This invention relates to a refrigerant system that incorporates an economizer heat exchanger and liquid-suction heat exchanger within a single common heat exchanger construction.
Refrigerant systems are utilized in applications to change the temperature and humidity or otherwise condition the environment. In a standard refrigerant system, a compressor delivers a compressed refrigerant to an outdoor heat exchanger, known as a condenser. From the condenser, the refrigerant passes through an expansion device, and then to an indoor heat exchanger, known as an evaporator. In the evaporator, moisture may be removed from the air, and the temperature of air blown over the evaporator coil is lowered. From the evaporator, the refrigerant returns to the compressor. Of course, basic refrigerant systems are utilized in combination with many configuration variations and optional features. However, the above provides a brief understanding of the fundamental concept.
An enhancement technique known as an economizer cycle has been utilized in refrigerant systems. The economizer circuit increases the capacity and efficiency of a refrigerant system. When the economizer circuit is functioning, a refrigerant is tapped from a main liquid refrigerant line at the position downstream of the condenser. This tapped refrigerant is expanded to a lower pressure and temperature and then passed through a heat exchanger where it exchanges heat to cool the main refrigerant flow. This tapped refrigerant is then returned to the compressor through the intermediate compression port. The main refrigerant flow having been cooled in the economizer heat exchanger has a greater cooling capacity when it reaches the evaporator.
Another way to increase refrigerant system performance is to use a liquid-suction heat exchanger. In such an arrangement, refrigerant downstream of the evaporator is passed through a heat exchanger where it subcools liquid refrigerant flowing from the condenser to the expansion device. This scheme provides additional cooling capacity when the refrigerant reaches the evaporator, but at the expense of having higher temperature and lower density refrigerant reaching the compressor.
The use of the economizer heat exchanger option would provide the most benefits under some operating conditions, while the use of the liquid-suction heat exchanger would provide the most benefits under other operating conditions. In the past, the designer had to choose between using either one option or the other. Providing both options has been expensive and somewhat cumbersome as two separate heat exchangers were required.
In the disclosed embodiment of this invention, the functions of the economizer heat exchanger and liquid-suction heat exchanger are provided within a refrigerant system, utilizing a single common heat exchanger construction. In a first schematic, a tap downstream of the condenser provides two refrigerant flows through a common heat exchanger. Another tap downstream of the evaporator selectively routes the refrigerant through the same common heat exchanger. A plurality of flow control devices such as valves are placed across the system to allow control and proper routing of refrigerant flow in various modes of operation. By selectively opening and closing these valves, the system can provide an economizer function, or the liquid-suction heat exchanger function, utilizing a single, common heat exchanger construction.
In a second schematic, the refrigerant downstream of the evaporator always passes through a common heat exchanger to provide the liquid-suction heat exchanger function. The economizer function is achieved selectively by activating an economizer circuit to pass tapped refrigerant through the common heat exchanger. In another variation of the second schematic, a bypass can allow at least a portion of refrigerant downstream of the evaporator to bypass this common heat exchanger, thus effectively disengaging a liquid-suction heat exchanger section (partially or entirely) from the active refrigerant circuit. In yet another variation of the second schematic, a flow control device selectively routes the refrigerant to a liquid-suction heat exchanger, or directly to the evaporator, while an economizer function and a liquid-suction heat exchanger function may be provided by separate units.
These and other features of the present invention can be best understood from the following specification and drawings, the following of which is a brief description.
A refrigerant system 20 is illustrated in
Another tap 40 is tapped from a point 42 downstream of the evaporator 28. The tap 40 also communicates with the supply line 48 passing through the common heat exchanger 31. A valve 54 downstream of the evaporator 28 is closed and a valve 56 is opened to deliver the refrigerant through the tap 40 to the common heat exchanger 31.
In addition, a valve 50 is placed on an economizer return line 34 delivering refrigerant back to the compressor 22 at some intermediate (between suction and discharge) pressure. Another valve 52 is placed on a bypass line 38 communicating refrigerant flowing in the return line 34 back to a point 44 and then returning it through a suction line 45 to the suction port of the compressor 22.
The refrigerant system can operate in a conventional non-economized mode, and without a liquid-suction heat exchanger function by closing the valves 46 and 56 and opening the valve 54. Also, at least one of the valves 50 or 52 has to be closed to prevent the refrigerant bypass flow from an intermediate compressor port back to suction. Refrigerant will then flow through a basic conventional cycle.
If an unloader function is desired, the valves 50, 52 and 54 are opened and the valves 46 and 56 are closed.
If an evaporator bypass function is desired, the valves 46, 54 and 56 are opened with the valves 50 and 52 are closed.
If an economizer function is desired, the valves 46, 50 and 54 are opened and the valves 52 and 56 are closed.
In case an unloader function is desired in the economized mode of operation, the valves 46, 50, 52 and 54 are opened and the valve 56 is closed.
If instead of an economizer function, a liquid-suction heat exchanger function is desired, the valves 46, 50 and 54 are closed and the valves 52 and 56 are opened. Refrigerant will now flow through the tap line 40, into the supply line 48, through the common heat exchanger 31, and will subcool the refrigerant in a main line 36. That refrigerant will pass back through the return line 34, through the bypass line 38, and return to the point 44 in the suction line 45 leading back to the suction port of the compressor 22.
The unloader function can also be achieved in combination with the liquid-suction heat exchanger function by opening the valve 50.
The above embodiment utilizes a single common heat exchanger to provide the function of either an economizer heat exchanger, or a liquid-suction heat exchanger. Thus, more flexibility is given to the refrigerant system designer, without the requirement of two distinct auxiliary heat exchangers. Of course, an appropriate control with the appropriate programming to actuate the proper flow control devices to achieve desired operating conditions in a desired mode of operation is to be included.
Also, a combination of the operating modes described above can be executed by opening and closing appropriate flow control devices. For instance, an evaporator bypass may be simultaneously provided with the economizer function, if desired. Furthermore, as known, the economizer tap can be located downstream of the heat exchanger 31 providing identical benefits to a system designer. It should also be pointed out that a function of two separate valves adjacent to a common piping junction can be substituted by a single multi-functional valve that can route the flow of refrigerant through the junction in the appropriate directions.
Another embodiment 100 shown in
An economized compressor 102 delivers refrigerant to a downstream condenser 104. A tap 106 from a main liquid refrigerant line 108 passes through an economizer expansion device 110, which is also utilized as a shut-off valve in this schematic. The refrigerant from both the tap 106 and main liquid refrigerant line 108 flows through the economizer heat exchanger 112. In fact, while the two are shown flowing in the same direction, in practice, it would be preferable if they were in a counter-flow relationship. If no economizer function is desired, then valve 110 is shut. The three-way valve 114 receives the refrigerant downstream of the economizer heat exchanger 112. The three-way valve 114 directs the refrigerant to a line 116, and then to a line 118 leading to a main expansion device 120, and an evaporator 122. The flow position of the three-way valve 114 for the line 116 is selected when no liquid-suction heat exchanger function is desired. Downstream of the evaporator 122, refrigerant passes through a liquid-suction heat exchanger 124, to a suction line 126, and then back to the compressor 102. Since there is no other refrigerant flow passing through the liquid-suction heat exchanger 124, no liquid-suction heat exchanger function is achieved when the valve 114 is in this position.
When a liquid-suction heat exchanger function is desired, the valve 114 directs the refrigerant into a line 128. The line 128 directs the refrigerant through the liquid-suction heat exchanger 124 for the heat transfer interaction with the refrigerant exiting the evaporator 122. The refrigerant having passed through the line 128, through the liquid-suction heat exchanger 124, then passes into the line 118, through the main expansion device 120, and then to the evaporator 122. As was mentioned above, the refrigerant downstream of the evaporator 122 flows through the liquid-suction heat exchanger 124 once again and then returns to the suction port of the compressor 102. As in previous embodiments, this schematic achieves the benefits of an economizer function and a liquid-suction heat exchanger function.
In all the embodiments, the economizer flow can be tapped downstream of the common/economizer heat exchanger, not altering any of the benefits of the invention. Also, it is well understood by a person ordinarily skilled in the art that a single economized compressor can be replaced by a compound compressor or a two-stage compression system that would provide the same benefits as described above.
The present invention provides a few schematics that would achieve the function of both a liquid-suction heat exchanger and an economizer heat exchanger with a single common heat exchanger. Obviously, a worker of ordinary skill in the art would recognize that many schematics would also be able to provide the function, as long as a single heat exchanger provides both functions, it would be within the scope of this invention.