The various embodiments of the present disclosure relate generally to systems and methods for electric circuits, e.g., for use with a phased array antenna, in particular for 5G, mm-Wave, or RADAR applications.
5G mm-Wave (24-40 GHz) is an enabling technology to support data traffic with a wide-available spectrum and spectrally efficient modulation schemes, such as high-order quadrature amplitude modulation (QAM) and orthogonal frequency-division multiplexing (OFDM). mm-Wave 5G wireless can readily support multi-Gb/s datalinks.
To overcome the mm-Wave free space path loss, phased arrays are widely employed. However, antenna element coupling within arrays is inevitable through near field couplings and substrate modes, causing the antenna driving impedance to deviate from the nominal 50Ω antenna's Voltage Standing Wave Ratio (VSWR) or the array's active impedance. In phased arrays, antenna VSWR is a dynamic phenomenon that can vary with the beam steering angle, antenna element placement, array configuration, and operation modes (e.g., MIMO/beamforming). That is, the antenna coupling can cause dynamic beam-dependent impedance variations (antenna VSWR) and front-end degradation. Even well-designed low-coupling arrays can experience up to 3:1 VSWR.
Multiple designs have demonstrated VSWR resilient impedance sensing on single-ended loads. However, they either add signal loss, limit the power amplifier (PA) output matching network (OMN) s bandwidth (BW), or modify the OMN's impedance transformation ratio, at a single frequency.
There is a benefit to improving phased array implementations for mm-Wave devices and other applications described herein.
A broadband-capable current/voltage sensing-based VSWR resilient true power/impedance detector (also referred to as a power/impedance sensor) and method are disclosed that can be used for single-ended interfaces of individual phased array elements of a phased array antenna, e.g., large-scaled integrated phased-arrays. The true power and impedance detectors, as Built-in-Self-Test (BiST or BIST) circuitries, may each employ an in situ load invariant power and impedance sensor to provide true measurements of power and impedance that can be used to detect and/or monitor for VSWR variations and/or variations in the antenna driving impedance due to antenna element coupling and/or other effects. The measured power and impedance output(s) of each BIST circuitry can then be used to adjust or drive respective passive or active tuning circuitry, e.g., in the power amplifier or other front-end circuitries of the phased array antenna, for performance recovery (or optimization) of a respective array element.
The term “array” is a set of multiple connected antennas which work together as a single antenna to transmit or receive radio waves and can include any type of array, such as, for example, multiple-input and multiple-output (MIMO) arrays.
The exemplary power/impedance may employ one or more sets of current and voltage sensing structures integrated into each phased array element to provide sensed current(s) and voltage(s). In some embodiments, one set of the sensed current and voltage measurements can be multiplied, via an analog multiplier, to provide the sensed power measurement for that phased array element, and the second set of the sensed current and voltage measurements may be employed in a spaced-optimized dual amplitude detector to determine the amplitude of the current and voltage to provide for the sensed impedance measurement. In an implementation, the exemplary sensor employs a balun in combination with a symmetric multiplier that can provide accurate broadband operation over the entire Ka-band and the 5G FR2 24/28/39 GHz bands and can be applied to any power-amplifier architecture.
A first prototype circuit employing the balun in combination with the symmetric multiplier was fabricated using 45 nm CMOS SOI processes. At 34 GHz, the prototyped circuit can provide measurements with a power sensing error (PSE) ≤±1 dB for 3:1 VSWR and ±0.5 dB for 2:1 VSWR. Over the 22-41 GHz, the measured PSE is ≤±3.4 dB for 3:1 VSWR and ±1.5 dB for 2:1 VSWR. In addition, the prototyped circuit under a 50Ω load demonstrated a maximum dynamic range of 22.89 dB at 42 GHz and a dynamic range >21.46 dB over 27-41 GHz. At 33 GHz, the measured |Γ|/∠Γ errors were ≤0.072/7.3° for 3:1 VSWR and ≤0.04/7.13° for 2:1 VSWR, while demonstrating |Γ|/∠Γ errors of ≤0.2/34° for 3:1 VSWR and ≤0.11/27° for 2:1 VSWR over the entire 27-41 GHz BW. The chip die occupied an area of 0.97×1.99 mm2 and a sensor core area of 0.48×1.66 mm2.
In another implementation, the exemplary sensor replaces the balun and symmetric multiplier of the power detector with a space-and-power-optimized parallel power detector comprising (i) a differential current/voltage sensor and (ii) a single-ended voltage passive sensing circuit that employs a differential voltage sensing in combination with an error cancellation circuit. With respect to space, rather than employing two sets of differential signals via the above-noted symmetric multiplier, the space-and-power-optimized-differential-current/voltage-and-single-ended-voltage sensing circuit employs a multiplier that (i) operates on a paired differential current and a voltage signal set and (ii) replaced the other differential signal set with a single-end voltage signal. The noted error cancellation circuit generates an intentional offset or error that is employed in the circuit to cancel out undesired errors resulting from the loss of accuracy in employing the single-end voltage signal.
With respect to power, the space-and-power-optimized-differential-current/voltage-and-single-ended-voltage sensing circuit includes (i) an active detector for the differential-current/voltage sensing and (ii) a passive detector using the single-end voltage sensing, as the parallel power detector in which the passive detector can be operated for the most part without any power consumption and in which the active detector provides the paired differential current and voltage signals to accurately update the proportionality function of the passive detector for the various varying loads. Without this update, the proportionality function would be inaccurate for the passive detector as the load varies.
A second prototype circuit employing the space-and-power-optimized differential current/single-ended voltage sensing circuit was fabricated also using 45 nm CMOS SOI processes. The space-and-power-optimized sensing circuitries can provide a 10× reduction in size for the baluns employed in the first prototype circuit while providing comparable operational performance and capabilities. With respect to power, in using the passive detector in combination with the active detector to track load, the space-and-power-optimized sensing circuitries substantially reduced power usage by almost 4× as compared to the first prototype circuit. By updating the passive detector using the active detector at a pre-defined update cycle, the power saving would increase greater than 4×. In addition, by employing the passive detector, a detector would be in continuous operations, thus improving latency metrics since the passive detector does not need to be turned off.
In an aspect, a system (e.g., a RADAR array system, a satellite payload system, a satellite ground terminal, a 5G and/or mmWave base station, or a 5G or mmWave handset) is disclosed comprising an array antenna comprising a set of N array antenna elements; a set of amplifiers (e.g., power amplifiers or reconfigurable power amplifiers), wherein each of the set of amplifiers is coupled to an array element of the set of N array antenna elements; and a set of built-in self-test circuits, including a first built-in self-test circuit, wherein each of the set of built-in self-test circuits is configured to measure a voltage standing wave ratio (VSWR) or the real or complex load impedance for a respective amplifier of the set of amplifiers (e.g., to reconfigure the respective amplifier to compensate for array element coupling or other couplings), wherein the first built-in self-test circuit comprises: a first voltage sensing structure and a second voltage sensing structure each co-located at, or proximate to, a single-ended terminal or multi-feed terminals defined by the array element; a first current sensing structure and a second current sensing structure each co-located at, or proximate to, the single-ended terminal or multi-feed terminals defined by the array element; a power sensing circuit operatively coupled to the first voltage sensing structure and the first current sensing structure to receive (i) a first sensed voltage signal from the first voltage sensing structure and (ii) a first sensed current signal from the first current sensing structure; and an impedance sensing circuit (e.g., implemented using amplitude detectors) coupled to (i) the first or second voltage sensing structure and (ii) the first or second current sensing structure to receive (iii) the first or a second sensed voltage signal from the first or second voltage sensing structure and (iv) the first or a second sensed current signal from the first or second current sensing structure.
In another aspect, a system (e.g., (i) front-end module (FEM) to couple to an antenna module or (ii) an integrated antenna module, e.g., on-chip, on-package, on-board) is disclosed comprising: a set of amplifiers (e.g., power amplifiers) for an array antenna comprising a set of N array antenna elements, wherein each of the set of amplifiers is coupled to a array element of the set of N array antenna elements; and a set of built-in self-test circuits, including a first built-in self-test circuit, wherein each of the set of built-in self-test circuits is configured to measure a voltage standing wave ratio (VSWR) or the real or complex load impedance for a respective power amplifier of the set of amplifiers (e.g., to reconfigure the respective amplifier to compensate for array element coupling or other couplings), wherein the first built-in self-test circuit comprises: a first voltage sensing structure and a second voltage sensing structure each co-located at, or proximate to, a single-ended terminal or multi-feed terminals defined by the array element; a first current sensing structure and a second current sensing structure each co-located at, or proximate to, the single-ended terminal or multi-feed terminals defined by the array element; a power sensing circuit operatively coupled to the first voltage sensing structure and the first current sensing structure to receive (i) a first sensed voltage signal from the first voltage sensing structure and (ii) a first sensed current signal from the first current sensing structure; and an impedance sensing circuit (e.g., implemented using amplitude detectors) coupled to (i) the first or second voltage sensing structure and (ii) the first or second current sensing structure to receive (iii) the first or a second sensed voltage signal from the first or second voltage sensing structure and (iv) the first or a second sensed current signal from the first or second current sensing structure.
In another aspect, an apparatus (e.g., a circuit in a FEM, an IC, or a component for an integrated antenna module) is disclosed comprising: a built-in self-test circuit for a array antenna, wherein the built-in self-test circuit is configured to measure a voltage standing wave ratio (VSWR) or real or complex load impedance for a power amplifier connected to an antenna array element (e.g., to reconfigure the respective amplifier to compensate for array element coupling or other couplings), wherein the built-in self-test circuit comprises: a first voltage sensing structure and a second voltage sensing structure each co-located at, or proximate to, a single-ended terminal defined by the array element; a first current sensing structure and a second current sensing structure each co-located at, or proximate to, the single-ended terminal defined by the array element; a power sensing circuit operatively coupled to the first voltage sensing structure and the first current sensing structure to receive (i) a first sensed voltage signal from the first voltage sensing structure and (ii) a first sensed current signal from the first current sensing structure; and an impedance sensing circuit (e.g., implemented using amplitude detectors) coupled to (i) the first or second voltage sensing structure and (ii) the first or second current sensing structure to receive (iii) the first or a second sensed voltage signal from the first or second voltage sensing structure and (iv) the first or a second sensed current signal from the first or second current sensing structure.
In another aspect, an apparatus (e.g., a circuit in a FEM, an IC, or a component for an integrated antenna module) is disclosed comprising: an impedance sensing circuit and a power sensing circuit for an antenna array or antenna element, wherein the impedance sensing circuit and the power sensing circuit are configured to measure a voltage standing wave ratio (VSWR) or real or complex load impedance for at least one of (i) power amplifier or (i) electronic circuit connected to the array antenna or the antenna element, wherein the impedance sensing circuit includes: a first voltage sensing structure and a first current sensing structure each co-located at, or proximate to, a single-ended terminal defined by the array element; wherein the power sensing circuit includes: a second voltage sensing structure and a second current sensing structure each co-located at, or proximate to, a single-ended terminal defined by the array element.
In another aspect, an apparatus is disclosed comprising one or more power sensing and impedance sensing structures located at a single-ended antenna array element of an antenna array (e.g., phased array); and an array-level built-in-self-test circuit configured to perform at least one of inter-element coupling evaluation, inter-element power flow, and/or impedance mismatch detection, wherein the array-level built-in-self-test circuit employs a VSWR power and impedance sensing circuit that includes the features of any one of claims 5-15.
In some embodiments, each antenna element, or a portion of the antenna elements, is coupled with a transmitter element.
In some embodiments, each antenna element, or a portion of the antenna elements, is coupled with a receiver element.
In some embodiments, each antenna element, or a portion of the antenna elements, is connected to one or multiple transmitters and receivers through a matching and/or switch network
In some embodiments, the one or more power sensing and impedance sensing structures include at least one of one or more voltage sensors, current sensors, power sensors, and impedance sensors.
In some embodiments, the array-level built-in-self-test circuit is configured to generate one or more test signals at one or more antenna array elements to be coupled to one or more adjacent or nearby antenna array elements to evaluate complex coupling, coefficient matrix, power flow, and impedance mismatches for multi-elements or all of the array (e.g., to achieve the whole array level calibration, built-in-self-testing (BiST), and performance optimization).
In another aspect, an apparatus is disclosed comprising two or more power sensing and impedance sensing structures located at an input or output of a subcircuit or components of an electric circuit; and a VSWR power and impedance sensing circuit coupled to the two or more power sensing and impedance sensing structures to detect power flow or impedance mismatch (i) within the subcircuit or components or (ii) between the subcircuit or components and other circuits. In some embodiments, the VSWR power and impedance sensing circuit include any of the below-discussed features.
In some embodiments, the power sensing circuit or the respective power sensing circuit comprises: a single-ended to differential signal converter (e.g., Balun); and an analog multiplier circuit operatively connected to the single-ended to differential converter.
In some embodiments, the power sensing circuit or the respective power sensing circuit either (i) further comprises a filter connected to the analog multiplier circuit or (ii) wherein the analog multiplier circuit comprises an integrated filter or has integrated filtering capability.
In some embodiments, the analog multiplier circuit comprises at least one of a single-balanced Gilbert multiplier (SBGM) circuit or a double-balanced Gilbert multiplier (DBGM) circuit, or a nonlinear circuit.
In some embodiments, the power sensing circuit or the respective power sensing circuit comprises a complementary analog multiplier configured to multiply the two sensed signals (e.g., while providing low-pass filtering).
In some embodiments, the complementary analog multiplier circuit comprises a complementary multiplier (PCM) comprising two parallel pairs of double-balanced Gilbert multiplier cells having inputs for a sensed current signal and a sensed voltage signal (e.g., wherein the signals are flipped).
In some embodiments, the two parallel pairs of double-balanced Gilbert multiplier cells comprise two or more symmetric signal paths between the multiplier and the respective sensors, wherein the symmetric signal paths provide symmetric input loading there between (e.g., avoid amplitude/phase mismatch to the sensor inputs and the multiplier cells).
In some embodiments, the power sensing circuit or the respective power sensing circuit further comprises an error cancellation circuit.
In some embodiments, the error cancellation circuit is configured to add a pre-defined phase offset (e.g., phase offset error), as a pre-defined load-dependent adjustment (e.g., load-dependent error), between the second voltage sensing structure and the second current sensing structure to cancel magnitude error in the first sensed voltage signal from the first voltage sensing structure and the first sensed current signal from the first current sensing structure.
In some embodiments, the error cancellation circuit is configured to receive calibration or updates from an active power detector.
In some embodiments, the impedance sensing circuit or the respective impedance sensing circuit comprises an amplitude detector (e.g., multi-stage Dickson rectifier) for the second sensed voltage signal and the second sensed current signal, or amplified signals thereof.
In some embodiments, the power sensing circuit or the respective power sensing circuit is configured to output a sensed power signal using the first sensed voltage signal and the first sensed current signal, wherein the impedance sensing circuit or the respective power sensing circuit is configured to output a sensed impedance signal using the second sensed voltage signal and the second sensed current signal, and wherein the sensed power signal and the sensed impedance signal are employed to reconfigure (i) the power amplifier, (ii) an array element associated circuit, or (iii) a combination thereof, to compensate for array element coupling (or other couplings) during operation of the array antenna.
In another aspect, a method is disclosed of compensating for array element coupling error during operation of a array antenna (e.g., array RADAR system, a 5G and/or mmWave base station, or a 5G or mmWave handset), the method comprising: measuring a voltage standing wave ratio (VSWR) or real or complex load impedance for a power amplifier of a array element based on a sensed power signal and a sensed impedance signal measured at a single-ended terminal defined by a array element, wherein the measurements of the sensed power signal and the sensed impedance signal are respectively determined (i) from one or more sensed current signals connected to one or more current sensing structures co-located at, or proximate to, a single-ended terminal defined by a array element and (ii) from one or more sensed voltage signals connected to one or more voltage sensing structures co-located at, or proximate to, the single-ended terminal defined by the array element; and reconfiguring (i) a power amplifier, (ii) a matching network, (iii) an impedance tuner, (iv) a array element associated circuit, or (v) a combination thereof, using the sensed power signal and the sensed impedance signal.
In another aspect, a method comprising: measuring a voltage standing wave ratio (VSWR) or real or complex load impedance for a power amplifier of a array element based on a sensed power signal and a sensed impedance signal measured at a single-ended terminal defined by a array element, wherein the measurements of the sensed power signal and the sensed impedance signal are respectively determined (i) from one or more sensed current signals connected to one or more current sensing structures co-located at, or proximate to, a single-ended terminal defined by a array element and (ii) from one or more sensed voltage signals connected to one or more voltage sensing structures co-located at, or proximate to, the single-ended terminal defined by the array element; and outputting the sensed power signal and the sensed impedance signal, wherein the outputted sensed power signal and the sensed impedance signal are employed to reconfigure (i) a power amplifier, (ii) a matching network, (iii) an impedance tuner, (iv) a array element associated circuit, or (v) a combination thereof.
In some embodiments, the steps are performed using any one of the above-discussed systems or apparatuses.
The following detailed description of specific embodiments of the disclosure will be better understood when read in conjunction with the appended drawings. For the purpose of illustrating the disclosure, specific embodiments are shown in the drawings. It should be understood, however, that the disclosure is not limited to the precise arrangements and instrumentalities of the embodiments shown in the drawings.
To facilitate an understanding of the principles and features of the present disclosure, various illustrative embodiments are explained below. The components, steps, and materials described hereinafter as making up various elements of the embodiments disclosed herein are intended to be illustrative and not restrictive. Many suitable components, steps, and materials that would perform the same or similar functions as the components, steps, and materials described herein are intended to be embraced within the scope of the disclosure. Such other components, steps, and materials not described herein can include, but are not limited to, similar components or steps that are developed after the development of the embodiments disclosed herein.
Some references, which may include various patents, patent applications, and publications, are cited in a reference list and discussed in the disclosure provided herein. The citation and/or discussion of such references is provided merely to clarify the description of the present disclosure and is not an admission that any such reference is “prior art” to any aspects of the present disclosure described herein. In terms of notation, “[n]” corresponds to the nth reference in the list. All references cited and discussed in this specification are incorporated herein by reference in their entireties and to the same extent as if each reference was individually incorporated by reference.
5G and/or mmWave Application. In the example shown in
The built-in-self-test circuitries (e.g., 110a, 110b, . . . 110n) is located in a front-end module 111, and each, or a subset thereof, is configured to provide single-ended broadband VSWR resilient joint true power/impedance sensing for a given phased array element 104. The BIST circuitries (e.g., 110a, 110b, . . . 110n) each may include a set of power-sensing sensors 112 (shown as “Power Sensors” 112a, 112b, . . . 112n) and a set of impedance-sensing sensors 114 (shown as “Impedance Sensors” 114a, 114b, . . . 114n). In
While the example in
Channel 115 shows the front-end components, sensor or sensing structure, and BIST for an example phased array element 104 (shown as 104′). The channel 115 includes a power amplifier 106 (shown as 106′), other front-end circuitry 107′ in addition to the power amplifier 106′ and built-in-self-test circuitries 110 (shown as 110′). In the example shown in
The power sensing circuit 118 is coupled to a power-sensing sensor 112 (shown as 112′) comprising (i) a current sensor or current sensing structure 122 (shown as 122a) and (ii) a voltage sensor or voltage sensing structure 124 (shown as 124a) to provide sensed current Isensing 130 and sensed voltage Vsensing 132 to be used to determine the true power of the phased array element (e.g., 104a, 104b, . . . 104n), or a variation thereof, at the singled-ended termination point of the element 104. In the example shown in
The impedance-sensing circuit 120 is coupled to an impedance-sensing sensor 114 (shown as 114′) comprising (i) a current sensor or current sensing structure 122 (shown as 122b) and (ii) a voltage sensor or voltage sensing structure 124 (shown as 124b) to provide sensed current 134 and sensed voltage 136 to be used to determine the true impedance of, or a variation thereof at, at the singled-ended termination point of the element 104′. In the example shown in
Other Applications. As noted above, the power/impedance sensing may be employed for other applications, e.g., by being (i) positioned at the output of the amplifier or (ii) at the input and output of the amplifier, among others. For example, the power gain of the amplifier or various circuits, may be sensed by sensing power and/or impedance at the input and output of the amplifier or circuit. The compressive behavior of the amplifier may be estimated, e.g., to evaluate magnitude or phase linearity or the performance metric of interest.
Amplifier power and/or impedance evaluation. In system 100b, the BIST circuitries (e.g., 110a′, 110b′, . . . ) each may include a set of power-sensing sensors (112a′, 112b′, . . . ) and a set of impedance-sensing sensors (114a′, 114b′, . . . ) positioned at the output of the amplifier (106a′, 106b′) to provide an evaluation of the amplifier.
Inter-Circuit Power and/or Impedance Evaluation. In systems 100c and 100d (
Channel-Level Power and/or Impedance Evaluation. In systems 100e and 100f (
Array-Level Power and/or Impedance Evaluation. In systems 100e, 100f (
In systems 100h (
Array-level BIST or channel-level BIST can additionally or alternatively be used to perform or assess inter-element coupling (113), power flow, and impedance mismatch detection, among others, for a portion or all the elements in an array. A practical antenna array always has inter-element coupling. For a typical antenna array, it can be assumed: (1) each antenna element is coupled with a transmitter element, i.e., the antenna is driven by the output(s) of one or more amplifiers through a matching and/or switch network, (2) each antenna element is coupled with a receiver element, i.e., the antenna is feeding the input(s) of one or more amplifiers through a matching and/or switch network, (3) each antenna element is connected to one or multiple transmitters and receivers through a matching and/or switch network. In some embodiments, the interfaces between the corresponding antenna element and its coupled transmitter/receiver circuits may be instrumented/implemented with one or more voltage sensors, current sensors, power sensors, and impedance sensors, as described herein.
In other antenna arrays, the antenna array can have a portion of array elements only connected to transmitters and a portion of the array elements, e.g., the remainder, only connected to receivers to which the transmitters and receivers are instrumented by the in-situ power-sensing sensors and/or one or more impedance-sensing sensors, e.g., as shown and described in relation to system 100h in
In some embodiments, one or more array elements can generate one or more testing signals, e.g., by using their transmitters, while the testing signals are coupled to other adjacent or non-adjacent antenna elements. Next, the BIST controller (e.g., 116), or a global controller (shown as 121) for the array, can read out the outputs of the one or more voltage sensors, current sensors, power sensors, and impedance sensors of the array elements that generate those test signals. Then, the BIST controller, or a global controller can read out the outputs of the one or more voltage sensors, current sensors, power sensors, and impedance sensors of the array elements that are coupled with the transmitter array elements. Finally, by processing and aggregating the aforementioned sensing data, the whole complex coupling coefficient matrix, power flow, and impedance mismatches for all the elements of the entire array can be determined to achieve the whole array level calibration, built-in self-testing, and performance optimization.
The global controller (e.g., 121) can process and aggregate sensing data from any number of BISTs (e.g., 110), including, e.g., those in systems 100a-100i shown in
RADAR application. As noted above,
Integrated Circuits. The broadband-capable current/voltage sensing-based true power/impedance detection may be employed in other form factors. For example, in
The current/voltage sensing-based VSWR power/impedance detector may be employed in combination with a coupling-based power/impedance detector, e.g., for redundancy and/or monitoring at different frequency ranges. An example coupling-based power/impedance detector is disclosed in [32] and [61′], which is hereby incorporated by reference in its entirety. The system may include a first sensing electromagnetic (EM) structure as a first sensing transmission line that is co-located to the output transmission line to be capacitively coupled therewith, the first sensing electromagnetic structure having (i) a first end that connects to a corresponding end of the output transmission line through a pre-defined impedance and (ii) a second end that connects to a first input of the built-in self-test circuit sensing circuit; and a second sensing electromagnetic structure as a second sensing transmission line that is co-located to the output transmission line to be capacitively coupled therewith, the second sensing electromagnetic structure having (i) a first end that connects to an impedance element having a value corresponding the phased array antenna element and (ii) a second end that connects to a second input of the built-in self-test circuit sensing circuit.
In some embodiments, the first sensing electromagnetic structure and the second sensing electromagnetic structure each have a length of λ/4.
Power Sensing. As noted above, in some embodiments, the true sensed power measurement for a given phased array element can be determined using the sensed current and voltage measurements, which can be multiplied via an analog multiplier.
In the example shown in
In Equation 1, Vout is the antenna output voltage peak amplitude, Iout is the antenna output current peak amplitude, θZ is the phase of the antenna impedance in which all are measured at the desired carrier frequency, and k1 and k2 are proportionality factors. The antenna output current peak amplitude Iout and the antenna output voltage peak amplitude Vout can be determined from a sensed current Icpl and a sensed voltage Vcpl via in inductive sensor or structure and a capacitive sensor or structure through inductive coupling and capacitive coupling, respectively, rather than a direct tap. Indeed, the sensor or structure can provide sensing via electrical coupling, magnetic coupling, and/or electromagnetic coupling.
This power sensing scheme aims to provide an output that is proportional to the true power delivered to the antenna load. This proportionality can be observed in Diagrams 202 and 204, which show the measured output power in Watts and the sensor voltage in Volts for 50Ω at 41 GHz. The true average power delivered to a complex antenna load [24] can be determined per Equation 2:
Using Equations 2, 3, and 4, the sensed power can be expressed as Equation 6.
In Equation 6, the sensed power VPsense is the DC output signal generated by the sensor structure under device under test (DUT) conditions. Using Equations (2)-(6), the sensed power VPsense can be defined per Equation 7:
Diagrams 202 and 204 show the DC output signal of the sensor DUT being proportional to the true output power Pout of the antenna load. As shown in diagrams 202 and 204, the measured sensor signal has the same dependence on the true output power in dBm as the true output power in Watts. To have a one-to-one correspondence between the sensor output and the true power, a proportionality factor PF can be defined as the average of the instantaneous ratio of the sensor output VPsense and Pout, e.g., as shown in Equation 8:
Due to noise and large signal compression of the multiplier and integrated op-amp, there could potentially be a limited power region, dynamic range, in which this proportionality factor is held constant to which output power monitoring can be accurately performed. To determine the power sensing dynamic range, the integral non-linearity (INL) may be evaluated of the actual PF versus its averaged value under the 50Ω load, e.g., per Equation 9.
This dynamic range allows for the evaluation of the region of operation where the sensed power VPsense is a proper linear fit compared to the predicted output power under any antenna load. The dynamic range may be defined as the region in which the INL is within ±0.5 dB error. Diagrams 206 and 208 show, respectively, the power sensing error plot (206) and linear fit plot (208) of the dynamic range as a function of output power. The plots are shown in relation to 50Ω.
Capacitive Coupling for Voltage Sensing. To sense the output voltage, the BIST circuit (e.g., 110) would need to have pure capacitive coupling or have capacitive coupling be dominant. However, when two conductors are placed close by, both capacitive and inductive couplings are present.
For voltage sensing, the BIST circuit may employ capacitive/voltage coupling based on an E-field-based coupling mechanism that operates as a capacitive divider due to the parasitic overlap between the two conductors and the parasitic overlap to the ground. In
It can be observed that the sensing ratio is frequency independent and a constant, assuming high Q capacitors with minimal routing inductance, thus broadband capable.
Inductive Coupling for Current Sensing. To sense the output current, e.g., along a trace path as in the example shown in
Assuming that the inductance and mutual inductance are time-invariant, Equation 15 can be simplified as Equation 16, in which the current through the sense coil Icpl is proportional to the current through the conductor Iout. The mutual inductance Mind can be defined per Equation 17.
In Equation 17, k is the inductive coupling coefficient, and Lcond is the inductance of the conductor. From Equations 16 and 17, the current sensing ratio (Current Sensing Ratio) can be defined per Equation 18.
From Equation 18, it can be observed that current sensing is insensitive to the frequency of operation and thus broadband capable. In practice, the sensing ratio and hence sensing strength can vary over frequency due to frequency-dependent factors, such as the magnetic coupling k.
Capacitive and Inductive Coupling for Single-Ended Loads. For single-ended load sensing, e.g., as described in relation to
By way of background, when placing a sensing coil 220 (see
In contrast, for single-ended loads 232, when placing a sensing coil 234 symmetrically in proximity to a single-ended trace 236, the capacitive coupling 238 contribution does not partially cancel and hence is no longer negligible as shown in diagram 240. As noted, in some embodiments, appropriate termination conditions can be selected for the desired coupling mechanism while suppressing the undesired.
Termination Conditions for Single-Ended Loads. As noted above, the sense coil (in diagram 240) can experience both inductive and capacitive coupling. The port voltages for the sense coil 234 due to both inductive and capacitive coupling mechanisms can be expressed per Equation 19:
Accurate current Sensing. To ensure accurate, current sensing and hence the inducive coupling is dominant, the effect of capacitive coupling should be mitigated. In
By implementing the short circuit termination, the voltage 244 at the port and capacitive coupling voltage contribution are forced to zero. By doing so, the resulting relationship shown per Equations 21-23 can be derived.
From Equations 21-23, it can be observed that the sense coil current is proportional to that of the output current, demonstrating current sensing. However, current-to-voltage conversion is desired to drive the post-processing circuitry (e.g., the BIST 110) while still ensuring that the port voltage is low enough to ensure inductive coupling is the dominant mechanism. In the example shown in
To quantify the current sensing accuracy under VSWR, the normalized current sensing ratio (NCSR) may be employed for the evaluation per Equation 24.
NCSR is the ratio between the sensed current Icpl and output current Iout over antenna VSWR normalized with respect to the ratio at 50Ω. An NCSR=1 would mean that the sensed current is perfectly tracking the output current under antenna load variation. The study simulated NCSR over the 22-41 GHz bandwidth with and without the additional 20Ω termination at Port “2.”
Accurate Voltage sensing. To ensure voltage sensing and hence that capacitive coupling is dominant, the effect of inductive coupling should be mitigated. In
The inductive coupling contribution is likely due to the magnetic coupling of the sense coil current and single-ended trace current. By implementing the open circuit termination 258, it is ensured that no current flows through the sense coil 124′ and that there is no mutual inductance present. The result relationships are shown in Equations 26 and 27.
From Equations 26 and 27, it can be observed that accurate voltage sensing can be ensured under a single-ended load by utilizing open circuit terminations. With this sensing, by ensuring phase alignment of the two sensed signals, the sensor or sensing structure can be implemented without the need for an integrated phase shifter [36]-[39]. In the example shown in
To quantify the voltage sensing accuracy under VSWR load mismatch, the normalized voltage sensing ratio (NCSR) may be employed for the evaluation per Equation 28.
NVSR is the ratio between the sensed voltage Vcpl and output voltage Vout over antenna VSWR normalized with respect to the ratio when the antenna load is 50Ω. An NVSR=1 means that the sensed voltage is perfectly tracking the output voltage under antenna load variation. The simulated NVSR over the 22-41 GHz bandwidth with and without the additional 50Ω termination at Port 4 is shown in
Phase Alignment. As mentioned in Equation 7 for power sensing (and later Equation 40 for impedance sensing), the phase offset between current and voltage coupling paths, if applicable, should be minimal to accurately track the true power delivered to the antenna load and extract the phase of the impedance when mismatched. In other words, the sensed signals must be phase-aligned, where they have the same phase over the frequency profile. The current sensing loop must have a resistive termination for the current-to-voltage conversion. Therefore, the port voltage can be defined per Equations 29 and 30:
Equation 31 can then be multiplied by an RC load for the current-to-voltage conversion to get Equation 32.
Equation 32 can then be rewritten as Equation 33:
Therefore, it can be observed that the current sensing loop can act as a second-order system whose phase profile over frequency can be determined by the damping factor ζ, which is, in turn, can by controlled by the resistive termination R1. For the capacitive coupling network with no resistive termination, it can be viewed as equivalent to a capacitive divider whose transfer function can be defined per Equation 35:
With the voltage sensing profile acting as a first order system which has a linear phase profile (45°/decade) over frequency, the pole location ωV may be controlled by the resistive termination R2. Both the sensing loops may have a varying phase over frequency profile and can be aligned. Because the current sensing loop may be a 2nd order system while the voltage sensing loop is a 1st order system, the phase response over frequency may not be the same between the sensing loops. But because the desired 22-42 GHz bandwidth may be only a 2:1 BW, so the slope difference is minimal, and the slope difference within the band of interest can be controlled through ζ.
To account for the absolute phase difference, the pole of the capacitive coupling path ov may be set at a lower frequency than the inductive coupling pole ωI through a careful choice of R2 to accommodate for the difference in slope.
In addition, the slope of the inductive coupling path may be carefully chosen by modifying R1. Both poles ωV and ωI may be much higher than the sensor operating frequency for broadband phase alignment.
Validation. To validate this operation and configuration, the simulated results was compared with the theoretical results using Equations 32-38. In the Equations, the parameters may be fixed in which R1=20Ω, R2=50Ω, C1=10 fF, C2=20 fF, C3=8 fF, and Lcpl=25 pH.
The deviation between simulation and theory may be attributed to imperfections in the sensing loop implementations. The coupling mechanisms are imperfectly implemented such that traces of both inductive coupling and capacitive coupling are both present even though only one of the coupling mechanisms is dominant per sensing loop. There are also other 2nd order phenomena, such as self-resonance, where around the self-resonant frequency, the current sensing loop is no longer acting as a magnetically coupled inductor.
The accuracy of the power sensing circuit (e.g., 118) may be dependent on the accuracy of the generation of the sensed current and voltage as well as on the subsequent analog multiplication. Other limitations, such as noise and swing, may limit the dynamic range in which the power sensing is accurate. To evaluate, the power sensing error (PSE) over VSWR was defined per Equations 39 and 40
Magnitude Sensing. As noted above, the NCSR and NVSR may not be perfectly “1” under 3:1 VSWR, so some error may be introduced as the sensed current and voltage do not perfectly reflect the output voltage and current that are meant to be multiplied. Because the NCSR and NVSR have an inverse trend over VSWR (e.g., when the NCSR peaks above “1”, the NVSR lags below 1), their product is kept closer to 1. Note that an NCSR and NVSR of 1 correspond to perfect magnitude tracking for the sensing loops, so an NVSR/NCSR product of 1 corresponds to perfect apparent power tracking.
Phase Alignment. Another aspect of operations for power sensing is phase alignment. Ideally, the sensing loops are configured such that for 50Ω, the phases are aligned, thus tracking the phase difference of the true output voltage and current. However, due to non-idealities and the broadband nature of the exemplary design, some undesired phase shift may be present as shown in Equation 42:
This phase offset can introduce error asymmetrically, affecting complex loads differently based on the phase of the impedance. As an example of this, the case: β=5° can be considered for a θz=10° and θz=45°. The PSE for both load scenarios is shown below per Equations 45 and 46:
From Equations 43-44, it can be observed that the more reactive the load is, the more error can be introduced by the phase offset of the two sensed signals. When the VSWR mismatch increases, the complex load becomes more reactive, increasing the PSE due to phase mismatch.
Impedance Sensing. As noted above, dual amplitude detectors may be implemented to determine the amplitude of the current and voltage to provide for the sensed impedance measurement.
In the example shown in
The sensed current Icpl and voltage Vcpl may be acquired using the same sensor or sensing structure 122 and 124 (shown as 122″ and 124″) and coupling structures described in relation to
Power Sensing Circuit. In the example shown in
The buffers 406 are connected to the current sensor or sensing structure 122a and voltage sensor or sensing structure 124a to receive the sensed current Isensing 130 and Vsensing 132. The buffers are configured to provide reverse isolation capabilities and include compatible with the termination conditions, e.g., described in relation to
The bandpass filter 408 may be connected to the buffers 406 to ensure balanced signals over the frequency bandwidth of interest (e.g., between 22-41 GHz for 5G, mmWave, or other frequencies described herein) prior to the signals being amplified, e.g., via gain 410, to be provided to the analog multiplier 412. In some embodiments, the bandpass filter 408 and gain 410 may be implemented in a single component, e.g., a Balun.
The analog multiplier 412 is connected to the output of the bandpass filter 408 and/or gain 410 to generate a combined signal using, e.g., transconductance multipliers. Examples of analog multipliers 412 that may be used include single-balanced Gilbert multiplier (SBGM), double-balanced Gilbert multiplier (DBGM), and complementary multiplier, among other circuits described herein.
The low pass filter 414 is connected to the output of the analog multiplier 412, e.g., to remove any 2nd harmonics generated from the multiplication. The output of the low pass filter 414 may be provided to the BIST controller (e.g., 116) or to an output matching network (OMN) or other impedance matching circuitries, e.g., of a reconfigurable power amplifier or front-end component.
Impedance Sensing. In the example shown in
The buffers 434 are connected to the current sensor or sensing structure 122b and voltage sensor or sensing structure 124b to receive the sensed current Isensing 134 and Vsensing 136. The buffers are configured to provide reverse isolation capabilities and include compatible with the termination conditions, e.g., described in relation to
The impedance matching circuit 436 is configured to broadband voltage gain for the frequency range of interest for the subsequent amplitude detection.
The amplitude detector is connected to the impedance matching circuit 436 and is configured to provide the sensed amplitude signal outputs for the sensed voltage and sensed current.
Power sensing implementation. The example power sensing circuit 402′ is shown in combination with an output matching network 416, e.g., implemented in a power amplifier (e.g., 106). The power sensing circuit 402′ may be connected to a pair of current/voltage sensing loops that are placed on each side of the output trace connecting to the ground-signal-ground (GSG) output pads.
In the example shown in
The complementary analog multiplier 428 may multiply the two sensed signals outputted from the Balun 426 while providing low-pass filtering to remove the 2nd harmonic term [24]. The complementary analog multiplier 428 can be considered to implement both the multiplier 412 and low pass filter 414. The power sensing circuit 402′, in this example, is terminated with a PMOS input single-stage op-amp 430 configured to enhance the dynamic range of the power sensing output [41]-[42], and that provides the output power sensed signal 136. Circuit 430′ shows an example implementation of the PMOS input single-stage op-amp 430. Other configurations may be employed.
Analog Multiplication. Conventional analog multiplier architectures based on the single-balanced Gilbert multiplier (SBGM) and double-balanced Gilbert multiplier (DBGM) support analog multiplication but can exhibit input asymmetry at mm-Wave frequencies [43]-[45]. This asymmetry may be due to the unequal loadings of the CS buffer (e.g., 422, 424) and cascode input paths, resulting in amplitude and phase offsets of the two inputs and the multiplier block itself. To resolve or mitigate these effects, the complementary multiplier (PCM) 428 may employ two parallel pairs of double-balanced Gilbert multiplier cells whose inputs for the sensed current and voltage signals are flipped or inverted. The inherent symmetry of the architecture can provide symmetric input loading and a symmetric signal path for the multiplier while removing any amplitude/phase mismatch to the sensor inputs and the multiplier block itself. Circuit 428′ shows an example implementation of the complementary multiplier 428.
The simulated phase offset of the SBGM, DBGM, and complementary multiplier with/without routing non-idealities are shown in
Example Impedance Sensing. The sensing loops (418′ and 420′) are connected to CS buffers 430 (shown as 430′, 430″) to provide sufficient reverse isolation. The CS buffers (430′, 430″) are also used in conjunction with the following transformer matching component 436 (shown as 436′) to provide broadband voltage gain. The voltage gain is to ensure a sufficient driving strength to terminate the amplitude detectors 438 (shown as 438′ and 438″) over the 22-41 GHz bandwidth. The detectors 438′, 438″ may be implemented as a fully passive amplitude detector approach which ensures sufficient RF-DC gain [45]-[46]. In
Example Die Design.
As noted above, in another implementation, the exemplary VSWR current/voltage sensing-based sensor/detector may be employed that replaces the balun and symmetric multiplier of the power detector, e.g., as described in relation to
Rather than employing two pairs of differential input, e.g., as shown in
The buffers 504 are connected to the current sensor or sensing structure 122a and voltage sensor or sensing structure 124a to receive the sensed current Isensing 130 and Vsensing 132. The buffers are configured to provide reverse isolation capabilities and include compatible with the termination conditions, e.g., described in relation to
The low pass filter 512 is connected to the output of the analog multiplier 510, e.g., to remove any 2nd harmonics generated from the multiplication. The output of the low pass filter 512 may be provided to the BIST controller (e.g., 116) or to an output matching network (OMN) or other impedance matching circuitries, e.g., of a reconfigurable power amplifier or front-end component.
Error Cancelation Operation. The use of the SBGM and differential current sensing offers large power detector area savings due to the ability to remove the previously-used on-chip baluns at a trade-off of accuracy due to the imperfections of differential current sensing. To compensate for the trade-off in current accuracy, the compact VSWR power sensing sensor/detector 502 employs the error cancelation circuit 508 (shown as 508′)
In the example shown in
For the sensed current and voltage-based power detector, the sensed signals Icpl and Vcpl are proportional to the output voltage and current Iout and Vout as previously discussed in relation to Equations 3-4, reproduced as Equations 41 and 42:
For the voltage-only-based power detector, the output voltage can be sensed and fed to a square law-based amplitude detector. The amplitude detector output VED can be determined per Equation 46.
From Equation 47, it can be deduced that the ratio of the voltage sensing-only-based detector (e.g., 526) and current/voltage sensing-based power detector (e.g., 524) changes by the same factor that the output power changes with respect to the voltage only-sensing power detector. This is expected from Equation 44. The result in Equation 47 can be used to derive the following relationships in Equations 48-51 where k5 is a proportionality factor.
Fig. DC shows a comparison between the power sensing scheme used in
To mitigate this, in
Small resistive terminations of 20Ω may be used on both ports of the sense coil to ensure that inductive coupling is dominant. Since the same current must flow through the loop, the port voltages generated are out of phase, generating a differential current to voltage signal. This mitigates any need for baluns in the design.
As the inductive coupling strength is not modified, the nonintrusive behavior is maintained. Since out-of-phase-current-to-voltage conversion was achieved for the same current sensing ratio, the equivalent sensing loop output voltage was doubled at a trade-off of current sensing accuracy.
From Equation 50, it can be observed that comparing the two power detector outputs and updating the amplitude detector's proportionality factor based on their relative ratio when the antenna load is mismatched would allow for VSWR resilient power tracking when operating with an appropriate calibration operation.
In some embodiments, a 50Ω calibration may be performed that compares the amplitude detector output to the true output power to generate a proportionality factor k5 for one-to-one correspondence for power tracking. To obtain
in a measurement environment where noise and compression effects are present, the average of the instantaneous ratio can be determined per Equation 52.
From this calibration operation, the passive voltage-only sensing-based detector can be used for VSWR resilient power tracking with no power consumption and could be periodically updated via the proportionality factor with respect to the amplitude detector and analog power detector. The calibration and update operation can provide dynamic range enhancement over VSWR.
As shown in
In
To this end, the use of two parallel power detectors can offer major power savings and dynamic range resilience. An additional calibration step is required between the two power detector outputs to support this. However, as both outputs are DC and specific to the sensor, it only adds additional latency and no additional measurement setup to perform this calibration.
Example Circuit Implementation.
PA Circuit/Testbed. The PA circuit/testbed includes a 2-stage amplifier utilizing a common source (CS) driver stage 528 (shown as 528′) and cascode PA stage 530 (shown as 530′). Capacitive neutralization is used, in this example, to enhance gain, stability, and reverse isolation over a broadband frequency range. Since the two-stage PA testbed provides sufficient reverse isolation, the input impedance and hence input power detector is unaffected by antenna VSWR. Therefore, the input power sensing scheme includes only the voltage sensing loop and a Dickson rectifier-based amplitude detector 532. Transformer-based and coupled line-based networks are used to provide broadband input/inter-stage/output matching.
Dickson Rectifier. The three-stage Dickson rectifier 532′ is employed in the example as the amplitude detector. The rectifier has high linearity, has a fully passive implementation, and has a controllable conversion gain based on the number of stages [68-69]. As the Dickson rectifier is a passive rectifier, there is no power or pad overhead, supporting an extremely compact form factor. The three-stage Dickson rectifier may be used for both the input power detection and voltage sensing only-based output power detection.
Analog Multiplier. The analog multiplier 510 includes a single-balanced Gilbert multiplier (SBGM) cell (shown as 510′). As only a single differential input is employed, which is provided by the differential current sensing scheme, the use of the SBGM architecture mitigates any need for baluns in the sensor core, enabling major area savings. To support the error cancelation scheme over frequency, a linear phase offset over frequency may be applied to the analog multiplier 510 to accommodate for the increasing magnitude error over frequency. The phase alignment network can provide a relatively flat phase over frequency profile [79]. However, as shown in
Op-Amp. The operational amplifier 430 includes a single-stage differential pair with PMOS inputs. PMOS inputs can minimize noise and can accommodate the multiplier DC output common mode. A single-stage amplifier may be implemented to minimize power, minimize noise, and ensure loop stability. The op-amp can also enhance the output signal strength and provide sufficient filtering of the multiplier's harmonic content.
Simulation Results.
A study was conducted that evaluated VSWR power/impedance sensing via voltage and current sensing and other schemes. The developed sensor/detector supports the accurate broadband operation and can be added to any power amplifier architecture (or other circuitries as described herein) as the coupling mechanisms are weak. The study developed a 22-41 GHz sensor prototype that demonstrated a PSE within ±3.4 dB for 3:1 VSWR and ±1.5 dB for 2:1 VSWR and a dynamic range >21.46 dB over 27-41 GHz. The prototype also demonstrated |Γ| and ∠Γ errors of ≤0.2/34° for 3:1 VSWR and ≤0.11/27° for 2:1 VSWR over 27-41 GHz. To the inventor's knowledge, this study was the first work to develop a broadband demonstration of mm-Wave joint power/impedance sensing up to 3:1 VSWR, covering the entire Ka-band and the 5G FR2 24/28/39 GHz bands.
Wilkinson Power Combiner Test Setup. The study employed a WPC OMN measurement test setup to characterize the performance and intrusiveness of the exemplary VSWR power/impedance sensor architecture. The study evaluated the change in the return loss as the sensor's impact on the OMN impedance transformation ratio and bandwidth. By looking at the insertion loss, the study determined the amount of additional loss the exemplary VSWR power/impedance sensor architecture incurred. The study employed a straightforward S-Parameter measurement to quantify the intrusiveness of the current/voltage sensing loop architecture.
From
Analog Multiplication Simulation. The study conducted a number of simulations in the development of the VSWR power/impedance sensing via voltage and current sensing schemes. In the development of the analog multiplier, e.g., the complementary multiplier (PCM) described in relation to
In
Measurement Setup. Several prototypes of the exemplary current/voltage sensing-based sensor were implemented in a 45 nm CMOS SOI process, including that shown and described in relation to
When performing the CW power sweeps to characterize the small and large signal behavior of the exemplary VSWR current/voltage sensing-based sensor, the study employed an N1914 power sensor to capture the output power while an Agilent 34411A multimeter was employed to capture the differential DC power sensing output VPsense. During the same power sweep, Agilent 34465 multimeters were employed to capture outputs of the two Dickson rectifiers for impedance sensing VED, IED. The study used the same data post-processing scheme as described in [41].
Power/Impedance Sensing. The study characterized all the losses of the cables, attenuators, connectors, and probes as a function of load over frequency for accurate VSWR power sensing. The study performed a probe-based Thru measurement with an input isolator to characterize the tuner loss variation as a function of VSWR. The Power Sensing Error (PSE) was the ratio of 10 log10(PFVSWR/PF50Ω). The study used a close-to-zero PSE to verify the accuracy of the power sensor over VSWR, such that the sensor can be used for unknown VSWR loads after performing its one-time 50Ω calibration. To simulate the 3:1 and 2:1 VSWR circles, the study fixed the magnitude of the gamma presented by the load tuner, |Γload|=0.5 and |Γload|=0.333, while the phase of the gamma was swept 360 degrees, ∠Γload=0:45:360°.
The study extracted the impedance in polar form using both the amplitude detector outputs and power sensing output. After extracting this, the effect of the chip's GSG pad capacitance was de-embedded to place the VSWR load reference plane at the end of the output signal trace. The study defined the impedance sensing magnitude/phase errors as the difference in the magnitude/phase of the reflection coefficient presented by the Maury load tuner, Γload, and the reflection coefficient determined by the sensor device under test (DUT), ΓDUT. The definition of these error metrics is shown below:
At 33 GHz, the study demonstrated |Γ|/∠Γ errors of ≤0.072/7.3° for 3:1 VSWR and ≤0.04/7.13° for 2:1 VSWR, while demonstrating |Γ|/∠Γ errors of ≤0.2/34° for 3:1 VSWR and ≤0.11/27° for 2:1 VSWR over the entire 27-41 GHz BW. The impedance sensing magnitude and phase errors decreased as a function of mismatch, demonstrating the VSWR power/impedance sensor's monotonicity.
Table 1 and Table 2, respectively show a comparison between the state-of-the-art for impedance sensors and power sensors.
From Tables 1 and 2, it can be observed that the study demonstrated competitive power and impedance sensing accuracy and range while supporting a direct interface with the single-ended antenna load and agnostic integration with mm-Wave PAs. At the cost of area overhead, this work is also the first to show on-chip VSWR-resilient mm-Wave joint true-power/impedance sensing over 27-41 GHz, covering the entire Ka-band and the 5G FR2 24/28/39 GHz bands.
Additional characterization of the system performance, e.g., in relation to process variation may be found at Munzer, David et al. “Broadband mm-Wave Current/Voltage Sensing-Based VSWR-Resilient True Power/Impedance Sensor Supporting Single-Ended Antenna Interfaces.” IEEE Journal of Solid-State Circuits (2022), which is hereby incorporated by reference herein in its entirety.
The study also designed and fabricated a compact VSWR-Resilient Power Gain Estimator, e.g., as described in relation to
While the error cancelation scheme is valid, special considerations were considered to support broadband operation. The phase error was implemented as an inverse function of the magnitude error. As shown in
Phase Imbalance Nonidealities. The error cancelation scheme employs the error introduced by the phase offset to be the inverse of the magnitude error. However, as demonstrated in [79′], the error introduced by phase offset has a sinusoidal dependence on ∠Γ for a fixed |Γ| and the simulated magnitude error. In contrast, as shown in
The differential voltage of the current sensing loop is meant to be phase-balanced due to the opposite current flow direction through each termination resistance. However, there is an undesired equivalent capacitive coupled voltage from the output transmission line. The coupled voltage from the output transmission line is also at a different point on the transmission line. Under a 50Ω antenna load, there is no reflection and hence no standing wave ratio. Therefore, the voltage contribution should be common mode, and the current sensing loop should be properly phase balanced. However, as load mismatch is applied, the input voltage applied to the capacitive coupling network per current sensing port varies due to the increased standing wave ratio. The asymmetric capacitive coupling will unbalance the current sensing loop and cause a load dependence on the phase imbalance as demonstrated in
It can be observed that the phase error is inverse to the magnitude error in
In contrast, a passive voltage sensing-based power detector approach, as employed in conjunction with the current/voltage sensing-based power detectors, is more efficient as it consumes no DC power. The passive voltage sensing-based power detector can support a high dynamic range due to the lower number of transistors contributing to flicker noise, a higher convergence gain and hence a larger output signal, and a stronger sensed input signal. Its dynamic range can be mainly determined by the maximum output of the detector, as it only needs to overcome the minimum threshold voltage for rectification and is less sensitive to compression. Therefore, the passive voltage sensing-based power detector can support a high nominal dynamic range, and its dynamic range can be reduced only for low impedance antenna loads where the output voltage is reduced, as shown in
PA 50Ω Results.
Sensor Intrusiveness. Due to the weak coupling of the current/voltage sensing mechanisms, the exemplary voltage/current sensing and resulting impedance/power sensing scheme should have minimal impact on the integrated PA. As the PA's output matching network (OMN) impacts the output power and efficiency and has more embedded sensing loops, we evaluate the sensor network's impact on the OMN to evaluate its intrusiveness.
The study evaluated the parameters for additional loss and any modification of the OMN's impedance transformation over frequency. To assess the loss added by the sensor network, the study considered the OMN's passive efficiency/loss with and without the sensing network. To evaluate the sensor's impact on the OMN's impedance transformation, the study compared the complex impedance presented by the OMN for a 50Ω antenna load.
As depicted, the sensor introduced an additional loss of 0.06 dB at the low-frequency band edge and an additional loss of 0.2 dB at the high-frequency band edge. Therefore, the sensor added minimal loss. It was contemplated that the loss could be further reduced for higher power integrated PA testbeds as lower coupling was required from the sensing loops to support the same dynamic range. For impedance transformation, the real and imaginary impedance can be varied by a maximum of ±2Ω and ±3Ω respectively. Therefore, the sensor would minimally impact the impedance transformation of the OMN. The impact on matching can also be further reduced when integrated with a high-power PA as lower coupling is required from the sensing loops.
50Ω Power Detector Results. To evaluate the exemplary VSWR power gain estimator's nominal and broadband performance, the study first evaluated the estimator under 50Ω.
VSWR Power Detector Results. A Maury MT985AL impedance tuner is used to characterize the exemplary impedance/power sensing sensor over VSWR. All of the cables, attenuators, connectors, and probes losses are characterized across load and frequency to ensure accurate VSWR power sensing. To characterize the input/output power detector performance under VSWR, the input/output PFs for the 50Ω load (PF50Ω) and VSWR load (PFVSWR) were measured. A perfect true power detector should have PF50Ω=PFVSWR. Hence, the Power Sensing Error (PSE) was defined as the ratio of 10 log10(PFVSWR/PF50Ω). A close-to-zero PSE verifies the accuracy of the power sensor, such that the sensor can be used in practice for unknown VSWR after its one-time 50Ω calibration.
Gain Curve Estimation. After evaluating the individual power detector's functionality, the study used the gain curve estimation for real-time PA reconfiguration evaluation. The measured PA power gain curves were compared using external power powers, and the power gain curves estimated from the sensor DUT for 3:1 and 2:1 VSWR to fully characterize the VSWR performance as shown in
Table 3 shows a comparison with the-state-of-the-art power detectors.
Per Table 3, it can be observed that the exemplary compact VSWR power estimator provides competitive broadband power detector accuracy and range while supporting a direct interface with the single-ended antenna load and agnostic integration with mm-Wave PAs. Due to the removal of buffers and baluns, the exemplary compact VSWR power estimator can achieve one of the most compact sensor core areas for VSWR resilient power detection, particularly with a 10× area reduction from the broadband power detector presented in [60′]. The exemplary compact VSWR power estimator is understood to be the first of its kind to utilize differential current sensing with phase error compensation for accurate power sensing with substantial area savings and an auxiliary voltage-sensing-based power detector output for enhancing dynamic range resilience over VSWR.
Indeed, the exemplary compact VSWR power estimator can support accurate broadband operation and can be added to any PA architecture as the coupling mechanisms are weak. The 27-41 GHz sensor prototype demonstrates an input/output PSE of ≤±0.5 dB/±0.6 dB for VSWR=3:1 and ±0.25 dB/±0.35 dB for VSWR=2:1 and 50Ω dynamic range >22.5 dB/24.2 dB for the current/voltage sensing-based output and voltage sensing-based output over 27-41 GHz. To the inventor's knowledge, the exemplary compact VSWR power estimator is the most compact broadband demonstration of mm-Wave power sensing up to 3:1 VSWR, covering the entire Ka-band and the 5G FR2 24/28/39 GHz bands. In addition, the exemplary compact VSWR power estimator employs an auxiliary passive power detector path for dynamic range enhancement and power savings and provides the first demonstration of VSWR resilient power gain estimation at mm-Wave.
5G mm-Wave (24-40 GHz) is a major enabling technology to support future exponential data traffic growth [1]-[2]. With a wide available spectrum and spectrally efficient modulation schemes such as high order quadrature amplitude modulation (QAM) and orthogonal frequency-division multiplexing (OFDM), mm-Wave 5G wireless can readily support multi-Gb/s datalinks [3]-[5]. To overcome the mm-Wave free space path loss, phased arrays are widely employed. However, antenna element coupling within arrays is inevitable through near-field couplings and substrate modes, causing the antenna driving impedance to deviate from the nominal 50Ω [6]. This is known as antenna Voltage Standing Wave Ratio (VSWR) variation or the array's active impedance. In phased arrays, antenna VSWR is a dynamic phenomenon, varying with the beam steering angle, antenna element placement, array configuration, and operation modes (e.g., MIMO/beamforming). Even well-designed low-coupling arrays can experience up to 3:1 VSWR [7].
Power amplifiers (PAs) are the most critical block within the TX chain as they govern the overall system efficiency, linearity, and output power but are the most susceptible to antenna VSWR as they directly interface with the antenna load [3]. The PA output matching network (OMN) is designed to transform the standard 50Ω antenna impedance to the PA's load pull impedance to maximize performance. With the antenna driving impedance variations, the PA load impedance deviates away from its optimum, drastically degrading the PA efficiency, output power, and linearity. While reconfigurable PAs can restore PA performance by passive or active tuning [8]-[16], they often require accurate performance assessment, even under large antenna VSWR variations. Hence, in situ VSWR-resilient sensors have become necessary, particularly for power and impedance sensing at each array element [17]-[20].
The most conventional power sensing scheme is voltage-only sensing, where the sensed voltage is fed to a rectification circuit [21]-[22]. However, this technique only tracks the true RF power delivered to the antenna load for a known real antenna driving impedance. An alternative approach shown in [23] and [24] is to sense both the output voltage and current to measure the true RF power over the antenna VSWR. This technique works for both varying and complex antenna loads but has only been demonstrated on differential PAs when most mm-Wave front ends and antenna interfaces are single-ended.
Multiple designs have demonstrated VSWR resilient impedance sensing on single-ended loads [25]-[32]. However, they either add signal loss, limit the PA OMN bandwidth (BW), or modify the OMN's impedance transformation ratio. In addition, they have only been demonstrated at a single frequency, while broadband VSWR-resilient operation is required to support the entire band of interest. To overcome the aforementioned issues, a single-ended broadband VSWR resilient joint true power/impedance sensor based on a current/voltage sensing scheme was developed and employed herein [33]. The exemplary VSWR voltage and current sensor is agnostic to PA designs and can be integrated at the element level to mm-Wave frontends.
Each and every feature described herein, and each and every combination of two or more of such features, is included within the scope of the present invention, provided that the features included in such a combination are not mutually inconsistent.
Although example embodiments of the disclosed technology are explained in detail herein, it is to be understood that other embodiments are contemplated. Accordingly, it is not intended that the disclosed technology be limited in its scope to the details of construction and arrangement of components set forth in the following description or illustrated in the drawings. The disclosed technology is capable of other embodiments and of being practiced or carried out in various ways.
It must also be noted that, as used in the specification and the appended claims, the singular forms “a,” “an” and “the” include plural referents unless the context clearly dictates otherwise. Ranges may be expressed herein as from “about” or “approximately” one particular value and/or to “about” or “approximately” another particular value. When such a range is expressed, other exemplary embodiments include from the one particular value and/or to the other particular value.
By “comprising” or “containing” or “including” is meant that at least the named compound, element, particle, or method step is present in the composition or article or method, but does not exclude the presence of other compounds, materials, particles, method steps, even if the other such compounds, material, particles, method steps have the same function as what is named.
Unless otherwise expressly stated, it is in no way intended that any method set forth herein be construed as requiring that its steps be performed in a specific order. Accordingly, where a method claim does not actually recite an order to be followed by its steps or it is not otherwise specifically stated in the claims or descriptions that the steps are to be limited to a specific order, it is no way intended that an order be inferred, in any respect. This holds for any possible non-express basis for interpretation, including: matters of logic with respect to arrangement of steps or operational flow; plain meaning derived from grammatical organization or punctuation; the number or type of embodiments described in the specification.
While the methods and systems have been described in connection with certain embodiments and specific examples, it is not intended that the scope be limited to the particular embodiments set forth, as the embodiments herein are intended in all respects to be illustrative rather than restrictive.
The following patents, applications and publications, as listed below and throughout this document, are hereby incorporated by reference in their entirety herein.
This PCT International Patent Application claims priority to, and the benefit of, U.S. Provisional Patent Application No. 63/267,847, filed Feb. 11, 2022, entitled “SYSTEMS AND METHODS FOR A SINGLE ENDED COUPLED BROADBAND SENSOR”; U.S. Provisional Patent Application No. 63/386,458, filed Dec. 7, 2022, entitled “A COMPACT AND BROADBAND VSWR-RESILIENT POWER GAIN ESTIMATOR WITH DYNAMIC RANGE COMPENSATION FOR PHASED ARRAY APPLICATIONS”; U.S. Provisional Patent Application No. 63/267,840, filed Feb. 11, 2022, entitled “SYSTEMS AND METHODS FOR A COUPLER-BASED SENSOR AND DETECTOR,” each of which is hereby incorporated by reference in its entirety.
Filing Document | Filing Date | Country | Kind |
---|---|---|---|
PCT/US2023/012927 | 2/13/2023 | WO |
Number | Date | Country | |
---|---|---|---|
63267840 | Feb 2022 | US | |
63267847 | Feb 2022 | US | |
63386458 | Dec 2022 | US |