This invention relates to the field of AC-DC conversion with a Three-Phase input voltage, which can provide the galvanic isolation and Power Factor Correction performance features. The present solutions can provide these functions but to do so they use at least two cascaded power-processing stages: non-isolated three-phase PFC converter followed by an isolated DC-DC converter resulting in low efficiency, big size and weight and high cost.
The present invention opens up a new class of single-stage AC-DC converters with Three-Phase Input voltage, which provides both galvanic isolation and Power Factor Correction features by processing the three-phase AC input power to DC output power in a single power processing stage, thus resulting in much improved efficiency, reduced size and weight and lower cost. The new class of single-stage Three-Phase AC-DC converters was made possible by heretofore not available hybrid switching method for step-up conversion, which in turns results in a number of distinct switching converter topologies.
The prior art AC-DC converters using two stages are characterized by each power processing stage consisting of even number of switches, such as six for PFC converter and 8 for Isolated Dc-DC converter. The even number of switches is postulated by the present PWM square-wave switching technology, which explicitly forbids the existence of the converters with odd number of switches, such as 3, 5, etc. In a clear departure from the present classification, the new single-stage three-phase AC-DC converters introduced here all have a distinguishing characteristic of having a total of three switches I each phase and hence a total of nine switches, both odd number of switches.
The objective of this invention is to replace the existing two stage Three-Phase AC-DC converters with a Three-Phase AC-DC converter providing both galvanic isolation and Power Factor Correction features in a single power processing stage.
Three-phase input power has naturally high power factor, since even a direct six diode rectification of the three-phase line leads to very high power factor of over 96% due to the fact, that these diodes each conducts during their peak voltage and peak current conduction. Although, the Power factor in itself is not a problem with three-phase inputs, the harmonic content injected into the line is excessive and some form of active control (not a passive diode bridge) is required to reduce the harmonics in order to meet stringent requirements of IEC-1000-3-2 regulations.
The following notation is consistently used throughout this text in order to facilitate easier delineation between various quantities:
1. DC—Shorthand notation historically referring to Direct Current but by now has acquired wider meaning and refers generically to circuits with DC quantities;
2. AC—Shorthand notation historically referring to Alternating Current but by now has acquired wider meaning and refers to all Alternating electrical quantities (current and voltage);
3. i1, v2—The instantaneous time domain quantities are marked with lower case letters, such as i1 and v2 for current and voltage;
4. I1, V2—The DC components of the instantaneous periodic time domain quantities are designated with corresponding capital letters, such as I1 and V2;
a and
a illustrates the present invention.
a illustrates the PFC control via control of switch S.
a shows a separate PFC control of each phase and
a illustrates the voltage of transformer and inductor,
a shows the schematic of PFC control with standard PFC controller IC circuit and
a shows a new Three-Phase Isolated Rectifier with PFC and corresponding Three-phase PFC Controller and
a illustrates the line voltage and line currents of the converter in
a shows the input three-phase currents and
a shows one input phase current and corresponding instantaneous input power and
a shows one output phase voltage and
a shows a three-stage approach and
a illustrates a practical implementation with Transorb,
a and
a is and
a shows RGIGBT implementation of switch S and
a shows MOSFET implementation and
a,b,c illustrates control methods.
a,b are the measurements of phase voltages and phase currents.
a,b are measurements of efficiency and power loss respectively
a is measurement of harmonies of the phase currents and
Electrical power is transmitted efficiently over the long distance by use of the Three-Phase alternating transmission voltage operating at very high voltages of over 100,000 Volts and proportionally much reduced current to reduce the transmission losses. Then at the user end this high alternating (sinusoidal) voltage at 60 Hz transmission frequency is via three-phase 60 Hz transformers reduced to three-phase low alternating voltages of 400V per phase Thus, when the users need for power exceeds 2 kW to 3 kW, then invariably three-phase power is used as a main source for electrical equipment in industrial centers and in data centers where many computer servers are used to store and process the search and other computing information. Thus, the need for an AC-DC converters which can operate directly from the Three-Phase input power, generate isolated DC power at low DC voltages such as 48V and/or 12V for computers, but also operate with near unity Power factor to reduce the harmonics of the line frequency and reduce each one bellow regulated limits allowed for a given power.
Until now no converter topology existed capable to do so in a single power processing stage. The most commonly used two-stage approach is illustrated n the prior art converter of
The present invention of a Three-phase AC-DC converters with isolation and Power Factor Correction provided in a single power processing stage is illustrated in general form illustrated in
Block diagram in
Isolation transformer of the converter in
The voltage waveforms of the inductor L and transformer T in the converter of
The single-stage Isolated PFC converter of
In addition to a Bridgeless PFC Converter stage as shown in
Such Bridgeless PFC Integrated Circuit Controllers do not exist currently. However, the existing PFC controller Integrated Circuits (IC's) operating from rectified AC line voltage and rectified AC line current could be used provided additional signal processing circuitry is implemented as shown in
Three-Phase Isolated Bridgeless PFC control
Although each phase can be operated independently and with its own separate isolated bridgeless PFC Controller, the controls for all three phases could be combined into a Three-Phase Isolated Bridgeless PFC controller as shown in
b shows yet another Isolated converter topology with pulsating input current, which satisfies the criteria needed to operate in a Three-Phase Isolated Bridgeless PFC converter structure of
One of the key characteristics of the new Three-Phase Bridgeless PFC converters of
After operation of the converters in
Finally, with operation under either positive or negative input voltages fully analytically characterized and understood, the operation from AC line voltage under Three=phase PFC control will be the easier to understand.
Here is a brief description of the converter operation, first for positive input voltage and then for negative input voltage.
Operation from Positive Input Voltage
First we analyze the operation of converter in
When switch S is turned-OFF, the DC current I of input inductor L forces the rectifier CR2 to turn-ON and resonant capacitors Cr1 and Cr2 are charging while the load current was provided from the input voltage source. Subsequent turn-ON of switch S causes the rectifier CR1 to turn-ON and capacitors Cr1 and Cr2 exchange their previously stored energy in a non-dissipative resonant fashion with the resonant inductor Lr. If this resonant inductor were not present, the energy stored in resonant capacitors would during this interval be dissipated and lost in parasitic ESRs of the capacitors. This would clearly result in the reduced efficiency. Therefore, the resonant capacitors and resonant inductor even though not transferring the current to the load is not wasted, since the resonance is used to prepare the resonant capacitors for the next charging interval in next cycle.
For simplicity of the analytical derivations we assume that the isolation transformer in
The Volt-second (flux balance) on inductor L in
V
g
DT
S=(V+VCr−Vg) (1−D)TS (1)
Unlike the PWM inductor L, which is flux balanced over the entire period TS, the resonant inductor Lr must be fully flux balanced during the ON-time interval only, resulting in:
VCr=0 (2)
as the resonant inductor cannot support any net DC voltage since the integral of the AC ripple voltage Δvr over the ON-time interval must be by definition zero. Therefore, the DC voltage VCr of the resonant capacitor Cr must be zero so that the volt-second balance is satisfied on the resonant inductor Lr.
Using the result (2) in (1), the DC conversion ratio is obtained as:
V/V
g=1/(1−D) (3)
Note that the same DC conversion ratio as in the prior-art boost converter is obtained. Furthermore, despite the resonant circuit consisting of resonant capacitor Cr and resonant inductor Lr, the DC conversion does not depend on either one of them and their values or the switching period TS, but only depends on the operating duty ratio D. Thus despite this hybrid switching described in later section, the simple DC conversion ratio as in square-wave switching converters is obtained. Hence, the regular duty ratio control can be employed to use this converter as a basis for PFC control as in prior-art boost converter. However, unlike prior-art boost converter, this converter will accept both positive and negative polarity input voltage. However, to achieve that function, we need to prove that the same DC conversion ratio as in (3) will also be obtained for operation with negative polarity input voltage source.
We now postpone the detailed analysis of the resonant circuit and development of analytical results for later section on Resonant Circuit Analysis.
Operation from Negative Input Voltage
Next we analyze the operation of the converter in
V
g
DT
S=(VCr−Vg)(1−D)TS (4)
The resonant inductor Lr must be once again fully flux-balanced during the same ON-time interval DTS only so that this time:
VCr=V (5)
as the resonant inductor cannot support any net DC during this ON-time interval.
Note that the steady state DC voltage on the resonant capacitor has changed from (2) to (5), that is from VCr=0 to VCr=V.
Replacing now (5) into (4) we get the DC conversion ratio for the negative polarity input voltage as:
V/V
g=1/(1−D) (6)
which is the same as (3) for positive input polarity voltage.
Therefore, despite different DC voltages on the resonant capacitor for positive input voltage (zero) and for negative input voltage (output DC voltage), the DC conversion gain functions are equal.
The DC voltage gain of the converter when the isolation transformer turns ratio is included is then given by
V/V
g
=N
S
/N
P(1−D) (7)
Operation of the converter in
For simplicity, and without loss of generality, we assumed that the input inductor current IL is large so that the superimposed ripple current is negligible and can be considered constant at the DC level IL. The resonant solution is obtained as:
i
r(t)=IP sin(ωrt) (8)
v
Cr(t)=Δvr cos(ωrt) (9)
Δvr=IPRN (10)
R
N
=√L
r
/C
r (11)
Where RN is the natural resistance and
ωr=1/√LrCr (12)
f
r=ωr/(2π) (13)
where fr is the resonant frequency and ωr radial frequency.
The initial voltage Δvr at the beginning of resonant interval can be calculated from input inductor current IL during (1-D)TS interval as:
Δvr=½IL(1−D)/(CrfS) (14)
Substitution of (10) and (11) into (14) results in
I
P
=I
L(1−D)πfr/fS (15)
The above relationship of equal DC conversion gains as a function of duty ratio for both positive and negative polarity input voltages, makes it possible to use the same converter topology with an AC input voltage directly and with the bridge rectifier being eliminated.
The new hybrid switching method is now emerging. The ON-time switching interval for either polarity of the input voltage will result in resonant switching network for ON-time interval, and regular PWM network for OFF-time interval, thus justifying the name proposed of hybrid switching consisting partly of square-wave switching (applicable to PWM inductor L for both switching intervals) and to resonant switching applicable to resonant inductor during only the ON-time interval. Hence hybrid switching is a combination of the square-wave (PWM) switching and resonant switching having the PWM inductor and resonant inductor.
The isolated converter in
Note that the odd number of switches, three (3), is already a distinctive characteristic of this converter with respect to all conventional switching converters, which always come with an even number of switches, such as 2, 4, 6 etc. In conventional PWM converters this was dictated by the requirement of square-wave switching using both inductive and capacitive energy transfers (often called PWM switching), which requires that the switches come in complementary pairs: when one switch is ON its complementary switch is OFF and vice versa. This, in turn, is consequence of the fact that when inductances store energy capacitances are releasing stored energy and vice versa.
Here no such complementary switches exist, as one active switch S alone is controlling both diode switches, not only for positive polarity of input voltage AC line voltage but also for negative polarity of input voltage.
Note that this is accomplished with the fixed topological connection of the two current rectifiers, which automatically change their ON-time intervals and OFF-time intervals as needed by the polarity of the input AC voltage. For example, for the positive polarity of the AC input voltage, current rectifier CR1 conducts during the ON-time interval of switch S. Then for negative polarity of AC input voltage, the same current rectifier conducts during the OFF-time interval of controlling switch S. The current rectifier CR2 also responds automatically to the polarity of the input AC voltage. For the positive polarity it is conducting during OFF-time interval of switch S and for negative polarity it is conducting during the ON-time interval of switch S.
Described from the switch S controlling point of view:
Thus the three switches are operating at all times, for both positive and negative cycles of the input AC line voltage. Hence in present invention the component utilization is 100%. The efficiency is especially for the low line of 85V AC since the two diode drops of full bridge rectifier are eliminated.
Resonant Capacitor and Inductor Size
The converter in
We now describe and analyze the unique operation of the Three-Phase Isolated Rectifier of
The equality of the DC conversion gains as a function of duty ratio D of the controlling switch S for either polarity of the input phase voltage is a very important pre-requisite for a converter to operate as a Single-Stage Three-Phase Isolated Bridgeless AC-DC converter. Another important factor is that both DC conversion gains are having a step-up DC gain characteristic which is another pre-requisite needed for the converter topology to qualify as boost type PFC converter. This therefore establishes that the present invention is indeed capable to operate as Single-Stage Three-Phase Isolated Bridgeless PFC converter.
The Power Factor Correction is based on controlling the average input current of the phase to neutral converters of the Three-Phase converter in
v1=V1 sin ω t (16)
v
2
=V
2 sin(ω t−120) (17)
v
3
=V
3 sin (ω t−240) (18)
ω=2π f (19)
where f is the utility line frequency such as 60 Hz in United States and 50 Hz I Europe.
Under the unity power factor control, the corresponding phase to neutral input current of each phase are then described analytically as:
it=I1 sin ω t (16)
i
2
=I
2 sin(ω t−120) (17)
i
3
=I
3 sin (ω t−240) (18)
One extraordinary property of the above balanced three-phase system is that the instantaneous power of such a system is constant in time as shown in
v
1
i
1
+v
2
i
2
+v
3
i
3=0 (19)
Another property of the three-phase current under a unity power factor operation and a balanced load conditions (equal load in each phase) is that the sum of all three input phase currents are equal to zero, so that the current in the neutral wire is also zero despite the large fluctuations of individual phase currents as seen in the waveforms of
i
1
+i
2
+i
3=0 (20)
However, each current delivered to the output by each individual phase converter is a rectified version of the respective sinusoidal input phase current so that the total output current consists of the summation of the three rectified sine wave phase shifted in time by 120 degrees, so that the contribution of each phase to the load current is depicted with the three rectified current waveforms in
IR-RMS=3 I1-RMS (21)
where I1-RMS is rms current delivered by one of the output phases. If the magnitude of individual phase currents on input are normalized and have peak value equal to 1, that is I1=1, then total rms load current is 2.12 and individual phase rms currents are 0.707=√2/2. Note also that the load current is almost constant with only 4% (or 25 time) smaller half-peak ripplre current relative to average current. In addition the ripple current is at frequency 6 times higher them the fundamental 60 Hz line frequency or at 360 Hz effectively. Thus, this 360 Hz ripple current can be considered to have a minimal effect o the output DC load.
Note also that one should not confuse the actual phase current discussed above with the average phase currents which in the above example are 0.637 in magnitude, where 0.637=2/π and the total average load current is then 1.91.
Each individual phase converter does not store any energy and therefore delivers the pulsating power to the load, but this time, the current is not full-wave sinusoid, but instead a rectified sinusoidal current as shown in
When all three instantaneous output powers are represented on the same diagram, the three pulsating powers are again shown at twice the line frequency and add together to the constant output power as also shown in
We now turn to the analysis of the output instantaneous voltage and its ripple voltage. Shown in
The conventional Single Phase power conversion is processing the input power in three stages and sequentially as illustrated in
In the present invention of Three-Phase Isolated PFC converter, the power is processed in a single-stage, so that the rectification, PFC conversion and isolation are performed in a single power processing stage and without the need to go to high voltage intermediate DC us voltage. Furthermore, the input power is divided processed in parallel through three individual phase converters. Thus for example a total 6 kW power is processed as 2 kW power per each phase. In the prior art converter of
The low voltage stresses of the switches in the isolated extension of converter of
Transorb Implementation
The current direction in resonant inductor is changing form one direction in OFF-time interval to another direction in ON-time interval. This change of the direction of inductor current during the short transition would cause the voltage spike on the switch S. The faster the change, the bigger the voltage spike would be. However, due to small energy stored in this small inductor, this spike can be effectively suppressed by use of a Zener diode, which would limit the voltage spike but dissipate the energy in Zener diode. Since the converter operates for both polarities of the input voltage, the bi-directional Zener diode, called Transorber is used as shown in later section. This, once again would dissipate all of the spike energy and limit the spike voltage such as in the converter of
The dissipative loss can be much reduced by use of the energy recovery switching circuit, such as for example one illustrated for the pulsating input current converters of
The current rectifiers, however, change their roles automatically, depending whether the input voltage is positive or negative as described above. In conclusion, the unique converter topology in conjunction with the single resonant inductor Lr results in implementation of three switches (one active two-quadrant switch and two passive, single quadrant current rectifier switches) is one of several reasons that a single-stage Bridgeless AC-DC converter is made possible. The second reason is that a single input inductor L generates in conjunction with the above switching action, the needed step-up conversion function for either polarity of input voltage. The third reason is the presence of the resonant inductor Lr placed in series with the resonant capacitor Cr, resulting in hybrid switching operation described above, which is the method enabling the same step-up voltage gain for either of the two input voltage polarities as detailed analysis enclosed reveals.
In addition to two simple diode rectifiers the present invention, the phase converter of
From the description of the converter operation for positive and negative output voltages, it is clear that this switch S has two-quadrant switching characteristic operating in the first and third quadrant as illustrated in definition of switch S in
One implementation is to use two Reverse Blocking Isolated Gate Bipolar Transistor (RBIGBT) devices in parallel such as illustrated in
The duty ratio modulation is used to control average input current of individual phase converters. The control of input current is then accomplished in two possible ways described below. The ON-time interval starts at zero level, which effectively constricts the resonant discharge interval to exactly one-half of the resonant period, that is
D
R
T
S
=T
r/2 (22)
T
r=1/fr (23)
We have also introduced here a notion of the resonant duty ratio DR. The resonant circuit is therefore formed by the loop consisting of two resonant components, Cr and Lr, switch S and respective current rectifiers connected in series as shown earlier hence limiting discharge current to only one direction. The discharge current starts at zero and ceases to conduct after half resonant interval when resonant current becomes zero again.
There are now two possible modes of operation to control the average input current:
For highest efficiency and best operational mode, zero coasting intervals present in constant switching frequency operation should be eliminated. This is easily accomplished as follows. If the ON-time of the switch S is equal to half of a resonant period, then the resonant discharge current waveform will be exactly half a sine wave. The best mode of operation is then to keep the ON-time constant as per:
T
ON
=DT
s
=T
r/2=constant (24)
so that duty ratio is proportional to switching frequency, or:
D=f
S/2fr (25)
where ωr and fr are as defined earlier.
Thus, voltage regulation is obtained by use of the variable switching frequency fS. However, this results in corresponding duty ratio D as per (25). Note that all DC quantities, such as DC voltages on capacitors and DC currents of inductors are still represented as a function of duty ratio D only, as in the case of constant-switching frequency operation.
The waveforms of
The Three-Phase isolated PFC converter on an experimental 900 W prototype, which converts Three-Phase input voltage into a 400V isolated output voltage (1:1 isolation transformer used) with very high efficiency over the wide range.
a shows the line voltage (top trace) and AC line current (bottom trace) of one phase of 60 Hz input voltage for 110V input voltage. The Power factor was measured at 900 W load to be 0.999 and THD 1.7%.
b shows the line voltage (top trace) and AC line current (bottom trace) of one phase at 220V AC and 60 Hz. The Power factor was measured at 900 W load to be 0.991 and THD 2%.
a shows the efficiency measurements at a 900 W level over the wide input AC voltage range from 85V AC to 240V AC and
Very high efficiency of over 97% is measured over the wide input AC voltage. In particular note the very high efficiency at the low AC line voltage of 85V AC as shown in
The measurement of harmonics currents is displayed in the Table shown in
The DC gain characteristic of (3) suggests that the isolated converter would have the start-up problem as the DC gain characteristic is always greater than 1. Yet at start-up the output DC voltage is zero (discharged output capacitor) which would tend to indicate that the converter would never be able to start-up as it does not have the Dc conversion gain extending to zero at low duty ratios. However, this is not correct as this converter does have a special mode of operation at low duty ratios.
Shown in
The Single-Stage Three-Phase Isolated Rectifier PFC is provided which provides the direct conversion form three-phase input to DC isolated output. Therefore, the present invention results in several basic advantages: