Tapchanging voltage regulators providing a regulating range of +/−10% are used on single and three phase power distribution lines. Some electric power distributions substations use sets of three regulators on three phase distribution lines as they leave the substation. Usually each regulator is supplied by a single phase transformer for reducing the voltage from that of the substation primary feed to the voltage of the regulator. Regulators so applied are referred to as “station regulators”.
Other substations supply voltage reduced by a single three phase transformer feeding lines from a distribution substations to users of electric power. Such transformers have taps on the winding switched by a tapchanging switch. Control devices for such switches are known as Load Tapchanging (LTC) Controls. Such devices control all three phase voltages based on sensing but one of the three phases.
In either instance line regulators are used along single and three phase distribution lines which extend from distribution substations for re-regulating the voltage where required. Regulators are often referred to as “station” or “line” regulators depending on their location even though they may be identical in construction.
Regulators are also used in large industrial complexes to regulate voltages to compensate for varying processing loads. To reduce the fire hazard of oil filled regulators there is a need for dry type regulators to regulate voltages in very tall buildings.
Prior art regulators generally use an autotransformer with 16 steps for raising and 16 steps for lowering the voltage by up to 10%. The steps are changed by a motor driven tapswitch. The 16 steps are derived from eight transformer taps using a bridging autotransformer to form a voltage step midway between each pair of autotransformer taps.
For economy of autotransformer construction, prior art regulators often use a single eight tap winding that is reversed so as to either raise or lower voltages by a combination tapchanging and winding reversal switch. Improvements in cost realized from polarity reversal may be partially offset by increased switch cost of the switch and the need for a larger switch drive motor. In the construction of either LTC transformers or regulators the transformer and switch are housed in a tank filled with oil.
To enable changing a regulator for maintenance without shutting off power, it is necessary to place the regulator in neutral and bypass the regulator. The bypass is accomplished by a lineman either using a temporary jumper cable or by operating a permanently mounted by pass switch operated by an insulated hook switch. Tanks have been known to explode with deadly results when a bypass cable was installed when the regulator was not truly on neutral and the lineman was not in a safe location.
This prior art material together with non-inventive
An RS232 “COM2” port is shown for connecting a computer with a user interface program for such things as entering setpoints and obtaining historic and present data.
LEDs light to indicate the tapchanger motor operating to “RAISE” the tap position and another to indicate operation to “LOWER” the tap position. Power may flow in reverse through the regulator to nearby loads from a power feed at the end of a distribution line. When this happens the “REV PWR” LED lights. An “OK” LED lights when power is on and the control is operating properly as determined by self checking features of the control.
In
The inventive regulator uses a series transformer connected between source and load connections. A shunt transformer is connected between the load connection and selected taps on a secondary winding of the series transformer. Taps are selected by a tapchanger control device operating in conjunction with a hydraulic/pneumatic contact mover and control. A linear tapswitch performs the tap selection and microswitches are used by the tapchanger control device to identify each of 17 tap positions. The taps include eight 5/8% raise taps, eight 5/8% lower taps and a neutral tap giving +/−5% voltage regulation. Voltage regulation automatically changes direction when the power direction reverses. When used in a Beckwith Electric Co. Autodaptive™ system voltages are held by the system well within the +/−5% range of the inventive regulator.
No external potential or current transformers are required.
The series winding provides the power to the load required to raise the load voltage and accepts power back to the source when lowering the load voltage.
Beckwith Electric Company BLUEJAY™ Wireless equipment provides a user interface complemented by light indicators visible from a safe distance. Wireless commands can be used to set the regulator on manual operation and then to manually raise or lower the regulator tap position.
The regulator can be operated in a system using a wirelessly controlled electrically operated regulator bypass switch. This permits a lineman using a PDA or laptop computer to manually operate the regulator and to bypass the regulator from a safe remote location.
Controls can be exchanged without taking the regulator out of service.
a and 7b are two views of the sliding commutating tapswitch contact used for limiting transient current flow when changing taps.
c identifies meanings of cross hatches used on figures herein.
a and 10b are two views of the series transformer.
a and 11b are two views of the shunt transformer.
a, 12b and 12c are views of the tapchanger control device socket and box illustrating methods of inserting and removing the control.
Beckwith Electric products using above reference invention 1 have been given the trademark Autodaptive™.
Beckwith Electric products using above reference inventions 2 and 3 have been given the trademark BLUEJAY™.
The present invention is directed to two embodiments of the invention. In comparison with
The first embodiment uses fire retardant insulation for two transformer windings so as to permit safe indoor use. These transformers have connection terminals to the source and load power lines.
The first embodiment is intended for use in high rise buildings where fire resistance greatly improves the buildings' safety. The regulators are located by an architect at one or more floors who will also use Autodaptive™ switched power factor capacitor banks on each floor. The Autodaptive™ thereby provides automatic +/−1% voltage control at all times of the day throughout the building. This is expected to improve the efficiency in the use of electric power in the building by approximately 5%. Note that the present invention is limited to the improvements obtained by use of the first embodiment regulator.
The inventive regulator uses series transformers 54 with primary windings 40 connection terminals 1 for connection to the source of electric power and primary windings 40 connection terminals 2 for connection to the load for electric power thereby sensing the differential in voltage across the regulator. This voltage varies between +5% rise from source to load to −5% drop from source to load. One half way between these two extremes the voltage drop is zero with no change in voltage from the regulator.
The secondary winding 41 of transformer 54 has 17 taps corresponding to +/−5% change from 16 taps with a neutral tap in the center making the total of 17 secondary winding 41 taps. The neutral tap (N) is connected to ground. A sliding contact 42 connects selected ones of the 17 taps to be connected to a load bar 43.
Shunt transformers 46 have connection terminals 3 for connection to said load for electric power and connection terminals 4 connected to load bar 43. A winding 48, having connection terminals 5 and 6, on transformers 46 carry a voltage, selectively of 3 Vac, to tapchanger control devices 47. Tapchanger control devices 47 use this voltage in a measurement of load voltage between load connection bushings 45 and ground. It also uses this voltage to develop a voltage, selectively +3 Vdc, for operating tapchanger control devices 47 and fluid pressure contact mover and control devices 49.
A current transformer 50 with burden 51 measures the regulator load current and is connected to tapchanger control devices 47 for use in computing the regulator load in Watts and VArs. Three wire connections are made to load current CTs 50, two connections to tapchanger control devices 47 and CTs 50 center taps to ground. CTs 50 and its burden 51 are designed to produce a full cycle of load current analog voltage input to tapchanger control devices 47 to convenience the scaling to the digital form of the current. The CTs 50 center taps permit tapchanger control devices 47 to sense both half cycles of the current wave to properly measure distorted load currents. Burdens 51 are designed to suppress voltage transient damage resulting from abnormal currents caused by power line faults on the regulator load. In this way damage to tapchanger control devices 47 circuity from line faults is prevented.
Sliding contacts 42 operates one of 17 microswitches collectively marked 52. These microswitches 52 have one common terminal connected to ground and the other 17 non-common terminals connected to tapchanger control devices 47. Pull-up resistors within tapchanger control devices 47 place +3 Vdc on the 16 microswitches 52 not closed by the position of sliding contact 42. The microswitch 52 closed by the position of sliding contact 42 reduces the +3 Vdc to zero thereby providing tapchanger control devices 47 an indication of which one of the 17 tap positions is selected by sliding contact 42 at any point in time.
Taps on windings 41 are marked from +1 through +8 representing 5/8% increase per tap in voltage through the regulator from source to load as selected by the sliding contact 42. Taps on windings 41 are marked from −1 through −8 representing 5/8% decrease per tap in voltage through the regulator from source bushing 44 to load bushing 45 as selected by the sliding contact 42. Each winding 41 tap marked (+) selected by sliding contact 42 will raise the load bar 43 above ground adding to the load voltage existing on load bushing 45 connection terminal to ground. Each winding 41 tap marked (−) selected by sliding contact 42 will lower the load bar 43 below ground subtracting from the load voltage existing on load bushing 45 connection terminals to ground.
The tapchanger control devices 47 compute the load voltage to ground by combining the voltage obtained from transformers 46 winding 48 terminals 5 and 6 with the voltage added or subtracted from load bar 43 as indicated by the closed microswitch 52 indicating the winding 41 tap position.
The connections from microswitches 52 are also used to provide the following light outputs from four arrays 53 of LEDs visible at a safe distance from the tapchanger control devices 47:
This diagram is identical with that described above under
The second embodiment is intended to fulfill the requirements of a portion of the of the worldwide market for regulators as defined by the following boundaries:
Note that regulators are used from line to ground making the nominal voltage of the inventive regulator from source or load to ground 8400 Volts ac.
Note also that wherever a regulator ground and/or a user electrical load ground have an indeterminate voltage difference from true earth ground that the quality of the effective voltage regulation from regulator to user may be compromised.
The invention has three major objectives as compared to prior art regulators:
The flow of power through the inventive regulator is as follows:
When the sliding contact 42 is on any position +1 through +8, the tapchanger control devices 47 are calling for a raise in voltage through the regulator and the proper amount of power is sent from the series transformer 54 to the shunt transformers 46 where it is received and sent to the load thereby increasing the load voltage to a desired level. When the sliding contact 42 is on any position −1 through −8, the tapchanger control devices 47 are calling for a lowering in voltage through the regulator and the proper amount of power is sent from the load, through the shunt transformers 46, through the series transformers 54 where it is received and sent back to the source thereby decreasing the load voltage to a desired level.
When the sliding contact 42 is on the “N” microswitch 52 tap position there is no voltage from the source to the load therefore there is no power flow through the regulator.
The sliding contact 42 is moved selectively using pressures within the oil which fills an embodiment 2 regulator. Whichever microswitch 52 closes as a result of the move is used to stop the sliding contact 42 when centered on a tap position. In dry type embodiment 1 regulators air pressures are used to move sliding contact 42.
a and 7b show two views of the first end of sliding contacts 42.
c indicates the background shading used to indicate material, copper, fluid or current limiting material as used herein.
Tapchanger control devices 47 are seen mounted on the outside surface of center tanks 74. On the controls are seen lights 55, 56, 57, 58 and wireless communications antennae 59. These items were described in greater detail under
The bushings 44 and 45, the series transformer 54, the tapswitch 60, and the shunt transformer 46 are fastened together mechanically and have lifting eyes not shown for removing the entire structure from the center 74 and lower 75 tanks. The upper tank can be lifted off by opening the upper bolt circle 78 and the bushing retainers 71 and 72. With upper tank 73 and tapchanger control devices 47 removed the oil tight socket for tapchanger control devices 47 may be removed and the entire structure lifted out of the lower two tank sections.
Tapswitches 60 are then in open view. The sliding contact 42 can be removed and the current limiting slabs 66 replaced. Other repairs can be made if found necessary.
a and 10b are two views of the series transformer 54 with the transformer primary windings 40 and secondary windings 41 encased in a molded fire retardant material. This provides the necessary winding insulation for dry type indoor use and improves the control of voltage gradients when used in an oil filled regulator.
a and 11b are two views of the shunt transformer 46. The transformer 46 primary windings 9 and secondary windings 48 are encased in a molded fire retardant material. This provides the necessary winding insulation for dry type regulators for indoor use and improves the control of voltage gradients when used in oil filled regulators.
a, 12b, and 12c illustrate tapchanger control devices 47 and shows the control sockets 85. The tapchanger control device 47 can be removed from sockets 85 with the tapswitch staying on the last position before control removal. Load voltage regulation will, of course, cease.
Tapchanger control devices 47 use control printed circuit (PC) boards 87 which are connected by flat blade connectors 84 to control sockets 85. Flat blade connectors 84 are shown in the socket view, the side view and the front view of
The tapchanger control devices 47 performs several functions:
Power reversal through the regulator is recognized by the controls. Prior art regulators following reference 1 U.S. Pat. No. 5,646,512 issued to Robert W. Beckwith, the present inventor, use a keep track method to determine regulator tap position. Existing prior art programs determine the real and imaginary components of power flow through a regulator with the change of sign of the real power flow used as the indication of power reversal.
Tapchanger control devices 47 continuously compute the real and imaginary components of power flow using load voltage from windings 48 of transformers 46 corrected for increase or decrease in voltage by currents from load bars 43 together with full wave current from center tapped CTs 50 all as shown on
In a substation application using the inventive regulator on three phases of several outgoing three phase lines, the communicating computer may be in a fixed location eliminating hard wiring within the substation.
The user interface computer can be used for determining that the regulator is on the neutral position and then for operating wirelessly controlled electrically operated regulator by pass switches 92. For maximum safety in this operation the following can be done to protect the system for misuse either from operator error or by unauthorized persons:
As shown by
Since a motor operated bypass switch is not presently available a motor operated actuator with wireless control is provided to operate existing mechanical switches. These switches are known to safely bypass the regulator and open circuits from the regulator without interrupting power flow. Security can be provided against unauthorized operation by use of a key operated switch in the motor power source which is only closed when the wireless operation is about to be made using the user interface computer at a safe distance from the regulator.
Preferably communications is via prior art Beckwith Electric BLUEJAY™ communication techniques. These products operate as described in references 2 and 3, cited above.
The motor operated regulator bypass switch can be added as an option to give the lineman greater security by allowing operation from a safe distance. A high speed fuse can be used in the bypass circuit which may prevent the regulator from exploding should the regulator not be on neutral.
Whether or not the motor operated by pass is used, a user interface program is used in a battery operated lap-top computer or in a PDA. This can be used to enter and change setpoints in tapchanger control devices 47 or to obtain data. Tapchanger control devices 47 have sufficient memory to hold four weeks of operating information with a time resolution of six minutes. The user interface computers use passwords to avoid unauthorized operation of the regulator or the bypass switch.
The preferred form of the inventive regulator shown in
One use of the preferred form of the regulator is to regulate voltages midway along three phase 13 kV power distribution lines feeding electric power to homes and businesses from electric distribution substations. Some electric power companies may also use the inventive regulator on each phase of three phase lines leaving electric power distribution substations.
The present inventive regulator can be modified for regulators meeting the requirements of other portions of the world market where different voltages and frequencies are used.
This patent application claims the filing date of provisional patent application Ser. No. 60/478,195 of Robert W. Beckwith, filed on Jun. 6, 2003. The title has been changed.
Number | Date | Country | |
---|---|---|---|
60478195 | Jun 2003 | US |