This patent generally pertains to HVAC systems (heating, ventilating and air conditioning systems) and, more specifically, to under-floor air ducts.
To heat, cool, filter, dehumidify, ventilate or otherwise condition the indoor air of a comfort zone, such as a room or area in a building, the floor of some buildings have a supply air plenum between a subfloor and a matrix of floor panels that are elevated about one or two feet just above the subfloor. The floor panels, which are usually supported by a matrix of pedestals extending upward from the subfloor, provide the surface upon which the building occupants walk and furniture is set.
With an under-floor HVAC system, a supply air duct discharges fresh or conditioned supply air into the plenum, which in turn conveys the supply air to a series of supply air registers or openings in the floor panels. The registers release the supply air from within the plenum up into the comfort zone. The general goal is to have a sufficient number of properly placed registers such that the supply air rises evenly up through the comfort zone for the benefit of the occupants at floor level. As the supply air continues to rise above the occupants, the eventually used or less-than-fresh air approaches the ceiling to where one or more return air ducts extracts the air for reconditioning and/or exhausting outdoors.
One problem, however, is that if the air from the supply air duct has to travel a great distance to a remote register, the supply air might lose much of its desirable temperature by heat transfer with the subfloor, particularly if the subfloor is made of concrete with a high specific heat. Also, as the supply air travels radially from the supply air duct, the air expands and loses much of its velocity. Additional velocity is lost when less remote registers release air before that air can reach more distant registers. Thus, remote registers receiving lower pressure air tend to release disproportionately less air to the comfort zone than registers that are closer to the supply air duct.
To avoid these problems, some under-floor HVAC systems include a relatively rigid sheet metal air duct or a pliable tubular air duct that is installed under-floor in the plenum between the subfloor and the floor panels. Under-floor air ducts help channel supply air along a more directed route from the supply air duct to certain remote registers. A drawback of such installations, however, is that under-floor air ducts, particularly pliable ones, tend to retract and extend longitudinally in response to changes in duct pressure. The resulting sliding movement can create noise and abrade the duct material. Moreover, there are endless possible floor layouts with various supply airflow needs, thus it can be difficult and expensive to custom build numerous air duct systems to meet all those needs.
Certain examples are shown in the above-identified figures and described in detail below. In describing these examples, like or identical reference numbers are used to identify the same or similar elements. The figures are not necessarily to scale and certain features and certain views of the figures may be shown exaggerated in scale or in schematic for clarity and/or conciseness. Additionally, several examples have been described throughout this specification. Any features from any example may be included with, a replacement for, or otherwise combined with other features from other examples.
A building floor 10, shown in
To create an air duct system 28 that ensures supply air 20 is evenly distributed or properly apportioned across comfort zone 26, a distribution air duct 30 is installed within plenum 18. Distribution air duct 30 receives supply air 20 from a supply air chamber 32 fed by supply air duct 22 and conveys supply air 20 to wherever it is needed. Distribution air duct 30 is particularly useful for conveying supply air 20 to remote areas of comfort zone 26 that are quite distant from supply air chamber 32.
For sake of example, distribution air duct 30 is shown to include two runs, a straight run 34 and a longer L-shaped run 36; however, any number of runs, shapes or branches of runs are well within the scope of the methods and apparatus described herein. Although the actual construction, assembly and installation of distribution air duct 30 may vary, example runs 34 and 36 are tubes of pliable material, thus distribution air duct 30 generally inflates when pressurized by supply air 20 and tends to collapse (i.e., sag or deflate) when supply air 20 is turned off. The pliable material of distribution air duct 30 can be cloth fabric, sheets of plastic or rubber, porous, nonporous, perforated, nonperforated, and various combinations thereof.
Run 34 of distribution air duct 30 comprises a pliable tubular inlet collar 38 at a proximal end 40 of run 34, a first duct segment 42 that can be porous or nonporous, a second duct segment 44 that is preferably perforated although not necessarily so, and an end cap 46 at a distal end 48 of run 34. To release more supply air 20 near distal end 48, second duct segment 44 includes a series of discharge air perforations 50. First and second duct segments 42 and 44 are examples of an upstream tubular wall section and a downstream tubular wall section, respectively, with first duct segment 42 being more or less air permeable than second duct segment 44. Alternatively, or to release even more supply air 20 near distal end 48, end cap 46 can be provided with a discharge opening 52. The amount of supply air 20 discharged through end cap 46 can be adjusted by tightening or loosening a drawstring 54 at the throat of discharge opening 52. An example of end cap 46 can be found in U.S. Pat. No. 6,558,250.
To assemble run 34, a strap clamp 56 fastens inlet collar 38 to a rigid tubular flange 58 that conveys supply air 20 from supply air chamber 32 to the interior of run 34. To balance or apportion the airflow between runs 34 and 36, a conventional baffle (not shown) can be installed within tubular flange 58. Inlet collar 38, first and second duct segments 42 and 44, and end cap 46 can be joined end-to-end via any suitable fastener 60 including, but not limited to, a zipper running circumferentially around the adjoining pieces. Once assembled, run 34 of distribution air duct 30 can simply rest upon subfloor 16 for vertical support.
For horizontal support, however, or to prevent run 34 from sliding around or repeatedly extending and retracting due to changes in air duct pressure, a fastener 62 preferably connects distal end 48 to one or more pedestals 14. In some examples, fastener 62 comprises an elongate pliable member 64 (e.g., cable, strap, chain, rope, cord, wire, etc.) that connects a loop 66 (e.g., hook, snap connector, etc.) that is sewn or otherwise attached to one end of second duct segment 44. To provide run 34 with horizontal support in two dimensions, elongate pliable member 64 can be attached to two or more pedestals 14 in a generally V-shaped layout as shown in
To aid service personnel in maintaining or troubleshooting air duct system 28, distribution air duct 30 preferably includes a series of decals 68 (e.g., label, tag, visual marker, sign, arrowhead, etc.) that are distributed along the upper surface of distribution air duct 30. Decals 68 are best placed at intervals that correspond to the standard dimension of floor panels 12 so that whenever any floor panel 12 above distribution air duct 30 is lifted for service reasons, such as panel 12′ of
Run 36 is similar in construction to run 34. Run 36 comprises inlet collar 38 at a proximal end 72 of run 36, first duct segment 42, a right-hand tubular elbow 74 made of a pliable material, a relatively long duct segment 76 that can be porous or nonporous, second duct segment 44, and a closed end cap 78. Similar to run 34, strap clamp 56 fastens inlet collar 38 to tubular flange 58, and the various pliable duct segments 42, 44 and 76, inlet collar 38 and elbow 74 can be joined end-to-end by way of zippers.
Run 36 includes a first distal end 80 at elbow 74 and a second distal end 82 at end cap 78. Fastener 62′ and loop 66 anchors second distal end 82 to pedestals 14a and 14b, and fastener 62″ anchors elbow 74 to pedestals 14c, 14d and 14e. Fasteners 62′ and 62″ each can be made of a single elongate member with multiple legs or multiple individual elongate members.
Since there are endless possible floor layouts with various supply airflow needs, it can be difficult and expensive to custom build numerous air duct systems to meet all those needs. To address this problem, air duct system 28 preferably is assembled from a predefined assortment of duct segments 83, as shown in
To create the two-run distribution air duct 30 after defining assortment 83, one strategically chooses a collection 88 of duct segments from assortment 83, wherein collection 88 is depicted by the parts encircled by the dashed lines in
The just-described modular method of assembling a distribution air duct is best achieved when duct segments 42, 44 and 76 are of predefined lengths that are substantially whole number multiples of standard width 70. If, for instance, standard width 70 is two feet, predefined short first duct segment 42 can be two, four, six, eight, . . . 2n feet long. The same is true for predefined long duct segment 76 but with long duct segment 76 being longer than short first duct segment 42.
At least some of the aforementioned examples include one or more features and/or benefits including, but not limited to, the following:
In some examples, an air duct system for a building comprises a collection of pliable tubular segments that are assembled end-to-end to create a distribution air duct that rests upon a subfloor below a plurality of removable floor panels. To help keep the distribution air duct from sliding freely along the subfloor, the air duct is held taut by anchoring a distal downstream end of the duct to at least one and preferable two or three pedestals that help support the floor panels above the subfloor.
In some examples, a distribution air duct is assembled from a collection of pliable tubular segments chosen from a predefined assortment of segments, wherein the assortment of segments are of discrete lengths based upon the width of a standard floor panel.
In some examples, a distribution air duct made of one or more pliable tubes rests directly upon a subfloor, thereby eliminating the need for any overhead mounting support, such as an overhead cable or track.
In some examples, a pliable distribution air duct includes a series of flow direction indicators that are distributed along the length of the duct at a spacing interval that corresponds to the width of a standard floor panel.
In some examples, an under-floor distribution air duct includes an end cap with an adjustable discharge opening.
Although certain example methods, apparatus and articles of manufacture have been described herein, the scope of the coverage of this patent is not limited thereto. On the contrary, this patent covers all methods, apparatus and articles of manufacture fairly falling within the scope of the appended claims either literally or under the doctrine of equivalents.
This patent arises from a continuation of U.S. patent application Ser. No. 16/397,692 (now U.S. Pat. No. 11,231,189), which was filed on Apr. 29, 2019, and which is a continuation of U.S. patent application Ser. No. 12/196,999 (now U.S. Pat. No. 10,274,216), which was filed on Aug. 22, 2008. U.S. patent application Ser. No. 16/397,692 and U.S. patent application Ser. No. 12/196,999 are hereby incorporated herein by reference in their entireties. Priority to U.S. patent application Ser. No. 16/397,692 and U.S. patent application Ser. No. 12/196,999 is claimed
Number | Date | Country | |
---|---|---|---|
Parent | 16397692 | Apr 2019 | US |
Child | 17583186 | US | |
Parent | 12196999 | Aug 2008 | US |
Child | 16397692 | US |