel#2 to control the temperature to about 846° C. Similarly, users preferably provide about 2:1 water/fuel m/m to control the exit temperature to about 1,611° C. This range of 7:1 to 2:1 covers the range of Turbine Inlet Temperatures of most commercial gas turbines (i.e., about 900° C. for uncooled blades to about 1,525° C. for the projected H class technology).
In another example, users preferably provide a ratio of about 1.5:1 water/fuel with Diesel#2 at about 110% excess air to achieve a temperature in the energetic fluid of about 1720° C. This is similar to Turbine Inlet Temperatures used in high temperature experimental ceramic turbines. A ratio of about 1:1 water/fuel with Diesel#2 achieves an energetic fluid temperature of about 1829° C.
Users readily calculate similar water/fuel ratios for other temperatures, for other ratios of excess oxidant or excess gaseous diluent, differing inlet conditions or heat recovery, or for natural gas or other fuels, using commonly available thermochemical reaction or computational fluid dynamics programs. With the embodiments described herein or in the previous application, users deliver thermal diluent to control the temperature of the energetic fluid exiting the combustor to below about 2,073 K (about 1,800° C., or about 3,272° F.). Users control the temperature above the temperature of cooled fluid diluent. (E.g., about 1° C. or about 34° F. for water.)
In many configurations, the mass flow rate of thermal diluent is preferably higher than the mass flow of fuel. E.g., users provide diluent to fuel mass ratios Omega of about 2:1 to about 7:1 for water/Diesel#2 to control the temperature of the energetic fluid to the range of about 1,611° C. to about 846° C. This covers the preferred design Turbine Inlet Temperature range of common commercial gas turbines at typical compression ratios.
Conventional technologies are limited in the amount of water they can deliver without quenching the flame or causing high CO emissions or pressure oscillations in the combustor. E.g., typically less than about 1.1:1 water/fuel by mass. In the present embodiments, users preferably achieve at least about 1.5:1 water/fuel by mass.
By injecting thermal diluent into the combustion system 4000 and reducing excess air, thermodynamic models of the VAST cycle show that there is insufficient vapor concentration for the thermal diluent (steam) to condense within the gas turbine as the energetic fluid is expanded and cooled, even when expanding to sub-atmospheric pressures. This results in very little condensate erosion of turbine blades from the expanding fluid. By contrast, heat recovery with a Heat Recovery Steam Generator with consequent expansion of steam through a condensing turbine results in condensed water impacting turbine blades which may cause substantial blade erosion.
Users preferably cool the expanded turbine exhaust gas using a coolant fluid near ambient temperature in some embodiments. The coolant fluid is cooled by ambient cold water or an air heat exchanger as available.
Cooling Hot Components
Energy conversion systems commonly have components that require cooling which are often air cooled with corresponding loss of the heat. In some configurations, users preferably use diluent cooling flows to cool such components and recover this low to medium grade heat. Users preferably rank components in order of thermal sensitivity to damage and cooling requirements. They preferably rank cooling flows by the life cycle benefits and/or damages. Users preferably cool components in order of thermal sensitivity and economic benefits in some configurations.
With reference to
For example, further referring to
E.g., Power conversion electronics are very sensitive to temperature such as when insufficient cooling or excessive cooling fluid temperatures allow the electronics junction temperature to rise above desired or required values. These are preferably controlled to less than 100° C. or a similar design temperature based on the cooling flow and heat sink. Higher temperatures rapidly reduce reliability, cause failure, reduce availability and increase replacement costs. However, water much colder than desired cooling does not further benefit the electronics as significantly as providing cooler water elsewhere.
The coldest thermal diluent (e.g., water or refrigerant) is preferably used in one or more of the coldest part of the economizer, the preheater, direct contact spray filtering/cooling of the intake air, direct contact entrainment cooling into the compressor spray, direct contact spray inter-cooling, and/or surface cooling between compressors. Users preferably evaluate the relative benefits and distribute the cooler thermal diluent amongst these applications in order of and in proportion to these benefits. Warmer thermal diluent (e.g., water) can be directed to Medium Temperature Heat Sources requiring or benefiting from cooling but with less stringent temperature requirements. For example, water that has been heated to near 90° C. to 95° C. by cooling the power conversion electronics is then preferably used to cool the generator and the pressure vessel.
Similarly, a splitter valve 6460 may be configured between the Low Temperature Heat Source and a Medium Temperature Heat Source to direct hot water as desired to a hot water use such as District Heating. Another splitter 6470 may similarly be provided to direct this hot water to the combustor 4000 as desired. These Medium Temperature Heat Sources are often electrical components that generate heat such as the Generator, Motors, Bearings, Pumps and Mechanical Drives.
These Medium Temperature Heat Sources may be classified into lower temperature components such as bearings, gear trains and variable speed drives that use lubricants. (Note that lubricants are now available to operate at 500° F.) The Pressure Vessel is a heated component that is preferably controlled below 500° F. Motors and Generators may similarly be limited by the temperature of insulating coatings and the melting temperature of solder.
The heated diluent may then be directed to High Temperature Heat Source to cool the respective components. For example, the hot path within the combustion system and the expansion system. These may include one or more of the combustion chamber liner, an equilibration zone and/or transition zone, one or more turbine vanes and/or turbine blades, a portion of the turbine hub, a turbine shroud, and turbine wall for one or more stages. A splitter valve 6480 may be configured between the Medium Temperature Heat Source and the High Temperature Heat Source(s) to deliver hot or evaporated diluent (e.g., steam) to a corresponding high temperature use (or steam use);
Similarly, a splitter valve 6490 may be configured between the High Temperature Heat Source and the Combustor 4000 to deliver superheated diluent to a super heated diluent or steam use. The remaining high temperature or superheated diluent is preferably delivered to the combustor. Here it is preferably mixed with one or more of the oxidant, diluent and/or fuel fluids upstream of the combustor outlet. In some circumstances, users may provide higher flows of diluent or cooler diluent sufficient to avoid evaporating or superheating the diluent. E.g., by using pressurized water.
These methods effectively recover lower grade heat and recycles it into the energetic fluid. This heat recycling method reduces the problems in the relevant art of using excess oxidant fluid to cool one or more hot section components and in doing so to cool the energetic fluid and loose cycle efficiency.
Combustor Configuration
Users provide and configure a combustor in the energy conversion system selected to provide control over the combustion and diluent delivery process according to one or more desired measures. In some embodiments, users may use a combustor operable to deliver and mix diluent in with the oxidant containing fluid, preferably comprising at least a portion of liquid diluent. For example, the combustors taught in the Ginter U.S. patents referred to above may be used. The fluid delivery to these combustors is preferably controllable to maintain a combustible mixture upstream of the start of combustion and operate with stable combustion.
Users preferably configure a combustor operable to deliver further diluent downstream of the start of combustion. Combustors with such capability preferably deliver diluent flows that exceed a diluent saturation limit rate common in the relevant art. This enables displacing a larger portion of the oxidant containing fluid with diluent. For example, cycles may use combustors such as those taught by Ginter that overcome the common air saturation limit in cycles evaporating water such as are used in the STIG, HAT (or “EvGT”), HAWIT, RWI, and Combined Cycles.
The combustor is more preferably selected to be operable to control the spatial delivery of diluent within the combustor so as to control the amount of diluent evaporated prior to the start of combustion to maintain a combustible mixture and stable combustion within the combustor. Correspondingly, the diluent delivery is preferably controllable to evaporate further diluent downstream of the start of combustion. For example, the VAST combustors taught in the Trifluid patent application are preferably used. In some configurations, these VAST combustors enable a higher liquid diluent delivery rate upstream of combustion than the conventional diluent delivery combustion stability limit. Such Trifluid combustors are preferably configured with the transverse spatial control of fluid delivery and mixing. This provides greater control over fluid composition and combustion, thus enabling reliable operation across a range of composition from near stoichiometric operation to near lean Brayton cycle operation.
The combustor is preferably operable to also deliver evaporated or gaseous diluent. For example, combustors with such capabilities such as are taught in the Trifluid patent application are preferably used. These are preferably operable to deliver both evaporated diluent and liquid diluent, e.g., steam and heated (or cooled) water. This enables delivery of more diluent and provides the ability to recover and recycle more heat from the expanded fluid than the diluent evaporation capability of relevant art cycles. For example, the VAST combustors as taught in the above-mentioned Hagen et al. '047 patent application may be configured to deliver two to four times as much total diluent as evaporated diluent, e.g., as steam and regular or heated water. This exceeds the amount of steam deliverable to the combustor in a STIG cycle.
They preferably deliver to the combustor 4000 the maximum amount of vaporized diluent that can be recovered from the heat recovery system 6000 that is not otherwise used in other applications. Users more preferably operate the combustor with less oxidant and more diluent than would sustain a combustible mixture were the fuel containing fluid, oxidant containing fluid and diluent containing fluid premixed at the fluid delivered conditions, i.e., they displace more gaseous non-condensable diluent such as oxidant containing fluid or as air used as diluent.
Note that in the figures given herein, the combustor is shown as a thermodynamic “black box” operable to deliver mix and combust fuel containing fluid, oxygen containing fluid and diluent containing fluid. These diagrams are not intended to show the order or location of diluent and fuel delivery. Further detail on actual fluid spatial delivery may be found in the above-mentioned Hagen et al. patent applications, and in one or more of the Ginter patents.
Users more preferably use a VAST Trifluid combustor which is operable to control the transverse spatial distribution of fluids, such as is taught in the complementary Trifluid patent application. They preferably configure this combustor to control the transverse distribution of temperature in at least one direction. E.g, in the radial direction of an annular combustor to control the temperature distribution or profile of the energetic fluid entering the turbine from the hub to tip of the turbine blades and vanes.
Users preferably use a combustion system operable with high precision control over the fluids and fluid ratios as taught in the Trifluid patent application. This enables operating the combustor to reliably deliver an energetic fluid with peak temperature closer to the design peak temperature of the expander.
They more preferably control the transverse distributions of fluid delivery and control the transverse temperature distribution near to the design temperature distribution. This enables operating at a higher mean temperature while staying within the spatial temperature design uncertainties.
In some embodiments, users preferably configure and control the combustor so that the transverse fluid composition is near to the stoichiometric combustion within numerous regions across the combustor exit as is taught in the complementary Trifluid patent application. This composition is preferably controlled to displace a portion of excess oxidant containing fluid diluent and to control at least one contaminant or pollutant below desired limits. E.g., carbon monoxide, residual or partially reacted fuel components, and oxides of nitrogen. This enables users to operate closer to stoichiometric for higher specific power while achieving pollutant emission limits. In other embodiments, users configure and operate the system at higher relative oxidant/fuel ratios to beneficially provide higher efficiencies.
Cycle Specifics
VAST Water Cycle: VAST-W
An embodiment of the thermodynamic cycle may configured as shown in
In this configuration, a portion of liquid diluent F275, which may include H2O, is injected directly into the combustor 4000. As shown the diluent flow F429 may be used to recover heat from expanded fluid F420 from the expander 5100 using the diluent heat exchange sub-system 6020 with an economizer 6500. (See also
Pumps, splitter valves, and combining valves may be added or removed as desired or needed to achieve desired results. While flow control is shown as using a variable ratio or splitter valve, it will be appreciated that other components or combinations of components may accomplish similar results, e.g., by using one or more controllable valves, pumps, and flow restrictions.
With liquid diluent being added to the combustion chamber 4100 diluent vapor is produced and mixes with the combustion products to produce an energetic fluid flow F405. In some embodiments, heat from this process may be recovered using the economizer 6500 in the diluent heat exchange sub-system 6020 after or downstream of the expander 5100.
Diluent Recovery System
With reference to
In embodiments comprising the diluent recovery system 6010, the expanded fluid is preferably processed to recover the diluent and in some embodiments, recycle this diluent back into the thermodynamic cycle. In some embodiments the diluent recovery system may be configured with a flue gas condenser or surface condenser (FGC) 7400. A cooling apparatus 7600 may be employed to reject heat from the cooling fluid used to cool the expanded fluid in the surface condensor 7400. Recovered diluent may be removed from the surface condensor 7400 and, if desired, recycled back into the system, e.g., as flow F295. In some embodiments, this may be through a diluent treatment system 2010.
In other embodiments, such as shown in
In embodiments of the diluent recovery system, the heated cooling fluid and recovered diluent may be used in applications that desire or require heat. The cooling and diluent fluids may be distributed to these applications and if desired, in some embodiments be returned for recycling into the system. One embodiment, with cooling and diluent fluid being used for district heating, is demonstrated in
With reference to
A recompressor 5300 in
VAST Water and Steam Cycle: VAST-WS
An embodiment of the VAST thermodynamic cycle may be configured to recover heat from the expanded energetic fluid into heated liquid diluent and diluent vapor using one or more heat exchangers as shown in
In the configuration of
With the diluent being added to the combustion chamber 4100 diluent vapor is produced and combines with the combustion products to produce an energetic fluid flow F405. Once the energetic fluid is expanded in the expander 5100, the resulting hot expanded fluid F420 may be delivered into a heat exchanger array or diluent heat exchange sub system 6020 to heat the diluent going to the combustion system 4000.
In
As demonstrated in
Expanded fluid from the economizer 6500 may be delivered to the Diluent Recovery System (DRS) 6010. In the diluent recovery system 6010, the expanded fluid is processed to recover the diluent and in some embodiments, recycle this diluent back into the thermodynamic cycle. Referring to
In some configurations, a coolant fluid is preferably used in the heat exchanger 7400 used to condense diluent. The coolant fluid is preferably selected with a freezing point below ambient conditions to avoid freezing the coolant in the diluent recovery system 6010, e.g., and alcohol such as glycol or propanol, and/or a refrigerant hydrocarbon. Diluent recovery system 6010 may comprise membranes permiable to diluent but not to other components of the cooled expanded fluid, e.g., membranes that are permiable to water and not to oxygen or nitrogen. Absorption/desorption separation and recovery methods may similarly be used.
Another embodiment shown in
In embodiments of the diluent recovery system, the heated cooling fluid and recovered diluent may be used in applications that desire or require heat. The cooling and diluent fluids may be distributed to these applications and if desired, in some embodiments be returned for recycling into the system. One embodiment, with cooling and diluent fluid being used for district heating, is demonstrated in
In some embodiments the diluent and cooling fluid flow F295, recovered from the direct contact condensor 7500, may be recycled back into the energy conversion system. In some embodiments, this recycling is preferably through a diluent treatment system 2010 to treat the flow F295. (See
A recompressor 5300 in
Referring to
Note that the VAST Steam cycle has comparable efficiencies but substantially lower capital costs than conventional relevant art cycles. In this example, the VAST Steam Cycle has about an Internal Rate of Return (IRR) of about 24% at base load of 8,000 hours/year and an IRR of about 12% at part load (˜50%) of about 4,000 hours/year at these conditions at about pressure ratios of 20 to 30 (with one spray intercooler between a low and high pressure compressor.)
This VAST Steam Cycle example, gives about two to four percentage points advantage in Internal Rate of Return (IRR %) compared to the Relevant art STIG cycle at these conditions for base versus 50% load. (i.e., about a 20% to 40% higher IRR %.) Similarly, for comparison, a relevant art two pressure level Combined Cycle (CC2L) in a similar 50 MW turbine operating at 4000 to 8000 hours per year achieves only about 2% to 4% Internal Rate of Return in contrast to the VAST Steam Cycle at 12% to 24%.
The VAST Steam Cycle appears to have similar advantages over the RWI, HAWIT and HAT cycles. (See, for example,
VAST Steam Cycle with Steam Blade Cooling (No Air Cooling)
With the VAST Steam Cycle, users preferably configure the flows and/or temperature of the thermal diluent vapor or superheated thermal diluent vapor. They preferably direct one of these flows to use as coolant to the expander hot sections. E.g., to one or more of turbine vanes, blades and shroud. This substantially improves system efficiency compared to using compressed air as the expander hot section coolant. This also reduces system cost and improves the thermoeconomics of the system. (See, for example,
For example, with a 50 MW industrial aero-derivative gas turbine operating on the VAST Steam cycle, displacing the air cooling with steam cooling increased the thermal efficiency from about 51.3% to about 53.3%. This assumes that after cooling the expander hot section(s), (e.g., turbine blades & vanes,) the heated steam is directed back into the combustor upstream of the expander.
In modified configurations, users use steam to cool one or more hot section components (e.g., blades, vanes, shrouds, wall, and/or hub) and then deliver heated steam into the energetic fluid flow within the turbine. This combination will increase the efficiency to between the 51.3% and 53.3% in these relative calculations.
In the VAST Cycle, the excess air used for turbine blade cooling was assumed to use about 18% of the air flow used for combustion at about 110% of stoichiometric flow. Eliminating the excess compressed air may reduce the compressor size in the VAST cycle by about 15%.
Displacing air cooling with steam cooling with this VAST cycle, reduces equipment cost and increases the Internal Rate of Return by about two percentage points from about 12% IRR to 14% IRR at air compression pressure ratios of about 20 to 30 in these relative calculations. More preferably, the heated steam is recycled upstream into the combustor after cooling one or more hot component to further improve thermal efficiency.
VAST Water and Steam with Recuperation Cycle: VAST-WSR
An embodiment of the thermodynamic cycle may configured with a recuperator 6800 as shown in
In this configuration the diluent heat exchange sub-system 6020 includes a gas-gas heat exchanger or recuperator 6800 and a packed bed humidifier or saturator 7300 as shown in
Advantages and results of these cycle embodiments are demonstrated in
Oxidant Supply System
Oxidant Source
For the complementary co-reactant fluid, in many embodiments users use an oxidant containing fluid, commonly air, an oxygen enriched fluid, or oxygen. Some oxidant containing fluids, such as air or oxygen enriched air, include one or more thermal diluents, such as nitrogen, water, carbon dioxide, and noble gases such as argon etc.
Many embodiments utilize air as the oxidant containing fluid to provide oxygen to the combustion system 4000 or reactor. Users preferably compensate for variations in the air humidity, temperature, and pressure in some embodiments.
In some embodiments, liquid oxygen, oxygen prepared by vaporizing liquid oxygen, oxygen formed by electrolysis, solid electrolyte oxygen separation, or oxygen prepared by other methods, can be employed.
Conventional oxygen fuel combustion produces a very hot energetic fluid F405. The very high temperature makes it very difficult to make durable long lasting combustor liners. In some embodiments, thermal diluent distribution tube arrays distribute fuel and thermal diluent in close proximity. This substantially constrains the temperature of the hot energetic fluid F405. In configurations using liquid oxygen, users preferably deliver the oxygen through direct contact tubes to improve intimate fairly uniform and/or controlled mixing of fuel, oxidant, and diluent.
Lower peak fluid temperatures obtained by such embodiments make it much simpler to make combustion system 4000 that will reliably tolerate the combustion. Similarly, the thermal diluent distribution tubes and radiation shields or fins strongly reduce the heat fluxes experienced by the fuel distribution tubes.
In some embodiments, users prefer a heat exchanger for vaporization of liquid oxygen, using the heat of at least one of the expanded combustion fluid, heated diluent, District Heating fluid, mechanical power, or electrical energy, generated from within the VAST Cycle or externally or both.
Some embodiments use oxygen “enriched” air where the oxygen concentration is increased over standard air by one or more of a variety of enrichment methods. These include pressure swing zeolite concentration systems and vacuum pressure swing concentration systems. Membrane oxygen enrichment methods may also be used. As with oxygen combustion, the perforated fuel and oxidant containing fluid distribution tube arrays substantially constrain the combustion temperatures and simplify combustor design.
Filter
With reference to
In some configurations, users preferably provide a differential pressure sensor to monitor the pressure drop across the intake gas/air filter to decide when to clean or replace the air filter. In some embodiments, more than one filter with flow control devices (valves, dampers, et al) may be employed, enabling on-line switching of intake sources such as when one filter is awaiting maintenance due to high differential pressure from build-up of particulates and other material that increase resistance to flow and thus decrease overall Cycle efficiency.
Users preferably use a cold liquid diluent to both cool and filter the air. Such filtering reduces the rate of fiber accumulation in the compressor 1300 (e.g., on compressor vanes and blades), and in the Expander 5100 (e.g., on expander vanes and blades.) Cooling the air gives compressors greater capacity, particularly on hot days. Filtering reduces the rate of compressor and expander fouling, thus reducing downtime, cleanup costs, and the typical compressor and expander fouling losses and reducing these losses in efficiency. It reduces the pressure drop across the fluid (gas/air) filters, reducing the pumping power of the compressor.
When using water sprays with a direct contact filter to filter the air, users preferably control diluent delivery prior to combustion to compensate for variations in moisture composition from variations in humidity and from using diluent through a spray direct contact filter.
Compressor
In medium to large gas turbine power systems, the compressor forms the largest single capital expense in high pressure ratio systems, costing more than the expander. In lower pressure ratio systems, the compressor is still a substantially significant expense. Referring to
For example, by preferably reducing the compressed air flow from ultra lean combustion at about 334% (for about 1300° C.) to about 110% of stoichiometric flow, users reduce that portion of the flow through the compressor by about 67%. Similarly, users preferably displace the compressed air commonly used to cool the expander hot sections, (e.g., turbine blades, vanes & shroud) by providing a diluent such as steam and/or water. See
Users preferably apply the substantial cost savings in compressor size at pressures commonly used, to increasing the overall effective pressure ratio Beta, and thus the turbine expansion ratio, thus improving system efficiency in some embodiments. In modified embodiments, the same compressors are used to feed multiple expanders compared to common configurations.
Users preferably provide a base low pressure compressor (LPC) 1310 to pressurize the oxidant containing fluid.
Users preferably add one or more high pressure compressors (HPC) 1350 to increase the pressure of the compressed oxidant containing fluid to the combustor 4000 and expander 5100 in some configurations. This increases the overall pressure ratio Beta as the product of the pressure ratio Beta of the low pressure compressor times the pressure ratio Beta of each of the high pressure compressor(s).
In some embodiments, users preferably adjust the pressure ratios of one or more compressors, e.g., comprising the low pressure compressor 1310 and the high pressure compressor 1350 and the recompressor 5300), to control the gross expansion ratio of the energetic fluid. This may be controlled to adjust one or more of the net specific power, the system power efficiency, system gross heat efficiency, and/or reduce life cycle thermo-economic costs.
For example, consider 50 MW gas turbines configured for VAST-WS (VAST Steam Cycle) with wet compression using water spray inter-cooling between low and high pressure compressors, operating at 1300° C. Turbine Inlet Temperature, using mean industrial costs of natural gas and prices of electricity in the USA for 2000. The efficiencies of turbines are taken as the mean between the GE and Rolls Royce aeroderivative turbines of 1990 class technology.
Some typical distribution of pressure ratios for the low pressure compressor, high pressure compressor, and recompressor for such a configuration are shown in
In a similar fashion, the low pressure compressor ratio is configured at about 3.16 for a pressure ratio Beta of about 30 for the oxidant containing fluid in typical spray intercooled industrial 50 MW aeroderivative turbine configuration.
Similarly, they preferably set the low pressure compressor ratio to about 2.53 for an air compressor pressure ratio Beta of about 10. They preferably increase this to about 3.64 for an air compressor pressure ratio Beta of about 44.
Similarly, for a pressure ratio Beta of about 30 for the oxidant containing fluid in typical industrial 50 MW aeroderivative turbine configuration, users preferably configure the high pressure compressor ratio to about 9.47 in some embodiments. (See, for example,
Similarly, they preferably set the recompression ratio to about 3.94 for an air compressor pressure ratio Beta of about 10. (See discussion of recompressor in Expansion System.) They preferably drop this to a pressure ratio Beta about 2.2 for an air compressor pressure ratio Beta of about 44.
Note that with these preferred results for the spray intercooler, the pressure ratios of 3.16 and 9.47 for the two compressors are substantially different from the optimum pressure ratio for a surface intercooler of the square root of the total pressure ratio or about 5.47.
Users preferably adjust the recompressor 5300 ratio to improve or optimize the system economics, e.g., higher Internal Rate of Return %, which is near the optimal thermal efficiency. (See discussion of recompressor in Expansion System.) The curve of Internal Rate of Return vs. Thermal Efficiency (
For a pressure ratio Beta of about 30 for the oxidant containing fluid in typical industrial 50 MW aeroderivative turbine configuration, users preferably configure the recompressor ratio to about 2.6 in some embodiments. i.e., the pressure in the cooled (condensed) expanded fluid at the recompressor intake is about 38% of ambient pressure. (See, for Example,
Similarly, they preferably set the recompression ratio to about 3.9 for an air compressor pressure ratio Beta of about 10. They preferably drop this to about 2.3 for an air compressor pressure ratio Beta of about 44. I.e., the pressure in the condensed expanded fluid at the recompressor intake in this configuration is about 25.6% (1/3.9) to about 44% (1/2.3) of the ambient pressure. (e.g., % of one atmosphere or about 26 kPa to 44 kPa.)
By preferably displacing gaseous compression with liquid compression, users substantially reduce the gross pumping work required to deliver the energetic fluid to the inlet to the expander inlet in some embodiments. (See, for example,
By the measures of increasing the system net power while reducing oxidant containing fluid flow, users increase the ratio of the system net power to the mass flow through the compressor exit or the Compressor Exit Specific Net Power. (i.e., the gross turbine power less the pumping power of the compressor(s) and pump(s), divided by the fluid mass flow through the exit of the compressor, including water from relative humidity, fogging, water entrainment, intra-compressor water spray or inter-compressor water spray.) This reduces the corresponding compressor capital costs per net power delivered. With reference to
Thermodynamic Efficiency % versus for the Compressor Exit Specific Net Power ratio in kW/(kg/s) or kJ/kg (i.e., the net power in kW or kJ/s divided by mass flow in kg/s is equivalent to the specific work kJ/kg to pressurize a unit mass of oxidant containing fluid or air). This compares the VAST-W and VAST-WS cycles with a surface condenser, and the VAST-WS with a direct contact condenser. These VAST Cycles are further compared with the major relevant art “wet” cycles over a range of pressure ratios Beta from about 10 to 40. e.g., at 50 MW, and TIT=1300° C. Note that each of the relevant art cycles are extended to the air saturation limit with corresponding resized compressors for a conservative comparison, not just to the conventional compressor surge limit.
Note that in the relevant art with ultra-lean combustion, the flow through the compressor is commonly similar to the mass flow through the turbine. However in relevant art “wet” cycles, and the VAST Cycles, the compressed flow of air and water vapor exiting the compressor is usually substantially smaller than the mass flow through the expander or turbine. In “wet” cycles, the Turbine Specific Net Power is substantially higher than in relevant art lean combustion systems. This Compressor Exit Net Specific Power is shown separately in
The VAST-W (VAST Water Cycle) delivers hot water to the combustor. As the pressure ratio Beta increases from about 10 to about 50, VAST Cycle 2 shows substantial increases in Compressor Exit Specific Net Power from about 1020 kJ/kg (kW/kg/s) to about 1200 kJ/kg (kW/kg/s). This correspondingly increases the LHV Cycle Efficiency from about 43.7% to about 51.3%.
Similarly VAST-WS (VAST Steam Cycle) delivers both steam and water into the combustor. It similarly increases Compressor Exit Specific Net Power from about 1120 kJ/kg (kW/kg/s) at a pressure ratio Beta of about 10, to about 1200 kJ/kg (kW/kg/s) at pressure ratio Beta of about 40.
With further reference to
In these initial calculations of the VAST cycle with economizer only, the water was assumed to be pressurized to 165 bar. The water injection pressure was reduced in the VAST Steam generation cycles. The systems efficiency, IRR % and electricity costs may be improved by reducing the excess water delivery pressure.
One embodiment of the VAST Steam cycle (VAST-WS) may be configured to provide no compressed air to cool turbine blades, and the compressor is preferably sized accordingly. When operating near stoichiometric conditions, this increases the Compressor Exit Specific Net Power. E.g., to about 1380 kJ/kg (kW/kg/s) at pressure ratio Beta of about 10 at a relative air ratio Lambda of 1.05. As the pressure ratio Beta is increased to about 50, this Compressor Exit Specific Net Power increases to about 1480 kJ/kg (kW/kg/s). These measures increase the system efficiency from about 49.6% at Beta of about 10 to about 53% at pressure ratio Beta of about 50 in this VAST-WS cycle with the 1990's technology compressors and turbines assumed. State of the art turbomachinery will provide correspondingly higher efficiencies.
Lower Intake and Exit Losses
Turbulence in drawing oxidant containing fluid into the thermodynamic cycle creates a pressure drop and reduces system efficiency. There are similar turbulence mixing and pressure losses on the exit. E.g., the relevant art typically assumes about a 1% pressure drop on the air intake and another 1% pressure drop at the exhaust or stack. (See, for example, Boyce, The Gas Turbine Handbook, 2003, Lefebvre, op. Cit., (1998) or Dixon, S. L., “Fluid Mechanics and Thermodynamics of Turbomachinery, 4th ed., Butterworth-Heinemann (1998), etc.) As the compressor comprises about 65% of net power, these intake and exhaust diffuser losses constitute about 1.3% of gross power or 3.7% of net power in an ultra-lean combustion system.
In some embodiments, users preferably use the preferred diluent to displace most of the gaseous excess oxidant containing fluid used as thermal diluent in the combustion system. For example, users reduce air flow by about 67% from about a Lambda of 334% of the stoichiometric rate to a Lambda of about 110% or less of the stoichiometric rate.
Consequently, users reduce the total intake and exit pressure-volume parasitic diffuser losses by about 67% to about 72% or more in preferred embodiments. E.g., from 2% to about 0.67% of gross power or to about 1.9% of net power, assuming the smaller compressor requires about 35% of gross power. Thus preferred VAST embodiments reduce the cost of intake and exhaust diffusers by about 67% to 72%, and reduce these diffuser power losses from about 3.7% of net power to about 1.9% to 1.6% of net power. I.e., this alone gives a saving of about 1.8% to 2.1% of net power.
With lower inlet and exit flows, users may reduce the intake duct size and diffuser size to accommodate the smaller resultant flows of oxidant containing fluid into the VAST Cycles. This reduces capital costs as well as space and land requirements.
In modified embodiments, users preferably increase the length and shape of the intake and exit diffusers to improve diffuser efficiency relative to relevant art designs. This reduces the pressure-volume parasitic pumping losses relative to conventional lean combustion systems.
In modified embodiments, users may add and control at least one damper or valve to control the intake flow rate into the compressor. This enables reduction of the air flow delivered, and of the compression power, such as on reduced expander power operations.
With reference to
Compressor/combustion system bypass flow may be used as an alternate or addition to using expanded combustion fluid such as for an economizer.
As with the intake and exit losses, by preferably reducing intake oxidant containing fluid flow, users similarly reduce the parasitic pumping losses through the intake gas filter in modified configurations e.g., by about 67% to about 72% or more of the conventional air intake filter losses.
With substantially lower intake flows, users preferably resize the intake filter area about in relation to the intake flow. This results in significant net present value savings due to lower filter capital costs, lower size and land costs, and very significant lower life cycle operating costs of lower parasitic pumping costs and lower filter replacement and labor costs.
With these significant savings, users preferably increase the filter cross sectional area per unit gas flow and reduce the parasitic intake filtration pressure losses and parasitic pressure-volume to about near the life cycle optimum values for the VAST cycle in modified configurations.
Filtration
By preferably reducing the intake oxidant containing fluid relative to conventional systems, users substantially reduce the amount of particulates, (fibers, dust etc.) entrained into the energy conversion system in some embodiments. E.g., by about 67% to about 72% or more relative to conventional ultra lean combustion (at 15% O2 in the exhaust).
In some configurations, users preferably reduce intake air below the conventional of about 150% or more of stoichiometric air flow commonly used in relevant art systems using water to humidify the compressed air such as the STIG, HAT, HAWIT, RWI, EvGT and other wet cycles where the amount of diluent delivered is limited by the saturation of the oxidant containing fluid. E.g., from a Lambda of about 150% where the amount of water delivered is limited by air saturation to a Lambda of about 110% or lower in some configurations. This reduces the intake air and associated filterable particulate load by about 27% compared to those relevant art wet cycles.
With reference to
In some embodiments, users preferably provide a direct contact delivery system to spray diluent into the intake oxidant containing fluid as taught in the Contactor (“191”) patent application e.g., to cool and/or filter the intake air. These preferably provide, lower filter pressure drops and lower pumping work than the relevant art. They provide direct contact Cooling Air flow. Such improved filtering is preferably sized and operated to reduce compressor fouling, reduce compressor cleaning maintenance, improve compressor efficiency and reduce life cycle costs.
Reduced Turbine Fouling
By reducing the oxidant intake flows by about 67% to 72% or more, users reduce the degree of turbine fouling caused by entrainment of particulates in the intake oxidant flows relative to ultra-lean combustion. This reduces the maintenance cleaning of turbine blades.
Compressor and Compression Cooling
With reference to
Users preferably provide surface heat exchangers between the oxidant-containing fluid and a cooler diluent-containing or other coolant fluid as shown in
With reference to
In
More preferably, as depicted in
These evaluations preferably use the configuration methods taught in the above-mentioned Hagen et al. Trifluid patent application and the Contactor (“191”) patent application to accommodate variations in the transverse distribution of the oxidant fluid velocity within the compressor. Heated diluent may be used to improve the vaporization rate while still providing cooling. In the last stage, the amount of fluid delivered may exceed the amount that can be evaporated by the exit of the compressor. The remaining fluid droplets will be smaller than droplets conventionally formed in sprays. These are preferably accounted for in configuring and controlling the combustor.
In some embodiments, the ratio of diluent delivery between the compressor and combustor is preferably controlled. More preferably, the distribution of diluent delivery is controlled between three or more locations in the compressor and the combustor. Care is preferably taken to see that the injected liquid evaporates fully in the oxidant-containing fluid stream. When shutting down the system, the compressor is preferably run without spray addition for a period of time to dry it out and reduce the probability of corrosion. As shown in
As shown in
VAST Steam Cycle (VAST-WS) with Expander Steam Cooling
In some configurations, users preferably use steam cooling of expander hot components and displace at least some and preferably all the excess air commonly used to cool blades. The excess air commonly used to cool expander hot section components such as turbine blades and vanes is often 10% to 18% of the flows through the turbine. Accordingly, in VAST cycles, providing steam cooling of blades alone enables users to reduce the size of the compressor by about 9% to 15% relative to air cooled systems.
VAST Steam Cycle with Expander Surface Steam Cooling Surface Intercooler(s)
In modified configurations, users preferably combine one or more surface intercoolers instead of steam mixing intercoolers and displace air cooling with steam cooling. The heated steam is preferably recovered from the expander hot sections and redirected upstream into the combustor. This reduces the cooling of the energetic fluid (working fluid) of conventional steam cooling. With such VAST Steam Cycle configurations, users expect about a three to four percentage point increase in efficiency relative to the VAST Steam Cycle with spray intercooling and using compressed air to cool turbine blades. e.g., users expect system efficiencies greater than 54% at 50 MW and 1300° C. with such VAST Steam Cycle configurations relative to about 51% without those measures with the component efficiency and parameter assumptions made by Traverso. i.e., about a 6% improvement in cycle efficiency for those configurations.
Diluent Supply System
Thermal Diluent/Heater
Many embodiments preferably deliver fluid water through the direct contact distributors as the thermal diluent to cool the reacting fluids and constrain the temperature of the energetic fluid. Cooler components like electronic components may use liquid water to keep them cool. Others such as the evaporator boil water to form steam. The superheater heats the steam used to recover heat from the expanded energetic fluid.
Some embodiments recycle a portion of the carbon dioxide formed by the combustion, as a thermal diluent or a component of the diluent, to constrain the combustion temperature.
Conventional lean combustion power systems use excess air as thermal diluent. The present embodiments preferably displace most of the excess air used as thermal diluent to improve thermal efficiency. In some configurations, users may recirculate some combustion gases or spent gases exiting the diluent recovery system comprising nitrogen, carbon dioxide, water vapor and some excess oxygen as thermal diluent.
Some embodiments use a low vapor pressure natural or synthetic oil as the thermal diluent in one or more of the distributed direct contactors. Synthetic thermal fluids such as fluorocarbons are used in some configurations as desired or needed for their special properties by applications.
In some embodiments, distributed contactors may provide at least one cooled (or heated) reactant and/or product to the reacting components and mix them to constrain (or boost) the temperature. In particular some measures recirculate a portion of the spent or exhaust gas including at least a portion of the carbon dioxide, water vapor, nitrogen and/or associated noble gases. Such measures substantially simplify the product separation and purification system as well as the reactant recycling system.
Storage System
In some configurations, users preferably provide a storage system to buffer one or more flows of fuel (E.g., diesel#2), thermal diluent (e.g., supply water, treated water), or oxidant containing fluid, (e.g., compressed air, enriched air, and/or oxygen.) The storage system may include tanks, pipes, reservoirs and other related vessels. Tanks are preferably provided for treated and for untreated fluids.
In configurations providing net positive water balance but no water sales, users preferably reduce the size of the water supply storage tanks relative to conventional system configurations. E.g., they provide sufficient water to start up until a positive water balance is achieved, and/or to shut down a system after a positive water balance is no longer available. These measures significantly reduce the cost and footprint for the water supply system.
In configurations providing net positive water balance with water sales, users configure the size of the treated water supply storage tanks to buffer periods of peak demand relative to quieter periods or between water shipments, e.g., with diurnal demand or periodic tanker pickups.
Pump
In providing a diluent fluid to displace conventional gaseous thermal diluent, users preferably pump liquid thermal diluent into the Heat and Mass Transfer System 6000 within the energy conversion system. See, for example,
Users preferably pump at least some of the liquid diluent into one or more of the heat recovery components, e.g one or more of the economizer, evaporator, super-heater and recuperator. Users thence duct at least some of the heated diluent upstream of the turbine outlet, into one of the oxidant containing fluid flow, products of combustion, and/or energetic fluid flow, usually upstream of the turbine. In some configurations, users provide the thermal diluent to the turbine blades, vanes and walls.
Users preferably size the liquid diluent pump(s) to provide the highest pressure needed to deliver it into the highest pressure location for the highest flow rate. This would be determined based on the highest pressure ratio for the energetic fluid in the combustor plus the excess or differential pressure needed to deliver the diluent through the direct fluid contactors, plus sufficient to overcome the pressure losses between the pump(s) and the combustor.
Diluent Treatment System
Thermal Diluent Filtration
With reference to
Where the VAST Cycles are configured with Trifluid Combustors, diluent spray into the oxidant containing fluid or other application of direct contactors, care is preferably taken to filter particulates from fluids that will be injected through distributed direct fluid contactor tubes, as taught in the above-mentioned Hagen et al patent applications.
Users preferably provide maximum orifice filters in the fluid treatment sections, to remove particulates from the thermal diluent (e.g., water) larger than a desired size, that are capable of clogging the distributed contactor orifices, to a desired high probability. Such particulate removal benefits the system by removing components from the thermal diluent that could foul the turbine (e.g., suspended particulates in water.) This improves average turbine efficiency and availability, and reduces maintenance and repair costs.
Thermal Diluent Treatment
To preserve the service life of hot gas path parts, gas turbine manufacturers commonly prescribe limitations on contamination in the hot gas path to preserve their warranties. Similar values are recommended to constrain hot path corrosion.
Of most concern are trace metal contaminants, primarily vanadium, sodium, potassium, lead, and calcium. These contaminants can produce corrosive products of combustion. e.g., sodium sulfate, sodium vanadates, and vanadium pentoxide. Limits on these metals (typically in the 0.5-2 ppm range) are typically prescribed for each potential source of contaminates—air, water, and fuel.
With normal air filtration and proper operation to provide minimal carryover from inlet air or evaporative coolers, air sources are small and are typically within such prescribed concentration limits except in harsh environments. Natural gas sources in regulated markets are not known to contain these trace elements in quantities sufficient to be of concern. Thus with filtered air and natural gas, such contaminants are typically not of major concern for VAST Cycles.
Liquid fuels from most sources do contain high enough levels of contaminants to be of concern, particularly of vanadium. Thus liquid fuel treatment to reduce the trace elements to prescribed levels is typically included to assist in meet these contamination levels, regardless of recovery and reuse of diluent. For cycles such as the STIG and HAT cycles where more diluent is used than is recovered, ongoing treatment of both makeup water and recovered diluent may be required continuously.
Diluent Treatment in VAST Cycles
In most VAST Cycles, the system is preferably configured and operated to recover more diluent than is delivered into the oxidant and energetic fluid flows upstream of the expander 5100 exit. This eliminates the need for makeup water in most circumstances. VAST Cycles may recover more water than is desired to be recycled, generating makeup water to replenish other water losses. (Some makeup may be needed in situations where high water losses in leaky users heat applications exceeds the VAST Cycle excess water recovery capabilities.)
With clean fuels such as natural gas, and well filtered air intake, further treatment of the recovered and reused diluent appears unnecessary in typical VAST Cycles (See Table 6). This conclusion is based upon applying one gas turbine manufacturer's published contaminant limits and assuming all gas path contaminants from all sources end up in the recovered diluent (a very conservative assumption.). The general formula used to estimate the flows is: (A/F)Xa+(W/F)Xw+Xf<Table 1 limit
Where Xa, Xw, Xf are the contamination limits for air, water, and fuel respectively, and W is the injected water flow and A, F are the air and fuel flows.
The results show that using natural gas, there is sufficient excess diluent produced by combustion and recovered to dilute the intake contaminant concentration enough that the recommended gas path contaminant limits are not exceeded. Thus no further diluent treatment to decrease contaminants may be needed in some embodiments beyond the concentration control by excess water discharge or “blowdown”.
Where liquid fuels (or gas fuels) with sufficient contaminants (See Table 7) are used or where highly contaminated inlet air conditions exist, treatment of the recovered diluent may be desired to reduce flows to the desired levels. Mixed bed demineralizers may be used as the treatment of choice to remove the contaminants. Regeneration rates would be correspondingly low due to the low contamination levels.
*GEK 101944 Table 2
(A/F + 1)/51
0.05
50.0
0.05
50.0
0.05
025.0
0.05
500.0
0.05
128.0
0.05
128.0
0.05
64.0
0.05
1280.2
*GEK 101944 Table 2; GER 3428 Table 22
In some embodiments, users more preferably provide “side-stream” treatment to treat just some of the diluent sufficient to control the contaminant levels. This provides a benefit of reducing the pumping work that would otherwise be required to push all the diluent through a treatment system. Excess diluent discharge plus side-stream treatment are preferable reduce diluent treatment costs.
Where the contaminant flows (or concentrations) delivered into the expander via recycled thermal diluent are substantial and life cycle costs can be reduced by reducing the concentrations or where such reductions in contaminant flows (or concentrations) are required, users preferably provide further treatment of the diluent in the treatment system 2300 to reduce those contaminants in some configurations.
Similarly, when treated water is desired or needed, it is preferable to treat the excess diluent flows formed to reduce these concentrations to the levels desired or needed. In some situations, the excess water available may be purified and sold for revenue, turning water treatment from a cost into an income generation source.
Water treatment such as by mixed-bed demineralizers may be used. Other types of treatment such as reverse osmosis and other types of demineralizers may be used where the chemistry is suitable. These treatment methods remove chemicals that are incompatible with the components into which it will be injected. Such as the turbine hot path components which may include one or more of the turbine blades, turbine vanes and shroud.
Users preferably filter the condensed diluent through one or more filters to reduce the particulate load. They preferably use a uniform orifice filter sized smaller than the orifices in the distributed contactors to prevent the diluent particulates from contaminating those orifices.
Coarse filters can be duplex type such that filter media can be cleaned or replaced on-line when other filter in the duplex arrangement is used. Automatic backwash filters media filters down to 100 microns may be used in an embodiment.
Fine filters may be used on some embodiments to filter particulates greater than about 10 microns. These filters may include media filters such as sand and anthracite.
In some configurations, users preferably reduce the CO2 concentration in the diluent condensate prior to subsequent pH treatment. Users preferably provide a recompressor and pull the pressure after the condensor down to sub-ambient pressures as needed or desired to reduce carbon dioxide in the diluent and/or to improve system thermoeconomics. In some configurations, the recompressor provided with the VAST Cycles provide sufficient carbon dioxide stripping in itself.
Some of the acid gases formed dissolve and are recovered with the condensed thermal diluent. Such as some portion of nitrogen dioxide, sulfur dioxide and carbon dioxide etc. The enhanced temperature control in VAST Cycle combustors significantly reduce the concentrations of the nitrogen oxides and carbon monoxide formed during combustion (NOx and the CO) compared to conventional relevant art, and similar to levels of catalyzed combustion. Users preferably control NOx and carbon monoxide below respective prescribed limits by controlling diluent distribution to control combustion temperatures within desired upper and lower ranges, and by controlling residence time in the combustor sufficient to oxidize carbon monoxide while keeping residence time below levels that cause substantial NOx formation.
In VAST Cycle configurations providing a net positive water balance, the concentration of these acidic components and dissolved contaminants will come to equilibrium in proportion to the rates formed, divided by the rate of water discharged. Users preferably configure system from components sufficiently acid resistant to operate with these acid component concentrations.
In systems requiring acidic treatment, users preferably provide ion exchange membranes or similar acid treatment system, sized as needed to treat the acidic flows. Users expect to size the recycled diluent treatment systems significantly smaller and less expensively than conventional systems because of the lower contaminants formed and because a portion are discharged with the excess water formed.
Corresponding to smaller treatment requirements and smaller treatment equipment, users expect to spend significantly less to treat and recycle condensate than in conventional relevant art “wet” cycles. Most to all external makeup water requirements are preferably eliminated in most configurations.
Combustion System
Combustor and Combustion Chamber
With reference to
Hot Section/Combustor Exit/Turbine Inlet Temperature.
With reference to
The temperature profile across a turbine blade may be two to three hundred degrees Celcius. Yet the life of turbine blades reportedly is doubled or halved when the energetic fluid temperature is reduced or increased by about 10K (18° F.) at a material thermal-stress design limit. E.g., with reference to
The VAST cycle preferably uses a diluent combustor operable to control the delivery of diluent and more preferably the spatial distribution of diluent, to more accurately control the magnitude of the hot fluid Tv at the control location Lv. In some embodiments, they preferably provide a Ginter VAST combustor such as taught in Ginter '666.
In some embodiments, users preferably configure the combustor with high accuracy fluid delivery and control. They more preferably configure and control the diluent delivery upstream of and near a streamline passing through, adjacent to, or thermally near the fluid control location Lv. With reference to
For example, the VAST Trifluid combustor disclosed in the Trifluid patent application is preferably used as providing substantially more accurate configuration and flow control over the diluent containing fluid, and preferably also the fuel containing fluid, especially when one or both are liquid. The Trifluid combustor preferably uses one or more direct contactors comprising numerous orifices distributed across one of the oxidant containing fluid, the fuel containing fluid, and the hot fluid, upstream of the control location Lv. One or more of the orifice spatial distribution, the orifice size distribution, and orifice orientation distribution in one or more direct contactors are preferably configured to deliver one or more of the diluent containing fluid and fuel containing fluid with respective prescribed spatial delivery distributions in a plane transverse to the fluid flow. Similarly, the VAST combustor provides substantially more accurate control over the ratio of oxidant to fuel by monitoring the residual oxidant concentration while operating near stoichiometric conditions. In some embodiments, the residual oxidant concentration is controlled, e.g., not to exceed a maximum oxidant level, such as 5% by volume.
To control the component temperature Tc at the component control location Lc at a radius Rc, users preferably control the fluid temperature Tv of the thermally proximate or coupled hot fluid at location Lv by controlling delivery of diluent containing fluid on or near a streamline upstream of the fluid control location Lv. A thermal sensor may be mounted at or near the fluid control location Lv to monitor the temperature Tv. The thermally proximate component control location Lc may be in the hot fluid near or adjacent to the thermally coupled component. These locations Lv and Lc may be located in a plane transverse to the fluid streamline at Lv, e.g., at a similar radius Rc.
The thermally proximate component control location Lc is preferably located on a component adjacent to the hot fluid. The related component control location temperature Tc may be monitored by a surface mounted thermal sensor. The control location Lc is more preferably located within the component near the hot fluid where it is thermally proximate or coupled to the temperature of the adjacent hot fluid Tv. This component control location Lc may be near the interface between the component and a protective or thermal barrier coating between the component and the energetic fluid. The related component control location temperature Tc may be monitored by an embedded or protected thermal sensor. A plurality of sensors may be used, e.g., with rapid control from fluid sensors near Lv, and longer term control from embedded sensors near Lc.
The diluent fluid delivery is preferably configured and controlled relative to the oxidant containing fluid and the fuel containing fluid to control the fluid temperature Tv at the fluid control location Lv, to not exceed a prescribed fluid temperature limit, Tw to greater than a prescribed probability. This fluid control location temperature design limit Tw is preferably prescribed as a desired maximum mean design temperature Tz of the hot component thermally proximate or thermally coupled to the control location, less a safety margin temperature difference DTv. This temperature difference DTv is preferably selected as a probability or safety parameter S times the standard deviation of the fluid temperature Tv at the control location Lv.
In embodiments comprising thermal cooling proximate to the control location, the upstream diluent fluid delivery control is preferably adjusted to accommodate the temperature difference between the hot fluid and the control location due to the thermal cooling. For example, with internal and external fluid cooling of a turbine blade, this may include one or more of the temperature gradient in the fluid near the component, cooling fluid flow over the component, effective fluid thermal resistance adjacent to the component, thermal resistance of an insulating coating on the component, thermal resistance within the component, the temperature gradient within the component, thermal resistance of a cooling fluid near the component wall, thermal temperature gradient in the cooling fluid, and radiation to/from the component surface, including the respective heat capacities, resitivities, thermal diffusivities, energetic fluid temperature, absorptivity, emissivity, and cooling fluid temperature.
With reference to
With the improved upstream diluent fluid configuration and control, more preferably, a safety parameter Sc is selected at the component location Lc, to prescribe an upper component control temperature limit Tg with a component temperature safety margin DTc(Rc) below the desired mean maximum design component temperature Th, such that the component temperature Tc not exceed the upper component control temperature limit Tg to a prescribed component temperature safety probability. More preferably, the safety parameter Sc is selected such that the cumulative failure hazard function H(S) for the component does not exceed a prescribed failure probability at the location Lc over a prescribed component life.
With reference to
A control location Ld is more preferably selected at a design radius Rd corresponding to a control location design temperature Td=Tg(Rd) where the thermally proximate component material is at the thermo-mechanical safe design stress at that temperature. The temperature Td is preferably selected as the corresponding mean maximum design temperature at that location Tz(Rd) minus the prescribed temperature difference DTv(Rd) based on the corresponding safety parameter Sv(Rd).
As described therein and herein, users preferably configure the combustor and control the thermal diluent flows to control one or more of the following parameters: Control the Combustor Outlet Temperature and/or Turbine Inlet Temperature Distribution or temperature “profile factor.” This reduces the deviations from prescribed temperature distributions and increases respective mean temperatures and efficiencies. Control the circumferential temperature “pattern factor,” reducing variations and improving the mean temperatures. Improving fluid delivery configurations and control accuracies, thereby reducing fluid and temperature uncertainties. Cooling liners with diluent, thereby reducing or eliminating oxidant cooling of liners and related compression work.
Transverse Safety Margin & Temperature Limit Distributions
With such a preferred combustor and the fluid configuration control measures provided, users preferably obtain substantially improved upstream fluid flow control, and thus improved uncertainty in temperature control of the hot fluid.
The safety parameter Sv at the fluid location Lv is preferably selected with the improved diluent fluid configuration and control to prescribe an upper control temperature limit Tw at radius Rv with a temperature safety margin DTv(Rv) below the desired mean maximum design fluid temperature at the fluid control location Tz(Rv), such that the temperature Tv will remain below (or not exceed) Tz to a prescribed temperature safety probability Pw. Most preferably, a safety parameter spatial distribution Sv(R) is prescribed, corresponding to the reduced transverse uncertainty distribution from the improved fluid configuration and control, to prescribe a transverse fluid temperature safety margin DTv(R). DTv(R) is then subtracted from the maximum mean fluid temperature distribution spatial Tz(R) to obtain the transverse hot fluid upper temperature limit spatial distribution Tw(R) across the hot section. The upstream diluent is preferably configured and controlled to maintain the fluid temperature along a plurality of fluid control locations Lv(R) to remain below the upper fluid temperature limit spatial distribution Tw(R) such that the maximum mean fluid temperature distribution Tz(R) is not exceeded to the probable temperature safety probability Pw.
More preferably, a plurality of component safety parameters are selected, preferably as a component safety parameter spatial distribution Sc(R), for the plurality of component locations Lc(R). These component safety parameters Sc(R) may be preferably used to prescribe a plurality and preferably a spatial array of corresponding component control temperature safety margins Dtc(R) for a probable component temperature safety probability Pg. These component safety margins DTc(R) are preferably subtracted from the plurality or array of maximum mean component temperatures Th(R) to form a plurality or distribution of upper component temperature limits Tg(R). In some embodiments, the fluid safety parameter distribution Sv(R) is configured in relationship to the component safety parameter distribution Sc(R), preferably accounting for thermal damping, in internal cooling, and external cooling as appropriate. The upstream diluent delivery is preferably controlled to maintain component temperature distribution Tc(R) below the component temperature limit distribution Tg(R) such that the component temperature Th(R) is not exceeded to the temperature safety probability Pg.
Controlling a Transverse Temperature Distribution
Users more preferably control the delivery of diluent containing fluid upstream of a plurality of fluid control locations to control respective fluid location temperatures thermally proximate to those control locations to be less than or equal to respective prescribed control location temperature limits, with greater than prescribed probabilities. The control locations are preferably selected in transversely distinct streamlines, e.g., displaced transversely across the fluid flow. In some embodiments, a near component control location Ln is preferably selected at a radius Rn on the near side (towards the Inner Radius) of one of the design location Ld, the midpoint Lm, or the peak temperature location Lp. A far component control location Lf is preferably selected at a radius Rf (nearer the Outer Radius) from one of the design location Ld, the midpoint Lm, or the peak temperature location Lp. One or more of temperature control locations Ln, Lc, and Lf are preferably selected within +/−5% of a span (Outer Radius−Inner Radius) from one of the locations Lm, Lp, and Ld, lying in a plane transverse to the streamwise flow of products of combustion in one of the combustor and the expander.
The diluent fluid delivery may be configured and controlled upstream of at least one and preferably a plurality of component control locations Ln, Lc, and Lf at or near the midpoint Lm. Preferably, the upstream diluent fluid delivery is controlled to control a plurality of component temperatures Tn, Tc, and Tf at component locations Ln, Lc, and Lf about the peak temperature location Lp. More preferably, the upstream diluent fluid delivery is controlled to control a plurality of component temperatures Tn, Tc, and Tf at component locations Ln, Lc, and Lf about the design stress location Ld.
In some embodiments, the upstream diluent delivery is preferably configured and controlled to constrain and preferably control a curvilinear fluid temperature spatial distribution Tv(R) to remain below a curvilinear fluid control limit spatial distribution Tw(R). More preferably, the upstream diluent delivery is preferably configured and controlled to constrain and preferably control a curvilinear component temperature spatial distribution Tc(R) to remain below a curvilinear component control limit spatial distribution Tg(R). In some embodiments, at least one and preferably a plurality of fluid temperature sensors are preferably used to monitor the temperature of the hot fluid at or thermally proximate the fluid control locations Lv(R). More preferably, some embodiments use at least one and preferably a plurality of component temperature sensors to monitor one and preferably a plurality of thermally coupled component temperatures Tc(R) at or near component control locations.
In a similar fashion, users preferably configure and control the transverse temperature distribution in the hot fluid to be offset from a desired transverse distribution of temperature entering the expander such as the temperature profile across a prescribed turbine vane or turbine blade from hub to tip. The transverse distribution of temperature in the energetic fluid is further preferably configured as the desired mean maximum transverse distribution of expander inlet temperature less the safety margin temperature difference of desired safety parameter times the spatially local uncertainty in the transverse distribution of the uncertainty in the component spatial temperature distribution Tv(R).
In some embodiments, the diluent is preferably controlled together with one or both of oxidant delivery and fuel delivery to control the hot gas temperature spatial distribution Tv(R), and/or the component temperature spatial distribution Tc(R). The oxidant/fuel composition may also be controlled, and preferably the composition of oxidant, fuel and diluent delivered to the combustor. One or more of fluid temperature, pressure, and humidity may be monitored and used together with controlling one or more fluid flows, or fluid or component temperatures.
By achieving a lower transverse distribution of spatial and temporal uncertainty and lower safety margin temperature difference DTv(R) across the expander entrance, users preferably configure a higher allowable transverse distribution of temperature in the energetic fluid entering the expander than the typical relevant art safety margin temperature difference DTr(R). With such a higher transverse distribution of temperature, users may achieve a higher mean energetic fluid temperature Tv compared to the relevant art mean energetic fluid temperature Tr. This higher mean temperature Tv provides a higher thermodynamic efficiency in the energy conversion system.
The mean hot fluid temperature Tv is preferably controlled near the Combustor Exit or Outlet to control the Combustor Outlet Temperature (COT). The mean hot fluid temperature Tv is more preferably controlled near the Turbine Inlet Temperature (TIT). This may be weighted by the area transverse to the flow. The mean fluid temperature is more preferably based on the mass flow weighted mean temperature. This mean Tv may be selected at one or more of industry temperature measure locations such as the inlet Temperature near the first vane inlet, the ISO TIT, or the Throat Temperature.
Heated Component Cooling System
Cool to warm cooling fluid is preferably used to first cool thermally sensitive components. With reference to
A portion of the coolant fluid may be water. Other coolants such as glycol or fluorinated components may be used and the heat recovered may be exchanged with water. Users then preferably use direct fluid contactors to deliver the heated diluent (e.g., water and/or steam) into the combustion chamber 4100. This significantly reduces the thermal losses from the combustor.
Users preferably provide a combustor wall or “liner” capable of handling the constrained combustion provided by the VAST cycle operating near stoichiometric combustion together with added thermal diluent cooling, such as taught in the above-mentioned Hagen et al. patent applications. Users may provide a liner cooling system to additionally cool the combustor liner and recover this high grade heat, such as shown in
Users may eliminate delivering of some of the excess oxidant containing fluid delivered as thermal diluent or coolant through the combustor liner walls. (e.g., compressed air and/or steam.) They preferably eliminate most to all of this diluent delivered through the combustor liner. This provides the benefit of improving the temperature distribution across the combustor by not cooling the energetic gas with such liner cooling thermal diluent. (i.e., a more controlled temperature profile, or providing a “Profile Factor” closer to unity.) Improving the “Profile Factor” in turn improves the system thermal efficiency.
In modified configurations, users provide thermal diluent to cool the walls of the combustor liner as desired or needed in some configurations. Further details for such combustor cooling systems are provided in the Hagen et al. '047 patent application, with particular reference to
Where needed or desired, users preferably provide thermal diluent to cool the walls of the combustor-turbine transition zone in some configurations similar to the methods to cool the combustion chamber liner. The resulting heated diluent is preferably delivered upstream into the combustor to provide more controlled and preferably more uniform temperature profiles and recover this heat rather than dilute and cool the energetic fluid.
Fuel Delivery System
Fluid Fuels, & Diluents/Heaters
VAST Cycle embodiments preferably utilize embodiments of Trifluid combustors capable of using at least one of a wide variety of fluid fuels or fluidized fuels as taught in the above-mentioned Hagen et al. patent applications, and as follows. Some embodiments preferably provide for multiple fuels selected from one or both of liquid and gaseous fuels, e.g., natural gas, propane, producer gas, diesel fuel, methanol, ethanol, and/or syncrude. This reduces economic risks from fluctuations in fuel price or availability. Some configurations may use multiple liquid fuels. Trifluid combustors may improve dynamic performance using liquid fuels. Other combustors capable of using one or more fuels may also be used.
Some embodiments provide for mixing more than one fuel to reduce costs associated with delivery and mixing fuels of differing heating values to reduce costs of one or more parameters of costs of fuel, delivery, and storage, cost of fuel treatment, and cost to mitigate such affects as polymerization. Pumps, compressors, and control valves are selectively used to provide flow and required pressure as desired for the combustion system. (See
Fuel Types
Some embodiments of the invention may use one or more of a wide variety of liquid fuels. For example:
Liquid petroleum fuels and distillate fuels, including aviation fuel, gasoline, kerosene, diesel fuels, fuel oils, bunker oil, crude oils, bitumen or tar sand oils, syncrude, shale oils, heavy fossil liquids, coal derived fuels, and liquefied natural gas (LNG).
Vegetable oils, including palm oil, coconut oil, soybean oil, rape seed oil, canola oil, and peanut oil. Esters of such vegetable oils, e.g., methyl, ethyl, propyl or butyl esters. Pyrolysis fuels formed by heating biomass or fossil hydrocarbons. Oxygenated fuels, including methanol, ethanol, and MTBE. Non-carbon liquid fuels, including liquid hydrogen, liquid ammonia.
Some embodiments of the invention may use one or more of a wide variety of gaseous fuels. For example:
Most fossil or petroleum based gas including natural gas, coal bed methane, propane, and butane.
Producer gas or synthesis gas made by gasifying fossil fuels with air, oxygen enriched air, or oxygen, such as from coal, tar sands, and heavy fuels, including varying quantities of carbon monoxide and hydrogen, with varying additional portions of methane and other hydrocarbons, and optionally residual unreacted fuels and/or diluents including nitrogen and carbon dioxide.
Producer gas or synthesis gas from gasifying biomass in air, oxygen enriched air or oxygen. Hydrogen, or other non-carbon gaseous fuel etc. Biogas or other gases emitted from biomass.
Fuel with Water
Some embodiments provide fluid water with one or more of the fuels. For example:
Oxygenated fuels, such as ethanol and methanol, which dissolve water.
Fuel water emulsions, including water emulsified with any of the above liquid fuels, optionally with emulsifiers or surfactants, e.g., “Orimulsion”® or MSAR™.
Water mixed with a fuel, such as water droplets within fuel, and/or fuel droplets within water. In some configurations, water comprising amounts of fuel may delivered as diluent in the energy transfer system. E.g., water contaminated with one or more fuels such as diesel fuel or bitumen is preferably sprayed into the combustor where the fuel combusts with oxygen and evaporating water cools the combustion.
Gaseous fuel mixed with water mist, water vapor, or steam.
Mixtures of the above fuels.
Suspended Solid Fuels
Some embodiments preferably suspend, entrain or fluidize solid fuel particles with the oxidant containing fluid. For example:
Any finely comminuted coal entrained or fluidized in air or fluid fuel including pulverized brown coal, bituminous coal dust, anthracite coal dust
Any finely comminuted biomass entrained or fluidized in air or fluid fuel including sawdust, wood dust, activated carbon dust, flour, rice husks, comminuted corn components, etc.
Fuel Treatment System
With reference to
Fuel Filtration
As described in the Hagen et al. patent applications, users preferably provide filters to remove particulates from the fluid fuel supplied. They preferably provide maximum orifice filters that remove particulates capable of clogging the distributed contactor orifices, to a desired probability, such as uniform filters with orifices sized about ⅔ the orifice size in the perforated direct contactors. Such particulate removal benefits the system by removing fuel components that could foul the turbine. This improves average turbine efficiency and availability, and reduces maintenance and repair costs. Fuel may be washed with water and/or diluent to remove one or more salts.
In modified embodiments, users may heat the fuel to improve performance. For liquid fuels, preheating to a selected temperature range may reduce deleterious effects of polymerization and coking. For gaseous fuels adding heat can eliminate entrained moisture that could harm the fuel-delivery system or the combustion system components. Heat may be added from one or more of the following: energetic fluid, expanded fluid, compressed oxidant fluid, heated diluent fluid, vaporized diluent, superheated diluent, and/or heated coolant fluid. One or more of these heated fluids are preferably mixed with the fuel using one or more direct contactors upstream of delivery into the combustor. The fuel may be heated using internally heated components such as the generator.
Expansion System
Turbine
Where mechanical energy or electrical energy is desired, users preferably deliver energetic fluid to an expander or expansion device, and expand the energetic fluid from a higher pressure to a lower pressure. They may use some of the mechanical energy produced to drive a generator, and then exhaust the expanded fluid to a diffuser (or stack). (See e.g.,
In larger systems, users preferably expand the energetic fluid through several expansion stages in series as depicted in
With reference to
With reference to
By providing a recompressor with the VAST-WS Cycle, this gross Turbine Expansion Ratio is preferably configured from about 37 at a total oxidant compression ratio Beta of about 10, to about 102.8 at an oxidant compression ratio Beta of about 44. Higher compression ratios may be used, such as a compressor beta of 80 to 160 which may give overall compression ratios of 120 to 400. Thus, the addition of the recompressor substantially increases the total Turbine Expansion Ratio without the use of ultra high pressure components. It further enables compression at lower temperatures, enabling closer compressor tolerances.
This overall turbine expansion ratio appears to vary approximately with the desired inlet oxidant compression ratio. More preferably, the recompression ratio is configured from about 3.7 at a compressor ratio of about 10, to about 2.3 at a compressor ratio of about 44, to about 1.5 at a compressor ratio of about 160.
Users preferably configure the overall gross Turbine Expansion Ratio (Beta Turbine) to help achieve the desired or improved performance with a VAST Steam Cycle (VAST-WS). Table 8, Table 9, and Table 10 show a configuration (the method of configurations is shown in Table 11 and
*This is added for generalities but may be removed in this configuration.
0.01
0.782
0
0.207
0.006
0.762
0.001
0.231
0.052
0.749
0
0.199
0.93
0.07
0.884
0.116
All Other Streams are Pure Liquid H2O
15
1.01
15
3
25
41.8
15
1.01
25
41.88
160
1300
1300
160
156.9
100
156.9
1.01
15
1.01
15
3
*This is added for generalities but in this configuration may be removed.
0.01
0.782
0
0.207
0.006
0.762
0.001
0.231
0.93
0.07
0.884
0.116
All Other Streams are Pure Liquid H2O
15
1.01
15
3
25
83.96
160
1300
1300
160
82.55
100
82.55
1.01
15
1.01
This Turbine Expansion Ratio (Beta turbine) is preferably selected to be about 76.1 for a VAST-WS cycle with a combined intake compressor pressure ratio of about 30. With a VAST Steam cycle (VAST-WS), the combined pressure ratio is more preferably adjusted to about 25 to improve economic performance to near optimum (the configuration of a VAST-WS at a compression ratio of 25 is shown in Tables 15-17 with the method of configuration in Table 18 and
*This is added for generalities but may be removed in this configuration.
0.01
0.782
0
0.207
0.006
0.762
0.001
0.231
All Other Streams are Pure Liquid H2O
15
1.01
15
3
25
35.75
15
1.01
25
35.75
1300
1300
86.7
86.7
15
15
With reference to
Excess Water Injection Losses vs Drag Losses
Drag pressure drops across one or more components and/or parasitic pumping loses reduce the effective oxidant compression ratio and then net turbine expansion ratio available to recover mechanical power. Users preferably reduce excess oxidant containing fluid and reconfigure energy conversion system to reduce the size of one or more of the related components relative to the net power output, such as one or more of the intake diffuser, intake oxidant fluid filter, intake water entrainment spray, intra-compressor water spray, inter-compressor water spray, inter-compressor surface intercooler, diffuser, combustor components including the diffuser, fluid delivery and equilibration zone (“transition piece”), superheater, evaporator, economizer, preheater, condensor, cooler, and diffuser. To reduce pressure drop, users preferably configure a water spray oxidant intake filter such as taught in the Hagen et al. '191 patent application. They also preferably configure a direct contact condensor to reduce pressure drop and improve thermal performance, such as taught in the Contactor (“191”) patent application.
Multi Axis Turbines
In some embodiments, users preferably configure a first compressor turbine and a first compressor on a first shaft. They preferably position a power turbine and generator on a second shaft. In embodiments using recompressors, users preferably configure a recompressor on the first shaft together with the compressor turbine and the compressor. They preferably configure the combination together with a motor that can control the speed of the compressor-recompressor combination. In other configurations, the recompressor and motor may be configured on a separate shaft.
Such combinations provide flexibility in varying the compressor-turbine rotational speed and associated flow rates of oxidant containing fluid and combustion. Since it does not have to drive a compressor, the power turbine is preferably configured to provide the torque and speed desired for an application. For example, it may be configured to deliver a very high torque at low speed applications. Similarly, the turbine and generator may operate at a fixed speed on a separate shaft proportional to the grid speed.
Rotational speed of at least one turbine may be varied up or down, to operate the turbine under more efficient parameters. For example the speed of the power turbine may be adjusted according to the desired output shaft speed. Similarly, the speed of the recompressor may be varied to control the net turbine expansion ratio.
In some configurations, users may provide an adjustable speed drive between the power turbine and the output drive shaft. This may accommodate most of the speed variation while keeping the turbine near its best efficiency for the desired power.
The power of the compressor turbine is preferably sized to the power required for the compressor. This may range from about 65% to about 72% smaller than conventional lean combustion compressor turbines at 15% O2 exhaust concentration per compressed air flow rate. When users add the recompressor, the compressor turbine is preferably sized to the combined power drawn by the two compressors on that first shaft.
In some embodiments, users preferably configure a second (low pressure) compressor turbine or electrical motor on a third shaft together with the inlet low pressure compressor. In such configurations, users preferably configure the recompressor on this third shaft while placing the high pressure compressor on the first shaft with the high pressure compressor turbine. The high pressure compressor turbine and low pressure compressor turbine or electrical motor are preferably configured to the corresponding power required by the associated compressors. Users preferably use the power turbine on a separate second shaft either directly or with the generator.
Some embodiments connect a mechanical device to the turbine, with or without an intermediary drive. Mechanical device may consist of at least one vessel propeller, Cycle ReCompressor, and Cycle pump in addition to compressors.
Turbine Specific Net Power
In some embodiments, users preferably increase the net power per unit mass flow or “specific power” of the turbine expander, i.e., net turbine power kW per turbine mass flow (kg/s)=(kJ/s)/(kg/s)=(kJ/kg). By increasing the power that can be generated through the same turbine, the VAST cycle reduces the capital cost to generate a desired power. The benefits of reduced specific capital become an increasingly large portion of the cost of power as the number of hours of use per year decrease. (E.g., $/kW, or the cost of energy, ¢/kWh or $/MWh, such as for peaking power and standby emergency generators.)
Users preferably configure the VAST Cycles to provide the following features and benefits in some configurations:
Increase Turbine Specific Power per Stage by evaporating diluent per stage.
Provide higher specific heat capacity in the energetic fluid by increasing water fraction and reducing the excess nitrogen and oxygen.
Provide higher specific enthalpy in the energetic fluid by increasing the specific heat capacity and/or the temperature of the energetic fluid.
Lower mass flow rate for a given net power rate by reducing the air/fuel ratio Lambda and increasing the water/fuel ratio relative to a Brayton cycle.
Higher power for a given temperature, mass flow rate, pressure by increasing the water/fuel and decreasing the air/fuel ratio Lambda versus a Brayton cycle.
Higher net Peak Specific Power for the same expander by reducing lambda and/or more closely matching the transverse temperature distribution to the prescribed transverse temperature distribution.
Higher Turbine Expansion Ratio
Net Turbine Expansion Ratio
In some embodiments, users preferably increase the turbine expansion ratio through which the energetic fluid is expanded. I.e., the ratio of the high pressure at the turbine inlet to the low pressure after the turbine exit.
In some configurations users replace most of the excess oxidant and compressed gaseous thermal diluent with a vaporizable diluent pumped in as a liquid. They preferably resize compressors and turbines accordingly as described herein. (e.g., they may displace about 15%, preferably 30%, more preferably displace about 65% to 85% or more of compressed air by pumping in water.) This gives the benefit of a very substantial increase in the Net Turbine Power per Turbine mass Flow Rate of energetic fluid through the turbine or Net Specific Turbine Power (kW per kg/s flow or kJ/kg energetic fluid measured at the turbine inlet.) (See, for example,
For example, with VAST Steam Cycle (VAST-WS), with steam and water heat recovery, the Net Turbine Power per Turbine mass flow the Net Turbine Power per turbine mass flow is about 843 kJ/kg (kW/kg/s), at an air pressure ratio Beta of about 30 (near the economic optimum), with the sample industrial 50 MW 1300° C. aeroderivative turbine. This ranges from about 791 kJ/kg at a air pressure ratio Beta of about 10 to about 852 kJ/kg at an air pressure ratio Beta of about 40.
Similarly, with VAST-W (VAST Water Cycle) with only water heat recovery, the Net Turbine Power per Turbine mass flow the Net Turbine Power per turbine mass flow is about 847 kJ/kg (kW/kg/s), at an air pressure ratio Beta of about 30 (near an industrial economic optimum), with the sample industrial 50 MW 1300° C. aeroderivative turbine. This may range from about 764 kJ/kg at an air pressure ratio Beta of about 10 to about 851 kJ/kg at an air pressure ratio Beta of about 40. This net specific turbine power drops back to about 848 kJ/kg at a pressure ratio Beta of about 58 in this example.
In some embodiments, users preferably displace turbine blade air cooling with water or steam, or utilize no turbine blade cooling. The VAST Steam Cycle (VAST-WS) configured with steam and water heat recovery but no air cooling achieves a higher thermal diluent/oxidant flow (water/air) ratios of about 41% to about 44% for pressure ratios Beta of about 50 to about 10 respectively. Consequently, this configuration achieves a very substantially higher Net Specific Turbine Power.
This VAST-WS embodiment without blade cooling achieves a Net Specific Turbine Power of about 980 kJ/kg (kW/kg/s) at a pressure ratio Beta of about 30, near the industrial economic optimum. This Net Specific Turbine Power ranges from about 912 kJ/kg at a pressure ratio Beta of about 10 to about 993 kJ/kg at a pressure ratio of about 50.
By comparison with the relevant art, the most similar HAWIT cycle has a Turbine Specific Net Power of about 612 kJ/kg (kW/kg/s) at similar conditions. (i.e., the gross power of the turbine less all pumping work in compressor(s) and pump(s) divided by the fluid mass flow exiting the turbine.) I.e., the VAST-WS has about 38% higher Turbine Specific Net Power. Similarly a single pressure STIG cycle configuration may have a Turbine Specific Net Power 533 kJ/kg. This gives the VAST-WS at that air/fuel ratio an advantage in the Turbine Specific Net Power of about 58% over this STIG cycle configuration. These parameters provide very substantial thermoeconomic benefits.
Similarly the high Net Specific Turbine Power of 980 kJ/kg for the VAST-WS without blade cooling and with no air cooling is about 60% higher than the HAWIT cycle and 84% higher than the STIG cycle in this 50 MW industrial aeroderivative turbine example at this air/fuel ratio.
Note also that VAST Cycles can utilize substantially higher ratios of thermal diluent added/oxidant containing fluid flow (at the compressor intake) (e.g., total water added/total compressed air flow). E.g., from 29% to 40% for the examples calculated with air cooled turbine blades at turbine inlet temperatures of 1300° C. By contrast the four relevant art cycles STIG, HAT, RWI, and HAWIT have water/air ratios generally ranging from 12% to 23% for typical air pressure ratios of 20 to 40. (Assuming full cycle redesign enabling those levels of additional diluent to be added.) Thus VAST cycles preferably provide more than 26% total water added/total compressed air flow at about 1300° C. At lower turbine inlet temperatures (TIT), these proportions of water/air further increase.
Turbine Requirements
High temperature gas turbine components desire low levels of ions in the energetic fluid such as sodium and vanadium to avoid component damage. They prefer low levels of particulates to avoid fouling the turbine vanes and blades which reduce efficiency. These deleterious components come from the intake oxidant containing fluid, the fuel and the thermal diluent. (E.g., compressed air, diesel fuel and water.)
Component Cooling & Recycling Cooling Heat
Users preferably provide thermal diluent cooling to one or more heat generating components (see
The turbine-generator drive system is a substantial source of thermal losses. Users preferably recover some of the heat generated in the drive system and recycle it using the thermal diluent in some embodiments.
Variable speed electronic power converters/controllers typically achieve about 95% to about 96% efficiency, e.g., in microturbine power systems. Consequently, about 5% to 4% of the gross power generated by the generator is converted to heat. Conventional power conversion systems typically provide air cooling to maintain the temperature of the electronic power converters. The fan pumping power forms a significant parasitic loss and reduction in efficiency.
Instead, with VAST Cycles, users preferably provide liquid heat exchangers to cool the power electronics in some configurations. Users preferably configure the heat exchangers and/or control the flow of thermal diluent to maintain the junction temperature of the power converters below the desired or needed levels according to the reliability desired (or to reduce the failure rate to the level desired.) Users preferably provide redundant pumps to provide coolant flow with a desired high operational probability.
With such measures, users recover heat from the power electronics and heat the thermal diluent from the temperature of the fluid exiting the condenser to near that of the allowable temperature exiting the power electronics heat exchanger, e.g., taking thermal diluent from temperatures of about 25° C. to about 30° C. and heating it up to about 95° C. to about 98° C. Users thereby recover about 3.5% to 4.5% or more of the energy otherwise dissipated from the variable frequency electronic power converter as heat.
Users preferably deliver this heated thermal diluent into one or more of the thermal diluent flows that collectively cool the energetic fluid. This reduces the amount of fuel needed to heat the oxidant containing fluid and the thermal diluent to the desired combustor exit temperature (or turbine inlet temperature.) By preferably recycling this heat, users usually achieve significant increases in thermal efficiency.
With such measures, users expect to recycle 3.5 to 4.5 kW of heat in a 100 kW microturbine power system. They also reduce the parasitic fan power required. Accordingly, in such a systems, they expect to improve the efficiency of such a 100 kW VAST microturbine power system by about one percentage point. E.g., from about 36% to about 37%.
In such configurations, users preferably form or line heat exchangers with a low solubility high conductivity material or coating to reduce dissolution of the heat exchanger into the thermal diluent. For example, tin plating or stainless steel coating can be used to reduce corrosion or dissolution of copper heat exchangers. This reduces the concentration of copper or other contaminants in the thermal diluent system and thus reduces their concentration in the energetic fluid flowing into the turbine.
Gear trains commonly result in 0.5% to 2% losses or higher. Users preferably use a fluid coolant to cool the gear trains and recover this heat in some embodiments. They preferably use the thermal diluent directly as the fluid coolant. In other configurations, they use a suitable intermediate coolant fluid or heat exchange fluid, and then recover that heat into the thermal diluent with a suitable heat exchanger.
In some configurations, users preferably use the thermal diluent to provide both lubrication and thermal cooling. The high purity deionized water used as thermal diluent contains few particulates and may form a useful lubricant as well as coolant. In such configurations, users preferably use corrosion resistant materials for the gear train.
Variable speed mechanical drives have similar losses and lubrication requirements. Users preferably use thermal diluent to cool the drive and recover the heat in some configurations. They preferably use the thermal diluent to also lubricate the drive where appropriate, or to cool the lubricant with the thermal diluent.
Generator
Generators have significant resistive losses from current flows in conductors. They also create windage losses. Generators are commonly air cooled and the resistive heat and windage is lost. Generator losses are of the order of 5% for small alternators, 1.5% to 2% for high speed small permanent magnet generators, dropping to 0.5% to 1.25% for large generators. In modified embodiments, the generator heat removal rate (i.e., temperature) may be varied to achieve generator (AC or DC) output power change.
Users preferably direct thermal diluent through and/or around rotor stators to cool them and recover a significant portion of the generator losses in some configurations. They preferably use thermal diluent warmed by more thermally sensitive applications such as power electronics. They preferably use higher temperature insulation coatings on windings and/or permanent magnets to operate the generators at higher temperatures and more effectively recover and recycle the thermal energy.
Where gases are used to cool generator rotors, users preferably provide heat exchangers to recover heat from those heated gases and to heat thermal diluent. E.g., to cool hydrogen that is used in cooling large generator rotors to both cool conductors and to reduce windage, and to heat water or steam.
Re-Compressor (RCP)
Referring to
Users preferably expand and re-compress the energetic fluid as described above and then additionally recover heat from the expanded fluid by heating and vaporizing diluent-containing fluid. This vaporized diluent may be injected between expansion stages. (See
Where additional compression is desired, users preferably recompress products of combustion instead of the reactant gases to reduce the gas mass flow rate being compressed. During combustion, the oxidant reacts with the fuel to form carbon dioxide and water. Water is preferably used for thermal diluent. The water formed and added is preferably condensed and removed in the condensor. This results in a significant reduction in the non-condensable volume of the products of combustion compared to the reactant gases (aside from the common flow of non-condensable diluent gases e.g., nitrogen, excess oxygen, and the noble gases including argon.)
By way of example, one mole of methane reacts with two moles of Oxygen to give one mole of carbon dioxide and two moles of water. This results in about a 67% reduction in volume of non-condensable gases from three moles to one mole. Similarly in burning diesel fuel, there is a reduction from about 18.5 moles of oxygen to 12 moles of carbon dioxide plus 13 moles of water. This gives a reduction of about 35% in these non-condensable reacting and product gases.
By cooling the expanded fluid with a direct contact condensor, users achieve temperatures fairly close to the coolant fluid, i.e., close to ambient conditions. This is typically cooler than the average temperature of the compressed oxidant containing fluid being compressed in the high pressure compressor (HPC) 1350. Accordingly the fluid is more dense, reducing the cost of the compressor relative to one compressing hotter fluids.
By this hybrid combination of compressor(s) before the Turbine 5100 and a recompressor 5300 afterwards, users preferably reduce both the cost of the compressor and the compression work.
In embodiments where the exhaust fluid is cooled and condensed, users preferably add a recompressor 5300 to discharge the expanded fluid back to the atmosphere. The cooling and condensation reduce the volume of the expanded gas. Consequently the recompressor 5300 reduces the pressure of the cooled expanded fluid to below ambient pressure downstream of the expander and upstream of the recompressor. Users preferably use this configuration to improve the net system thermodynamic cycle efficiency and operating costs (see
Based on Cost equations from Traverso 2003 as in Table 3; For US 2000 mean Industrial Gas costs
Liquid-Gas Fluid Contacting Apparatus
Some embodiments utilize the carbon dioxide rich exhaust fluid (or flue gas) as a carbon feed product for food production, energy crop production, aquaculture, or mariculture. The “VASTgas™” formed (comprising products of combustion and vaporized diluent) typically has about 8.5% to 21% carbon dioxide by mass. This may be up to 300% of the Carbon Dioxide that is in conventional lean combustion at about 15% O2 in the exhaust. (E.g., See, Table 3.)
The very low NOx concentrations formed from in these embodiments provide a highly desirable carbon feed for such applications. This significantly reduces the action of NOx on accelerating ripening of vegetables, fruit or other horticultural products. In other configurations, users preferably increase the temperatures in the combustion chamber 4100 to actively increase NOx production when there is a desire to actively enhance and accelerate ripening.
The high humidity in the exhaust is ideal for horticultural applications.
In other embodiments, users separate the carbon dioxide from the exit gas and provide a carbon dioxide enriched gas for pharmaceutical production, biosynthetic processes, or other high carbon applications.
In some embodiments, the carbon dioxide rich exhaust (VASTgas™) or exhaust gas enriched carbon dioxide is preferably used as a flooding fluid and/or a thermal heating fluid in petroleum recovery processes. Heated diluent such as steam or hot water, is preferably mixed with the carbon rich exhaust gas (VASTgas™) in some configurations. E.g., in extracting bitumen or heavy hydrocarbon fossil resources. In other embodiments users sequester the carbon dioxide in deep waters, in partially depleted petroleum fields, or in geological formations to reduce the enhanced greenhouse effect. The embodiments described provide more efficient and cost effective methods to recover and utilize or sequester the carbon dioxide. The recompressor may be used to compress one or more of these exhaust fluids to prescribed pressures. A compressor downstream of the condensation system or the recompressor may also be used.
Diffuser/Stack
In some embodiments, users preferably control one or both of the parameters of the coolant flow through the expanded fluid condensor 7500 and the recompressor speed to adjust the recompression ratio. These control the pressure of the expanded fluid F420 and the expanded fluid gas temperature. By controlling these parameters relative to the water/fuel ratio, air/fuel ratio and fuel composition, users preferably adjust the dew point of the discharged exhaust fluid (or “stack gas”). By so doing, they adjust the fraction of thermal diluent condensed in the condensor 7500. They preferably adjust the spent fluid F475 composition and temperature so that its temperature is above its dew point or saturation temperature. By such control, users may avoid condensation within a diffuser or stack 5900.
Cooling the turbine exhaust gas, condensing the thermal diluent and recompressing the non-condensable spent fluid typically results in an unsaturated stack gas. By so doing, they reduce or eliminate the size of the visible plume formed above the exhaust under typical ambient conditions. In some configurations, they may control or reduce the exhaust dew point so that no plume is formed when the exhaust fluid is discharged to the atmosphere.
This benefits perceptions of the nearby public as to environmentally clean power systems. It also provides a means to comply with local regulations such as those that require avoiding visible plumes in urban areas. This facilitates locating such VAST Cycle systems within municipalities that prohibit plume formation. It provides more efficient and economical methods of controlling plumes compared to relevant art methods of reheating the exhaust to prevent plumes. The recompressing VAST cycle provides these benefits without having to use burners and fuel etc. to reheat the stack gas.
Control System
Some embodiments of the invention preferably comprise a controller which preferably controls and monitors the overall operation of the system such as filter pressure drop, pump head, pump speed, compressor and/or blower speed, combustor pressure and temperature, expander shaft torque, generator output, and the like. Suitable sensors may be utilized, such as rotational speeds, pressure, temperature, flow meters and the like, as needed or desired. The controller may efficaciously incorporate a feedback system.
The controller is preferably configured to control the delivery of diluent within the configured VAST thermodynamic cycle. The liquid and vapor diluent flows are directed as desired to recover heat and cool energetic fluid flows such as shown in
Heated diluent may be directed to one or more utilization devices comprising one or more thermal devices for heat use applications and/or mechanical devices for mechanical use. e.g., as is shown in
The control system preferably controls the amount of diluent within the energy conversion system above a lower limit to maintain a minimum quantity needed for the operation. This may be achieved by controlling the portion of diluent condensed and recovered from the expanded fluid, and the portion of recovered diluent discharged from the energy conversion system. A buffer tank of diluent is preferably provided, and the diluent level is maintained between a lower and an upper level.
In some embodiments, users preferably control the diluent flow sufficient to constrain the temperature of one or more heated components to not exceed one or more respective selected design temperature limits. In some embodiments, users preferably control the temperature of one or more heat generating or self heating components to not exceed one or more respective selected design protective temperature limits. Where one or more temperature or heat-sensitive components are actively cooled, users preferably provide priority diluent flows to keep them below their respective design temperature limits. Sensors such as temperature or flow sensors are preferably provided to sense temperature or flow conditions. Measures are preferably taken to control the flow and initiate power reductions or other measures should the diluent flow not be sufficient to control the temperature as desired. As backup, passive emergency diluent flows may be provided from the diluent buffer tank.
Some utilization devices require minimum flows of heated diluent. These may require a temperature greater than a minimum temperature limit. Accordingly, in recovering heat from the energetic fluid, users preferably control the diluent or coolant flows to ensure that fluid temperatures are greater than the minimum temperature limit to a desired probability. To do so, the turbine inlet temperature is preferably controlled within a desired range such as below a Turbine Inlet Temperature design limit, and above a practical temperature sufficient to achieve the minimum desired temperatures out of the heat recovery system. The diluent fluid flows through the heat recovery heat exchangers are preferably delivered with a flow controlled to achieve the desired degree of heating and fluid temperature to the desired utilization device or application to be equal to or greater than a minimum temperature suitable for district heating hot water, such as 80° C., or steam delivery such as 125° C. or 250° C. etc. In some applications, the heated diluent fluid temperature is configured to be greater than a minimum temperature such as prescribed for air conditioning, cooling, chilling, or refrigeration equipment.
The fuel flow is preferably controlled to achieve the desired thermal and mechanical or electrical power from the energy conversion system. The diluent flow is preferably adjusted to control the turbine inlet temperature at a desired temperature or to within a desired temperature range while the power output is controllably varied. The examples shown typically assumed a relative oxidant/fuel ratio Lambda of about 1.05. More generally, using the VAST Trifluid combustor, the relative oxidant/fuel ratio may range from from less than one for selected chemical reaction systems to near the ratio for lean combustion Brayton systems. E.g., about 90% of typical lean relative air/fuel ratios. The VAST Steam cycles using Trifluid combustor could use steam with or without water for power, combined heat and power, for cooling and power, or combinations thereof. This suggests reductions in compressor size from 10% to more than 85% depending on the turbine inlet temperature and oxidant/fuel ratio selected.
While controlling temperature or heat-sensitive components, temperatures of thermal flows, and power levels, users preferably configure and deliver portions of diluent to the oxidant delivery system to cool the oxidant fluid being compressed and increase the efficiency of the compression process. Where vaporizable diluent is sprayed into the oxidant fluid being compressed, users preferably control the diluent flow delivered to below desired flow design limits. These flow limits are preferably set to avoid compressor surge or choking. The diluent flow rates may also be adjusted and the liquid diluent drop size and/or temperature adjusted to achieve diluent evaporation within desired distances and/or to reduce or avoid compressor erosion. Multiple flows are preferably delivered to the inlet to the compressor and between compressor stages to provide the incremental cooling and achieve near saturated conditions in the compressed oxidant.
Users preferably configure the remaining diluent among the heat recovery system components to improve the specific power and cycle efficiency while achieving these other control objectives. Where there are high demands for heated fluids, users may even deliver warm or unheated liquid diluent into the combustor to control the turbine inlet temperature, and similarly cool the combustor liner. For example, using warm or cold water into the combustor to complement the available steam and/or hot water as appropriate to control the temperature of the energetic fluid and the Turbine Inlet Temperature. This provides a flexible method of controlling the energy conversion system to achieve multiple and/or changing objectives.
Configurations of combined heat and power preferably maintain at least one of heat delivery to a thermal use and power delivery to a mechanical or electrical use to be greater than a prescribed minimum level. More preferably both the heat delivery and the power delivery are controlled. Similarly some configurations include controlling one of the rate of cooling a fluid and delivering it a cooling use and the rate of delivering one of mechanical and/or electrical power to a mechanical or electrical use. More preferably both the rate of cooling and power delivery are controlled. In other configurations, at least two of delivering heated diluent to a heating use, delivering cooled coolant to a cooling use, and delivering power to a mechanical and/or electrical use are maintained above desired levels. More preferably all three of delivering heating, cooling, and power are controlled. One or more of these combined heat and power (CHP) configurations are preferably controlled together with controlling at least one the temperature of the control location thermally proximate to the heat heated by products of combustion, and the temperature of the heat generating component cooled by diluent.
Emissions Control
In one embodiment, a combined heat and power system (CHP) is configured to maintain at least one product of combustion such as carbon dioxide below a desired product emission rate and maintain a byproduct of combustion such as oxides of nitrogen (NOx) below a byproduct emission rate, by controlling fuel and diluent delivery within the CHP system. Preferably this emission control is achieved while maintaining the mechanical power above a desired mechanical power level and/or maintaining the heat delivered to a thermal use above a desired thermal delivery rate level.
These methods are preferably combined with other emission reduction methods described herein or in the technology incorporated by reference. E.g., spraying intake air with water to remove particulates and fibers, washing fuel with water to remove salts; recovering and discharging excess water to control emissions levels, controlling diluent within the system, and using a direct contact condensor on the cooled expanded fluid. In embodiments resulting in significant concentrations of acid gases, the direct contact condensor preferably uses a component which reacts with the acid gas and transfers it from the residual expanded fluid to the recovered diluent. Examples include carbonate solutions or slurries, or alkali solutions, or amine solutions, or similar chemical components that will react with oxides of nitrogen, oxides of sulfur, or carbon dioxide. Other reactive components may also be used in the direct condensor or similar spray or scrubbing system to remove portions of these or other contaminants. The direct contactor further reduces particular emissions, and excess water is beneficially condensed and recovered to control soluble contaminants or particulates or other contaminants that can be preferentially entrained with the water or similar treatment solution. These measures help reduce the emission rates of one or more such contaminants on a mass basis and preferably on a mass per energy basis in the cooled or residual expanded fluid and/or in thermal diluent delivered to a thermal use, e.g., kg/hour, or kg/MWh of mechanical power or more preferably cogeneration power.
These emission control measures are preferably combined with controlling the mechanical power and/or the thermal use rate. Diluent within CHP system is preferably maintained between upper and lower limits on the quantity of water. In some configurations, the diluent delivery within the system and fuel delivery are further controlled to control the cogeneration efficiency and further reduce carbon dioxide emissions for given mechanical power and thermal use. Ways to accomplish this include better matching temperatures of one or more heated diluents flow to required temperatures; increasing temperatures of diluent delivered upstream of the combustor, and/or adjusting the distribution of diluent delivered between the compressor and combustor.
Generalization
From the foregoing description, it will be appreciated that a novel approach for forming thermodynamic cycles using liquid diluents has been disclosed using one or more methods described herein. While the components, techniques and aspects of the invention have been described with a certain degree of particularity, it is manifest that many changes may be made in the specific designs, constructions and methodology herein above described without departing from the spirit and scope of this disclosure.
Where dimensions are given they are generally for illustrative purpose and are not prescriptive. Of course, as the skilled artisan will appreciate, other suitable fluid compositions, pressures, temperatures, heat flows and power levels, may be efficaciously utilized, as needed or desired, giving due consideration to the goals of achieving one or more of the benefits and advantages as taught or suggested herein.
While certain compressors, heat exchangers, turbines, pumps, treatment systems, ducts, valves, mixers and other components are shown in some configuration for some embodiments, combinations of those configurations may be efficaciously utilized, including varying the nominal compressor size, number of compressor stages, compression ratio, turbine size, turbine expansion ratio, number of stages, heat exchanger size, surface heat exchanger or direct contact heat exchangers, type and method of flow control, temperature control, power control, enthalpy control, and other dimensions and parameters for thermodynamic cycles may be used.
Though turbines have been used for expanders in some embodiments, other types of expanders may be used including positive displacement expanders such as reciprocating or rotating screw expanders. Other combustors utilizing delivery of vaporizable and/or vaporized diluent may be used.
Where the terms fuel, diluent, water, air, oxygen, and oxidant have been used, the methods are generally applicable to other combinations of those fluids, or to other combinations of other reacting and non-reacting fluids. Where fluid quantities are referred to, these methods are generally applicable to include quantities delivered at intermittent flows, and to continuous fluid flows. Where assembly methods are described, various alternative assembly methods may be efficaciously utilized to achieve configurations to achieve the benefits and advantages of one or more of the embodiments as taught or suggested herein.
Where transverse, axial, radial, circumferential or other directions are referred to, it will be appreciated that any general coordinate system using curvilinear coordinates may be utilized including Cartesian, cylindrical, spherical or other specialized system such as an annular system. Similarly when one or more transverse or axial distributions or profiles are referred to, it will be appreciated that the configurations and methods similarly apply to spatial control in one or more curvilinear directions as desired or prescribed. Similarly, the contactor, array, device or duct orientations may be generally rearranged to achieve other beneficial combinations of the features and methods described.
While the components, techniques and aspects of the invention have been described with a certain degree of particularity, it is manifest that many changes may be made in the specific designs, constructions and methodology herein above described without departing from the spirit and scope of this disclosure.
Various modifications and applications of the invention may occur to those who are skilled in the art, without departing from the true spirit or scope of the invention. It should be understood that the invention is not limited to the embodiments set forth herein for purposes of exemplification, but includes the full range of equivalency to which each element is entitled.
This application is a continuation-in-part of U.S. patent application Ser. No. 10/763,057 filed Jan. 22, 2004, (the “Thermodynamic Cycles application”), which, in turn, is based on and claims the benefit under 35 U.S.C. 119(e) of U.S. Provisional Application 60/442,096, filed Jan. 22, 2003, and 60/442,844 filed Jan. 24, 2003. This application is also related to Hagen et al. U.S. patent application Ser. No. 10/763,047 filed Jan. 22, 2004, entitled TRIFLUID REACTOR, Hagen et al. U.S. patent application Ser. No. 10/686,191 filed Oct. 15, 2003, entitled METHOD AND APPARATUS FOR MIXING FLUIDS, the entire disclosures of which applications are hereby incorporated herein by reference. This application is also related to Ginter U.S. Pat. Nos. 3,651,641, 5,627,719, and 6,289,666, the entire disclosures of which are hereby incorporated herein by reference.
Number | Date | Country | |
---|---|---|---|
60442096 | Jan 2003 | US | |
60442844 | Jan 2003 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 10763057 | Jan 2004 | US |
Child | 11548281 | Oct 2006 | US |