1. Technical Field of the Invention
This invention relates generally to HVAC zone climate control systems, and more specifically to a zone climate control system for room-by-room climate control in a residential building.
2. Background Art
The majority of single-family houses in the United States have forced air central heating systems. Many of these also have air conditioners that use the same air distribution system. These heating, ventilation, and air conditioning (HVAC) systems are typically controlled by a single, centrally located thermostat. The thermostat controls the HVAC equipment to maintain a constant temperature at the thermometer. The temperatures in other rooms of the house are not actively controlled, so the temperatures in different rooms can differ by many degrees from the temperature at the thermostat.
Manually adjusting the airflow to each room, by opening or closing louvers behind the vents, is the primary method available to control the temperature away from the thermostat. However, the temperatures away from the thermostat depend on many dynamic factors such as the season (heating or cooling), the outside temperature, radiation heating and cooling through windows, and the activities of people and equipment in the rooms. The desired temperature also depends on the activity of the occupant, for example lower temperatures for sleeping and higher temperatures for relaxing. Maintaining comfortable temperatures requires constant adjustment, or may not be possible.
These temperature control problems are well known to HVAC suppliers, installers, and house occupants. Zone control systems have been developed to improve temperature control. Typically, a small number of thermostats are located in different areas of the house, and a small number of mechanized airflow dampers are placed in the air distribution ducts. A control unit dynamically controls the HVAC equipment and the airflow to simultaneously control the temperatures at each thermostat. These conventional systems are difficult to retrofit, and provide limited function and benefit. They are provided by several companies such as: Honeywell, 101 Columbia Road, Morristown, N.J. 07962; Carrier, One Carrier Place, Farmington, Conn. 06034; Jackson Systems, LLC100 E. Thompson Rd., Indianapolis, Ind. 46227; Arzel Zoning Technology, Inc., 4801 Commerce Parkway, Cleveland, Ohio 44128; Duro Dyne, 81 Spence Street, Bay Shore, N.Y. 11706; and EWC Controls, Inc., 385 Highway 33, Englishtown, N.J. 07726.
U.S. Pat. No. 5,772,501 issued Jun. 30, 1998 to Merry, et al. describes a system for selectively circulating unconditioned air for a predetermined time to provide fresh air. The system uses conventional airflow control devices installed in the air ducts and the system does not use temperature difference to control circulation. This system is difficult to retrofit and does not exploit selective circulation to equalize temperatures
U.S. Pat. No. 5,024,265 issued Jun. 18, 1991 to Buchholz, et al. describes a zone control system with conventional thermostats located in each zone. This system teaches one method for distributing conditioned air to zones based dependent on the zone that has the greatest need for conditioning. However, the thermostats make on-off requests for conditioning based on local set points, so the system must deduce need based on the duty cycle of on-off requests. The control system does not have access to the actual temperature in the zone nor any other characteristic of the zone such as thermal resistance or thermal capacity. This system is not practically adaptable to a residential system.
U.S. Pat. No. 5,949,232 issued Sep. 7, 1999 to Parlante describes a method for measuring the relative energy used by each unit of many units served by a single furnace based on the accumulated time each unit draws energy. The method prorates the total based on time and does not account for different rates of energy use by each unit. The method requires individual timers for each unit and a method for communicating times to a central location. The method does not provide accurate results when each unit draws energy at different rates from the common source, and is not adaptable to a residential zone controlled forced air HVAC system.
U.S. Pat. No. 6,349,883 issued Feb. 26, 2002 to Simmons, et al. describes a control system for a set of zones that draw energy from a common supply. The system claims to save energy using occupant sensors and parameters entered locally in each zone to request conditioning only when the zone is occupied. The system does not have a centralized way to specify and control the zones as groups or as an entire house, and the system is not practical for residential retrofit or use.
The invention will be understood more fully from the detailed description given below and from the accompanying drawings of embodiments of the invention which, however, should not be taken to limit the invention to the specific embodiments described, but are for explanation and understanding only.
I. Zone Climate Control
II. Thermal Model
III. Operating Methodology
The zone climate control system, thermal model, and operating methodology will be described with reference to specific embodiments and, in the interest of conciseness, will focus more on heating than on cooling. The invention is, of course, not limited to these specific details, which are provided for the reader's convenience and education only.
I. Zone Climate Control
A. Forced Air Central HVAC Systems
A thermostat 21 is connected by a multi-conductor cable 73 to an HVAC controller 22 that switches power to the blower, furnace and air conditioner. The thermostat commands the blower and furnace or blower and air conditioner to provide conditioned air to cause the temperature at the thermostat to move toward the temperature set at the thermostat.
B. Retrofit Zone Climate Control Systems
A small air pump in air pump enclosure 50 provides a source of low-pressure (˜1 psi) compressed air and vacuum at a rate of e.g. ˜1.5 cubic feet per minute. The pressure air tube 51 connects the pressurized air to the air valves 40. The vacuum air tube 52 connects the vacuum to the air valves. The air pump enclosure also contains a low voltage (typically 5 or 12 volts) power supply and control circuit for the air pump. The AC power cord 54 connects the system to 110V AC power. The power and control cable 55 connect the low voltage power supply to the control processor and servo controlled air valves and connect the control processor 60 to the circuit that controls the air pump. The control processor controls the air valve servos to set each air valve to one of two positions. The first position connects the compressed air to the air tube so that the bladder inflates. The second position connects the vacuum to the air tube so that the bladder deflates.
A wireless thermometer 70 is placed in each room in the house. All thermometers transmit, on a shared radio frequency of 418 MHz, packets of digital information that encode 32-bit digital messages. A digital message includes a unique thermometer identification number, the temperature, and command data. Two or more thermometers can transmit at the same time, causing errors in the data. To detect errors, the 32-bit digital message is encoded twice in the packet. The radio receiver 71 decodes the messages from all the thermometers, discards packets that have errors, and generates messages that are communicated by serial data link 72 to the control processor. The radio receiver can be located away from the shielding effects of the HVAC equipment if necessary, to ensure reception from all thermometers.
The control processor is connected to the existing HVAC controller 22 by the existing HVAC controller connection 74. The existing thermostat 21 is replaced by a graphical display 80 with a touch sensitive screen. The graphical display is connected to the processor using the same wires that had been used by the existing thermostat. Therefore, no new wires need be installed through the walls. The program executing in the processor controls the graphical display and touch screen to provide the occupant a convenient way to program the temperature schedules for the rooms and to display useful information about energy usage and the operation of the HVAC system.
The control processor controls the HVAC equipment and the airflow to each room according to the temperature reported for each room and according to an independent temperature schedule for each room. The temperature schedules specify a heat-when-below-temperature and a cool-when-above-temperature for each minute of a 24-hour day. A different temperature schedule can be specified for each day for each room.
The present invention can set the bladders so that all of the airflow goes to a single air vent, thereby conditioning the air in a single room. This could cause excessive air velocity and noise at the air vent and possibly damage the HVAC equipment. This is solved by connecting a bypass air duct 90 between the conditioned air plenum 15 and the return air plenum 11. A bladder 91 is installed in the bypass 90 and its air tube is connected to an air valve 40 so that the control processor can enable or disable the bypass. The bypass provides a path for the excess airflow and storage for conditioned air. The control processor is interfaced to a temperature sensor 61 located inside the conditioned air plenum. The control processor monitors the conditioned air temperature to ensure that the temperature in the plenum does not go above a preset temperature when heating or below a preset temperature when cooling, and ensures that the blower continues to run until all of the heating or cooling has been transferred to the rooms. This is important when bypass is used and only a portion of the heating or cooling capacity is needed, so the furnace or air conditioner is turned only for a short time. Some existing HVAC equipment has two or more heating or cooling speeds or capacities. When present, the control processor controls the speed control and selects the speed based on the number of air vents open. This capability can eliminate the need for the bypass.
A pressure sensor 62 is mounted inside the conditioned air plenum and interfaced to the control processor. The plenum pressure as a function of different bladder settings is used to deduce the airflow capacity of each air vent in the system and to predict the plenum pressure for any combination of air valve settings. The airflow to each room and the time spent heating or cooling each room is use to provide a relative measure of the energy used to condition each room. This information is reported to the house occupants via the graphical display screen.
This brief description of the components of the present invention installed in an existing residential HVAC system provides an understanding of how independent temperature schedules are applied to each room in the house, and the improvements provided by the present invention. The following discloses the details of each of the components and how the components work together to proved the claimed features.
II. Thermal Model
A. Parameters
The present invention uses one instance of a first set of parameters to describe and control the climate control of each respective room, and to make energy usage calculations regarding that room. In this context, a “room” is defined as a portion of a house associated with a particular smart controller (wireless thermometer 70). In one embodiment, there may be up to 32 rooms. The invention also uses one instance of a second set of parameters to describe and control the operation of each HVAC system in the house. In one embodiment, there may be up to 5 HVAC systems. The invention also uses a third set of parameters to describe and control the entire house. Customarily, any given room gets its conditioned air supply from a single, predetermined one of the HVAC systems. In other words, the room's ductwork is connected to exactly one HVAC system. This is not a necessary limitation on the invention, although for convenience the house will be described in such terms herein.
The parameters are either measured, or derived from data measured while controlling the HVAC systems, and they become more accurate over time, as more data are gathered and factored into the derivation. Upon initial installation, default values may be utilized. In some embodiments, the default values may be customized to suit the particular house and/or local climate.
Before explaining the climate control methodology and its algorithms in detail, it will be useful to the reader to have an understanding of the data, parameters, and values used by such.
In one embodiment, there are eight parameters associated with each room:
Naturally, the current temperature in the room has the most significant impact on whether the HVAC system will be run. If the temperature does not need to be changed in order to bring the room into a specified target temperature range, then the room will not be the cause of the HVAC system being turned on.
The airflow parameter is a unit-less value indicating the relative portion of the airflow that goes to a particular room compared to the total airflow in the plenum of the HVAC system. The bypass vent also has an airflow parameter associated with it. The airflow value is used in predicting plenum pressure for any combination of open and closed air vents, and in prorating energy usage to each room. The airflow value is always used in a ratio or with a calibrated scale factor, so it has no units and its absolute value is not important. In one embodiment, the average value of the airflow parameter for each room in the house is chosen to be an integer value of 100, and each airflow parameter will typically be within the range of 30 to 300, corresponding to airflows of 0.3 to 3 times the average airflow. The range can, of course, vary depending on the specific duct system.
Plenum pressure is predicted according to the equation:
where:
In typical residential HVAC systems, the plenum pressure should be limited to ˜0.5″ to 1.0″ H2O (inches of water), equivalent to ˜0.018 to 0.36 psi (pounds per square inch). In one embodiment of the invention, it is beneficial to use only integer arithmetic for all calculations. Therefore inches-H2O is scaled by 1,000 to be “thousandths of inches of water” so that the maximum plenum pressure typically has an integer value of 500 to 1,000. For example, if four average rooms (AirflowX=100) must be turned on to make the plenum pressure equal 500, then the value of KHVAC is 200,000=500*(100+100+100+100). The measured plenum pressure is scaled in a corresponding way, so that when the plenum pressure is 0.5″ H2O, the measured value used in calculations is 500.
The parameter AirflowX for each room and for the bypass is determined using a set of measured plenum pressures for a set of predetermined combinations of room and bypass vent settings. The process for determining Airflowbypass for the bypass is the same as for rooms, so in the following description, the bypass is treated as an additional room. The combinations are generated by representing the OPEN/CLOSED states of the vent(s) in rooms as bits in a circular binary array. Suppose there are n−1 rooms and a bypass. The binary array then has n elements and the elements are numbered 1, 2, . . . , n. The array is indexed using modulo arithmetic, so that an index value of n+1 accesses element 1, n+2 accesses element 2, etc. Thus, indexing is “circular” so that the end connects to the beginning. When the value of an element is 0, the air vent of the corresponding room is CLOSED (room is CLOSED). When the element has a value of 1, the air vent of the corresponding room is OPEN (room is OPEN).
Two groups of combinations are generated. The A group starts with j=n/3 (rounded down to an integer) rooms OPEN, and n-j rooms CLOSED. The B group starts with n-j rooms OPEN and j rooms CLOSED. The first combination in the A group sets rooms 1 through j OPEN and rooms j+1 through n CLOSED, and the plenum pressure PPA1:J is measured. The second combination in the A group additionally sets room j+1 OPEN, and the plenum pressure PPA1:j+1 is measured. The third combination sets room 1 CLOSED, and the plenum pressure PPA2:j+1 is measured, the fourth combination sets room j+2 OPEN and the plenum pressure PPA2:j+2 is measured. Setting the next room OPEN, followed by setting the last room CLOSED sequentially generates the combinations. The difference between successive combinations is one additional room OPEN, or one previously OPEN room CLOSED. The number of rooms OPEN alternates between j and j+1. 2n such A group combinations are generated until the combination repeats. B group combinations are generated in the same way, beginning with rooms 1 through n-j set OPEN. The number of rooms set OPEN alternates between n-j and n-j+1. 2n such B group combinations are generated. The following is an example for 6 rooms with the nomenclature for the 24 measured plenum pressures and the corresponding combinations in the 6 element binary array:
This combination generating method yields 4n pressure measurements to determine n airflow values. Each room is OPEN and CLOSED an equal number of times, and there are 4 pairs of measurements for each room where the difference is only that one room. Using the equation for predicting plenum pressure, a typical pair of equations is:
PPAk:i−1=kHAVC/sum(Airflowk:i−1)
PPAk:i=kHAVC/(sum(Airflowk:i−1)+Airflowi)
This pair can be combined to eliminate the term: sum(Airflowk:i−1), the combined airflow for the common set of rooms that are OPEN for the two measurements. The resulting equation is:
Airflowi=(kHAVC/PPAk:i)−(kHAVC/PPAk:i−1)
Since kHAVC is a common scale factor, it can be conveniently selected so that the average Airflowi term is about 100 and so that integer arithmetic can be used for the calculations. A value of 200,000 for Airflowi can be used (as described above), so the equation produces a calibrated value for Airflowi. Three other pairs of plenum pressure measurements can be used to find independent measurements of Airflowi:
PPAi:k With PPAi+1:k
PPBi:k with PPBi+1:k
PPBk:i−1 with PPBk:i.
Each pair yields a value of Airflowi for a different set of rooms in combination with the ith room. The airflow may be slightly different for different combinations because rooms may share the same trunk duct so that the room airflows are somewhat dependent on each other. Using the average of the four values partially compensated for such dependencies.
Energy usage is prorated according to the equation:
where:
The value of PE is bounded 0<PE<=1, and thus represents a unit-less percentage of energy usage attributed to the particular room.
The heat capacity, CapacityHEAT, is the time in seconds the furnace must run to raise the temperature of the room by 1 degree. CapacityHEAT considers only the ability of the room to hold heat energy and the ability of the furnace to produce heat, and is independent of thermal losses or gains caused by differences between inside and outside temperatures.
The cool capacity, CapacityCOOL, is the time in seconds the air conditioning must run to lower the temperature of the room by 1 degree, and is similar in nature to CapacityHEAT.
The heat offset, TempOffsetHEAT, is an empirical correction factor derived from stored operating data that corrects for secondary heat sources such as sunlight through a window, incandescent lights, appliances, and thermal coupling to other heated rooms. Its units are seconds per hour.
The heat loss factor, LOSSHEAT, represents the amount of heat required to keep the room at a specific temperature, and is determined according to the equation:
LossHEAT=TempOffsetHEAT+(Temproom−Tempoutside)*UFHEAT
where:
The calculated LOSSHEAT value is valid only if it has a positive value. If it is zero or negative, the outside temperature is not low enough for the room to need heat.
The cool offset factor, TempOffsetCOOL, is an empirical factor similar to TempOffsetHEAT, and corrects for sources of heating and cooling. A source of cooling could be a basement room kept cool by the ground and having little thermal contact with the outside air.
The cool loss factor, LOSSCOOL, represents the amount of cooling required to keep the room at a specific temperature, and is determined according to the equation:
LossCOOL=TempOffsetCOOL+(Temproom−Tempoutside)*UFCOOL
where:
The calculated LOSSCOOL value is valid only if it has a positive value. If it is zero or negative, the outside temperature is not high enough for the room to need cooling.
Typical rooms have sources of heating, so LOSSHEAT becomes positive only if the outside temperature is several degrees cooler than the target temperature (“heat when below” temperature) for heating. Likewise, LOSSCOOL becomes positive when the outside temperature is several degrees cooler than the target temperature for cooling (“cool when above” temperature).
Many residential HVAC systems use different fan speeds for the different HVAC functions. For example, the fan speed is lowest for the circulation function, higher for the heating function, and highest for the cooling function. Since the plenum pressure increases as fan speed increases, the plenum pressure KHVAC scale factors KHEAT, KCOOL, and KCIR, are different for the functions as described above. The calibration process is done using the circulation function, so KCIR is arbitrarily set to a value of 200,000. KHEAT and KCOOL are then determined by comparing the measured plenum pressure for the heating and cooling functions with the predicted plenum pressure using KCIR.
The thermal behavior of the house as a whole is the composite of the behaviors of all of the rooms. Therefore there is a set of six corresponding thermal parameters for the whole house: CapacityHEAT, TempOffsetHEAT, UFHEAT, CapacityCOOL, TempOffsetCOOL, and UFCOOL, which are used to calculate LOSSHEAT and LOSSCOOL, and to control the HVAC equipment to achieve the desired temperatures in each of the rooms. There is no separate Airflow factor for the whole house.
When the outside temperature is cold enough to require heating of a room, the room is heated (by warm air flow) for a period of time and its temperature increases. The room is then unheated for a period of time while the CapacityHEAT of the room supplies the heat lost to the outside (and perhaps to other rooms) and its temperature decreases. After some period of time, the temperature will have decreased sufficiently such that heating is again required for the room. The time between the heating cycles, and the difference between the outside temperature and the room temperature, can be used to calculate the heat lost (LOSSHEAT) during that period. The CapacityHEAT is then (heat lost)/(room temperature change). This is more accurate if the average of the LOSSHEAT at the beginning of the period and the LOSSHEAT at the end of the period is used. Using the average is important when the outside temperature changes significantly during the measurement period.
In one embodiment, parameters are measured and stored for each room as the system controls the heating cycles according to the temperatures in the rooms. A CapacityHEAT is calculated for each room and for each time period between the heating cycles for that room. (Since rooms are heated only when needed, the time period between cycles is typically different for different rooms.) During each 24-hour period, the individual measurements of CapacityHEAT are accumulated, and at the end of the 24-hour period, the average CapacityHEAT is calculated for each room and is stored into long term storage.
This method of measuring CapacityHEAT is meaningful only if the room continuously cools between heating cycles, the change in temperature between cycles is sufficient to be measured accurately, and the environment (outside air temperature and activity in the room) has not changed significantly between heating cycles. In one embodiment, the temperature measurement has a resolution of 0.25 degree, so the change in temperature needs to be at least 0.5 degree for the measurement to have any significance. A special case occurs when the target heat temperature is reduced. The time between heating cycles may be unusually long since the room temperature may decrease several degrees before heating is required, so it is likely the environment will change significantly before heating in again needed. However, the larger change in room temperature will produce a more accurate measurement of CapacityHEAT. Therefore the measurement is terminated when the time since the last heat cycle exceeds two hours, and a value for CapacityHEAT is calculated. Considering the possible sources of error when measuring CapacityHEAT, the measured value of CapacityHEAT is used in the average only if all of the following conditions are satisfied:
The method for measuring CapacityCOOL is similar. When the outside temperature is high enough to require the room to be cooled, the room temperature decreases while the room receives cool airflow. The temperature increases between cooling cycles as heat from the outside overcomes the CapacityCOOL of the room at a rate of LOSSCOOL. CapacityCOOL is then (heat gain)/(room temperature change).
During any 24-hour period, only CapacityCOOL or CapacityHEAT may be measured. If both heating and cooling are used during the 24-hour period, the environmental conditions are extremely variable and the Capacity values measured are likely to have large errors. Therefore no value for either Capacity is stored long term.
B. Stored Data
In one embodiment, the system gathers the following data and stores it for a relatively short period of time, such as a few days. In one embodiment, the total storage for one day is set to 32 Kbytes so that one bank of flash memory can store two days of data for a maximally configured system with 32 rooms and 5 HVAC systems. In one embodiment, the system includes flash memories, operated in ping-pong fashion in which one memory or block is used until it is full, and then the other, older block is erased and used for new data.
Room Temperature. For each room, the current room temperature, recorded every 6 minutes, stored as 1 byte. The daily data quantity is 32 rooms*1 sample/room*1 byte/sample*10 samples/hour*24 hours=7,680 bytes.
Room Target Temperature Changes. For each target temperature change for any given room, the following data are stored in a structure:
This structure requires 4 bytes of storage per transition. In one embodiment, 451 such structures (˜16 per room in a maximally configured system)=1804 bytes are provided for one day of short term storage. These changes can be caused by daily temperature schedules (no more than 6 per day) or by button pushes at the Smart Controllers. In the very unlikely event the storage is fully used, the transitions for the remainder of the day are not stored.
HVAC System Cycle. For each cycle of the HVAC equipment, the following data are recorded:
This structure uses 18 bytes of storage per HVAC cycle. In one embodiment, 1280 such structures=23,040 bytes are provided for each day of short term storage. This is sufficient for any operating conditions of a maximally configured system.
Outside temperature. Current outside temperature, recorded every 6 minutes, stored as 1 byte. The daily data quantity is 1 byte/sample*10 samples/hour*24 hours=240 bytes.
Date. The year, month, and day stored in a 4-byte word. This value is only used when recovering from a power failure.
In one embodiment, the total daily short term data storage provided is:
32 *240=7,680 bytes for room temperatures
451*4=1,804 bytes for target temperature transitions
1280*18=23,040 bytes for HVAC equipment cycles
240 bytes for outside temperature
4 bytes for date
Total=32,768 bytes (32 Kbytes).
Every day, shortly after midnight, the short-term data from the previous day are processed to derive a smaller data set for longer-term storage.
The following data are stored for each room in the house:
These parameters require a total of 32 bytes per day per room, for a maximum daily data quantity of 1,024 bytes for 32 rooms.
The following data are stored for each of the up to 5 HVAC systems:
This gives a total daily data quantity of 128 bytes per HVAC system, 5*128=640 bytes for 5 HVAC systems.
The following data are stored for the whole house:
This gives a total of 14 bytes of whole-house data per day. The total daily long term data storage is 1024+540+14=1,675 bytes. In one embodiment, 13 segments of 64 Kbytes (851,968 bytes) are allocated for long term storage, enough for 508 days.
C. Calibrating the Thermal Model Using the Stored Data
As described in the previous section, the heat loss factor, LOSSHEAT, represents the amount of heat required to keep the room at a specific temperature, and is determined according to the equation:
LossHEAT=TempOffsetHEAT+(Temproom−Tempoutside)*UFHEAT
This equation is a first order linear equation of the form:
y=a+b*x
Given a series of N measurements of x and y, the values of a and b can be determined using the formulas
where sum(xi) is the sum of all the x values for the N measurements.
TempOffsetHEAT is calculated as
where LOSSHEAT is the stored prorated heating time (appropriately scaled to account for conversion from seconds to hours).
UFHEAT is calculated as
The method for calculating TempOffsetCOOL and UFCOOL is identical, except the prorated time for cooling is used to determine LOSSCOOL.
At the end of each 24-hour period, the thermal mode parameters are calculated for each room based on the short term data gathered for that day. Each cycle of HVAC activity for a room is evaluated as a pair of data values where one value is the Loss (3,600*[prorated seconds of*HVAC activity]/[time between cycles]), and the other value is the difference between the room temperature at the beginning of the cycle and the outside temperature.
At the beginning of each 24-hour period, a new set of thermal model parameters are calculated for each room, and these are used throughout the following 24-hour period. The simple average of the most recent values is used. Averaging the last 15 values smoothes day-to-day variations while compensating for systematic changes in the seasons. Other numbers of values can be averaged, depending on the dynamics of the local climate. If there are fewer than 15 values stored, then as many as are available are averaged.
Only parameter values for one of the HEAT or COOL thermal models are calculated each day. It may be necessary to search backward many months to retrieve the 15 most recent values of the “off season” thermal model. For example, in some temperate climates with short cooling seasons, it may be up to a year between the last day needing cooling of the previous season to the first day needing cooling of the new season.
III. Operational Methodology
A. Initial Installation
When the system is first installed, the Airflows value for each room is determined through the set of measurements and calculations described above in section II.A.1.b.
Default values are automatically assigned to the other six parameters: CapacityHEAT, UFHEAT, TempOffsetHEAT, CapacityCOOL, UFCOOL, and TempOffsetCOOL. The quality of the default values is important, to make the system work as well as possible upon initial installation, to avoid customer dissatisfaction during the first few days while the system extracts calibrated values from measured data. The default values should, ideally, be customized for the local climate at that particular time of year, and for the house itself e.g. the size of the house and the quality of its insulation. These default values will typically assume that the HVAC system is properly designed. A properly designed heating system can keep the house at 70 degrees on the coldest day, and a properly designed cooling system can keep the house at 72 degrees on the hottest day. A properly designed HVAC system can heat or cool the house temperature 5 degrees per hour. A properly designed heat pump system can typically change the house temperature only 2 degrees per hour, however. For a properly designed system, the airflow to each room should be proportional to the heating and/or cooling requirements of that room; however, in practice, most houses have problems here, and sometimes they are significant problems.
Reasonable default values for the six remaining parameters are:
TempOffsetHEAT=10 degrees
TempOffsetCOOL=10 degrees
The “5 degrees” factor is default degrees per hour the heating or cooling system can change the temperature of the whole house. This should be “2 degrees” for heat pumps.
B. Temperature Control
The temperature control method uses the thermal model, described above, to predict the conditioning time (in seconds) needed to keep all of the rooms within a predetermined number of degrees—DeltaT—of the target temperature. A reasonable default value for this global parameter may be 1 degree, but it may be changed, based on field experience, the local climate, and the homeowner's preference. When heating, it is acceptable to heat a room until its temperature is DeltaT above its target heating temperature. And when cooling, it is acceptable to cool a room until its temperature is DeltaT below its target cooling temperature.
In order to maximize the efficiency of the heating or cooling, and to minimize the number of cycles—which the occupants may find distracting, and which may stress the HVAC equipment excessively—the temperature control method attempts to make each cycle at least a minimum duration, if possible. A reasonable minimum duration may be 15 minutes. When bypass is used, it may be necessary to use a lower duration target, to avoid overheating or overcooling the plenum; therefore, the method attempts to maximize the number of open vents, and will reduce the cycle time, to avoid using the bypass, if possible.
At the start of the control cycle, the amount of heating and cooling needed for each room during the next 15 minutes is calculated, in seconds. The target temperature used for this calculation is adjusted by DeltaT. If the time value is negative, it is set to zero. In order to ensure that both heating and cooling are never required at the same time, the system may require that the TargetTempHEAT be at least twice DeltaT below the TargetTempCOOL.
In one embodiment, the TargetTempHEAT and TargetTempCOOL are specified with 1-degree resolution, while the wireless thermometers report the current temperature with 0.25-degree resolution.
If (101) one or more rooms coupled to the HVAC system needs heat, meaning that the temperature reported by the room's wireless thermometer is lower than the TargetTempHEAT assigned to that room in the currently running program, then the heating method is undertaken. Otherwise, no heat is needed (102) and the HVAC controller can check whether cooling or circulation may be needed.
When heating is to be undertaken, the HVAC controller may begin by logically setting (103) all room vents to CLOSED. Then, the vents are set (104) to OPEN for all rooms which need heat.
The HVAC controller calculates (105) the timeHEAT (total time), in seconds, of heating required to raise all OPEN rooms to their respective TargetTempHEAT settings+DeltaT. The timeHEAT-ROOM for each room is:
CapacityHEAT*(TargetTempHEAT+DeltaT−room temperature)+LOSSHEAT
where LOSSHEAT is calculated from the equation for the room, using the current room temperature, outside temperature, and an initial time of 15 minutes (the target time between HVAC cycles). This total heating required is timeHEAT, the sum of the timeHEAT-ROOM values for each of the rooms that need heat.
The timeHEAT-ROOM is calculated again for each room with its vent OPEN (called an OPEN room) using the prorated (106) heat to the room using the Airflow parameters of all OPEN rooms and using timeHEAT as the time between HVAC cycles. This compensates for the potential unequal distribution of the airflow to the OPEN rooms. The shortest of these timeHEAT-ROOM values is the timeHEAT that will not overheat any of the OPEN rooms. (A room is considered overheated if it is more than DeltaT warmer than its TargetTempHEAT.)
The HVAC controller then calculates (107) the longest duration timeHEAT for which the heater may be run, without overheating any OPEN room.
In one embodiment of the method, the HVAC controller then attempts to maximize timeHEAT (the duration of the heating cycle), by testing (108) all remaining CLOSED rooms with temperatures below their TargetTempHEAT+DeltaT. These are rooms that, although not requiring heat, could receive additional heat without becoming overheated. Each candidate room is set OPEN (one at a time), and the calculation of timeHEAT (the minimum of all of the timeHEAT-ROOM values) is repeated, using the adjusted prorated airflows. If making the room OPEN increases timeHEAT, then that room is left OPEN. If timeHEAT is reduced, then that room is left CLOSED. This means that even if the room temperature is above its TargetTempHEAT, it may still receive additional heating, provided its final predicted temperature does not exceed TargetTempHEAT+DeltaT, and that including the room will increase timeHEAT.
The HVAC controller then calculates (109) the predicted plenum pressure PPpred according to the Airflow values of the OPEN vents. If (110) the predicted plenum pressure is less than or equal to the specified maximum plenum pressure PPmax, the heater is run (111) for the timeHEAT duration.
If the predicted plenum pressure is too high, the HVAC controller attempts to lower the plenum pressure by various means. In one embodiment, the HVAC controller first attempts to lower the plenum pressure by sequentially opening additional room vents at the cost of reducing the timeHEAT. One at a time, for each room currently CLOSED (and not needing heat) whose temperature is lower than its TargetTempHEAT+DeltaT, the HVAC controller logically sets (113) the vent to OPEN and timeHEAT is calculated again. The calculated timeHEAT for each candidate room is compared (114), and if the longest timeHEAT is greater than a predetermined threshold, such as 120 seconds, the HVAC controller sets the vent for that one room OPEN and goes back (A) to again predict (109) the plenum pressure.
If either there are no rooms with CLOSED vents that are below their TargetTempHEAT+DeltaT (112), or the timeHEAT has fallen below the first threshold (114), the HVAC controller sets (115) the bypass to OPEN. All of the rooms previously set open (in 113) are set CLOSED, since they do not require heat this cycle, but were set OPEN only as a means of reducing plenum pressure.
The HVAC controller then again predicts (116) the plenum pressure with the bypass set OPEN. If (117) the plenum pressure is less than or equal to the maximum, the heater is run (118) for the timeHEAT duration calculated for the rooms set OPEN. Otherwise, the HVAC controller may take further measures to try to lower the plenum pressure.
The HVAC controller sets (119) OPEN the CLOSED room that will reduce timeHEAT the least if heated to DeltaT plus its TargetTempHEAT. If (121) the timeHEAT is greater than a second threshold, e.g. 60 seconds, the HVAC controller then again predicts (116) the plenum pressure. Otherwise, the HVAC controller predicts (122) the plenum pressure and, if (123) the predicted plenum pressure is below the maximum allowed, the heater is run (124) for the second threshold of time. Otherwise, the HVAC controller (125) searches one at a time for the room currently CLOSED that would be least above its TargetTempHEAT if heated for 60 seconds. That room is set OPEN and the HVAC controller returns to (122) to predict the plenum pressure. This is repeated until sufficient rooms are set OPEN so that with bypass set OPEN, the plenum pressure is less than the maximum.
In summary, the heating control process is to always provide heat to all rooms below their TargetTempHEAT. The timeHEAT is maximized by also heating rooms up to DeltaT above their TargetTempHEAT. If the plenum pressure is too high with just these rooms set OPEN, rooms are set open one at a time, selected in the order that reduces timeHEAT the least. Rooms are added until the plenum pressure is satisfied or until the timeHEAT becomes less than 120 seconds. If the timeHEAT becomes less than 120 seconds, all the rooms set OPEN that reduced the timeHEAT are set CLOSED and the bypass is set OPEN. If the plenum pressure is not satisfied, rooms are again added one at a time selected in the order that reduces timeHEAT the least. This is repeated until the plenum pressure is satisfied or until the timeHEAT becomes less than 60 seconds. If timeHEAT becomes less than 60 seconds, it is set to 60 seconds and the CLOSED rooms are search one at a time for the one room that will be the closest to its TargetTempHEAT if heated for 60 seconds, and that room is set OPEN. Rooms are added one at a time until the plenum pressure is satisfied. Then the rooms now set OPEN are heated for 60 seconds.
The method for cooling is similar to the method for heating, appropriately exchanging the roles of TargetTempCOOL and TargetTempHEAT, and using the corresponding values and equations for LOSSCOOL and CapacityCOOL. It is much less likely that rooms will be overcooled than overheated, because there are many sources of heating and only few sources of cooling.
C. Circulation
If neither a heating cycle nor a cooling cycle is possible, then circulation may be used to heat, cool, equalize temperatures, or maintain air quality. Four different conditions are considered for circulation:
In one embodiment of the system, each temperature schedule setting for each room specifies a low, medium, or high level of circulation, which influences how circulation is used. At the low circulation setting, circulation is only used to ensure a minimum of new air is sent to the room each day, or as a last resort source of heat or cool to satisfy another room which has a high circulation setting. The low circulation setting is ordinarily only applied to rooms that are set for minimal conditioning to save energy. At the medium circulation setting, the room can be used as a source of heat or cool, but does not itself trigger circulation for equalization if its temperature is significantly greater than its TargetTempHEAT or significantly less than its TargetTempCOOL; in other words, a medium circulation room accepts over-conditioning. At the high circulation setting, the room calls for circulation when it is excessively conditioned.
A room is considered excessively conditioned (different than over-conditioned) when it is more than a predetermined threshold, such as 3 degrees above its TargetTempHEAT or below its TargetTempCOOL. In some embodiments, there may be separate excessively conditioned thresholds for heating and for cooling. In some embodiments, the excessively conditioned thresholds may have seasonal adjustments; for example, a room may be excessively heated if it is 3 degrees too hot in the summer, but 5 degrees too hot in the winter.
Circulation for temperature equalization or control is only utilized when the temperature difference between the warmest and coolest participating rooms is greater than a predetermined threshold, such as 3 degrees. The bypass is not used in circulation for temperature equalization; sufficient vents are opened to prevent over-pressurizing the plenum and to maximize the effect of circulation.
Circulation for air quality is done when most cost effective. During heating season, circulation to unconditioned rooms is done in the afternoon, when the outside temperature is highest. During cooling season, circulation to unconditioned rooms is done after midnight, when the outside temperature is lowest.
If (142) such a room is not found, circulation for heating is not needed (143), and the HVAC controller can move on to evaluating the cooling needs of the house.
But if such a room is found, which is to be heated by circulation, the HVAC controller finds (144) the highest temperature room that does not need heat (is more than DeltaT above its TargetTempHEAT and thus can be a source of heat. This room is potentially the heat source room for heating the cold room by circulation.
If (145) the temperature in the potential heat source room is less than a predetermined threshold, such as 3 degrees, warmer than the temperature in the room to be heated, circulation heating would not be effective (146). Otherwise, circulation heating will be attempted.
The HVAC controller logically sets (147) all rooms vents to CLOSED, sets (148) the vents of the heat source room and the room to be heated OPEN, and sets (149) to OPEN the vents of all rooms which can use heat and whose temperature is at least the threshold amount, such as 3 degrees, cooler than the heat source room.
Optionally, the HVAC controller then attempts to increase the amount of heat source, by setting (150) to OPEN all rooms which (1) do not need heat and (2) are at least the threshold amount warmer than the coolest OPEN room which can use heat.
With this baseline set of participating rooms' vents set OPEN, the HVAC controller then predicts (151) the plenum pressure. If (152) the predicted plenum pressure is less than or equal to the maximum allowed, the HVAC controller causes the HVAC system to circulate (153) the air into the participating rooms for a predetermined amount of time, such as 10 minutes. In some embodiments, the amount of time may be determined according to dynamic factors, such as the total CapacityHEAT of the participating rooms.
If the plenum pressure is predicted to exceed the maximum allowed pressure, the HVAC controller attempts to lower the pressure by finding (154) the warmest CLOSED room not needing heat. If (155) the temperature in that room is greater than the temperature in the warmest room that can use heat, then that room can be used as a heat source, although it may not be an especially good one, such as if its temperature is only very slightly above that in the warmest room that can use heat. The HVAC controller sets (157) that room's vent OPEN, and goes back to re-predict (151) the plenum pressure and so forth. If, after the initial or a subsequent check of the predicted plenum pressure, it exceeds the maximum pressure, and if (154) there is no other CLOSED room not needing heat or if (155) the temp of such room is too low, recirculation for heating cannot be done (156).
The method for circulation cooling is substantially similar to the method for circulation heating.
Circulation for equalization is used to reduce excessive conditioning and to keep temperatures more equalized. It is done only for rooms having the high circulation setting.
The HVAC controller starts by logically initializing all vents to CLOSED state. It then searches to find (171) the warmest room which is at least 3 degrees excessively heated and has a high circulation setting. If (172) no such room is found, circulation for equalization is not needed. Otherwise, a “hot room” has been found, which needs to be cooled down toward its TargetTempHEAT. The hot room temperature will be lowered by mixing hot air from the hot room with air from a cooler room, the “source of cool”.
The HVAC controller tries to find (174) the coolest room which is at least 3 degrees cooler than the hot room, and which has a circulation setting of high or medium. If (175) no such room is found, the HVAC controller tries to find (176) the next preferred type of source of cool, the coolest room that has a low circulation setting and that has not had sufficient circulation yet today to maintain its air quality. If (177) no such room is found, the HVAC controller tries (178) to find the next preferred type of source of cool, the coolest room that has a low circulation setting and that has received sufficient circulation already today. If (179) no such room is found, there simply is not a suitable source of cool, and circulation for equalization cannot be performed (180).
If (175, 177, 179), however, a suitable source of cool has been found, the HVAC controller logically sets (181) the vents in that room and in the hot room OPEN. To maximize the redistribution of heat, the HVAC controller also sets (182) OPEN the vents of all rooms that are at least 3 degrees excessively heated, have the high circulation setting, and are warmer than the cool room. To maximize the effectiveness of the cooling, the HVAC controller also sets (183) OPEN the vents of all rooms that: (1) are at least 3 degrees cooler than the warmest excessively heated room, and (2) have (a) high or medium circulation settings, or (b) the low circulation setting and have not received sufficient circulation yet today.
The HVAC controller predicts (189) the plenum pressure. If (190) the predicted plenum pressure is less than or equal to the maximum allowable pressure, the fan is run (191) for a predetermined period of circulation, such as ten minutes. As air is pushed into the overheated rooms and the source of cool rooms, it will mix in the hallways etc. and in the plenum, quickly equalizing to a middle temperature cooler than the overheated rooms were and warmer than the source of cool rooms were.
If the predicted plenum pressure is too high, the HVAC controller attempts to lower it by opening more vents. The HVAC controller attempts to find (192) the coolest CLOSED room that has the medium or high circulation setting. If (193) the temperature in that room is lower than that of the coolest overheated room, the HVAC controller sets (194) that room's vents OPEN, and goes back to re-predict (189) the plenum pressure. Otherwise, the HVAC controller attempts to find (195) the coolest CLOSED room with the low circulation setting and insufficient air circulation today, which is at least 3 degrees cooler than the warmest excessively heated room. If (196) such a room is found, the HVAC controller sets (197) its vents OPEN, and goes back to re-predict (189) the plenum pressure. Otherwise, the HVAC controller attempts to find (198) the coolest CLOSED room with the low circulation setting and sufficient circulation, which is cooler than the warmest excessively heated OPEN room. If (199) such a room is found, the HVAC controller sets (200) its vents OPEN, and goes back to re-predict (189) the plenum pressure. Otherwise, there are no suitable rooms whose vents can be opened to lower the plenum pressure, and circulation for equalization cannot be performed (201).
Otherwise, the HVAC controller sets (215) OPEN the vents of all rooms which have not had sufficient circulation. The HVAC controller predicts (216) the plenum pressure. If (217) the predicted plenum pressure is less than or equal to the maximum allowed, the HVAC controller turns on the fan to circulate (218) the air for a predetermined period of time, such as 10 minutes. In some embodiments, the period of time may be dynamically determined, such as in response to the least amount of prior circulation, or the Airflow parameters of the OPEN rooms.
If the plenum pressure will be too high, the HVAC controller sets (219) the bypass OPEN, and re-predicts (220) the plenum pressure. If (221) the plenum pressure is low enough, the HVAC controller runs the fan to circulate (222) the air for a predetermined period, such as 10 minutes. Otherwise, the HVAC controller attempts to lower the plenum pressure by opening the vents of certain rooms which do not actually need circulation.
The HVAC controller finds (223) the CLOSED room whose temperature is closest to the average temperature of the OPEN rooms. The HVAC controller sets (226) its vents OPEN, and goes back to re-predict (220) the plenum pressure.
The bypass is used in preference to using more rooms, to reduce the mixing of conditioned and unconditioned air.
D. Anticipation
The seven room parameters, and other data, are also used for providing an accurate “anticipation” function when one or more different temperature schedules (“setback”) are in use. Anticipation is needed when making a transition to a new target temperature that requires an increase in energy usage—moving to a higher TargetTempHEAT or a colder TargetTempCOOL, because the user commonly understands the schedule time to specify the time at which the room should be at the new target temperature, not the time at which the HVAC system should begin heating or cooling to the new target temperature. It takes some amount of time for the HVAC system to raise or lower the house temperature, so heating or cooling must be started early, to reach the new target temperature by the specified time. Various factors will influence the amount of anticipation time needed, such as the outside temperature, the Capacity of the rooms, the number of rooms moving to a new target temperature, the Airflow available to those rooms, and so forth. The more extreme the outside temperature, the longer the anticipation time will need to be, because more of the HVAC system capacity will be needed simply to maintain the current temperature.
The anticipation function uses the thermal model described above, and looks ahead in time for the changes in target temperature that will require additional conditioning. The time when the new target temperature becomes effective is advanced sufficiently to ensure that the new target temperature is reached at or before its specified time. The anticipation function calculates an anticipation time for every room, responding to changes in room temperature and outside temperature. The anticipation function is a separate process from the HVAC temperature control process described above. The temperature control process adds the separately calculated anticipation time to the current time, and uses this adjusted time to get the target temperatures from the programmed temperature schedules. This is a simple way to cleanly separate the longer-term anticipation function from the shorter-term HVAC control function.
The anticipation function considers the capacity of the HVAC system, and the ability to use that capacity to change the temperature in each room. Even though the HVAC equipment may have sufficient capacity, it may not be possible to effectively get the capacity to the room needing the temperature change.
A portion of the total HVAC conditioning capacity is needed for keeping the rooms at their current temperatures. This is calculated by summing the LOSSHEAT or LOSSCOOL for all the rooms. The excess heating capacity available to raise the temperature can be calculated as
The excess cooling capacity is calculated similarly. As the outside temperature becomes more extreme, there is less excess capacity available for changing the room temperature.
The maximum conditioning that can be delivered to a room is proportional to the room's Airflow. When only a few rooms change target temperature at the same time, the fraction Fraci of the excess conditioning that can be delivered to a room is roughly
When many rooms change target temperature at the same time, the fraction Fraci of the excess conditioning that can be delivered to a room is roughly
The sum is taken over all the rooms that are changing target temperatures in a way that requires more conditioning at the same time. This calculation takes into account the time calculated the last time the anticipation function was executed.
The smaller of these two values of Fraci is used in calculating the anticipation. Consider the case of heating. The anticipation function first looks ahead in all the temperature schedules to find the first change in each schedule that requires additional heating to reach the target temperature, or, in other words, new target temperatures which are higher than current target temperatures. This is referred to as the TempDelta. The extra heating time ExtraTimeHEAT (in seconds of heating) required to get the room to its new target temperature is:
ExtraTimeHEAT=CapacityHEAT*TempDelta
The room also needs heating time to overcome the heat losses to the outside. This is calculated using the thermal model
LossHEAT=TempOffsetHEAT+((Temproom−Tempoutside)*UFHEAT)
where LOSSHEAT is the seconds of heating per hour.
Both ExtraTimeHEAT and LOSSHEAT must be prorated by the fraction of the total airflow received by the room. The maximum prorated seconds of airflow per hour the room can receive is 3,600*Fraci, so the excess airflow available to increase the temperature of the room is 3,600*Fraci−LOSSHEAT. Combining these terms (including scale factors), the anticipation time (in seconds of “real time”) required to supply the extra heat is
is used to calculate the anticipation time for each room. Then, additional iterations are made using the calculated anticipation values from the previous iteration for all other rooms, taking into account the anticipation times. The airflows for all rooms with overlapping anticipation times are summed. If
is used, and the anticipation is recalculated. This makes the anticipation longer, so the overlap of anticipation must be checked again, and Fraci adjusted if necessary. This iteration continues until Fraci is acceptably stable for this room, such as the value changes less than 5% between iterations.
At the limits of the capacity of the heating system, the HVAC controller must limit the amount of anticipation time to some predetermined maximum, such as 4 hours.
Anticipation is regularly calculated as part of the main control loop. Anticipation has no effect when the change in target temperature is farther in the future than the anticipation value. The anticipation value strongly depends on the outside temperature, and changes as the outside temperature changes. Therefore, the anticipation value needs to be recalculated fairly frequently. For example, if the outside temperature at 4 am is 20 degrees, and there is a 5 degree increase in room temperature scheduled for 10 am, the anticipation value calculated at 4am might be 3 hours, suggesting that the heating will need to be turned on at 7 am. However, when 7 am arrives, the outside temperature may have risen to 40 degrees, resulting in an anticipation value of only 2 hours, or 8 am. In this instance, the rising outside temperature shortens the anticipation value, causing the turn-on time to recede into the future. The opposite can also happen, when a falling outside temperature causes the anticipation value to increase and the turn-on time to advance earlier and earlier. The same general methodology can be used with cooling, but with the opposite effects caused by changing outside temperatures, of course.
The various features illustrated in the figures may be combined in many ways, and should not be interpreted as though limited to the specific embodiments in which they were explained and shown. Those skilled in the art having the benefit of this disclosure will appreciate that many other variations from the foregoing description and drawings may be made within the scope of the present invention. Indeed, the invention is not limited to the details described above. Rather, it is the following claims including any amendments thereto that define the scope of the invention.
This application is a continuation-in-part of, and claims filing date priority of, application Ser. No. 10/249,198 entitled “An Improved Forced-Air Climate Control System for Existing Residential House” filed Mar. 21, 2003 now U.S. Pat. No. 6,983,889 by this inventor.
Number | Name | Date | Kind |
---|---|---|---|
4071745 | Hall | Jan 1978 | A |
4089462 | Bradford | May 1978 | A |
4531573 | Clark et al. | Jul 1985 | A |
5245835 | Cohen et al. | Sep 1993 | A |
5400852 | Nakae et al. | Mar 1995 | A |
5810245 | Heitman et al. | Sep 1998 | A |
6378317 | Ribo | Apr 2002 | B1 |
6415617 | Seem | Jul 2002 | B1 |
6782945 | Eisenhour | Aug 2004 | B1 |
7017827 | Shah et al. | Mar 2006 | B2 |
Number | Date | Country | |
---|---|---|---|
20040238653 A1 | Dec 2004 | US |
Number | Date | Country | |
---|---|---|---|
Parent | 10249198 | Mar 2003 | US |
Child | 10873921 | US |