The present invention generally relates to power generating facilities that are interconnected by a power distribution grid and, more particularly, to providing protection of such facilities and the grid by rapidly detecting disconnection of power generation apparatus or facility from the power distribution grid.
At the present time, electrical power is available to virtually all people in most civilized countries of the world. Consumers of such electrical power are often distributed over a wide geographic area while power generation facilities are generally located in the proximity of either a fuel or energy source (e.g. hydroelectric facilities are often located near where a water reservoir naturally exists or can be economically constructed) or population centers such as cities although nuclear reactors used for power generation are often located somewhat more remotely.
All such power generation facilities inherently have limited power generation capacity although that capacity may be quite large. Many facilities are most efficient when operating continuously near their full power generation capacity while demand for electrical power can be quite variable. At the same time, greater power generation capacity of a given facility may greatly increase the initial capital expenditure required as well as possibly increasing cost of maintenance over the service life of power generation equipment. Therefore, while it is desirable to provide electrical power to consumers located near a power generation facility to limit inefficiency due to power transmission losses and to limit capital expenditures by limiting the power generation capacity of respective facilities to a small excess capacity over anticipated peak demand, it is also desirable to interconnect many such power generation facilities so that excess generated power at a given location can be distributed to locations where demand may, from time-to-time, exceed local power generation capacity. Such interconnection infrastructure is generally referred to as a grid and requires that power generation facilities be carefully and precisely synchronized in both frequency and phase so that power can be delivered between the grid and the local power generation and distribution network. It is also critical that a the connection between local power generation equipment or facility and the grid be maintained, not only to allow frequency and phase information of grid power to be maintained but to avoid power being delivered to the grid being redirected to local loads by a disconnection. Such a disconnection, sometimes referred to as grid loss, can rapidly cause significant damage to local loads and local power converters must be rapidly shut down when a disconnection is detected to prevent or mitigate such damage.
A lack or loss of grid confections is referred to as islanding and the likelihood of disconnection has been aggravated in recent years by the proliferation of relatively small power generation facilities deriving energy from so-called renewable resources such as solar and wind power that may not be consistently available. Such systems usually generate power as a direct current (DC) voltage and use a controllable converter to derive alternating current (AC) for transmission. Therefore stringent standards have been promulgated for detection of loss of synchronization and disconnection of a local network from the grid.
At the present time, the standard for detection of islanding and providing anti-islanding protection is the IEEE 1547 standard which requires that any distributed power generation facility under 10 MW capacity must be able to detect islanding and de-energize the area electric power system (EPS) within two seconds. The test load specified by the standard is a paralleled RLC (//RLC) load which is resonant at 60 Hz (or the frequency that may be used for the grid) which represents a worst case for islanding detection since such a load presents a near-zero impedance similar to the impedance of the grid at the resonant frequency. (An ideal grid would exhibit zero impedance and a grid exhibiting any significant impedance is referred to as a weak grid. The limiting case of grid weakness would be a grid exhibiting infinite impedance and would appear substantially identical to a disconnection from the grid although some voltage or phase information might still be derived.) The standard also requires so-called low-voltage ride through (LVRT) to accommodate a condition when the grid voltage drops but the grid connection is maintained such that the local power generation facility can and should continue to deliver power to the grid. Islanding detection should also achieve an almost zero non-detection zone (NDZ) such that virtually no islanding condition or event can exist or occur without detection.
Output-frequency based islanding detection (OFID) methods that detect changes in frequency and/or phase between the grid and local power generation equipment have been of substantial interest since, in general, they do not violate the LVRT requirement and can provide an almost zero NDZ. Many OFID methods are known that make modifications to the voltage or current control loop of converters and thus are configured to generate so-called frequency positive feedback that will drive the converter system frequency away from the steady state frequency when a reference frequency signal from the grid is not available. However, suitable positive feedback mechanisms and characteristics and design procedures for such methods are not well-developed at the present time and over-design or excessive experimentation have often been required to meet the islanding detection standard. While approaches to islanding detection has recently been the subject of substantial study, few studies have considered the impact of OFIDs on power converter operation, entire system stability or performance of sophisticated power systems such as multi-converter systems.
It is therefore an object of the present invention to provide frequency-based islanding detection using a phase-locked loop (PLL) system based on a small signal model to develop appropriate system responses and behaviors to frequency or phase perturbations which satisfy current and foreseeable islanding detection standards.
It is another object of the present invention to provide a methodology for evaluation of existing OFID systems.
It is a further object of the invention to provide an islanding detection apparatus and method exhibiting a zero non-detection zone by modifying the synchronization, itself, rather than the voltage or current control loop of the converter to thus cause the converter to become unconditionally unstable in the absence of phase information from a power distribution grid.
In order to accomplish these and other objects of the invention, a method for detection of an islanding condition of a power converter is provided comprising steps of tracking phase of a waveform using a phase locked loop having large signal non-linear positive feedback of phase information, adding a small signal representing angular frequency to the signal in the large signal, non-linear positive feedback loop or to an output of the phase locked loop to move a pole of said phase locked loop from a left half plane to a right half plane of the response of the phase locked loop, and detecting frequency drift of operation of the phase locked loop.
In accordance with another aspect of the invention, a phase locked loop and islanding condition detector is provided comprising an abc/dq converter, a transfer function element responsive to an output of the abc/dq converter containing phase information to determine bandwidth and transient performance of the phase locked loop, a frequency converter to convert an output of the transfer function element to a frequency signal, a phase integrator for integrating the frequency signal to produce a phase signal, a large signal feedback path to allow comparison of the phase signal with the phase information, and a small signal feedback path to combine the output of the transfer function element with the phase signal, or a small signal feed-forward path to combine the output of the transfer function element with an output of the phase locked loop.
The foregoing and other objects, aspects and advantages will be better understood from the following detailed description of a preferred embodiment of the invention with reference to the drawings, in which:
Referring now to the drawings, and more particularly to
As alluded to above, most smaller power generation systems (e.g. under the 10 MW capacity to which the above standard is directed) receive power as direct current (DC) at a relatively constant voltage. as depicted by current source and filter/storage capacitor or battery 12. This input power is converted to, for example, three branches of alternating current (AC) power by pairs of switches 14. Pulse width modulation (PWM) is preferred at the present time since any desired waveform can be generated under digital control in response to current controller 16 responsive to currents in each of the three branches and output of a phase locked loop (PLL) 20 which is, in turn, responsive to the waveforms vCa, vCb and vCc after the waveforms have been filtered by inductors 22 in each respective branch or phase.
In
The key element in the interface of
This converter effectively imposes a rotating frame of reference, s, on the signals input to it; allowing the phase to be accurately tracked and the frequency adjusted to bring the phase of the output signal into exact alignment with the input phase. The inverse operation is indicated by the element 29 performing the 1/s conversion following the addition of 2π60, representing the operation angular frequency, to the signal. The 1/s operation is thus essentially integration of the angular frequency, ω, over time to again yield a phase angle, θC since ∫ωt=θ.
From equations (1) and (2), it can be seen that the three respective phases are all functions of θg which is developed by transfer function element 26 (in which Kp and Ki are gains corresponding to design parameters that affect bandwidth and transient response of the PLL and thus comprise a loop filter, LF, depicted by a dashed line in
In order to understand the PLL behavior during islanding condition (e.g. following an islanding event), a simplified one-line circuit depicted in
The injected current IC flows into the system network, generating the corresponding voltage vC at the terminal of the converter. Therefore, vC can be derived as:
{right arrow over (v)}C=ZL{right arrow over (i)}C=|ZL|ICej(θ
φ2=Phase(ZL) (3)
using the phasor representation in which K2 and φ2 are the impedance and phase shift of ZL, respectively.
Based on the characteristics of abc/dq converter 12, under islanding conditions, the PLL model of
vq=sin [(φ2(ωC)]×IC×K2(ωC) (4)
If considering the parallel RLC (//RLC) test load specified by IEEE 1547, the K2 and φ2 of equation (3) can be alternatively derived as:
Thus it is easily seen that φ2=0 only when ωC=ωr. In other words, when the resonance of the //RLC load equals the line frequency, the large signal feedback loop in the PLL effectively disappears and the PLL continues to operate at the line frequency when the islanding condition occurs and the system is in a steady-state, fully synchronized condition until a perturbation occurs. Thus, the response required by IEEE 1547 cannot be guaranteed since the PLL may not become unstable and exhibit a detectable behavior until an unpredictable time subsequent to an islanding event. Therefore, the information provided by this PLL model is insufficient to fully evaluate the PLL behavior and determine if the IEEE 1547 standard would be met by a particular converter or PLL design.
To further study PLL behavior and derive a PLL design capable of providing a near-zero non-detection zone (NDZ) within the IEEE 1547 standard or capable of unconditional detection (e.g. a zero non-detection zone), in accordance with the invention, a small-signal model at the equilibrium (e.g. steady-state, fully synchronized) point is preferably employed as will now be discussed. To do so, non-linear terms of equation (5) are linearized at the equilibrium point as
in which k2 and kφ are the linearized small signal gains of K2 and φ2, respectively, at the equilibrium point and are given by:
Using the //RLC impedance load, the parameters of equations (6)-(9), derived by substituting equation (5) therein to derive a small signal model from the large signal model of
from which it may be helpful to observe that
This model is only valid for study of the low frequency dynamics of the PLL within the PLL bandwidth because the non-linear model is established using the phasor representation which is only valid for dynamics much lower than the line frequency. However, since the PLL bandwidth is usually designed to be less than the line frequency to reduce sensitivity and avoid response to grid voltage variation (since only phase information is of interest and tracked by the PLL), much of the high frequency information is already attenuated. Therefore, the small signal model is useful for study of low frequency dynamics.
As can be seen from the model as illustrated in
which is a first order system with one single pole given by
since kφ is a negative value, ωpole is a left hand plane (LHP) pole and thus ωr is a stable equilibrium point of the PLL for the //RLC load and kφ is critical for determination of the type of equilibrium point.
That is, whether the equilibrium point is stable or unstable can be determined directly by examining the off-line impedance of the local or test load. Initially, the steady-state equilibrium point is found at the frequency where the phase of the impedance is zero. Then the sign of kφ is found by determining the slope of the phase of the impedance near the equilibrium point. If kφ is negative, as illustrated in
Thus, in order to detect an islanding condition by an OFID method, the PLL must be unstable at the equilibrium point such that frequency drift will occur when a reference frequency is lost. To do so, the equilibrium point can be modified in accordance with the invention to be an unstable equilibrium point.
In accordance with a first embodiment of the invention, the PLL can be modified as illustrated in
It can be seen from
Thus N can be designed in accordance with
As a practical matter, kφ+N is designed to be a small number and the PLL proportional gain, Kp, is also small. Thus, the following condition is valid:
Accordingly, the closed-loop pole will be moved to the right half plane (RHP) in the s domain because of the additional feedback shown in
ΔωC=ωr−ωo (17)
and is a small value when ωr is close to the system frequency.
It is also significant to determine the frequency drift speed or rate since the frequency must drift sufficiently to be detected and the system de-energized within the two second limit specified by IEEE 1547. Considering the worst case, where the voltage does not change under islanding event conditions, equation (14) can be further simplified to:
which indicates that the PLL dynamic performance (e.g. the value developed by the proportional gain and phase integrator (PI−1/s block 29), alone, determines the frequency drift rate. That is, when the voltage Vg remains the same before and after phase information is lost, there is no grid voltage information to cause or contribute to a change in ωpole and is thus the worst case. Considered from this perspective a somewhat increased PLL bandwidth is desirable.
In this regard and referring now to
Both the natural frequency ωnM and the damping factor ζM of the PLL in accordance with the first embodiment of the invention change with the value of N.
That is, if N=0, ωnM and ζM are the same as the natural frequency and damping factor of a typical PLL. If the PI values in equation (19) are designed by choosing N=0, ωn=2π6 (one-tenth of the line frequency) and ζ=1, the normalized natural frequency, ωnM/ωn of the PLL in terms of N is shown in
N<1/Kp (20)
limiting the usable design region shown in
As alluded to above, a reduced bandwidth of the PLL can slow the frequency drift under islanding conditions and thus may preclude the detection and response time requirement of IEEE 1547 from being unconditionally met even though islanding detection in accordance with the invention as discussed above, is, in fact, unconditional and provides a zero non-detection zone that cannot be achieved by typical PLLs.
Conversely,
Referring now to
It should also be noted in regard to the second embodiment of the invention that, in terms of the grid-tied condition, all the small-signal effects introduced by injection current are decoupled by the grid voltage due to the grid impedance being substantially zero. However, for weak grid conditions where the grid impedance may be significant, the additional feed forward loop still affects system operation. That is, if the grid were an ideal grid having zero impedance, there would be no measured voltage response to injected current to cause a change in PLL frequency. However, with a weak grid where the grid impedance is significant, the additional current injected into the grid by the feed forward loop of the second embodiment of the invention causes a strong voltage response that affects PLL frequency in the same manner as discussed and analyzed above for the first embodiment of the invention even when coupled to a test or local load closely simulating a stiff grid-tied condition, particularly since N can be made arbitrarily large in the second embodiment of the invention. (It should be noted that while the grid voltages were assumed to go to zero under islanding conditions or upon the occurrence of an islanding event, the inputs to the abc/dq converter 25 remain in place and are connected in parallel with the connection to the grid or local of test load as shown in
The second embodiment of the invention as described above is suitable and may be preferable for most applications since the response can be made arbitrarily rapid but, perhaps more importantly, the second embodiment affects PLL performance only under islanding and very weak grid conditions where grid impedance is significant and which rarely occurs. In a typical weak grid case, the grid impedance is typically small and the second embodiment does not impose a change on PLL operation.
While both the first and second embodiments of the invention are clearly well-suited to meeting the IEEE 1547 standard for islanding detection without over-design or undue experimentation, it should be understood that neither the direction nor the rate of drift can be rigorously predicted because both responses remain highly dependent on initial conditions. Nevertheless, the invention provides an initial design to be developed for a given application and anticipated load and, at a minimum, provides a vanishingly small zone of conditions where detection of islanding might not occur and the two embodiments as described above provide for frequency drift response to be made unconditional and arbitrarily rapid. Therefore the invention provides for PLL designs to be created for various applications that are virtually certain to be suitable, based on the statistical variation of ΔωC. The invention also provides a methodology for analysis of a given design to determine acceptability to meet IEEE 1547 based on the local or test load and design parameters Kp and Ki as discussed above in connection with
The methods and PLLs for small signal stability based islanding detection described above have been experimentally verified using the system parameters given in Table 1.
According to the load parameters, the small signal phase shift term can be calculated as −0.008, and the value of N for the test was chosen as 0.009 to move the closed loop pole from the LHP to the RHP. The PI (1/s block 29) values are Kp=1 and K1=2 such that ΔωC is maintained the same.
In view of the foregoing, it is clearly seen that the invention provides a first embodiment of a PLL where frequency drift is virtually guaranteed while providing a quickly increasing degree of frequency drift that is readily detectable within a very short period of time. The second embodiment of the invention provides a virtually identical response to an islanding condition while allowing the frequency drift response to be made arbitrarily rapid.
While the invention has been described in terms of a single preferred embodiment, those skilled in the art will recognize that the invention can be practiced with modification within the spirit and scope of the appended claims.
Number | Name | Date | Kind |
---|---|---|---|
7292649 | Atkinson et al. | Nov 2007 | B2 |
7386286 | Petrovic et al. | Jun 2008 | B2 |
Number | Date | Country | |
---|---|---|---|
20140312882 A1 | Oct 2014 | US |
Number | Date | Country | |
---|---|---|---|
61815040 | Apr 2013 | US |