The present inventions relate generally to building management systems, and more particularly, to a building management system for providing safe rooms to reduce the spread of viruses.
The Covid-19 pandemic of 2020 has raised significant safety concerns due to the contagious nature of this virus and its potentially deadly consequences. One solution that has been widely adopted is mask wearing and social distancing. This effort has been moderately successful in reducing the spread and exposure to the virus. However, mask wearing and social distancing can be difficult to practice in some settings such as indoor offices, and particularly conference rooms and the like. Moreover, even where mask wearing and social distancing are practiced in such environments, occupants may still feel unsafe in indoor environments since masks and social distancing cannot completely prevent the transmission of all viruses. Thus, improved building systems would be desirable that can more effectively reduce the spread of viruses between occupants.
A building management system is described for minimizing the spread of viruses between occupants of a room in a building. The system includes a ventilation system that supplies fresh air to the room and removes old air. A sensor measures a property which is used by a controller to operate the ventilation system. An indicator is also provided that may be observed by users in order to determine the status of the room. The invention may also include any other aspect described below in the written description or in the attached drawings and any combinations thereof.
The invention may be more fully understood by reading the following description in conjunction with the drawings, in which:
In the described Building Management System (BMS) room sensors may be used in an automation system to control rooms within the building to provide a safe environment for users of the rooms. Providing a safe indoor environment in rooms, workplaces and buildings may be more challenging when there are additional restrictions required due to a pandemic or epidemic, such as spread of Covid-19 during 2020. Two safety considerations are particularly important to ensure a safe indoor environment during a pandemic, which includes providing safe and healthy air to breath in a room, and having enough space available in the room to maintain safe physical distancing. In system and method described herein may be especially helpful in providing a safe indoor environment despite risks associated a single or multiple viruses.
Although building systems exist to manage air quality in buildings, systems do not currently exist with the ability to indicate and/or provide a safe indoor environment against a single or multiple viruses, such as Covid-19, etc., either in touch-free or touch system configurations. Conventional and currently available room sensor systems typically require physical interaction with the users of the rooms. For example, a user may need to physically touch the sensor to engage the screen (if any), adjust set points, change viewing parameters, initiate overrides, review the indicators, etc. Moreover, room sensor systems currently available in the market are not able to provide a safe indoor environment and/or specific information and/or indications regarding the safety status of a room based on governmental or medical safety guidelines and benchmarks for specified viruses, such as Covid-19.
The intelligent pandemic safe room system described herein may be used in a touch-free safe mode which is not presently available. By activating this mode, the system may sense room data, such as temperature, humidity, volatile organic compounds (VOC), carbon dioxide (CO2) levels, Bluetooth Low Energy (BLE) strength, etc. The system also communicates with a room controller as a part of the building management system (BMS). The controller may then use programmed algorithms to take measures to control room safety and provide indicators to users of the rooms. Thus, the system may provide a safe indoor environment against pandemic-causing viruses while offering a safe touch-free user interaction with the sensors, indicators and user interfaces. User interaction may be performed through a dedicated smart phone app, BLE, voice recognition, hand gestures or any other means to communicate without physical contact. Moreover, a clear touch-free feedback may be displayed by the system to the user to indicate the safety status of the room under various circumstances considering virus specific safety benchmarks, e.g., Covid-19, and compliance with such safety benchmarks for both indoor air health/safety and physical distancing standards. Thus, the system may provide an easy to understand display to the user that indicates whether safe and healthy air is provided in the room or not and/or whether there is enough space in the room to maintain safe physical distancing by users or not.
The pandemic safe room system may be able to control the environment of a room before a room is occupied and while a room is occupied. In one possible mode, touch-free operation of the room is possible with auto-initiation safe preparation of the room by the BMS before and even after a room is occupied. This may be implemented through an elevated air-exchange initiation to refresh the air in the room when it is unoccupied and to increase air flow velocities within the room. This may be set up to be in compliance with a virus specific safety benchmark on safe indoor environment requirements to reduce virus transmission risk. In addition, when a user is approaching the room, a safety indicator installed outside the room may also indicate the status of system and whether it is safe to enter the room or not through an obvious visual indication, such as multi-colored LEDs (e.g., red, green, etc). This may also be reported to the user through a phone app indication. The safety status of the room may also be used to manage the room entrance door, e.g., access to the room may not be granted when the room is not safe to enter.
In another possible mode, a touch-free indication of room safety may be displayed when a room is occupied. This may be done with an intelligent Machine Learning algorithm to estimate whether there is enough room available for the occupants in the space to maintain safe physical distancing to minimize the spread of any virus. The system preferably indicates whether the room is safe or not through an obvious visual indication, such as multi-colored LEDs (e.g., red, green, etc), a phone app, etc. The system may also provide internal contact tracing to determine who an infected person came into contact with. To review additional room parameters, users of the rooms may interact with the system through a phone app, Bluetooth, BLE, voice recognition, physical gestures, or other touch-free communication methods which may reduce the potential for any contamination of the user interface (e.g., a touchscreen), indicator, sensor, occupant's bodies, etc. and any subsequent cross contamination of the occupants.
One algorithm that may be implemented by the system is shown in
In another case, rooms may be non-bookable such that use of the room cannot be predicted. In this case, data collected from the room or adjacent thereto may be used to inform the controller about when the room is about to be occupied or about conditions in the room while it is being occupied. For example, data may be obtained from occupancy sensors, such as passive infrared sensors (PIR), lights, a phone app connected to the BMS by Wi-Fi, BLE, etc., or any other data sources and mechanisms to detect occupancy. In response to inputs from the data sources, the controller ventilates the room in the most efficient manner possible, considering that the speed of ventilation may need to be increased, while clearly indicating the process and the room status. When the room is determined to be safe for occupation considering the specified virus safety benchmarks on safe indoor environments, the system may indicate to users that the room is safe. The user of the room may also be allowed to adjust the temperature, lights, etc. using their smart phone, Bluetooth, BLE, voice recognition, hand gestures or any other touch-free methods.
Another algorithm that may be implemented by the system is shown in
The system herein may be especially useful in addressing building safety concerns and making buildings pandemic resistant. One advantage of the system is the use of touch-free and safe user interfaces. Feedbacks via clear room indications, e.g. a room sensor LEDs, phone app, etc., may provide an indication of whether the room is safe or not considering the specified virus safety benchmarks, such as Covid-19 safety benchmarks on safe indoor environments. The indicators may include healthy safe air and physical distancing indications. Clear and visual touch-free indications may be provided for virus safety levels of occupied and unoccupied rooms. Real-time indications of the safety level in an indoor environment against viruses may provide increased reassurance. An auditable history of the safety indicators for an indoor environment may also be possible using the BMS system. Ventilation of a room may be initiated in response to detecting the CO2 level as a measure of the room air safety based on a determination of the number of users in the room. Ventilation may also be done automatically after a meeting has been completed (i.e., when the users leave the room) using occupancy sensing and/or a scheduling system. For example, the system may include an automatic unbookable time after each booked meeting during which the room is ventilated. Room history and room safety records may also be retained as a track and trace assistant. For example, the track and trace assistant may include a history of the room CO2 level and meeting attendees in a report. The system may be especially useful in managing virus occupancy guidelines, for example, Covid-19 occupancy guidelines. Touch-free operation (e.g., via a phone app, Bluetooth, BLE voice recognition, hand gestures or any other touch-free methods) may also be used for temperature setpoint adjustments, lighting, blind control and other room control functions. Room access permission, room air exchange and air velocity may also be controlled. For example, ventilation may be adjusted so that the room supply air/extract fan(s) runs at a higher speed when the room is vacated. Ventilation may run at the highest fan speed for a pre-set period to reduce any virus-related risks, such as Covid-19 related risks. CO2 concentration may also be used to determine ventilation requirements in order to satisfy indoor environment benchmarks.
A schematic of a building 10 with a building management system (BMS) is shown in
The sensors 22 may monitor properties in the rooms or may collect other data about the rooms, building and/or users. For example, the sensors 22 may include a temperature sensor, a humidity sensor, a VOC sensor, a CO2 sensor, a BLE sensor, a voice recognition module, a PIR sensor, a WiFi device or phone app. Preferably, the sensors 22 are non-contact sensors that do not require the user to contact a surface that is also contacted by other users. The indicators 26 are also preferably non-contact indicators that do not require the user to contact a surface that is also contacted by other users in order to view the status of the indicator. For example, the indictors 26 may be multi-colored lights where a green light is visible when the room 12 is safe, a blue light is visible when ventilation is in process in the room 12, and a red light is visible when the room 12 is not ready to be occupied. Similar status information may also be reported to the user through a phone app. The controller 28 preferably determines the number of users that will be occupying the room 12 and/or the number of users currently occupying the room 12. The controller 28 may also determine a size of the room 12 relative to the number of users that will be occupying the room 12 and/or the number of users currently occupying the room 12 (i.e., space per person). The controller 28 may also have access to a calendar database that schedules appointments of the users for the rooms 12. In response to the number of users, space per person and/or calendar database, the controller 28 may operate the ventilation system 18 and the indicators 26 to ensure a safe room 12 for the users. For example, the ventilation system 18 may be operated in response to the number of users, space per person and/or calendar database. The indictors 26 may also be operated in response to the number of users, space per person and/or calendar database. Preferably, the controller 28 operates the ventilation system 18 individually for each of the rooms 12. It is also preferred for the controller 28 to have access to a medical safety benchmark for a virus such that the controller 28 operates the ventilation system 18 and/or indicators 26 in response to the properties collected by the sensors 22 and the medical safety benchmark.
While preferred embodiments of the inventions have been described, it should be understood that the inventions are not so limited, and modifications may be made without departing from the inventions herein. While each embodiment described herein may refer only to certain features and may not specifically refer to every feature described with respect to other embodiments, it should be recognized that the features described herein are interchangeable unless described otherwise, even where no reference is made to a specific feature. It should also be understood that the advantages described above are not necessarily the only advantages of the inventions, and it is not necessarily expected that all of the described advantages will be achieved with every embodiment of the inventions. The scope of the inventions is defined by the appended claims, and all devices and methods that come within the meaning of the claims, either literally or by equivalence, are intended to be embraced therein.
Number | Name | Date | Kind |
---|---|---|---|
5326028 | Kano | Jul 1994 | A |
6369716 | Abbas et al. | Apr 2002 | B1 |
6916239 | Siddaramanna et al. | Jul 2005 | B2 |
7396212 | Parker et al. | Jul 2008 | B1 |
8086352 | Elliott | Dec 2011 | B1 |
8100746 | Heidel et al. | Jan 2012 | B2 |
8536998 | Siu et al. | Sep 2013 | B1 |
8622314 | Fisher et al. | Jan 2014 | B2 |
9182751 | Reeder | Nov 2015 | B1 |
9303890 | Haines et al. | Apr 2016 | B2 |
9423779 | Agarwal | Aug 2016 | B2 |
9528715 | Aiken | Dec 2016 | B2 |
10139380 | Abehessera et al. | Nov 2018 | B2 |
10145831 | Angeli et al. | Dec 2018 | B2 |
10353362 | Thomas | Jul 2019 | B2 |
10410504 | Tabe | Sep 2019 | B2 |
10443873 | Johnson et al. | Oct 2019 | B1 |
10503847 | Hoff | Dec 2019 | B2 |
10613504 | Chowdhury | Apr 2020 | B2 |
20070008064 | Donohue | Jan 2007 | A1 |
20100305761 | Remsburg | Dec 2010 | A1 |
20130127620 | Siebers | May 2013 | A1 |
20130245837 | Grohman | Sep 2013 | A1 |
20140244043 | Foster | Aug 2014 | A1 |
20140244298 | Robinson | Aug 2014 | A1 |
20150168003 | Stefanski et al. | Jun 2015 | A1 |
20150204551 | Nair et al. | Jul 2015 | A1 |
20150330817 | Law | Nov 2015 | A1 |
20160116512 | Ji | Apr 2016 | A1 |
20160195856 | Spero | Jul 2016 | A1 |
20160209065 | Hagström | Jul 2016 | A1 |
20160370029 | Kurelowech | Dec 2016 | A1 |
20160377305 | Kwa | Dec 2016 | A1 |
20170030605 | Heller et al. | Feb 2017 | A1 |
20170049915 | Brais | Feb 2017 | A1 |
20180299153 | Ajax | Oct 2018 | A1 |
20190172165 | Verteletskyi | Jun 2019 | A1 |
20190196432 | Morley | Jun 2019 | A1 |
20190209806 | Allen | Jul 2019 | A1 |
20190240362 | Corsetti | Aug 2019 | A1 |
20190338976 | Chakraborty | Nov 2019 | A1 |
20190376712 | Miwa | Dec 2019 | A1 |
20210048206 | Forzani | Feb 2021 | A1 |
20210052758 | Brais | Feb 2021 | A1 |
20210090417 | Bailey | Mar 2021 | A1 |
20210199360 | Watanabe | Jul 2021 | A1 |
20210313075 | Mc Namara | Oct 2021 | A1 |
20210356153 | Nesler | Nov 2021 | A1 |
20210390812 | Chaurasia | Dec 2021 | A1 |
20220042694 | He | Feb 2022 | A1 |
20220113050 | Douglas | Apr 2022 | A1 |
20220154958 | Manoharan | May 2022 | A1 |
Number | Date | Country |
---|---|---|
110696857 | Jan 2020 | CN |
210050954 | Feb 2020 | CN |
4427356 | Jan 1996 | DE |
102021128678 | May 2022 | DE |
2272731 | Jul 2012 | EP |
2357419 | Oct 2016 | EP |
3147880 | Mar 2017 | EP |
2357420 | Jan 2018 | EP |
3316583 | May 2018 | EP |
2006099337 | Sep 2006 | WO |
2006107308 | Oct 2006 | WO |
2007073477 | Jun 2007 | WO |
2007104240 | Sep 2007 | WO |
2008088020 | Jul 2008 | WO |
2011020058 | Feb 2011 | WO |
2011022379 | Feb 2011 | WO |
2012053230 | Feb 2012 | WO |
2013177290 | Nov 2013 | WO |
2014006293 | Jan 2014 | WO |
2014041896 | Mar 2014 | WO |
2014063201 | May 2014 | WO |
2014123531 | Aug 2014 | WO |
2017142346 | Aug 2014 | WO |
2015006777 | Jan 2015 | WO |
2015095753 | Jun 2015 | WO |
2015130019 | Sep 2015 | WO |
2015134755 | Sep 2015 | WO |
2016100138 | Jun 2016 | WO |
2016116784 | Jul 2016 | WO |
2016126363 | Aug 2016 | WO |
2016141199 | Sep 2016 | WO |
2017083134 | May 2017 | WO |
2017172123 | Oct 2017 | WO |
2018035161 | Feb 2018 | WO |
2018039433 | Mar 2018 | WO |
2018098301 | May 2018 | WO |
2018148420 | Aug 2018 | WO |
2018191635 | Oct 2018 | WO |
2018191703 | Oct 2018 | WO |
2019014671 | Jan 2019 | WO |
2019136097 | Jul 2019 | WO |
2019148074 | Aug 2019 | WO |
2019152996 | Aug 2019 | WO |
2019164804 | Aug 2019 | WO |
2020117973 | Jun 2020 | WO |
2020146766 | Jul 2020 | WO |
WO-2021195538 | Sep 2021 | WO |
WO-2022026366 | Feb 2022 | WO |
Entry |
---|
Jiang, C., Masood, M.K., Soh, Y.C. and Li, H., 2016. Indoor occupancy estimation from carbon dioxide concentration. Energy and Buildings, 131, pp. 132-141. (Year: 2016). |
Ke, Y.P. and Mumma, S.A., 1997. Using carbon dioxide measurements to determine occupancy for ventilation controls. (Year: 1997). |
Bosch.IO, “Smart buildings and the future of work in the post-COVID world”, https://bosch.io/resources/on-demand-webinar/smart-buildings-and-the-future-of-work/, Aug. 5, 2020, (9 pp). |
Umwelt-Campus Birkenfeld, “COVID-19 prevention: CO2 measurement and demand-oriented ventilation”, http://www.umwelt-campus.de/forschung/projekte/iot-wekstatt/ideen-sur-corona-krise, Mar. 17, 2021, (18 pp). |
Fraunhofer, IBP-Bericht 001/2010/283 “IBP-Bericht 001/2010/283”, Dec. 31, 2009, (194 pp). |
“Indoor Air Quality (IAQ)”, https:///www.vaisala.com/en/industries-applications/hvac-construction-material-and-artifact-monitoring/indoor-air-quality, 2021, (5 pp). |
haustex.de, “Carbon dioxide in indoor air: monitoring protects health”, https://www.haustec.de/klima-lueftung/Queftungstechnik/kohlendioxid-der-raumluft-ueberwachen-bewahrt-gesundheit?page=all, Aug. 12, 2020, (10 pp). |
Schwee, Jens Hjort, et al.Scientific Data, “Room-level occupant counts and environmental quality from heterogeneous sensing modalities in a smart building”, www.nature.com/scientificdata, https://doi.org/10.1038/s41597-019-0274-4, 2019, (11 pp). |
SafeCount, “Live occupancy monitoring solution”, https://www.irisys.net/products/safecount-occupancy-monitoring-solution?utm_source=adwords&utm_medium=cpc&utm_campaign=safecount&utm, Mar. 17, 2021, (12 pp). |
Number | Date | Country | |
---|---|---|---|
20220244686 A1 | Aug 2022 | US |