A portion of the disclosure of this patent document may contain material that is subject to copyright protection. The copyright owner has no objection to the facsimile reproduction by anyone of the patent document or the patent disclosure, as it appears in the Patent and Trademark Office patent file or records, but otherwise reserves all copyright rights whatsoever.
This invention generally relates to control systems for heating, ventilation and air conditioning (HVAC) systems. More particularly, embodiments of this invention relate to wiring connectors for use in HVAC system thermostats.
As is known, for example as discussed in the technical publication No. 50-8433, entitled “Power Stealing Thermostats” from Honeywell (1997), early thermostats used a bimetallic strip to sense temperature and respond to temperature changes in the room. The movement of the bimetallic strip was used to directly open and close an electrical circuit. Power was delivered to an electromechanical actuator, usually relay or contactor in the HVAC equipment whenever the contact was closed to provide heating and/or cooling to the controlled space. Since these thermostats did not require electrical power to operate, the wiring connections were very simple. Only one wire connected to the transformer and another wire connected to the load. Typically, a 24 VAC power supply transformer, the thermostat, and 24 VAC HVAC equipment relay were all connected in a loop with each device having only two external connections required.
When electronics began to be used in thermostats the fact that the thermostat was not directly wired to both sides of the transformer for its power source created a problem. This meant either the thermostat had to have its own independent power source, such as a battery, or be hardwired directly from the system transformer. Direct hardwiring a “common” wire from the transformer to the electronic thermostat may be very difficult and costly. However, there are also disadvantages to using a battery for providing the operating power. One primary disadvantage is the need to continually check and replace the battery. If the battery is not properly replaced and cannot provide adequate power, the electronic thermostat may fail during a period of extreme environmental conditions.
Since many households did not have a direct wire from the system transformer (such as a “Common” wire), some thermostats have been designed to derive power from the transformer through the equipment load. The methods for powering an electronic thermostat from the transformer with a single direct wire connection to the transformer is called “power stealing” or “power sharing.” The thermostat “steals,” “shares” or “harvests” its power during the “OFF” periods of the heating or cooling system by allowing a small amount of current to flow through it into the load coil below its response threshold (even at maximum transformer output voltage). During the “ON” periods of the heating or cooling system the thermostat draws power by allowing a small voltage drop across itself. Hopefully, the voltage drop will not cause the load coil to dropout below its response threshold (even at minimum transformer output voltage). Examples of thermostats with power stealing capability include the Honeywell T8600, Honeywell T8400C, and the Emerson Model 1F97-0671. However, these systems do not have power storage means and therefore always rely on power stealing or must use disposable batteries.
According to some embodiments a thermostat is provided for controlling HVAC systems. The thermostat includes one or more wiring terminals each adapted and configured to make an electrical connection with an HVAC system conductive wire. The making of the connection with the HVAC system wire actuates switching in a loop of an electrical circuit that does not include the HVAC system conductive wire. According to some embodiments, making the connection with the HVAC wire switches open the loop, and the loop is used for power harvesting. For example the loop can include an HVAC wire for a controlling part of a cooling system and/or part of a heating system, and the wire connected to the terminal can be a common wire. According to some embodiments the making of the connection is used to electronically sense the presence of the HVAC wire. According to some embodiments, the making of the connection is used to automatically isolate Rc and Rh wires from each other when both are present. According to some embodiments, the wiring terminal includes actuation of a moveable part of the terminal so as to accommodate the HVAC system wire that in turn actuates the switching of the loop. According to some embodiments the wiring terminal actuates switching in more than one other loops. According to some embodiments the thermostat is primarily designed for controlling residential, and/or light commercial HVAC systems. According to some embodiments, the HVAC system has a cooling capacity of less than about five tones.
According to some embodiments a method of installing a thermostat in an HVAC system is provided. The method includes connecting an HVAC system conductive wire to a terminal in the thermostat; and, in response to the connecting, automatically actuating switching in a loop of an electrical circuit that does not include the HVAC system conductive wire.
According to some embodiments, a thermostat for controlling an HVAC system is provided that includes a wiring terminal adapted and configured to make an electrical connection with an HVAC system conductive wire, wherein connecting the HVAC system wire causes switching open of a loop of an electrical circuit used for power harvesting.
According to some embodiments, a wiring terminal for connecting to a conductive wire is provided. The terminal includes an opening to accept the conductor by actuating a moveable portion of the terminal so as to accommodate the conductive wire, wherein the actuating of the moveable portion actuates switching a loop of an electrical circuit that does not include the conductive wire.
As used herein the terms power “harvesting,” “sharing” and “stealing” when referring to HVAC thermostats all refer to the thermostat are designed to derive power from the power transformer through the equipment load without using a direct or common wire source directly from the transformer.
As used herein the term “HVAC” includes systems providing both heating and cooling, heating only, cooling only, as well as systems that provide other occupant comfort and/or conditioning functionality such as humidification, dehumidification and ventilation.
As used herein the term “residential” when referring to an HVAC system means a type of HVAC system that is suitable to heat, cool and/or otherwise condition the interior of a building that is primarily used as a single family dwelling. An example of a cooling system that would be considered residential would have a cooling capacity of less than about 5 tons of refrigeration (1 ton of refrigeration=12,000 Btu/h).
As used herein the term “light commercial” when referring to an HVAC system means a type of HVAC system that is suitable to heat, cool and/or otherwise condition the interior of a building that is primarily used for commercial purposes, but is of a size and construction that a residential HVAC system is considered suitable. An example of a cooling system that would be considered residential would have a cooling capacity of less than about 5 tons of refrigeration.
As used herein the term “common wire” when referring to HVAC systems refers to a direct wire from an HVAC power transformer that is in addition to the power or return wire to the transformer. Thus, power can be drawn from a circuit including the common wire and the power or return wire without risk of switching on or off relays, switches and/or contactors for operating various HVAC systems since those switching means are not in series in such a circuit.
As used herein the term “silent” or “silently” when referring to thermostat operation and/or control means that any sound made by the thermostat is generally inaudible to the human ear at a range of greater than 1 meter.
It will be appreciated that these systems and methods are novel, as are applications thereof and many of the components, systems, methods and algorithms employed and included therein. It should be appreciated that embodiments of the presently described inventive body of work can be implemented in numerous ways, including as processes, apparata, systems, devices, methods, computer readable media, computational algorithms, embedded or distributed software and/or as a combination thereof. Several illustrative embodiments are described below.
The inventive body of work will be readily understood by referring to the following detailed description in conjunction with the accompanying drawings, in which:
A detailed description of the inventive body of work is provided below. While several embodiments are described, it should be understood that the inventive body of work is not limited to any one embodiment, but instead encompasses numerous alternatives, modifications, and equivalents. In addition, while numerous specific details are set forth in the following description in order to provide a thorough understanding of the inventive body of work, some embodiments can be practiced without some or all of these details. Moreover, for the purpose of clarity, certain technical material that is known in the related art has not been described in detail in order to avoid unnecessarily obscuring the inventive body of work.
Thermostat 110 controls the HVAC system 120 through a number of control circuits. In particular, there are often separate control systems for heating and cooling. The heating system can include a low voltage, for example 24 VAC, operated gas valve which controls the flow of gas to the furnace; the cooling system includes a contactor having a low-voltage coil and high-voltage contacts which control energizing of the compressor; and the circulation system includes a fan relay having a low-voltage coil and high-voltage contacts which control energizing of the fan which circulates the conditioned air. The electrical power for energizing such low-voltage operated devices is provided either by a single transformer 260 for both heating and cooling, or by two separate transformers 260 for heating and 262 for cooling. Often, a single transformer is provided when the heating and cooling system is installed as a complete unit. If the cooling system is added to an existing heating system, sometimes an additional transformer is used.
An electronic programmable thermostat that requires power from the HVAC system is provided. The thermostat is flexible in that it can be installed in buildings having different types of HVAC systems. In particular, the thermostat can be wired directly to an HVAC system having a common wire, so that the thermostat can draw power directly from the power transformer, it can be wired to an HVAC system which does not have a common wire, so the thermostat can draw power using power harvesting circuitry from the HVAC system control loops. In order to have a single thermostat that can be connected to either type of HVAC system (i.e. with our without a common wire), the thermostat must detect which power sources are present and then draw power from the best available power source.
Relay 370 controls the gas valve for the HVAC heating system. When sufficient AC current flows through the gas valve relay 370, gas in the heating system is activated. The gas valve relay 370 connected via a wire to terminal 334, which is labeled the “W” terminal, on thermostat 310. Relay 372 controls the fan for the HVAC heating and cooling systems. When sufficient AC current flows through the fan relay 372, the fan is activated. The fan relay 372 connected via a wire to terminal 340, which is labeled the “G” terminal on thermostat 310. Contactor (or relay) 374 controls the compressor for the HVAC cooling system. When sufficient AC current flows through the compressor contactor 374, the compressor is activated. The contactor 374 connected via a wire to terminal 330, which is labeled the “Y” terminal, on thermostat 310. The heat power transformer 360 is connected to thermostat 310 via a wire to terminal 336, which is labeled the “Rh” terminal. The cooling power transformer 362 is connected to thermostat 310 via a wire to terminal 332, which is labeled the “Rc” terminal. Note that unlike the HVAC system shown in
Thermostat 310 has a number of components that are not shown. For further details of components of thermostat 310, according to some embodiments, see co-pending U.S. patent application Ser. No. 13/034,674 entitled “Thermostat Circuitry for Connection to HVAC Systems,” and Ser. No. 13/034,678 entitled “Thermostat Battery Recharging During HVAC Function Active and Inactive States,” filed Feb. 24, 2011, both of which are incorporated herein by reference. Thermostat 310 has power harvesting circuitry 320, including circuitry 322, 324 and 326 for harvesting power from the cooling control circuit 666, heating control circuit 364 and a common wire, which is not available in the HVAC system shown in
Note that although the HVAC systems shown in
The connector 400 also includes one or more pairs of secondary conductors such as secondary conductor 460 and 462. The two conductors within each secondary conductor pair are in contact with one another when the there is no HVAC wire conductor inserted in connector 400, such as shown in the
When an HVAC wire conductor is inserted in connector 400, as shown in
According to some embodiments, the connector 400 shown in
The first primary conductor 630 is made of metal is shaped so as to be stable in the position shown in
As in the case of connector 400 of
When an HVAC wire (not shown) is inserted, it passes through the conical opening 604, cylindrical opening 606, and through the window portion 632 of first primary conductor 630. The HVAC wire conductor is also held in place by contacting the upper flat portion 646 of the second primary conductor 640. The spring force from the deformation of conductor 630 acts to urge the HVAC wire into contact with both the lower portion of the window 632 of conductor 630 and the lower surface of the upper flat portion 646 of conductor 640. The HVAC wire is thus maintained securely in connector 600 and in electrical contact with both conductor 630 and conductor 640. Additionally, when an HVAC wire conductor is inserted in connector 600 the lever portion 612 of button 610 is positioned as shown such that the secondary conductors 660 and 662 are not in contact with one another. In particular, the conductor 662 is shaped such that it exerts a spring force towards the lever portion 612 and away from the upper portion of conductor 660. Thus, when the HVAC wire conductor is inserted in the connector 600 the contact between conductor 660 and conductor 662 is broken. The same action takes place in the other two pairs of secondary conductors such that the electrical connection in all three pairs of secondary conductors is broken by the pressing of button 610. The connector 600 thus acts to automatically actuate switches formed by each secondary conductor pair when an HVAC wire conductor is inserted.
Note that the primary conductors 630 and 640 are not normally in electrical contact with each other when there is no wire inserted, and when a wire is inserted, the two primary conductors 630 and 640 are electrically connected through the inserted wire. Thus, a normally-open switch is formed by the pair of primary conductors 630 and 640 which can be used for detection of electrical communication with an inserted wire, and/or high current applications, due to the relatively large contact surfaces on conductors 630 and 640.
According to some embodiments, the connector 600 shown in
Backplate 740 also includes, according to some embodiments, a bubble level 762, a connector block 780 for connection to the head unit, and a body 760 for housing electronics.
Additionally, each connector shown in
Although the foregoing has been described in some detail for purposes of clarity, it will be apparent that certain changes and modifications may be made without departing from the principles thereof. It should be noted that there are many alternative ways of implementing both the processes and apparatuses described herein. Accordingly, the present embodiments are to be considered as illustrative and not restrictive, and the inventive body of work is not to be limited to the details given herein, which may be modified within the scope and equivalents of the appended claims.
This patent application claims the benefit of U.S. Prov. Ser. No. 61/415,771 filed Nov. 19, 2010; and of U.S. Prov. Ser. No. 61/429,093 filed Dec. 31, 2010. The subject matter of this patent application also relates to the subject matter of the following commonly assigned applications: U.S. Ser. No. 12/881,430 filed Sep. 14, 2010; U.S. Ser. No. 12/881,463 filed Sep. 14, 2010; U.S. Ser. No. 12/984,602 filed Jan. 4, 2011; U.S. Ser. No. 12/987,257 filed Jan. 10, 2011; U.S. Ser. No. 13/034,674, entitled “Thermostat Circuitry for Connection to HVAC Systems,” filed Feb. 24, 2011; and U.S. Ser. No. 13/034,678, entitled “Thermostat Battery Recharging During HVAC Function Active and Inactive States,” filed Feb. 24, 2011. Each of the above-referenced patent applications is incorporated by reference herein.
Number | Name | Date | Kind |
---|---|---|---|
1639299 | Kinnard | Aug 1927 | A |
2101637 | Howlett | Dec 1937 | A |
2492774 | Wild | Dec 1949 | A |
3025484 | Cunningham | Mar 1962 | A |
3948441 | Perkins et al. | Apr 1976 | A |
3991357 | Kaminski | Nov 1976 | A |
4049973 | Lambert | Sep 1977 | A |
4157506 | Spencer | Jun 1979 | A |
4177923 | Krump | Dec 1979 | A |
4249696 | Donnelly et al. | Feb 1981 | A |
4308991 | Peinetti et al. | Jan 1982 | A |
4460125 | Barker et al. | Jul 1984 | A |
4528459 | Wiegel | Jul 1985 | A |
4632303 | Rodittis | Dec 1986 | A |
4695246 | Beilfuss et al. | Sep 1987 | A |
4798971 | Gravely | Jan 1989 | A |
4842510 | Grunden et al. | Jun 1989 | A |
4872828 | Mierzwinski et al. | Oct 1989 | A |
4898229 | Brown et al. | Feb 1990 | A |
4948040 | Kobayashi et al. | Aug 1990 | A |
4948044 | Cacciatore | Aug 1990 | A |
4955806 | Grunden et al. | Sep 1990 | A |
5065813 | Berkeley et al. | Nov 1991 | A |
5107918 | McFarlane et al. | Apr 1992 | A |
5127464 | Butler et al. | Jul 1992 | A |
5158477 | Testa et al. | Oct 1992 | A |
5161606 | Berkeley et al. | Nov 1992 | A |
5175439 | Haerer et al. | Dec 1992 | A |
5181389 | Hanson et al. | Jan 1993 | A |
5251813 | Kniepkamp | Oct 1993 | A |
5255179 | Zekan et al. | Oct 1993 | A |
5260669 | Higgins et al. | Nov 1993 | A |
5277363 | Hart | Jan 1994 | A |
5318224 | Darby et al. | Jun 1994 | A |
5347982 | Binzer et al. | Sep 1994 | A |
5352930 | Ratz | Oct 1994 | A |
5381950 | Aldridge | Jan 1995 | A |
5422808 | Catanese, Jr. et al. | Jun 1995 | A |
5452762 | Zillner, Jr. | Sep 1995 | A |
5456407 | Stalsberg et al. | Oct 1995 | A |
5460327 | Hill et al. | Oct 1995 | A |
5462225 | Massara et al. | Oct 1995 | A |
5467921 | Shreeve et al. | Nov 1995 | A |
5485953 | Bassett et al. | Jan 1996 | A |
5506569 | Rowlette | Apr 1996 | A |
5544036 | Brown, Jr. et al. | Aug 1996 | A |
5570837 | Brown et al. | Nov 1996 | A |
5595342 | McNair et al. | Jan 1997 | A |
5611484 | Uhrich | Mar 1997 | A |
5635896 | Tinsley et al. | Jun 1997 | A |
5646349 | Twigg et al. | Jul 1997 | A |
5655709 | Garnett et al. | Aug 1997 | A |
5673850 | Uptegraph | Oct 1997 | A |
5697552 | McHugh et al. | Dec 1997 | A |
5736795 | Zuehlke et al. | Apr 1998 | A |
5808294 | Neumann | Sep 1998 | A |
5903139 | Kompelien | May 1999 | A |
5918474 | Khanpara et al. | Jul 1999 | A |
5931378 | Schramm | Aug 1999 | A |
5950709 | Krueger et al. | Sep 1999 | A |
5957374 | Bias et al. | Sep 1999 | A |
6032867 | Dushane et al. | Mar 2000 | A |
6060719 | DiTucci et al. | May 2000 | A |
6072784 | Agrawal et al. | Jun 2000 | A |
6084518 | Jamieson | Jul 2000 | A |
6089310 | Toth et al. | Jul 2000 | A |
6102749 | Lynn et al. | Aug 2000 | A |
D435473 | Eckel et al. | Dec 2000 | S |
6196468 | Young | Mar 2001 | B1 |
6207899 | Gillespie | Mar 2001 | B1 |
6213404 | Dushane et al. | Apr 2001 | B1 |
6222719 | Kadah | Apr 2001 | B1 |
6275160 | Ha | Aug 2001 | B1 |
6295823 | Odom et al. | Oct 2001 | B1 |
6315211 | Sartain et al. | Nov 2001 | B1 |
6336593 | Bhatnagar | Jan 2002 | B1 |
6347747 | Nesbitt | Feb 2002 | B1 |
6356038 | Bishel | Mar 2002 | B2 |
6437999 | Wittenbreder | Aug 2002 | B1 |
6509838 | Payne et al. | Jan 2003 | B1 |
6513723 | Mueller et al. | Feb 2003 | B1 |
6560977 | Hupfel et al. | May 2003 | B1 |
6566768 | Zimmerman et al. | May 2003 | B2 |
6622925 | Carner et al. | Sep 2003 | B2 |
6657418 | Atherton | Dec 2003 | B2 |
6743010 | Bridgeman et al. | Jun 2004 | B2 |
6794771 | Orloff | Sep 2004 | B2 |
6798341 | Eckel et al. | Sep 2004 | B1 |
6804117 | Phillips et al. | Oct 2004 | B2 |
6826454 | Sulfstede | Nov 2004 | B2 |
6851621 | Wacker et al. | Feb 2005 | B1 |
6851967 | Miyoshi et al. | Feb 2005 | B2 |
6886754 | Smith et al. | May 2005 | B2 |
6888078 | Loeffelholz et al. | May 2005 | B2 |
6888441 | Carey | May 2005 | B2 |
6933655 | Morrison et al. | Aug 2005 | B2 |
6956463 | Crenella et al. | Oct 2005 | B2 |
6997390 | Alles | Feb 2006 | B2 |
7055759 | Wacker et al. | Jun 2006 | B2 |
7083109 | Pouchak | Aug 2006 | B2 |
7156318 | Rosen | Jan 2007 | B1 |
7167079 | Smyth et al. | Jan 2007 | B2 |
7174239 | Butler et al. | Feb 2007 | B2 |
7181317 | Amundson et al. | Feb 2007 | B2 |
7200467 | Schanin et al. | Apr 2007 | B2 |
7209870 | Simmons et al. | Apr 2007 | B2 |
7331852 | Ezell et al. | Feb 2008 | B2 |
7360370 | Shah et al. | Apr 2008 | B2 |
7476988 | Mulhouse et al. | Jan 2009 | B2 |
7510126 | Rossi et al. | Mar 2009 | B2 |
7537171 | Mueller et al. | May 2009 | B2 |
7555364 | Poth et al. | Jun 2009 | B2 |
7562536 | Harrod et al. | Jul 2009 | B2 |
7566263 | Snyder | Jul 2009 | B2 |
7571865 | Nicodem et al. | Aug 2009 | B2 |
7634504 | Amundson | Dec 2009 | B2 |
7648077 | Rossi et al. | Jan 2010 | B2 |
7673809 | Juntunen | Mar 2010 | B2 |
7748640 | Roher et al. | Jul 2010 | B2 |
7755220 | Sorg et al. | Jul 2010 | B2 |
7775452 | Shah et al. | Aug 2010 | B2 |
7809472 | Silva et al. | Oct 2010 | B1 |
7821218 | Butler et al. | Oct 2010 | B2 |
7841542 | Rosen | Nov 2010 | B1 |
7844764 | Williams | Nov 2010 | B2 |
7845576 | Siddaramanna et al. | Dec 2010 | B2 |
7847681 | Singhal et al. | Dec 2010 | B2 |
7900849 | Barton et al. | Mar 2011 | B2 |
7904209 | Podgorny et al. | Mar 2011 | B2 |
7904830 | Hoglund et al. | Mar 2011 | B2 |
8067912 | Mullin | Nov 2011 | B2 |
D651529 | Mongell et al. | Jan 2012 | S |
8091375 | Crawford | Jan 2012 | B2 |
8195313 | Fadell et al. | Jun 2012 | B1 |
8265798 | Imes | Sep 2012 | B2 |
8280536 | Fadell et al. | Oct 2012 | B1 |
8415829 | Di Cristofaro | Apr 2013 | B2 |
8442695 | Imes et al. | May 2013 | B2 |
8544285 | Stefanski et al. | Oct 2013 | B2 |
8708242 | Conner et al. | Apr 2014 | B2 |
20020074865 | Zimmerman et al. | Jun 2002 | A1 |
20030037555 | Street et al. | Feb 2003 | A1 |
20030064335 | Canon | Apr 2003 | A1 |
20030069648 | Douglas et al. | Apr 2003 | A1 |
20030090243 | Atherton | May 2003 | A1 |
20030231001 | Bruning | Dec 2003 | A1 |
20040058637 | Laiti | Mar 2004 | A1 |
20040120084 | Readio et al. | Jun 2004 | A1 |
20040130454 | Barton | Jul 2004 | A1 |
20040193324 | Hoog et al. | Sep 2004 | A1 |
20040209209 | Chodacki et al. | Oct 2004 | A1 |
20040238651 | Juntunen et al. | Dec 2004 | A1 |
20040245349 | Smith | Dec 2004 | A1 |
20040245352 | Smith | Dec 2004 | A1 |
20050040250 | Wruck | Feb 2005 | A1 |
20050043907 | Eckel et al. | Feb 2005 | A1 |
20050080493 | Arntson | Apr 2005 | A1 |
20050145705 | Shah et al. | Jul 2005 | A1 |
20050159846 | Van Ostrand et al. | Jul 2005 | A1 |
20050159847 | Shah et al. | Jul 2005 | A1 |
20050195757 | Kidder et al. | Sep 2005 | A1 |
20050270151 | Winick | Dec 2005 | A1 |
20060090066 | Maze et al. | Apr 2006 | A1 |
20060102731 | Mueller et al. | May 2006 | A1 |
20060102732 | Garrett et al. | May 2006 | A1 |
20060124759 | Rossi et al. | Jun 2006 | A1 |
20060186214 | Simon et al. | Aug 2006 | A1 |
20060196953 | Simon et al. | Sep 2006 | A1 |
20060219799 | Schultz et al. | Oct 2006 | A1 |
20070045432 | Juntunen | Mar 2007 | A1 |
20070045433 | Chapman et al. | Mar 2007 | A1 |
20070045441 | Ashworth et al. | Mar 2007 | A1 |
20070095082 | Garrett et al. | May 2007 | A1 |
20070103824 | Patterson et al. | May 2007 | A1 |
20070114848 | Mulhouse et al. | May 2007 | A1 |
20070115135 | Mulhouse et al. | May 2007 | A1 |
20070131787 | Rossi et al. | Jun 2007 | A1 |
20070132503 | Nordin | Jun 2007 | A1 |
20070157639 | Harrod | Jul 2007 | A1 |
20070158442 | Chapman et al. | Jul 2007 | A1 |
20070183475 | Hutcherson | Aug 2007 | A1 |
20070183478 | Becker et al. | Aug 2007 | A1 |
20070205297 | Finkam et al. | Sep 2007 | A1 |
20070208461 | Chase | Sep 2007 | A1 |
20070221741 | Wagner et al. | Sep 2007 | A1 |
20070227862 | Yim et al. | Oct 2007 | A1 |
20070228183 | Kennedy et al. | Oct 2007 | A1 |
20070241203 | Wagner et al. | Oct 2007 | A1 |
20070272527 | Mattlar et al. | Nov 2007 | A1 |
20070296280 | Sorg et al. | Dec 2007 | A1 |
20080006709 | Ashworth et al. | Jan 2008 | A1 |
20080015742 | Kulyk et al. | Jan 2008 | A1 |
20080048046 | Wagner et al. | Feb 2008 | A1 |
20080054082 | Evans et al. | Mar 2008 | A1 |
20080054084 | Olson | Mar 2008 | A1 |
20080094010 | Black | Apr 2008 | A1 |
20080099568 | Nicodem et al. | May 2008 | A1 |
20080128523 | Hoglund et al. | Jun 2008 | A1 |
20080133956 | Fadell | Jun 2008 | A1 |
20080142344 | Hickam | Jun 2008 | A1 |
20080147242 | Roher et al. | Jun 2008 | A1 |
20080151458 | Beland et al. | Jun 2008 | A1 |
20080161977 | Takach et al. | Jul 2008 | A1 |
20080179412 | Rhodes | Jul 2008 | A1 |
20080183335 | Poth et al. | Jul 2008 | A1 |
20080185450 | Kwon et al. | Aug 2008 | A1 |
20080202135 | Francis | Aug 2008 | A1 |
20080238660 | Dayton et al. | Oct 2008 | A1 |
20080273754 | Hick et al. | Nov 2008 | A1 |
20090012959 | Ylivainio et al. | Jan 2009 | A1 |
20090057425 | Sullivan et al. | Mar 2009 | A1 |
20090065595 | Kates | Mar 2009 | A1 |
20090099697 | Li et al. | Apr 2009 | A1 |
20090140056 | Leen | Jun 2009 | A1 |
20090140057 | Leen | Jun 2009 | A1 |
20090140064 | Schultz et al. | Jun 2009 | A1 |
20090140065 | Juntunen et al. | Jun 2009 | A1 |
20090143879 | Amundson et al. | Jun 2009 | A1 |
20090143880 | Amundson et al. | Jun 2009 | A1 |
20090194601 | Flohr | Aug 2009 | A1 |
20090195349 | Frader-Thompson et al. | Aug 2009 | A1 |
20090236433 | Mueller et al. | Sep 2009 | A1 |
20090259713 | Blumrich et al. | Oct 2009 | A1 |
20090261174 | Butler et al. | Oct 2009 | A1 |
20090312968 | Phillips | Dec 2009 | A1 |
20100000239 | Lifson et al. | Jan 2010 | A1 |
20100006660 | Leen et al. | Jan 2010 | A1 |
20100012737 | Kates | Jan 2010 | A1 |
20100025483 | Hoeynck et al. | Feb 2010 | A1 |
20100070089 | Harrod et al. | Mar 2010 | A1 |
20100070099 | Watson et al. | Mar 2010 | A1 |
20100076605 | Harrod et al. | Mar 2010 | A1 |
20100084482 | Kennedy et al. | Apr 2010 | A1 |
20100084918 | Fells et al. | Apr 2010 | A1 |
20100106305 | Pavlak et al. | Apr 2010 | A1 |
20100106322 | Grohman | Apr 2010 | A1 |
20100114382 | Ha et al. | May 2010 | A1 |
20100131112 | Amundson et al. | May 2010 | A1 |
20100163635 | Ye | Jul 2010 | A1 |
20100182743 | Roher | Jul 2010 | A1 |
20100193592 | Simon et al. | Aug 2010 | A1 |
20100198425 | Donovan | Aug 2010 | A1 |
20100250009 | Lifson et al. | Sep 2010 | A1 |
20100261465 | Rhoads et al. | Oct 2010 | A1 |
20100298985 | Hess et al. | Nov 2010 | A1 |
20100318227 | Steinberg et al. | Dec 2010 | A1 |
20110015798 | Golden et al. | Jan 2011 | A1 |
20110015802 | Imes | Jan 2011 | A1 |
20110025257 | Weng | Feb 2011 | A1 |
20110137467 | Leen et al. | Jun 2011 | A1 |
20110152024 | Kuehl | Jun 2011 | A1 |
20110160918 | McMasters et al. | Jun 2011 | A1 |
20110166712 | Kramer et al. | Jul 2011 | A1 |
20110241624 | Park et al. | Oct 2011 | A1 |
20110253796 | Posa et al. | Oct 2011 | A1 |
20120017611 | Coffel et al. | Jan 2012 | A1 |
20120024969 | Kates | Feb 2012 | A1 |
20120031984 | Feldmeier et al. | Feb 2012 | A1 |
20120126019 | Warren et al. | May 2012 | A1 |
20120126020 | Filson et al. | May 2012 | A1 |
20120248211 | Warren et al. | Oct 2012 | A1 |
20120258776 | Lord et al. | Oct 2012 | A1 |
20120273580 | Warren et al. | Nov 2012 | A1 |
20130073506 | Camp et al. | Mar 2013 | A1 |
20130087629 | Stefanski et al. | Apr 2013 | A1 |
20140084072 | Conner et al. | Mar 2014 | A1 |
20150293541 | Fadell et al. | Oct 2015 | A1 |
Number | Date | Country |
---|---|---|
101305248 | Nov 2008 | CN |
101522447 | Sep 2009 | CN |
101849311 | Sep 2010 | CN |
207295 | Jan 1987 | EP |
447458 | Sep 1991 | EP |
510807 | Oct 1992 | EP |
660287 | Jun 1995 | EP |
690363 | Jan 1996 | EP |
2302326 | Mar 2011 | EP |
2294828 | May 1996 | GB |
09298780 | Nov 1997 | JP |
20556 | Oct 2001 | SI |
274364 | Apr 1996 | TW |
316955 | Oct 1997 | TW |
362230 | Jun 1999 | TW |
532469 | May 2003 | TW |
535320 | Jun 2003 | TW |
2007009529 | Mar 2007 | TW |
201232994 | Aug 2012 | TW |
2005019740 | Mar 2005 | WO |
2007027554 | Mar 2007 | WO |
2008054938 | May 2008 | WO |
2012068437 | May 2012 | WO |
2013058820 | Apr 2013 | WO |
Entry |
---|
Aprilaire Electronic Thermostats Model 8355 User's Manual, Research Products Corporation, Dec. 2000, 16 pages. |
Braeburn 5300 Installer Guide, Braeburn Systems, LLC, Dec. 9, 2009, 10 pages. |
Braeburn Model 5200, Braeburn Systems, LLC, Jul. 20, 2011, 11 pages. |
Bryant, SYSTXBBUID01 Evolution Control Installation Instructions, 2004, 12 pages. |
Ecobee Smart Thermostat Installation Manual, Jun. 29, 2011, 20 pages. |
Ecobee Smart Thermostat User Manual, May 11, 2010, 20 pages. |
Honeywell Installation Guide FocusPRO TH6000 Series, Honeywell International, Inc., Jan. 5, 2012, 24 pages. |
Honeywell Operating Manual FocusPRO TH6000 Series, Honeywell International, Inc., Mar. 25, 2011, 80 pages. |
Honeywell Prestige THX9321-9421 Operating Manual, Honeywell International, Inc., Jul. 6, 2011, 120 pages. |
Hunter Internet Thermostat Installation Guide, Hunter Fan Co., Aug. 14, 2012, 8 pages. |
Lennox ComfortSense 5000 Owners Guide, Lennox Industries, Inc., Feb. 2008, 32 pages. |
Lennox ComfortSense 7000 Owners Guide, Lennox Industries, Inc., May 2009, 15 pages. |
Lennox iComfort Manual, Lennox Industries, Inc., Dec. 2010, 20 pages. |
Lux PSPU732T Manual, LUX Products Corporation, Jan. 6, 2009, 48 pages. |
RobertShaw Product Manual 9620, Maple Chase Company, Jun. 12, 2001, 14 pages. |
RobertShaw Product Manual 9825i2, Maple Chase Company, Jul. 17, 2006, 36 pages. |
SYSTXCCUIZ01-V Infinity Control Installation Instructions, Carrier Corp, May 31, 2012, 20 pages. |
TB-PAC, TB-PHP, Base Series Programmable Thermostats, Carrier Corp, May 14, 2012, 8 pages. |
TP-PAC, TP-PHP, TP-NAC, TP-NHP Performance Series AC/HP Thermostat Installation Instructions, Carrier Corp, 2007, 56 pages. |
Trane Communicating Thermostats for Fan Coil, Trane, May 2011, 32 pages. |
Trane Communicating Thermostats for Heat Pump Control, Trane, May 2011, 32 pages. |
Trane Install XL600 Installation Manual, Trane, Mar. 2006, 16 pages. |
Trane XL950 Installation Guide, Trane, Mar. 2011, 20 pages. |
Venstar T2900 Manual, Venstar, Inc., Apr. 2008, 113 pages. |
Venstar T5800 Manual, Venstar, Inc., Sep. 7, 2011, 63 pages. |
VisionPRO TH8000 Series Installation Guide, Honeywell International, Inc., Jan. 2012, 12 pages. |
VisionPRO TH8000 Series Operating Manual, Honeywell International, Inc., Mar. 2011, 96 pages. |
VisionPRO Wi-Fi Programmable Thermostat, Honeywell International, Inc Operating Manual, Aug. 2012, 48 pages. |
White Rodgers (Emerson) Model 1F81-261 Installation and Operating Instructions, White Rodgers, Apr. 15, 2010, 8 pages. |
White Rodgers (Emerson) Model IF98EZ-1621 Homeowner's User Guide, White Rodgers, Jan. 25, 2012, 28 pages. |
International Patent Application No. PCT/US2011/061391, International Search Report, mailed Apr. 11, 2012, 3 pages. |
Arens et al., Demand Response Electrical Appliance Manager—User Interface Design, Development and Testing, Poster, Demand Response Enabling Technology Development, University of California Berkeley, 2005, 1 page. |
Arens et al., Demand Response Enabled Thermostat—Control Strategies and Interface, Demand Response Enabling Technology Development Poster, University of California Berkeley, 2004, 1 page. |
Arens et al., Demand Response Enabling Technology Development, Phase I Report: Jun. 2003-Nov. 2005, University of California Berkeley, Apr. 4, 2006, pp. 1-108. |
Arens et al., New Thermostat Demand Response Enabling Technology, Poster, University of California Berkeley, Jun. 10, 2004. |
Auslander et al., UC Berkeley DR Research Energy Management Group, Power Point Presentation, DR ETD Workshop, State of California Energy Commission, Jun. 11, 2007, pp. 1-35. |
Chen et al., Demand Response-Enabled Residential Thermostat Controls, Abstract, ACEEE Summer Study on Energy Efficiency in Buildings, Mechanical Engineering Dept. and Architecture Dept., University of California Berkeley, 2008, pp. 1-24 through 1-36. |
Detroitborg, Nest Learning Thermostat: Unboxing and Review, [online], retrieved from the Internet: <URL: http://www.youtube.com/watch?v=KrgcOL4oLzc> [retrieved on Aug. 22, 2013], Feb. 10, 2012, 4 pages. |
Ecobee Smart Si Thermostat Installation Manual, Ecobee, Apr. 3, 2012, 40 pages. |
Ecobee Smart Si Thermostat User Manual, Ecobee, Apr. 3, 2012, 44 pages. |
Energy Joule, Ambient Devices, retrieved from the Internet: <URL: http://web.archive.org/web/20110723210421/http://www.ambientdevices.com/products/energyjoule.html> [retrieved on Aug. 1, 2012], Jul. 23, 2011, 2 pages. |
Green, Thermo Heat Tech Cool, Popular Mechanics Electronic Thermostat Guide, Oct. 1985, pp. 155-158. |
Honeywell CT2700, An Electronic Round Programmable Thermostat—User's Guide, Honeywell, Inc., 1997, 8 pages. |
Honeywell CT8775A,C, The digital Round Non-Programmable Thermostats—Owner's Guide, Honeywell International Inc., 2003, 20 pages. |
Honeywell Prestige THX9321 and THX9421 Product Data, Honeywell International, Inc., Jan. 12, 2012, 126 pages. |
Honeywell T8700C, An Electronic Round Programmable Thermostat—Owner's Guide, Honeywell, Inc., 1997, 12 pages. |
Honeywell T8775 The Digital Round Thermostat, Honeywell, 2003, 2 pages. |
Honeywell T8775AC Digital Round Thermostat Manual No. 69-1679EF-1, www.honeywell.com/yourhome, Jun. 2004, pp. 1-16. |
ICY 3815TT-001 Timer-Thermostat Package Box, ICY BV Product Bar Code No. 8717953007902, 2009, 2 pages. |
Installation and Start-Up Instructions Evolution Control SYSTXBBUID01, Bryant Heating & Cooling Systems, 2004, 12 pages. |
Meier et al., Thermostat Interface Usability: A Survey, Ernest Orlando Lawrence Berkeley National Laboratory, Environmental Energy Technologies Division, Berkeley California, Sep. 2010, pp. 1-73. |
Peffer et al., A Tale of Two Houses: The Human Dimension of Demand Response Enabling Technology from a Case Study of Adaptive Wireless Thermostat, Abstract, ACEEE Summer Study on Energy Efficiency in Buildings, Architecture Dept. and Mechanical Engineering Dept., University of California Berkeley, 2008, pp. 7-242 through 7-253. |
Peffer et al., Smart Comfort at Home: Design of a Residential Thermostat to Achieve Thermal Comfort, and Save Money and Peak Energy, University of California Berkeley, Mar. 2007, 1 page. |
Salus, S-Series Digital Thermostat Instruction Manual-ST620 Model No. Instruction Manual, www.salus-tech.com, Version 005, Apr. 29, 2010, 24 pages. |
Sanford, iPod (Click Wheel) (2004), www.apple-history.com, retrieved from: http://apple-history.com/ipod [retrieved on Apr. 9, 2012], 2 pages. |
Shadrach, Energy Scavenging for Wireless Sensor Nodes with a Focus on Vibration to Electricity Conversion, Dissertation [online], retrieved from the Internet: <URL: http://users.cecs.anu.edu.au/˜Shad.Roundy/paper/ShadThesis.pdf>, Jun. 2003, 297 pages. |
The Clever Thermostat, ICY BV Web Page, http://www.icy.nl/en/consumer/products/clever-thermostat, ICY BV, 2012, 1 page. |
The Clever Thermostat User Manual and Installation Guide, ICY BV ICY3815 Timer-Thermostat, 2009, pp. 1-36. |
Wright, et al., DR ETD—Summary of New Thermostat, TempNode, & New Meter (UC Berkeley Project), Power Point Presentation, Public Interest Energy Research, University of California Berkeley, 2005, pp. 1-49. |
ISR/WO mailed on Apr. 3, 2012 for International Patent Application No. PCT/US2011/061339 filed on Nov. 18, 2011, all pages. |
ISR/WO mailed on Jul. 6, 2012 for International Patent Application No. PCT/US2012/030084 filed on Mar. 22, 2012, all pages. |
International Preliminary Report on Patentability mailed on May 1, 2014 for International Patent Application No. PCT/US2012/030084 filed on Mar. 22, 2012, all pages. |
ISR/WO mailed on Jan. 22, 2013 for International Patent Application No. PCT/US2012/061148 filed on Oct. 19, 2012, all pages. |
Taiwanese Office Action issued on Mar. 18, 2014 for ROC (Taiwan) Patent Application No. 100142429 filed on Nov. 8, 2011, all pages. |
Taiwanese Office Action issued on Sep. 30, 2014 for ROC (Taiwan) Patent Application No. 100142428 filed on Nov. 18, 2011, all pages. |
U.S. Appl. No. 60/512,886, Volkswagen Rotary Knob for Motor Vehicle—English Translation of German Application filed Oct. 20, 2003, all pages. |
U.S. Patent Office Action issued on Dec. 23, 2014 for U.S. Appl. No. 14/504,220 filed on Oct. 1, 2014, all pages. |
Written Opinion mailed Apr. 11, 2012 for International Patent Application PCT/US2011/061391 filed Nov. 18, 2011, 5 pages. |
International Preliminary Report on Patentability issued Feb. 25, 2014 for International Patent Application PCT/US2011/061391 filed Nov. 18, 2011, 6 pages. |
International Preliminary Report on Patentability mailed on May 30, 2013, for International Patent Application No. PCT/US2011/061339, filed Nov. 18, 2011, 8 pages. |
International Preliminary Report on Patentability mailed May 1, 2014, for International Patent Application No. PCT/US2012/061148, filed Oct. 19, 2012, 10 pages. |
Taiwanese Office Action issued on May 5, 2014, for ROC (Taiwan) Patent Application No. 100142428 filed on Nov. 18, 2011, 12 pages. |
Honeywell Prestige IAQ Product Data 2, Honeywell International, Inc., Jan. 12, 2012, 126 pages. |
Number | Date | Country | |
---|---|---|---|
20120126020 A1 | May 2012 | US |
Number | Date | Country | |
---|---|---|---|
61415771 | Nov 2010 | US | |
61429093 | Dec 2010 | US |