The present invention relates to the relay protection for power system, in particular to a monitoring and protection method for parallel capacitors and parallel capacitor bank.
Parallel capacitors are widely used in power systems to provide reactive capacity for the system, they are frequently switched, and their safe operation is critical to the safety and stability of the power system. At present, the main protection method of parallel capacitors is unbalance protection. Unbalance protection is a protection scheme based on the principle of branch symmetry or three-phase symmetry of capacitor banks, and it is closely related to capacitor capacity, wiring method and capacitor component type, Subject to this restriction, it is unable to make selection freely; and needs to change the primary or the secondary wiring method or needs to increase the peripheral equipment. For example, when the single-star type capacitor bank uses the phase difference voltage protection, it is necessary to increase the tap of the discharge PT, and differential connection with secondary side of discharge PT; when the H-bridge capacitor bank is protected by bridge current, it is necessary to add a bridge current CT to the bridge arm.
Due to the characteristics of the unbalance protection, the protection sensitivity and reliability will be affected. For example, when the single-star capacitor bank uses open triangle voltage protection for the discharge PT, the unbalance voltage introduces the transmission error of the three-phase discharge PT, which expands the scope of errors and reduces the protection accuracy, and these initial unbalance values must be avoided during setting the protection value, so the sensitivity is greatly affected. However, even in this case, it is impossible to avoid the influence of some factors such as three-phase voltage asymmetry and harmonics in the operation system. Moreover, due to the characteristics of the unbalance protection, there must be a problem that the dead zone of the fault cannot be discriminated when a symmetrical fault occurs. Taking a double-star capacitor bank using a neutral point unbalance current protection as an example, when a capacitor unit breakdown occurs in the A-phase capacitor bank on both branches, the unbalanced voltages generated at the neutral points of the two branches are equal, the neutral point unbalance current is still zero, and the fault cannot be detected, no protection action will be performed.
It has been proposed to use the capacitor capacitance variation as a monitoring and protection scheme for the capacitor. As an energy storage component, the capacitor has a relatively fixed capacitance, which is not affected by the capacity, wiring method and component type. There is no need to avoid the initial unbalance, and no dead zone problem occurs. However, in actual operation, the capacitor capacity is not constant, it is affected by the higher harmonics in the system, and also affected by external environmental temperature, humidity and other factors. The capacitor bank is used as a complete set of equipment, its front end is connected with other devices such as reactors, so that the actual impedance is not completely equal to the capacitive reactance of the capacitor bank. When the fault occurs, not only the capacitance value is changed, but also a change in the resistance value can be found. Under certain conditions, the capacitance value may change little, and the resistance value may change greatly. Therefore, if the change of the capacitance value is used as an action criterion for protection, the sensitivity and reliability for protection will be greatly reduced in the actual application process.
In view of the above problems, the present invention provides an adaptive protection method for impedance of parallel capacitors, which is simple to implement, adapts to various working conditions, and effectively improves capacitor protection accuracy and reliability for various fault conditions.
In order to implement the above method, the technical solution provided by the present invention is described as below:
In the above solution, the terminal voltage and current of the capacitor are monitored; the terminal voltage of the capacitor is a vector difference between the bus voltage of each phase and the neutral point voltage of the capacitor, or is a terminal voltage of the discharge PT; the current is a current of each phase of the capacitor, or is a vector sum of the currents of each phase branch of the capacitor. The real-time impedance of the capacitor is calculated based on the monitored current and voltage of the capacitor.
In the above solution, the initial impedance of the capacitor is automatically calibrated when put into operation, wherein the calibration equation for the initial impedance is described as follows:
Furthermore, the automatically calibrated initial impedance of capacitor must meet the following requirements:
is a single-phase theoretical rated impedance of the capacitor; {dot over (U)}n is a rated line voltage, and {dot over (S)}n is the rated capacity.
Furthermore, if the above conditions are met, the calibration is accomplished, take Zinit_(P) as the actual impedance Zreal_(P) of the capacitor when put into operation. If the calibration fails, need to perform the calibration until it is accomplished, otherwise take the Zideal as the actual impedance Zreal_(P).
In the above solution, during normal operation, the real-time impedance per phase of the capacitor and the relative value of the modulus of the real-time impedance change per phase of the capacitor are calculated as follows:
Furthermore, the actual impedance at the initial moment of operation results from the calibration. During normal operation, the actual impedance Zdyn_(P) of the capacitor is updated periodically with the real-time impedance Zreal_(P) which satisfies requirements. If the update period is reached and the update condition is satisfied, the impedance change is considered to be a normal change, and the actual impedance Zreal is updated; otherwise, the update fails and the actual impedance is not updated. The update condition is described as
εdyn_(P)<εset_alm_dyn
max(|εdyn_A−εdyn_B|,|εdyn_B−εdyn_C|,|εdyn_C−εdyn_A|)<εset_ub_dyn
Furthermore, under the non-fault condition, i.e., normal operation, the dynamic change of the capacitor is small in a short time; and the dynamic update period T can be set according to the actual situation, namely:
T=t
dyn,set
In the above solution, in the event of a fault, if the relative value of the modulus of the real-time impedance change of the capacitor satisfies the protection alarm condition; and the delay time is reached, generating a protection alarm, and the protection alarm condition is:
εdyn_(P)<εset_alm
In the above solution, in the event of a fault, if the relative value of the modulus of the real-time impedance change of the capacitor satisfies the protection trip condition, and the delay time is reached, perform the protection for trip, and the protection trip condition is:
εdyn_(P)>εset_trip
The present invention has the following beneficial effects: it is not affected by the capacitor voltage, the wiring mode and the component type, and is not affected by the system voltage level, the operation mode and the power quality, and is not affected by the monitoring system error or the sensing device error, and is not affected by the electromagnetic environment, external environment impacts such as weather and temperature, no additional primary or secondary equipment, no additional primary or secondary wiring complexity, suitable for various operating conditions, suitable for various fault conditions of capacitors and capacitor banks, simple calculation of the set value, easy to implement, and improved sensitivity and reliability of the protection for capacitor.
The invention will now be further described with reference to the accompanying drawings.
Take a parallel capacitor bank of 35 kV voltage level as an example, the capacitor bank model is TBB35-12000/200AKW, the capacitor unit model BFM 11-200-1 W, the capacitor bank of each phase has 10 capacitors in parallel and 2 capacitors in series, the rated capacity of capacitor unit is 200 Kvar, the rated voltage is 11 kV and the capacitor unit is an external fuse capacitor.
As shown in
The relationship between the number of external fuse units of the capacitor unit that are blown and the overvoltage multiple of the sound phase unit and the total impedance of each phase is calculated according to the number of capacitors connected in parallel and in series, as follows:
When 1 fuse of the capacitor is blown, the overvoltage multiple of the healthy component is 105.34%, which does not exceed 110%. Therefore, the capacitor is allowed to continue to work, and a fault warning is issued. When 2 fuses of the capacitor are blown, the overvoltage multiple of the component is 111.11%, the capacitor shall be tripped. Considering 1.5 times sensitivity to set the parameters as follows:
εset_alm=5.55/1.5=3.7
εset_trip=(12.62−5.55)/1.5+5.55=10.26
The protection alarm set value and the trip set value are set as follows:
According to the relevant provisions of “GB/T 11024.1-2010 parallel capacitors with nominal voltage more than 11.000V used for AC power system, Part 1: General”, the set values are as follows:
(3) Monitor the terminal voltage and current of the capacitor; the voltage at the capacitor terminal can be the voltage difference between the bus voltage of each phase and the neutral point voltage of the capacitor, or is the terminal voltage of the discharge PT; the current is the current of each phase of the capacitor, or is the vector sum of the currents of each phase branch of the capacitor. The real-time impedance of the capacitor is calculated based on the monitored current and voltage of the capacitor.
(4) The initial impedance of the capacitor is automatically calibrated when put into operation, wherein the calibration equation for the initial impedance is described as follows:
The calibrated initial impedance of capacitor must meet the following requirements:
If the capacitor wiring works normally, and the sensor accuracy meets the requirements, the capacitor is automatically calibrated successfully.
(6) Then put into operation, in normal operation, calculate the real-time impedance of each phase of the capacitor and the relative change of the real-time impedance. The calculation equation is as follows:
(7) Determine whether the capacitor is faulty. When the real-time impedance of the capacitor meets the fault condition, if the delay time of capacitor is reached at this time, the capacitor is considered to be faulty and protect the trip. The protection condition is:
εdyn_(P)<εset_alm_dyn
max(|εdyn_A−εdyn_B|,|εdyn_B−εdyn_C|,|εdyn_C−εdyn_A|)εset_ub_dyn
If the update condition is satisfied, the impedance change calculation result is considered as normal, and the actual impedance Zreal is updated, otherwise the update is not updated and the update fails.
Under the non-fault condition, i.e., normal operation, the dynamic change of the capacitor is small in a short time, and the dynamic update period T can be set according to the actual situation, namely:
T=t
dyn_set
The above embodiments are merely illustrative of the technical idea of the present invention, and the scope of protection of the present invention cannot be limited thereto, any technical changes made in accordance with the present invention or based on the technical solutions should fall within the scope of protection of the present invention.
Number | Date | Country | Kind |
---|---|---|---|
201611185611.3 | Dec 2016 | CN | national |
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/CN2017/092430 | 7/11/2017 | WO | 00 |