This disclosure relates in general to control systems and more particularly to an autonomous ventilation system.
Ventilation systems are commonly found in modern residential, restaurant, and commercial kitchens. Heat, smoke, and fumes are an ordinary byproduct of cooking many foods and must be removed in order to protect the health and comfort of those present in the kitchen and adjacent areas. Ventilation systems provide an effective way to capture excessive heat, smoke, and fumes generated in kitchens and ventilate them to the atmosphere where they pose no threat to health or safety.
A typical ventilation system consists of an exhaust hood positioned over pieces of cooking equipment that are known to produce heat, smoke, or fumes. This exhaust hood is usually connected via ducts to an exhaust fan and in turn to a vent located on the outside of the building housing the kitchen. The exhaust fan is operated in a way to create a flow of air from the exhaust hood to the outside vent. This creates a suction effect at the exhaust hood that captures the air and any airborne contaminants around the hood. Consequently, any heat, smoke, or fumes generated by the cooking equipment will rise up to the overhead exhaust hood where it will be captured by the suction and transported out of the kitchen to the outside vent. There, it will dissipate harmlessly into the atmosphere.
Most ventilation systems must be manually activated and deactivated by the user. In a typical fast-food restaurant, for example, an employee must manually activate the kitchen ventilation system early in the day or before any cooking occurs. The system will then remain active in order to capture any smoke or fumes that may result from cooking. The system must then be manually deactivated periodically, at the end of the day, or after all cooking has ceased. This manual operation of the ventilation system typically results in the system being active at times when ventilation is not actually required. This needlessly wastes energy not only associated with the operation of the ventilation system, but also due to the ventilation of uncontaminated air supplied to the kitchen by a heating and cooling system. By operating when no smoke or fumes are present, the ventilation system will remove other valuable air that was supplied to heat or cool the kitchen and thus cause the heating and cooling system to operate longer than it would have otherwise.
The present disclosure provides an autonomous ventilation system that substantially eliminates or reduces at least some of the disadvantages and problems associated with previous methods and systems.
According to one embodiment, an autonomous ventilation system includes a variable-speed exhaust fan, a controller, an exhaust hood, and a spillage sensor. The exhaust fan removes air contaminants from an area. The controller is coupled to the exhaust fan and adjusts the speed of the exhaust fan. The exhaust hood is coupled to the exhaust fan and directs air contaminants to the exhaust fan. The spillage sensor is coupled to the controller, detects changes in an environmental parameter in a spillage zone adjacent to the exhaust hood, and communicates information relating to detected changes in the environmental parameter to the controller. The controller adjusts the speed of the exhaust fan in response to information relating to changes in the environmental parameter detected by the spillage sensor.
Technical advantages of certain embodiments may include a reduction in energy consumption, an increase in the comfort of the ventilated area, a decrease in noise, and an increase in the lifespan of environmental sensors and fans. Embodiments may eliminate certain inefficiencies such as needlessly ventilating valuable air from an area that was supplied by a heating, ventilation, and air conditioning (“HVAC”) system.
Other technical advantages will be readily apparent to one skilled in the art from the following figures, descriptions, and claims. Moreover, while specific advantages have been enumerated above, various embodiments may include all, some, or none of the enumerated advantages.
For a more complete understanding of the present disclosure and its advantages, reference is now made to the following description, taken in conjunction with the accompanying drawings, in which:
Removing air contaminants 122 from kitchen 102 helps ensure that kitchen 102, as well as adjacent room 104, remains safe, sufficiently free of air contaminants 122, and at a comfortable temperature for anyone inside. The volume of air exhausted via exhaust hood 116 should be carefully regulated to minimize the quantity of conditioned air (air entering facility 100 through HVAC system 110) that is vacated from kitchen 102 and facility 100 while ensuring that enough air is ventilated to prevent buildup of air contaminants 122. Because a particular piece of cooking equipment 114 may not be in use at all times and thus will not continuously generate air contaminants 122, it becomes beneficial to vary the rate at which exhaust hood 116 ventilates air contaminants 122 from kitchen 102 as well as the rate at which ceiling supply air vent 118 supplies air to kitchen 102 as a means to conserve energy and increase occupant safety and comfort. The embodiments discussed below provide a convenient alternative to manually activating a ventilation system as the level of air contaminants fluctuates.
While facility 100 has been described in reference to a restaurant, it should be noted that there are many facilities in need of such ventilation systems. Such facilities include manufacturing facilities, industrial facilities, residential kitchens, and the like. Likewise, embodiments in this disclosure are described in reference to kitchen 102, but could be utilized in any facility requiring ventilation.
Autonomous ventilation system 200 also includes a spillage probe assembly 214 containing one or more spillage sensors 230 (not pictured in
Spillage probe assembly 214 also contains a termination box 224, and in some embodiments, an override button 226. The one or more spillage sensors 230 are coupled to termination box 224. In some embodiments, override button 226 is also coupled to termination box 224. Override button 226, however, may be located on spillage probe assembly 214, exhaust hood 116, or any other location that is accessible to a user.
Autonomous ventilation system 200 is controlled by a controller 220. As an example only, controller 220 may consist of the Kontar MC8 process controller manufactured by Current Energy, Inc. However, any suitable controller may be used. Controller 220 is coupled to exhaust fan 210, supply air fan 212, cooking equipment 114, an exhaust temperature sensor (not pictured), an ambient kitchen temperature sensor 228, override button 226, and/or one or more spillage sensors 230. Controller 220 receives information from spillage sensors 230 to determine fluctuations in an environmental parameter(s) in spillage zone 216. Controller 220 also communicates with exhaust fan 210 to control its speed and consequently the rate of ventilation of autonomous ventilation system 200. In some embodiments, controller 220 additionally communicates with supply air fan 212 to control its speed and thus the amount of air that is re-supplied to kitchen 102. Controller 220 may also be coupled to cooking equipment 114 in order to determine when it has been turned on and off.
In operation, autonomous ventilation system 200 automatically starts and stops according to a predetermined schedule and/or by sensing the activation of cooking equipment 114 under exhaust hood 116. In addition, the ventilation rate of autonomous ventilation system 200 automatically adjusts according to fluctuations in one or more environmental parameters in spillage zone 216 as sensed by spillage sensors 230. Additionally or alternatively, a user may manually control autonomous ventilation system 200 by momentarily pressing override button 226.
First, autonomous ventilation system 200 may automatically start and stop according to a predetermined schedule. A user may configure a schedule or modify an existing schedule through a local or remote interface to controller 220. Controller 220, in turn, may turn exhaust fan 210 on and off and/or adjust its speed based on this predetermined schedule. Additionally or alternatively, controller 220 may turn exhaust fan 210 on and off and/or adjust its speed based on the state of cooking equipment 114 under exhaust hood 116. In one embodiment, for example, controller 220 may be coupled to cooking equipment 114 in order to detect when it has been activated. In such an embodiment, controller 220 may turn on exhaust fan 210 when cooking equipment 114 has been activated, and may turn off exhaust fan 210 when cooking equipment 114 has been deactivated. By automatically starting and stopping according to a predetermined schedule and/or the state of cooking equipment 114, autonomous ventilation system 200 provides increased energy efficiency and comfort level while minimizing unnecessary noise and ventilation of conditioned air.
Additionally, controller 220 may turn exhaust fan 210 on and off and/or adjust its speed based on fluctuations in an environmental parameter in spillage zone 216 due to spillage air contaminants 128. In one embodiment, for example, spillage probe assembly 214 contains one or more spillage sensors 230 that measure the temperature of spillage zone 216. As an example only, spillage sensors 230 may consist of the Betatherm G10K3976AIG1 thermistor. In this embodiment, controller 220 may communicate with an ambient kitchen temperature sensor 228 to determine the ambient temperature of kitchen 102 away from the spillage zone (e.g., receive temperature measurements from sensors) and with spillage sensors 230 of spillage probe assembly 214 to determine the temperature of spillage zone 216. Controller 220 may then compare the temperature of spillage zone 216 with that of kitchen 102 to determine if the difference in temperature has reached or exceeded a predetermined amount, for example, two degrees Fahrenheit. If, for example, the temperature of spillage zone 216 exceeds the temperature of kitchen 102 by this predetermined amount (or any other suitable amount), controller 220 may accelerate the speed of exhaust fan 210 to increase the ventilation rate of autonomous ventilation system 200 and eliminate spillage air contaminants 128. Controller 220 may maintain this increased ventilation rate for a predetermined period of time or until it is determined that the increased rate is no longer needed. For example, controller 220 may decrease the speed or deactivate exhaust fan 210 when the difference in temperature between kitchen 102 and spillage zone 216 returns to a value that is less than the predetermined amount. By automatically adjusting its ventilation rate based on environmental parameters in spillage zone 216, autonomous ventilation system 200 alleviates disadvantages of other ventilation systems such as wasted energy and unnecessary noise. In addition, by locating spillage sensors 230 in spillage zone 216 outside of exhaust hood 116, the sensors are less susceptible to normal deterioration and corrosion caused by air contaminants 122. As a result, spillage sensors 230 require less cleaning and maintenance and will have a longer life.
In another embodiment, spillage probe assembly 214 may contain one or more spillage sensors 230 that measure bidirectional airflow through spillage zone 216. In this embodiment, spillage sensors 230 are orientated in such a way as to detect air flow in the up and down directions through spillage zone 216. If the ventilation rate of autonomous ventilation system 200 is insufficient to capture and remove all air contaminants 122 associated with the operation of cooking equipment 114, spillage air contaminants 128 will spill out of exhaust hood 116 and pass through spillage zone 216 creating an upward flow of air. Controller 220 may detect this upward flow of air by receiving airflow measurements from spillage sensors 230. If the flow of air up through spillage zone 216 reaches or exceeds a predetermined amount, controller 220 may accelerate the speed of exhaust fan 210 to increase the ventilation rate of autonomous ventilation system 200 and eliminate or reduce spillage air contaminants 128. Controller 220 may then decrease the ventilation rate after a predetermined period of time or after it detects with spillage sensors 230 that there is no longer a flow of air up through spillage zone 216 equal to or greater than the predetermined amount.
In some embodiments, controller 220 may additionally or alternatively adjust the speed of exhaust fan 210 based on the state of override button 226. In this embodiment, a user may momentarily push override button 226 in order to manually control the speed of exhaust fan 210 and thus the ventilation rate of autonomous ventilation system 200. For example, if exhaust fan 210 is not on, a user may press override button 226 in order to activate autonomous ventilation system 200 for a predetermined amount of time. If exhaust fan 210 is already on, a user may press override button 226 in order to accelerate the ventilation rate of autonomous ventilation system 200 for a predetermined amount of time. In some embodiments, there may be more than one override button 226. In these embodiments, override buttons 226 may provide the user a means to turn autonomous ventilation system 200 on and/or off, increase and/or decrease the ventilation rate, or any combination of the proceeding. The one or more override buttons 226 provide the user with a means of manual control over autonomous ventilation system 200 when desired.
In some embodiments, controller 220 may also automatically control the speed of supply air fan 212 to provide a desired pressurization of kitchen 102. For example, it may set the speed of supply air fan 212 to match the speed of exhaust fan 210. As a result, the rate at which air is removed and supplied to kitchen 102 is approximately equal and thus the temperature and air pressure remains relatively constant. Controller 220 may also set the speed of supply air fan 212 to a speed that is greater than the speed of exhaust fan 210 to create positive pressure in kitchen 102. Additionally or alternatively, controller 220 may set the speed of supply air fan 212 to a speed that is less than the speed of exhaust fan 210 to create negative pressure in kitchen 102. This ensures that the environment in kitchen 102 remains safe and comfortable regardless of how much air is being ventilated through exhaust hood 116.
Exhaust fan 210 and supply air fan 212 may be powered by various types of motors including, but not limited to, AC single-phase electrical motors, AC three-phase electrical motors, and DC electrical motors. The speeds of exhaust fan 210 and supply air fan 212 may be adjusted by controller 220 by modulating the frequency of the output of a variable frequency drive in the case of AC single-phase or three-phase electrical motors, by a phase cut modulation technique in the case of a single-phase motor, or by changing voltage in case of a DC electrical motor.
Modifications, additions, or omissions may be made to autonomous ventilation system 200 and the described components. As an example, while
Spillage probe assembly 300 includes a housing 302, a tensioned cable 304, one or more spillage sensors 230, a termination box 224, and an override button 226. The one or more spillage sensors 230 and override button 226 are coupled to termination box 224, which may in turn be coupled to controller 220 (not pictured). Tensioned cable 304 is coupled to housing 302 and provides support to spillage sensors 230. Tensioned cable 304 suspends spillage sensors 230 in spillage zone 216 and isolates them from housing 302. Spillage sensors 230 are attached to tensioned cable 304 in such a way that allows a user to slide the sensors on tensioned cable 304 to a location that is above a piece of equipment such as cooking equipment 114 below exhaust hood 116. Tensioned cable 304 may be any material including, but not limited to, metal and/or plastic. In some embodiments, tensioned cable 304 may be replaced with any other suitable means of supporting spillage sensors 230 and isolating them from housing 302.
In operation, spillage probe assembly 300 is mounted to exhaust hood 116 in a manner that allows spillage sensors 230 to monitor spillage zone 216. Spillage probe assembly 300 is mounted to exhaust hood 116 with fasteners via mounting holes 306. Once mounted in the appropriate position above a piece of equipment such as cooking equipment 114, a user may manually adjust the position of one or more spillage sensors 230 by sliding them along tensioned cable 304 so that they are located over the piece of equipment to be monitored. Once in the desired position, spillage sensors 230 communicate information relating to detected changes in environmental parameters in spillage zone 216 to controller 220. For example, if the ventilation rate of autonomous ventilation system 200 is insufficient to capture and remove all air contaminants 122 associated with the operation of cooking equipment 114, spillage air contaminants 128 will spill out of exhaust hood 116 and pass through spillage zone 216. Spillage sensors 230 may detect spillage air contaminants 128 in a manner as described above in reference to
Modifications, additions, or omissions may be made to spillage probe assembly 300 and the described components. As an example, spillage probe assembly 300 as seen in
With reference now to
Autonomous ventilation control method 400 comprises three main states: OFF, LOW, and HIGH. In OFF state 402, controller 220 turns off exhaust fan 210 where it is not ventilating air from kitchen 102 via exhaust hood 116. In LOW state 410, controller 220 sets the speed of exhaust fan 210 to a minimal speed, Qmin, as will be described in more detail below. In HIGH state 422, controller 220 sets the speed of exhaust fan 210 to a maximum speed, Qmax.
Autonomous ventilation control method 400 begins in OFF state 402. While in OFF state 402, exhaust fan 210 is turned off. However, autonomous ventilation control method 400 will transition to LOW state 410, where the speed of exhaust fan 210 is set to minimum speed Qmin, if various events occur. Such events may include event 404 where a user presses override button 226, event 405 where a scheduled start time arrives, event 406 where cooking equipment 114 is turned on, or event 408 where an environmental parameter in spillage zone 216 meets or exceeds a predetermined threshold. Conversely, autonomous ventilation control method 400 will transition from LOW state 410 to OFF state 402 if other events occur. These events include event 412 where cooking equipment 114 is turned off, event 414 where a scheduled stop time arrives, event 416 where a period of time elapses after a user pushes override button 226, and/or event 417 where when the environmental parameter in spillage zone 216 returns to normal.
In event 404, a user pushes override button 226 while autonomous ventilation control method 400 is in OFF state 402 and exhaust fan 210 is off. Override button 226 is provided to give the user manual control of autonomous ventilation system 200. When the user presses override button 226 while exhaust fan 210 is off, autonomous ventilation control method 400 will transition to LOW state 410 in order to turn on exhaust fan 210 and ventilate the area. In some embodiments, a timer is started when the user pushes override button 226 in event 404. In event 416, this override button timer expires according to a predetermined, but configurable, amount of time and autonomous ventilation control method 400 transitions from LOW state 410 back to OFF state 402. By monitoring the activity of override button 226, autonomous ventilation control method 400 provides the user a manual means by which to control autonomous ventilation system 200.
In event 405, a predetermined scheduled start time arrives. A user may interface with controller 220 to establish scheduled times for autonomous ventilation system 200 to turn on. Predetermined start times may also be preprogrammed into autonomous ventilation system 200. When a scheduled start time arrives in event 405, autonomous ventilation control method 400 will transition from OFF state 402 to LOW state 410 in order to turn on exhaust fan 210 and set its speed to Qmin. Conversely, a user may interface with controller 220 to establish scheduled times for autonomous ventilation system 200 to turn off, and/or stop times may be preprogrammed into autonomous ventilation system 200. In event 414, a scheduled stop time arrives while autonomous ventilation control method 400 is in LOW state 410. If event 414 occurs, autonomous ventilation control method 400 will transition to OFF state 402 where exhaust fan 210 is set to off.
In event 406, cooking equipment 114 below exhaust hood 116 is turned on while autonomous ventilation control method 400 is in OFF state 402 and exhaust fan 210 is off. If autonomous ventilation control method 400 determines that cooking equipment 114 has been turned on but exhaust fan 210 is off, it will transition to LOW state 410 and set the speed of exhaust fan 210 to Qmin. Conversely, event 412 occurs when cooking equipment 114 below exhaust hood 116 is turned off while autonomous ventilation control method 400 is in LOW state 410. If autonomous ventilation control method 400 determines that event 412 has occurred, it will transition from LOW state 410 to OFF state 402 and turn off exhaust fan 210.
In event 408, an environmental parameter in spillage zone 216 meets or exceeds a predetermined threshold while autonomous ventilation control method 400 is in OFF state 402. Autonomous ventilation control method 400 may determine by communicating with one or more spillage sensors 230 that an environmental parameter in spillage zone 216 has changed sufficiently to warrant the activation of exhaust fan 210. Such environmental parameters may include temperature and airflow as previously described in reference to
Autonomous ventilation control method 400 also includes HIGH state 422. While in HIGH state 422, exhaust fan 210 is set to its maximum speed, Qmax. Autonomous ventilation control method 400 will transition to HIGH state 422 from LOW state 410 when various events occur. Such events include event 418 where a user presses override button 226, and event 420 where an environmental parameter in spillage zone 216 meets or exceeds a predetermined threshold. Conversely, autonomous ventilation control method 400 will transition from HIGH state 422 to LOW state 410 and set the speed of exhaust fan 210 to Qmin if other events occur. Such events include event 424 where a period of time elapses after an environmental parameter in spillage zone exceeds a threshold, event 426 where an environmental parameter in spillage zone returns to normal, and/or a period of time elapses after a user pushes override button 226 in event 428. Similarly, autonomous ventilation control method 400 will transition from HIGH state 422 to OFF state 410 if a scheduled stop time arrives in event 430.
In event 418, a user pushes override button 226 while autonomous ventilation control method 400 is in LOW state 410 and exhaust fan 210 is set to Qmin. When a user presses override button 226 while exhaust fan 210 is already set to Qmin, autonomous ventilation control method 400 will transition to HIGH state 422 in order to set exhaust fan 210 to its maximum rate Qmax and ventilate the area. In some embodiments, a timer is started when the user pushes override button 226 in event 418. In event 428, this override button timer expires according to a predetermined, but configurable, amount of time and autonomous ventilation control method 400 transitions from HIGH state 410 back to LOW state 410. By monitoring the activity of override button 226, autonomous ventilation control method 400 provides the user a manual means by which to control autonomous ventilation system 200.
In event 420, an environmental parameter in spillage zone 216 meets or exceeds a predetermined threshold while autonomous ventilation control method 400 is in LOW state 410. If, for example, spillage sensors 230 are comprised of temperature sensors, event 420 will occur when autonomous ventilation control method 400 determines that the temperature of spillage zone 216 exceeds that of kitchen 102 by a predetermined amount. If autonomous ventilation control method 400 determines that this event has occurred while it is in LOW state 410, it will transition to HIGH state 422 and set the speed of exhaust fan 210 to Qmax. In some embodiments, this transition from Qmin to Qmax may be instantaneous. In other embodiments, however, the transition may be gradual and/or stair-stepped and may not actually reach Qmax if conditions in spillage zone 216 return to normal during the transition.
Conversely, event 426 occurs when autonomous ventilation control method 400 is in HIGH state 422 and the environmental parameter in spillage zone 216 returns to normal. If autonomous ventilation control method 400 determines that event 426 has occurred, it will transition back to LOW state 410 and set the speed of exhaust fan 210 to Qmin. In some embodiments, autonomous ventilation control method 400 may set a timer after an environmental parameter in spillage zone 216 meets or exceeds a predetermined threshold in event 420. In event 424, this spillage timer expires according to a predetermined, but configurable, amount of time. If autonomous ventilation control method 400 determines that this timer has expired in event 424, it may then transition from HIGH state 422 back to LOW state 410 and set the speed of exhaust fan 210 back to Qmin.
In event 430, a predetermined scheduled stop time arrives in a similar manner as event 414. When a scheduled stop time arrives in event 430, ventilation control method 400 will transition from HIGH state 422 to OFF state 402 in order to turn off exhaust fan 210.
The minimal speed, Qmin, for exhaust fan 210 may be determined by various methods. Initially, Qmin may be preprogrammed to be the lowest capable speed of exhaust fan 210, or it may be a speed that is calculated to provide the minimal amount of ventilation as required by applicable standards. However, Qmin may be automatically adjusted by autonomous ventilation control method 400. For example, if the temperature of spillage zone 216 exceeds that of kitchen 102 by a predetermined amount in event 420, autonomous ventilation control method 400 may gradually increase the speed of exhaust fan 210 from Qmin. It may continually monitor the temperature of spillage zone 216 while it is increasing the speed to determine the speed at which the difference in temperature drops to an acceptable level. It may then record this speed as the new Qmin and use it whenever it is in LOW state 410. In addition or alternatively, a user may initiate a recalibration of Qmin through a local or remote interface while all cooking equipment 114 under exhaust hood 116 is idle. In this procedure, autonomous ventilation control method 400 gradually decreases the speed of exhaust fan 210 from Qmax until the temperature in spillage zone 216 begins to rise. It may then record the speed of exhaust fan 210 at the point the temperature started rising and use it as the new Qmin.
The speed Qmax of exhaust fan 210 is the maximum operating speed of the fan. This speed may be predetermined and/or preset by the manufacturer. In some embodiments, Qmax may be controlled/set by a user through a local or remote interface.
While a particular autonomous ventilation control method 400 has been described, it should be noted that certain steps may be rearranged, modified, or eliminated where appropriate. Additionally, while certain embodiments have been described in detail, numerous changes, substitutions, variations, alterations and modifications may be ascertained by those skilled in the art, and it is intended that the present disclosure encompass all such changes, substitutions, variations, alterations and modifications as falling within the spirit and scope of the appended claims.
This application claims the benefit under 35 U.S.C. §119(e) of U.S. Provisional Application No. 60/915,974 filed May 4, 2007 entitled “Smart Kitchen Ventilation Hood.”
Number | Date | Country | |
---|---|---|---|
60915974 | May 2007 | US |