The field of invention is related to vane-type compressors, expanders, and the integral compressor/expander.
Virtually all of the existing air-conditioning, heat pump, and refrigeration systems operate on a thermodynamic cycle using a compressor, condenser, expansion valve or expansion-device, and evaporator. System efficiency (Coefficient-of-Performance COP) is largely dependent on the compressor efficiency.
Now currently, piston-based auto air-conditioning system compressors are the most commonly used, even though they typically have only isentropic efficiencies of about 55%, the other 45% corresponding to wasteful internal energy losses of largely leakage and friction.
Devising detailed ways to minimize the huge 45% losses is the subject of this patent. In addition, a suitable expander can recover expansion energy normally wasted, leading to significant reduction in power consumption.
North American auto air-conditioning, for one example, consumes over 27 Billion dollars worth of fuel annually, with commensurate global warming effect from CO2 produced, so doubling compressor efficiency could have huge effects. Range limitation in electric vehicles is another huge issue, indicating the need for vastly improved air-conditioning systems, and heat pumps.
Vane-type compressors have the potential to reach high efficiency. Studies have shown which internal leakage and friction losses are most significant. Minimizing these losses by careful detail design is outlined, and collectively are the key to raising isentropic compressor efficiency significantly.
Similar solutions can be applied to vane-type expanders, and in particular the integral compressor/expander. A well-designed vane-type expander can recover expansion energy that is normally wasted passing through the expansion valve or device. System COP can be improved by up to ˜30% with current refrigerant fluids.
The first major region of significant energy loss is the rotor-flat-end/casing clearance. Traditionally this is reduced to only about one thousandth of an inch clearance, yet must accommodate thermal expansion. Refrigerant vapor leakage, and oil suppression of leakage must be adjusted for minimal net energy loss. Vapor leakage increases with clearance, and oil flow with clearance cubed, while oil-shearing friction is inversely proportional to clearance. Oil viscosity can vary significantly due to refrigerant solubility and local temperature. A further complication is due to the factor-of-ten speed variation, typical of belt driven auto air-conditioning compressors.
One solution is to eliminate the large leaking area of the conventional rotor-flat-end clearance and replace by some suitable low-friction seal. The key is the type of seal, and use of a seal consisting of a wearable thermoplastic ring, mounted in the static casing and pressed onto essentially hardened discs at the rotor ends via an elastomeric ring achieves requirements. The same refrigerant fluid exists on either side of the seal, so slight leakage is acceptable, making this type of seal viable.
Additional seal features are a cut, or lap joint, in the ring to allow for thermal expansion, and means to locate the cut at a suitable radial location for minimal local pressure difference and hence local leakage. An alternative consists of an uncut ring with sealing at a fine shaped deformable tip. Local oiling on the high-pressure side, or sides, of the seal suppresses leakage from imperfections and lubricates. Increasing clearance, and minimizing the area adjacent to the seal under oil shear, can reduce this local friction loss significantly compared to other designs. Seal friction can be made even less, by promoting hydrodynamic lubrication, and the limiting rpm increased.
A second region of significant leakage is at the minimum clearance, where the rotor almost touches the casing, separating high-pressure refrigerant fluid from low-pressure fluid. Here again clearance in current machines is about a thousandth of an inch, and thermal expansion must be accommodated. Viscous oil injection can inhibit refrigerant vapor leakage, but oil flow must not lead to excessive out-gassing and heating of the inlet refrigerant fluid, or complete loss of oil in the sump due to excessive oil flow.
In the case of auto units, that are belt driven, the rpm can vary from about 600 to 6000 rpm depending on engine speed, creating problems using a shaft driven oil pump. In addition oil viscosity can vary by three orders of magnitude, depending on temperature and refrigerant solubility. The oil can be supplied to the clearance either via a pumped jet arranged to largely flood the clearance, or pushed ahead of the vanes if supplied at lower pressure.
The solution, in the case of pumped oil, is to keep the oil supply pressure steady, irrespective of rpm, via a relief valve. An additional reduction in oil flow can be achieved by cooling the oil to increase its viscosity.
Friction is the third major energy loss, and it has been shown that the friction of the vane tip rubbing on the casing is the dominant friction loss. The solution is to provide an oil film on the casing inside surface that promotes vane skidding on oil. The coefficient-of-friction drops from about 0.1 to 0.001 for one hundredth the friction with hydrodynamic lubrication. Data for journal bearings indicate the effect of rpm, viscosity and pressure effects to a first approximation. Supplying a radius to the vane tip, and casing covering of adequately viscous oil is indicted for minimal friction.
A fourth effect, on reducing the system power consumption, is achieved via an expander mounted on the compressor drive shaft. Similar internal details are needed to make the expander leakage and friction negligible. An efficient unit can recover up to 20% of ideal compressor power that is conventionally wasted as pressure drops through the expansion valve. System COP improvement can reach almost 30% with current refrigerants.
A fifth leakage area is past the edges of the vanes but is usually of small value. By supplying oil to a slight recess in the vane edge, this loss can be minimized.
U.S. Pat. Nos. 5,819,554, 5,769,617, and 7,823,398B2 discussed vane-type expanders, and integral compressor/expander designs. The detailed compressor energy minimization techniques above can obviously also be applied to individual expanders and integral compressor/expanders, and to circular rotor and elliptical casing designs.
Heating and cooling can be achieved via a reversible heat pump system. In the case of a compressor with energy recovery expander, the use of an additional 6-way reversing valve leads to viability.
A casing 1, contains a rotor 2, mounted on a shaft 3, supported in bearings 4, and connected to an external drive system via the shaft end 5, the rotor being positioned in the casing such that a minimal clearance 6 occurs at one position, the low pressure refrigerant fluid enters at port 28 leading to inlet volume 7, where it is compressed as the rotor rotates to a high pressure region 8, the rotor having a plurality of slots 9, containing substantially rectangular vanes 10, which have profiled tips 11, the rotor having hardened cylindrical discs 12, on which seals 13 (see
Reading
Reading
An individual expander would have an axial section as