Non-halogenated heavy metal free vehicular cable insulation and harness covering material

Abstract
Described is a vehicular harness comprising a plurality of insulated non-halogenated, heavy metal free vehicular cables, each comprising an inner core of a copper based metal wire having a thickness area of at least about 0.1 mm, an outer insulation, covering the length of the inner core, comprised of a thermoplastic polyphenylene ether composition that has no halogen or heavy metal added thereto, the insulated cable capable of meeting the testing standard ISO 6722, and a tape comprised of the thermoplastic polyphenylene ether composition wrapped around the plurality of cables to hold the cables together. Also described is a tape having a plastic PPE layer with an adhesive on the bottom and a pealable layer.
Description

BRIEF DESCRIPTION OF THE DRAWINGS

Further objects and advantages of the invention will be apparent from the following description and appended claims, reference being made to the accompanying drawings forming a part of the specification, wherein like reference characters designate corresponding parts in several views.



FIG. 1 is a perspective view of the vehicular cable of the present invention;



FIG. 2 is a cross-section of FIG. 1 taken along lines 2-2;



FIG. 3 is a die used to manufacture an embodiment of the insulated vehicular cable of the present invention; and



FIG. 4 is a cross-section of FIG. 3 taken along lines 4-4.



FIG. 5 is a tape of the present invention; and



FIG. 6 is the tape of the present invention wrapped around a plurality of vehicular cables of FIG. 1.





DETAILED DESCRIPTION OF THE INVENTION

With increasing electronic content in automobiles there is an ever growing need for miniaturizing the size of the cables that provide resistance to physical abuse and provide resistance to flame and automotive fluids among other requirements to be met for the automotive industry such as ISO 6722. It has been found to be particularly desirable to utilize an insulated non-halogenated, heavy metal free vehicular cable containing a copper based metal wire that has a diameter of at least about 0.1 mm or more and an outer insulation covering the length of the inner core comprised of a thermoplastic polyphenylene ether composition which has no halogen or heavy metal added thereto.


Definitions:


By “non-halogenated” is meant that the polymeric material that is utilized has no halogen material that is added to the composition, as a desirable component of the composition.


By “heavy metal free” is meant that no heavy metal such as mercury, hexavalent chrome, cadmium, lead and the like are added to the metal core, as a desirable component of the metal composition.


By “copper based metal” is meant that the metal wire is comprised of greater than 50% by weight of the metal being copper, or copper alloyed with other metal components as is well known in the industry yet maintaining suitable electrical conductivity. Well known copper based alloys may be used such as HPC-80EF, trademark Phelps Dodge.


By “polyphenylene ether” is meant a thermoplastic polymeric material which is commercially available and generally are polymers of monohydroxy aromatic materials. Other readily available materials are 2,6-xylenol or a 2,3,6-trimethylphenyl and polymers thereof. Polyphenylene ether (PPE) is also known as polyphenylene oxide (PPO) and is described in the literature. See U.S. Pat. Nos. 3,306,874, 3,306,875; 3,257,357; and 3,257,358, which are herein incorporated by reference.


Frequently polyphenylene ether materials are a blend of other thermoplastic or cross-linked ethylenically unsaturated materials such as polyolefinic materials, styrene or styrene butadiene or polyacryamide and the like. These materials are commercially available such as Noryl, Luranyl, Ultranyl or Vestoblend, trademarks of GE. Some materials that may be utilized include Noryl WCV072, WCV072L-111, and the like of GE.


It has been found that the ultra thin cable and cable wall that is utilized in the present case even at a small cross section of 0.1 mm2 give a very satisfactory result in abrasion cycling tests such as that called for in ISO-6722.


The cross sectional area of the copper wire can range from about 0.1 to about 3 square millimeters, such as 26 AWG to 12 AWG, alternatively 0.13 to 1.5 square millimeters.


The insulated cable of the present invention is prepared utilizing normal well known commercially available equipment where the desired polyphenylene ether polymer is fed to an extrusion machine where the molten viscous polymer is passed through a die, as shown in FIGS. 3-4, so that the insulating PPE is wrapped around the linear portion of the metal conductor wire. The processing temperatures that may be utilized can vary as is well known in the industry. However, it has been found desirable to heat the resin material obtained from the supplier as follows. The thermoplastic polyphenylene ether material is dried at about 180° F. for at least 2 hours and is then passed through the first stage of an extrusion machine. The feed temperature is approximately 115° F. The compression temperature and the metering temperature in the barrels of the extruder can vary. A compression temperature may be from about 475° F. to 490° F. The metering temperature is approximately 500° F. to 540° F. The cross head or the die temperature is approximately 540° F. to 560° F. After the wire is extruded with the insulated material thereon, it passes through a cooling water bath and mist which is maintained at room temperature and then is packed as a cable in a barrel for subsequent handling.


Turning now to a description of the drawings. FIG. 1 is the insulated vehicular cable 10 of the present invention having an insulated member 12 of PPE extruded or wrapped around the copper base metal core 14. An embodiment is shown in FIGS. 1 and 2 wherein the inner copper core is comprised of several wires 14 A-G with a central wire 14 A. The central wire 14A is surrounded by the other wires 14 B-G. There can be 7, 19 or 37 strands in metal core 14, in some instances they are compressed and in the other they are bunched.


During the extrusion process of the insulated vehicular cable 10, the copper based core is fed through the middle of die 20 entering the back end 22 of the die and exiting from the die at 24. The die has a central portion 26 through which the copper based wire 14 passes. The hot viscous PPE will be passed into the space 28 at the entrance end 22 of the die 20 and proceeds to envelop the copper wire. The die begins to narrow at 30 as PPE is extruded with the copper based wire passing from 30 through exit 24 of the die. At the exit 24 of the die, the insulated vehicular cable 10 of the present invention is obtained. The cooling process as described above and the packaging of the cable follows thereafter.


The diameter of the insulated vehicular cable 10 of the present invention can vary substantially. A cable diameter that has been found useful is between 0.85 and 0.92 mm in case of 0.13 mm2 cable. Other dimensions of an insulated vehicular cable would be one that has approximately 0.13 square millimeters of wire as its cross sectional area but which is used to form the embodiment shown in FIG. 1 namely a central wire with six surrounding wires. In that case, the conductor diameter may be approximately 0.465 millimeters with a cable diameter 10 of approximately 0.88 millimeters with the minimum insulated wall thickness of 0.198 millimeters.


As indicated above a wide variety of commercially available extruding equipment may be utilized such as an extruder identified as BMD60-24D or a Nokia Maillefer, and the like.


The die utilized in the present invention may be manufactured from a wide variety of commercially available materials such as D2 hardened tool steel.


Following the procedures outlined in ISO-6722, scrape abrasion resistance using 7(N) load and 0.45 millimeter needle was used on three sets of cables, the first being compressed halogen free cable ISO ultra thin wall cable referred as CHFUS, the second ISO thin wall cable referred as HFSS and the third ISO thick wall cable referred as HF. The test results are identified in tables 1 and 2 below.


Following the procedures outlined in ISO-6722 a number of tests were so performed where the thickness of the copper wire varied as well as the diameter of insulated polyphyenelyene ether varied as is shown in tables 3-4.









TABLE 1







CHFUS















0.13*
0.22*
0.35*
0.50*
0.75*
1.00*
1.25*


















Normal Force(N)
4.0
4.0
5.0
5.0
6.0
6.0
6.0


Minimum cycles
100
100
100
150
150
180
180


required at the


normal force


Result
166
550
338
376
536
526
1315


7N Load
151
338
244
1150
836
960
2181



125
379
223
458
1078
1171
610



174
397
287
560
722
984
2673


Minimum cycles
125
338
223
376
536
526
610


attained by the


cable at


7 Newton load


Pass/Fail












*Wire Size (square mm)













TABLE 2







HFSS





















HF



0.35*
0.50*
0.75*
1.00*
1.25*
2.00*
3.00*


















Normal Force(N)
5.0
5.0
6.0
6.0
6.0
7.0
7.0


Minimum cycles required
100
150
150
180
180
750
750


at the normal force


Result
443
4067
7193
6043
10434
12586
*>5000


7N Load
2396
893
9636
3896
5158
10835



830
4271
4512
7771
3559
11203



1031
2586
6198
8776
16333
12308


Minimum cycles
443
893
4512
3896
3559
10835
*>5000


attained by the


cable at 7 Newton load


Pass/Fail












*Wire Size (square mm)






Following the procedures outlined in ISO-6722 a number of tests were so performed where the cross sectional area of the copper wire varied as well as the diameter of insulated polyphyenelyene ether varied as is shown in tables 3-4.











TABLE 3









Cable Type and Size









CHFUS



Size




















Test

Item

Unit
Wire Thickness Area (square mm)
0.13
0.22
0.35
0.50
0.75
1.00
1.25
1.50























ISO6722
Certifi-
Dimensions
Thickness of
(mm)

0.179
0.274
0.190
0.211
0.194
0.196
0.210
0.223



cation

Ins. (min)





Cable Outer
(mm)

0.872
1.027
1.127
1.279
1.391
1.590
1.794
1.849





Dia.




Electrical
Resistance
(mΩ/m)
Sec 6.1 Must be smaller than requirement
157.100
78.600
49.600
34.600
24.300
17.200
14.100
12.000







(Measured result) See Table 4






(mΩ/m)
Requirement
169.900
84.400
54.400
37.100
24.700
18.500
14.900
12.700





Ins. Resistance

Sec. 6.2 Breakdown shall not occur
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





in water





Spark test

Sec. 6.3 No breakdown shall occur when the earthed
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass







cable is drawn through the test electrode




Mechanical
Pressure test at

Sec. 7.1 Breakdown shall not occur during the
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





high temp.

withstand voltage test




Low-temp
Winding under

Sec. 8.1 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





low temp

During the withstand voltage test,







breakdown shall not occur.




Abrasion
Scrape
(N)
Sec. 9.3 Load requirement
4
4
5
5
6
6
6
6






(times)
Scrape requirement
100
100
100
150
150
180
180
200






(times)
Min. scrape result
1309
3052
951
1636
441
844
883
1058




Heat aging
Short high

Sec. 10.1 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





temp

During the withstand voltage test,







breakdown shall not occur.





Long high

Sec. 10.2 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





temp 85 deg C.

During the withstand voltage test,







breakdown shall not occur.





Shrinkage by
(mm)
Sec. 10.4 The maximum shrinkage shall not exceed
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





high temp

2 mm at either end




Resistance
Gasoline

Sec. 11.1 The maximum outside cable diameter change
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass




to chemical

(%)
shall meet the requirement shown in Table 13. After
5.15
5.40
0.09
2.83
−6.39
0.06
0.00
0.32





Diesel

winding, no conductor shall be visible. During the
Pass
Pass
Pass
Pass
Pass
pass
Pass
Pass






(%)
withstand voltage test, breakdown shall not occur.
4.56
4.72
8.63
−0.58
−0.40
6.20
3.55
1.88





Engine Oil


Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

5.75
2.44
2.70
−8.91
−5.66
−4.84
0.83
0.70




Flame
Flamability at
(Sec)
Sec. 12 Any combustion flame of insulating material
0.0
0.0
0.0
0.0
0.0
0.0
4.0
4.0





45 degree angle

shall extinguish within 70 s, and a minimum of 50 mm







of insulation at the top of the test sample shall remain







unburned



If
Electrical
Insulation
Ohm mm
Sec. 6.4 Greater than 109 Ohm mm
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass



required

volume


1.6E+15
1.0E+16
1.70E+16
2.50E+21
8.60E+17
3.50E+21
7.30E+17
9.10E+19





resistivity




Mechanical
Strip force
(N)
Sec. 7.2 Greater than specified by customer
28.8 Pass
31.6 Pass
41 Pass
69.7 Pass
52.5 Pass
75.7 Pass
70.1 Pass
63.8 Pass







Requirement (Min)
2
2
5
5
5
5
5
5




Low-temp
Impact

Sec. 8.2 After impact, no conductor shall be visible.
Not
Not
Not
Not
Not
Not
Not
Not







During the withstand voltage test, breakdown
required
required
required
required
required
required
required
required







shall not occur.




Heat aging
Thermal

Sec. 10.3 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





overload

During the withstand voltage, breakdown shall not occur




Resistance
Ethanol

Sec. 11.1 The maximum outside cable diameter change
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass




to chemical

(%)
shall meet the requirement shown in Table 13. After
4.01
4.42
2.70
−6.98
−6.06
−5.26
1.33
1.61





Power steering

winding, no conductor shall be visible. During the
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





fluid
(%)
withstand voltage test, breakdown shall not occur.
4.00
6.39
3.68
5.76
−4.73
−3.48
1.33
3.71





Automatic


Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass





transmission
(%)

4.07
5.52
4.31
6.05
−2.46
−3.96
2.11
1.51





fluid





Engine coolant


Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

3.09
0.29
0.99
1.65
−0.20
0.06
0.44
−0.32





Battery


Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

−0.11
1.46
1.08
2.12
−1.00
0.24
0.00
−0.32












Ozone

Sec. 11.3 The visual examination of the insulation shall
Pass





not reveal any crac



Hot water
(Ω · mm)
Sec. 11.4 The insulation volume resistivity shall not be
Pass





less than 109 Ohm mm. A visual examination of





the insulation



















Temp. and

Sec. 11.5 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass
Pass



humidity

During the withstand voltage test, breakdown shall



cycling
not occur



















TABLE 4









Cable Type and Size











PPO



HFSS
HF



Size
Size



















Test

Item

Unit
Wire Thickness Area (square mm)
0.35
0.50
0.75
1.00
1.25
2.00
3.00






















ISO6722
Certifi-
Dimensions
Thickness
(mm)

0.258
0.231
0.252
0.322
0.320
0.348
0.653



cation

of Ins. (min)





Cable Outer
(mm)

1.289
1.481
1.773
1.943
2.088
2.551
3.598





Dia.




Electrical
Resistance
(mΩ/m)
Sec 6.1 Must be smaller than requirement
46.200
33.100
23.200
16.800
13.900
8.840
5.76







(Measured result) See Table 4






(mΩ/m)
Requirement
54.400
37.100
24.700
18.500
14.900
9.420
6.150





Ins. Resistance

Sec. 6.2 Breakdown shall not occur
Pass
Pass
Pass
Pass
Pass
Pass
Pass





in water





Spark test

Sec. 6.3 No breakdown shall occur when the earthed cable
Pass
Pass
Pass
Pass
Pass
Pass
Pass







is drawn through the test electrode




Mechanical
Pressure test

Sec. 7.1 Breakdown shall not occur during the withstand voltage test
Pass
Pass
Pass
Pass
Pass
Pass
Pass





at high temp.




Low-temp
Winding under

Sec. 8.1 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass





low temp

During the withstand voltage test,







breakdown shall not occur.




Abrasion
Scrape
(N)
Sec. 9.3 Load requirement
5
5
6
6
6
7
7






(times)
Scrape requirement
100
150
150
180
180
750
750






(times)
Min. scrape result
1688
2141
>5000
>5000
>5000
10835
>5000




Heat aging
Short high

Sec. 10.1 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass





temp

During the withstand voltage test,







breakdown shall not occur.





Long high

Sec. 10.2 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass





temp 85

During the withstand voltage test,





deg C.

breakdown shall not occur.





Shrinkage by
(mm)
Sec. 10.4 The maximum shrinkage shall not exceed
Pass
Pass
Pass
Pass
Pass
Pass
Pass





high temp

2 mm at either end




Resistance
Gasoline

Sec. 11.1 The maximum outside cable diameter change shall
Pass
Pass
Pass
Pass
Pass
Pass
Pass




to chemical

(%)
meet the requirement shown in Table 13. After winding,
−4.79
−4.54
−3.57
2.07
2.23
6.77
13.4





Diesel

no conductor shall be visible. During the withstand voltage test,
Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)
breakdown shall not occur.
−3.50
−2.71
−1.65
3.16
−2.00
2.20
1.63





Engine Oil


Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

−6.36
−5.74
1.17
2.19
−3.91
0.94
0.14




Flame
Flamability at
(Sec)
Sec. 12 Any combustion flame of insulating material shall
0.0
0.0
4.0
5.0
4.0
8.0
14





45 degree

extinguish within 70 s, and a minimum of 50 mm of insulation





angle

at the top of the test sample shall remain unburned



If
Electrical
Insulation
Ohm mm
Sec. 6.4 Greater than 109 Ohm mm
Pass
Pass
Pass
Pass
Pass
Pass
Pass



required

volume


2.90E+21
7.70E+17
8.30E+16
2.80E+16
3.20E+16
9.70E+16
3.40E+21





resistivity




Mechanical
Strip force
(N)
Sec. 7.2 Greater than specified by customer
63 Pass
115.3
69.4 Pass
88.0 Pass
112 Pass
113.3 Pass
230







Requirement (Min)
5
5
5
5
5
10
15




Low-temp
Impact

Sec. 8.2 After impact, no conductor shall be visible.
Not
Not
Pass
Pass
Pass
Pass
Pass







During the withstand voltage test, breakdown shall not occur.
required
required




Heat aging
Thermal

Sec. 10.3 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass





overload

During the withstand voltage, breakdown shall not occur




Resistance
Ethanol

Sec. 11.1 The maximum outside cable diameter change
Pass
Pass
Pass
Pass
Pass
Pass
Pass




to chemical

(%)
shall meet the requirement shown in Table 13. After winding,
5.93
−5.36
1.17
5.97
−3.82
1.45
1.3





Power steering

no conductor shall be visible. During the withstand voltage test,
Pass
Pass
Pass
Pass
Pass
Pass
Pass





fluid
(%)
breakdown shall not occur.
−5.36
−3.72
−3.52
6.99
−2.64
2.08
0.36





Automatic


Pass
Pass
Pass
Pass
Pass
Pass
Pass





transmission
(%)

−5.65
−4.61
−3.09
6.99
−2.55
1.92
0.58





fluid





Engine coolant


Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

−7.22
0.13
−5.54
−1.17
0.00
0.74
0.64





Battery


Pass
Pass
Pass
Pass
Pass
Pass
Pass






(%)

0.78
−0.19
−0.32
5.00
0.38
−0.04
0












Ozone

Sec. 11.3 The visual examination of the insulation shall not
Pass





reveal any cracks



Hot water
(Ω · mm)
Sec. 11.4 The insulation volume resistivity shall not be less
Pass





than 109 Ohm mm. A visual examination of the insulation


















Temp. and

Sec. 11.5 After winding, no conductor shall be visible.
Pass
Pass
Pass
Pass
Pass
Pass
Pass



humidity

During the withstand voltage test, breakdown shall not occur



cycling










Listed below in Table 5 is a measurement of the PPE toughness for ISO 6722 needle abrasion cycles to failure compared to material thickness using a 7-N load and 0.45 millimeter needle.












TABLE 5






0.4-mm cable




Insulation
insulation
0.25-mm cable
0.16-mm cable


Material
thickness
insulation thickness
insulation thickness







PPE
10000
200
110









Current PVC tape construction has thicknesses for backings of 0.09-mm and above. This thickness for PVC is required to provide a minimum amount of toughness or abrasion protection while also providing sufficient tensile and tear strength that PVC tape may be applied. Given data from Table 5 and the current film thickness, one can conclude that significantly thinner backings are possible with PPE. PPE backings as thin as 0.03-mm or less could be achieved and still maintain equivalent abrasion protection and toughness to the current PVC backings. Given this potential for reducing backing thickness and specific gravity differences, a weight reduction of 75% seems reasonable with a PPE tape compared to a PVC tape.


With thinner backings, greater linear length of tape can be put up on each roll of tape. This is important for handling in and application of tapes on substrates or wire harnesses. The physical dimensions of a tape roll are limited to physical constraints with a manufacturing operation and by human ergonomic issues. Too large of roll diameters are ergonomically awkward and uncomfortable for continuous daily use. However with thinner tapes, longer roll lengths are possible while still maintaining an acceptable roll diameter. This then benefits the manufacturing by minimizing the number of times workers must retrieve new rolls. For an automotive wire harness manufacturing, a new roll may be required as often as once or twice per wire harness. Also benefit is achieved in shipping since more tape can be shipped for a given container volume.


In addition to being halogen free and tougher than PVC, PPE also offers ability to be used in higher temperature environments. Currently PVC may be rated for use at 105° C. which limits it to select exterior automotive applications. Many of the applications however, such as engine and chassis require temperature ratings of 125° C. and above. This is feasible with PPE which has been rated to 125° C. for continuous use and with excursions to 150° C. and above.


PPE backings could be used with any desired pressure sensitive adhesive available today. This would include natural rubber, natural rubber/synthetic rubber blends, synthetic rubber, acrylic, or other adhesive systems.


Turning now to FIG. 5 it is a schematic representation of the tape 50 of the present invention with the PPE material 52 having top 53 and bottom 55 surfaces where an adhesive 54 would be attached to the bottom surface. The adhesive is generally a pressure sensitive adhesive which would facilitate the adhesion of the PPE tape to a desirable substrate. The tape would frequently be made available with a pealable backing 56.


There are a wide variety of pressure sensitive adhesives well known in the trade for applying such adhesives to thermal plastic materials. Such adhesives can be natural rubber, synthetic rubber, cross-link acrylics or blends of these polymers. Formulated adhesives may be include Morscic, Acronyl or Duro-Tak that are particular types of acrylic adhesive to be used to coat the bottom portion of the PPE material. The pealable tape can be a variety of materials such as paper, cellulose or any plastic film materials that can be coated with a release layer such as a silicone coating well known in the art.

Claims
  • 1. A vehicular harness comprising: a plurality of insulated non-halogenated, heavy metal free vehicular cables, each comprising:an inner core of a copper based metal wire having a thickness area of at least about 0.1 sq. mm, andan outer insulation, covering the length of the inner core, comprised of a thermoplastic polyphenylene ether composition that has no halogen or heavy metal added thereto, the inner core of a copper based metal wire with the outer insulation capable of meeting the testing standard ISO 6722; anda tape comprising a layer, wherein the layer has a first surface and a second surface, of the thermoplastic polyphenylene ether composition that has no halogen or heavy metal added thereto, and a contact adhesive adhering to the first surface, wrapped around the plurality of cables to hold the cables together.
  • 2. The vehicular harness of claim 1 wherein the copper core has a thickness area in a cross section of the core of about 0.1 to 1.5 sq. mm.
  • 3. The vehicular harness of claim 1 wherein the copper core has a thickness area in a cross section of the core of up to about 3 sq. mm.
  • 4. The vehicular harness of claim 1 wherein the polyphenylene ether is further comprised of a polymer formed from an ethylenically unsaturated material.
  • 5. The vehicular harness of claim 4 wherein the ethylenically unsaturated material is comprised of an olefinically unsaturated material.
  • 6. The vehicular harness of claim 5 wherein the ethylenically unsaturated material is comprised of a styrene butadiene material.
  • 7. A tape comprised of a layer, having a top and bottom thereto, of a thermoplastic polyphenylene ether composition that has no halogen or heavy metal added thereto; a contact adhesive adhering to one side the thermoplastic polyphenylene ether composition; and a pealable layer adhered to the contact adhesive, which pealable layer is capable of being pealed off the tape, thereby permitting the thermoplastic polyphenylene ether composition to be applied to a desired surface.
  • 8. The vehicular harness of claim 1 wherein the testing standard ISO 6722 comprises the inner core of a copper based metal wire with the outer insulation being constructed and arranged to withstand flame at a 45 degree angle such that any combustion flame of the outer insulation extinguishes within 70 seconds and a minimum of 50 mm of insulation at the top of the insulated cable remains unburned.
  • 9. The vehicular harness of claim 1 wherein the inner core of a copper based metal wire has a thickness area of about 0.1 mm2 to about 0.13 mm2.
  • 10. The tape of claim 7 wherein the thickness of the tape is 0.03 mm or less.
  • 11. The tape of claim 7 wherein the thickness of the tape is 0.03 mm to 0.09 mm.
  • 12. The vehicular harness of claim 1 wherein the thickness of the tape is 0.03 mm or less.
  • 13. The vehicular harness of claim 1 wherein the thickness of the tape is 0.03 mm to 0.09 mm.