This invention relates to an apparatus for testing an arc fault detector.
Arcing is a normal function when switching loads on or off. Such normal arcing occurs with switches and electrical equipment and is usually harmless. As a result it rarely results in a hazardous condition. On the other hand, arc fault conditions can arise anywhere along a circuit or installation which can give rise to high and sustained levels of arcing which can result in electrical fires, and it is desirable to detect and eliminate such arcing faults quickly and effectively.
There is a requirement in UL1699 for detection of two types of arc fault current-series arc fault currents and parallel arc fault currents.
The conditions under which each of these types of arc faults can occur are represented schematically in
In the case of series arcing,
In the case of parallel arcing,
In both case, such arcing will generate combustion and heat which could give rise to electrical fires. Arc fault detectors (AFDs) are intended to provide protection against such faults, and such devices are described in patent application nos. S2010/0361 and S2010/0534, which are incorporated herein by reference in their entireties.
AFDs are required to detect series and parallel arc fault currents, and it is generally accepted that detection of series arc fault currents is the more difficult of the two because the arcing current is always limited by a load whereas parallel arc fault currents can be substantially greater and easier to detect.
Two critical problems encountered with AFDs in practice are nuisance tripping and masking. In the case of nuisance tripping the AFD trips when operating a load which can produce arcing, e.g. vacuum cleaners, etc. In the case of masking, the AFD fails to trip under a fault condition when an appliance is connected but trips when the appliance is not connected. This problem is caused by the appliance masking the arc fault current signature which is normally detected by the AFD, and once the appliance is switched off the AFD detects the arc current signature. The problem of masking is largely dependent on the arc current detection technique used in the AFD.
AFDs are fitted with a test button to enable the user to test the device after installation. However, the test button can only generate pulses or signals which are detected by the AFD and cause it to trip automatically, but such testing means is not truly representative of an arc fault condition. AFD testers are readily available on the market to enable electricians to test the AFD, but these devices also generate pulses or signals which are not truly representative of an arc fault condition. Furthermore, AFD designs vary considerably with the result that conventional AFD testers may be compatible with some AFDs whilst being incompatible with others. As a result an electrician may need to use different AFDs testers for different AFD designs. Given that in all cases the AFD tester does not produce actual arcing currents, there is always some doubt as to the efficacy of existing AFD test devices.
It is an object of the invention to provide an improved AFD tester.
According to the invention there is provided an apparatus for testing an arc fault detector, comprising a housing having an ac power input device connected to supply ac power to electrical conductors inside the housing, and an arc generator inside the housing connected to at least one of the conductors, the arc generator comprising at least one pair of contacts and means to vibrate said contacts alternately open and closed to generate arcing.
The arc generator may comprise a loose electrical connection and means to vibrate said connection.
In such a case the means to vibrate said connection may comprise a mechanical oscillator operated by at least one electromagnetic winding.
The mechanical oscillator may comprise two electromagnetic windings which are energised alternately to drive a ferromagnetic member alternately in opposite directions.
Alternatively, the mechanical oscillator may comprise an electromagnetic winding which is intermittently energised to drive a ferromagnetic member in one direction and a resilient device to return the ferromagnetic member in the opposite direction between successive energisations of the electromagnetic winding.
The arc generator may alternatively comprise a pair of contacts which are caused to vibrate alternately open and closed by repeated energisation of an electromagnetic winding.
In certain embodiments the arc generator is connected in series with one of the conductors inside the housing to simulate a series arc fault.
In other embodiments the arc generator is connected across a pair of conductors inside the housing to simulate a parallel arc fault.
Preferably the vibration means is arranged to vibrate the contacts at the supply frequency.
In order to test an AFD on a dc system the housing may have externally accessible terminals and the arc generator is also connected across said terminals.
Preferably the power input device comprises an electrical plug.
Preferably, too, the housing further has an output device allowing connection of an external appliance for receiving power from the input device through the internal conductors.
In such a case the power output device may comprise an electrical socket.
Embodiments of the invention will now be described, by way of example, with reference to the accompanying drawings, in which:
In the various figures of the drawings the same or equivalent components have been given the same references.
Referring to
The diameter of the aperture in each terminal 20 is just slightly larger than the diameter of the respective stud 18 so as to create a small gap 26 between the terminal and the stud,
Each solenoid SOL1, SOL2 is connected to a supply derived via diodes D1 and D2 and a mains transformer TFMR from the ac mains. The transformer provides isolation from the AC mains supply and may also be used to change the secondary voltage to any convenient value. The secondary winding of the transformer TFRM has a centre tap to provide a common connection for two electronic switches in the form of silicon controlled rectifier SCR1 and SCR2.
When the mains supply is turned on each silicon controlled rectifier will conduct alternately for up to one half cycle of the mains supply and when SCR1 is turned on SOL1 will be energised during which time SCR2 will not be conducting and SO12 will not be energised. As a result the plunger 14 will initially be drawn into the bobbin 10 and, via a collar 15 on the plunger which extends between two limit stops 17 on the slider, the plunger will pull the slider 16 in the same direction as the plunger. When SCR1 turns off at the end of a half cycle SCR2 will turn on and the plunger 14 will be drawn in the opposite direction into the bobbin 12, pulling the slider 16 also in the opposite direction.
The two solenoids will conduct on alternate half cycles of the mains supply at the supply frequency, for example 50 Hz, and as a result the slider 16 will oscillate back and forth at this frequency. The cable 22 will thus be thrown back and forth between the two studs 18 and this will cause arcing between each cable terminal 20 and its respective stud 18 as the cable vibrates rapidly between the two studs alternately opening and closing the pair of contacts 18,20 at each end. The arcing current will occur predominantly at the mains supply frequency and its magnitude will be determined by the current setting load connected via the leads L1 and L2. Thus an arcing current of a precise magnitude and frequency can be generated by the arc generator shown in
This arc generator can be connected on the load side of an AFD, for example via a protected socket outlet, and it will generate genuine arcing currents which will enable the AFD to be tested. The arcing current can be selected by suitable choice of the current setting load within the generator to ensure that the current is greater than the minimum threshold of detection for an AFD. This is presently 5A for AFDs based on UL1699. With the arrangement of
The apparatus shown in
An arc generator 100 as shown in
Various switches SW1, SW2 and SW3 inserted in the internal circuitry of the housing 30 are manually operable from outside the housing for enabling a plurality of different arc fault tests to be made. The switch SW1 allows the user to selectively shunt the arc generator 100, the switch SW2 allows the user to selectively connect an internal load LD, and the switch SW3 allows the user to selectively isolate the socket 34.
In use the tester is plugged into an AFD-protected mains socket using the plug 32. The tester may have an on-off switch and when the tester is powered from the mains supply and SW1 is open and SW2 is closed an arcing current will flow through the internal current setting load LD as previously described. As the current is flowing in a series circuit, this represents a series arc fault condition. This current can be set at the lowest threshold of detection of the AFD, e.g. 5A, to verify that the AFD is still able to operate correctly within its specified level.
When SW1 and SW2 are open and SW3 is closed and an external load such as an electrical appliance 36 is connected to the socket 34, arcing current will flow through the external load, and provided this current is above the minimum operating threshold of the AFD, the device should trip. In this way it can be verified that the AFD detects arcing currents with different loads, e.g. vacuum cleaners, etc.
If SW1 is closed and SW2 is open and a range of appliances is connected to the socket 34, the AFD should not trip because no arc fault exists. In this way the AFD can be tested via the AFD tester to ensure that the device is not prone to nuisance tripping. If SW2 is then closed followed by opening of SW1, thus simulating a series arc fault, the AFD should trip. If it fails to trip it will indicate that the load is masking the arcing current signature and preventing its detection. It should be noted that with SW1 open, SW2 and SW3 closed and an external load connected to socket 34, testing under a parallel arc fault condition can be made.
It would be possible to use the tester to test an AFD on a DC system, for example a photovoltaic solar panel, by arranging for connections L1 and L2 to be made accessible in the form of externally accessible terminals for connecting in series with the DC supply, for example as shown at X and Y in
The AFD tester can be refined or improved without departing materially from the invention. For example, the use of electronic switches SCR1 and SCR2 controlled by the mains supply frequency obviates any need for calibrating the arc current frequency. However the arcing frequency could be set by use of an oscillator instead of SCR1 and SCR2. Lights could be fitted to indicate current flow, and a single electromagnet may be used, etc.
In this arrangement an electromechanical relay RLA1 comprises a bobbin 50 with a solenoid winding 52, a frame 54, a pole piece 56 and a ferromagnetic armature 58 which is pivoted to the frame 54 and biased to an open position (i.e. away from the pole piece 56) by a spring 60. On each positive half cycle of the mains supply the solenoid 52 is energised and the armature 58 is pulled toward the pole piece 56. On negative half cycles the armature 58 moves to its open position under the action of the spring 60 because the solenoid 52 is de-energised. The armature 58 is used to vibrate the slider 16 back and forth and generate arcing as previously described.
In this arrangement the relay RLA1 of
With this arrangement a standard relay can be used, and it can be replaced after a certain number of operations when the contacts have deteriorated to an unacceptable extent.
The armature 58 is used to directly vibrate the conductive bar 70 back and forth such that the slot 72B in the bar causes rapid intermittent connections between the bar and the right hand (as seen in
In
This arrangement offers several advantages over previous embodiments, such as its simplicity, concentrating of arcing at one point so as to facilitate optimisation of arcing, etc. Another advantage is that, because the spring 76 will hold the bar 70 in contact with the right hand stud 18 when the arc generator is not in use, the available arcing current will flow through the circuit prior to commencement of the arcing and thereby facilitate measurement and verification of the available arcing current.
A timer could be included in the tester to limit the duration of arcing current flow at each operation. The tester could be fitted with a counter to alert the user to replace the relay or cable after a certain number of operations. A relay with an AC or DC coil could be used. A shading ring is fitted to AC relays to prevent them from chattering, but if the shading ring was removed the inherent chatter could be used to generate the arcing current. Under such an arrangement the relay could be operated directly from the mains supply if its coil was suitably rated.
In the examples above, the symmetry of the arcing current will be to some extent determined by the phase within each half cycle at which conduction of the electromagnetic means commences. However some degree of asymmetry and randomness can be introduced into the arcing current by allowing relay chatter or by overdriving the relay or solenoid coil such that the mechanical action ceases to be in synch with the electrical energisation cycles. Asymmetry and randomness may be also be achieved by driving the SCRs from an alternative source, for example a randomly variable signal generator, etc.
As before, the apparatus comprises a power in plug 32 and a power out socket 34 with live L and neutral N supply conductors L, N extending between them for the supply of AC power at the plug 32 to a load connected to the socket 34. It will be understood that, although not shown, the conductors L, N and the other circuitry shown in
In this case the arc generator 102 is connected across the supply conductors L, N inside the housing 30 to simulate a parallel arc fault. The arc generator 102 comprises a basic arc generator 100 as shown in any one of
The arc generator 100 is activated by a control signal issued by an electronic control circuit 104 on a control line 106 when a test button 108 on the exterior of the housing 30 is pressed. The control signal on line 106 closes a normally open switch (not shown) in the arc generator drive circuit.
The control circuit 104 monitors the mains supply voltage and measures the available test current at Rcs before the arc generator is activated by pressing the test button 108. A power supply unit PSU provides power to the control circuit 104. If the supply voltage is below a certain level the available test current will be too low to enable a valid test to be done, in which case an “AC Low” indicator LED will be lit. If the available test current is too low, for example because of an open circuit or high impedance in the arc generating circuit, a “Current Low” indicator LED will be lit.
When the arc generator 100 is activated by pressing the test button 108, it will generate a parallel current representative of that shown in
The control circuit 104 preferably incorporates a timer to limit the duration of the flow of arcing current, and also to set a certain interval between repeated tests so as to reduce the risk of overheating or damage to the tester. The arc generator preferably includes a temperature sensor Tc which will detect excessive heat in the resistor Ra and enable the control circuit to inhibit further testing until the temperature has reached a safe level.
When an upstream AFD trips, power will be removed from the tester. However, by suitable storage of power, e.g. in a capacitor or in a battery, the result of the test can continue to be indicated for a certain period after the test.
The status of supply Line, Neutral and Earth are monitored by indicators N1, N2 and N3. When the supply connections are correct, indicators N1 and N2 will be lit and N3 will not be lit. In the event of loss of supply E, N2 will not be lit, but N1 and N3 will be lit, but possibly not at full brightness because they will share the supply voltage. In the case of loss of supply N, N2 will be lit at full brightness, and N1 and N3 will be lit, but not necessarily at full brightness because they will share the supply voltage. In the event of loss of supply L, no indicator will be lit.
Described herein is an AFD tester which produces realistic arc fault currents at the frequency of the protected AC circuit and which facilitates testing of the AFD for problems of nuisance tripping and masking.
Although the foregoing has described embodiments of AFD tester having an output socket 34 for connection of an external load, the output socket could be omitted if it were desired to have a simple AFD tester based only on the arc generator with no provision for connection of an external load.
The invention is not limited to the embodiments described herein which may be modified or varied without departing from the scope of the invention.
Number | Date | Country | Kind |
---|---|---|---|
S2011/0168 | Apr 2011 | IE | national |
This application is a 35 USC 371 national phase filing of PCT/EP2012/050935, filed Jan. 23, 2012, which claims priority to Irish national application 52011/0168 filed Apr. 8, 2011, the disclosures of which are incorporated herein by reference in their entireties.
Filing Document | Filing Date | Country | Kind | 371c Date |
---|---|---|---|---|
PCT/EP2012/050935 | 1/23/2012 | WO | 00 | 9/19/2013 |