Not Applicable
Not Applicable
Not Applicable
1. Field of the Invention:
This invention relates to improvements in a system to connect and multiplex sensor signals. More particularly, it is an exemplary embodiment of the invention that uses split core inductive sensors that connect to multiplexable sensor boards to monitor and communicate power loads without requiring the power loads to be de-activated for installation or maintenance of the sensors.
2. Description of Related Art including information disclosed under 37 CFR 1.97 and 1.98:
Electrical distribution panels (e.g. circuit breaker panels) have limited space to install voltage and current sensors necessary for branch circuit monitoring. Running individual wires from each breaker to a central location is complicated and space constrained. Also changing the sensors with different configurations of the breakers is even more complicated. A number of patents and or publications have been made to address these issues. Exemplary examples of patents and or publication that try to address this/these problem(s) are identified and discussed below.
U.S Pat. No. 7,215,109 issued on May 8, 2007 to and U.S. Pat. No. 7,309,979 that issued on Dec. 18, 2007, both to Richard A. Angerame et al., disclose monitoring power at a residence or power consumption point and provide a utility report. While these patents disclose a monitoring and reporting they require that the power is disconnected to tap into the power line and the monitoring devices can't be multiplexed together to provide for a greater number of reading sensors at a specific location.
U.S. Pat. No. 5,502,374 issued on Mar. 26, 1996 to Roger S. Cota discloses current sensors from multiple simultaneous sources. While these sensors monitor the current being consumed by each motor the sensors do not monitor voltage and therefore the power consumption can't be determined. The sensors provide a signal to a single control panel with a fixed number of inputs.
U.S. Pat. No. 4,974,327 issued on Dec. 27, 1988 and U.S. Pat. No. 4,855,671 issued on Aug. 8, 1989, both to Rossevelt A. Fernandes both disclose an electrical parameter power line monitoring apparatus. The apparatus provides a split core monitor. The monitor is placed around each conductor to monitor the power running through the conductor. While these patents cover monitoring the power through a conductor the signals are not multiplexed and are not expandable.
U.S. Pat. No. 6,330,516 issued on Dec. 11, 2001 to John B. Kammeter discloses a branch circuit monitor. The branch circuit monitor includes a plurality of non-contact current sensors arranges to sense current on each of the plurality of branch circuits. While this patent discloses branch circuit monitoring the signals are not multiplexed and are not expandable to monitor additional circuits.
What is needed is a system to connect and multiplex sensor signals. The system should also be adapted to three phase monitoring and ground fault measurement and monitoring which is not conveniently provided by existing hard wired systems. The system should be adaptable to different types of sensors which existing solutions do not. This disclosure provides the solution that is not being provided by other available or disclosed devices.
It is an object of the system to connect and multiplex sensor signals to install on any panel board configuration where the device gathers precise power information for amps, volts, power factor, watts and kWh—and is certified to provide utility-grade data on each branch circuit metering.
It is an object of the system to connect and multiplex sensor signals to monitor power metrics from the iBCPM can integrate with any BMS or DCIM system via Modbus TCP, SNMP or BACnetIP. The system is powered by a TrendPoint xD processor for the iBCPM to provide data and event logging as a standard feature.
It is an object of the system to connect and multiplex sensor signals for the EnerSure iBCPM to be part of an EnerSure platform of products that provides the most accurate, flexible, and adaptable power metering solutions in the market and is used in some of the most prestigious facilities in the world.
It is another object of the system to connect and multiplex sensor signals for the EnerSure® iBCPM panel board strip to be linked with EnerSure Bus cards to provide additional monitoring up to 120 circuits on a single iBCPM system. Additional circuits can be added in 4 or 8 circuit groups.
It is another object of the system to connect and multiplex sensor signals for the EnerSure iBCPM to employ 21 power meter-on-a-chip units on each panelboard strip. Up to 4 panel board strips per units can be connected together to, each EnerSure iBCPM thereby to accommodate up to 84 circuits of utility grade panelboard power data.
It is still another object of the system to connect and multiplex sensor signals for the system to be adaptable to three phase monitoring and ground fault measurement and monitoring which is not conveniently provided by existing hard wired systems. The system should be adaptable to different types of sensors which existing solutions do not. The number of plug connections may line up with and match the number of circuit breakers on one side of the panel.
Various objects, features, aspects, and advantages of the present invention will become more apparent from the following detailed description of preferred embodiments of the invention, along with the accompanying drawings in which like numerals represent like components.
Existing systems are hard wired and necessitate de-energizing the panel 72 for modification for current sensors 60. This system gives the user the ability to plug and play sensors of different sensitivity. It also allows multiple sensors on the same breaker. Existing systems don not allow energized replacement of modification of sensors. The number of plug connections 20 may line up with and match the number of circuit breakers 72 on one side of the panel 71.
In this embodiment the circuit board(s) 11 include multiple plug and play connections 20 for multiplexing signals from sensors 60 that may match in number and spacing with circuit breakers 72 in most panels 71. Connector(s) 20 are for input from sensor 60. Each circuit board 11 includes an integrated circuit 30 for converting sensing input to digital multiplexed output. A power input 40 supplies power to the board assembly 11. Information from the conversion integrated circuits 30 are communicated through a multiplexed single output 50. A second multiplexed signal output 51 allows for multiple circuit boards 11 to be multiplexed to monitor more than the number of current sensors 60 that can be connect to a single circuit board 11. It is contemplated that four circuit boards 11 can be connected together to monitor 84 current sensors 60.
In these figures the sensor component 60 is an example of a split core current sensing toroid that is shown in
Relationship Between The Components:
The current measuring system 60, 70, 80, 90 measures the current through circuit breaker conductor 72. The circuit board 11 and components 20, 30, 40, 50 and 51 takes a number of current sensor 60 (or other sensor) inputs through the plug(s) 80 in socket(s) 20 on the board 11 and changes the analog signal of each to a digital signal and sends this information through the output connections 50, 51 through connected wires to a central monitoring device.
How The System Operates:
How To Make The System:
Standard electrical and electronic components are assembled to make this invention. The board may be a printed circuit board of high quality. Optional components may be the number of sensors installed. Blank input sockets may be saved for future sensor installation. The board size can be from a few input channels to many. A typical 21 circuit input board 11 would match one side of a typical 42 position breaker panel. Input sensors can be changed as mentioned above. Different sensors of temperature, ground leakage, ground fault, voltage, amps, volts, vibration, leak, power factor, watts, three phase voltage, three phase amps, three phase power and kWh and humidity are all examples of different input sensors that can be used. Also tow current sensors of different sensitivity can be used. For instance a 1 to 50 amp current sensor can be combined on a separate channel with a low current high sensitivity 0.001 amp to 1 amp sensor. The various input types can use a look-up table or mathematical conversion to determine, display and or output an output in known units.
How To Use The System:
One key to the system is the ability to configure different current sensors (of different sensitivity or in fact either sensor types, e.g. ground fault) conveniently and while the panel is energized. Also a panel board may be reconfigured from single phase to 3 phase or circuit breakers of different capacity may be installed. This system lets the installation precede in a much quicker fashion and at much less expense. It also allows replacement of failed sensor components without disturbing the primary wiring. While this system was inspired for branch circuit monitoring in data centers, it can be used for any facility that needs branch circuit monitoring. For instance, hospitals, laboratories and office buildings could use this system.
The EnerSure iBCPM's pluggable CT design allows users to vary the CTs used in the system. CTs can be added or removed after the system is deployed and are available in any size from 75 and 300 amp series to 4000 amps. Onboard Ethernes allows the EnerSure® iBCPM to provide all standard forms of data connectivity without the need for gateways or additional hardware. The open protocols allow EnerSure® iBCPM to be easily integrated into any DCIM and/or Building Management System (BMS). The iBCPM supports concurrent sessions across multiple software systems.
Data logging and event logging is provided with 9 onboard data logs can record 120 data points each with intervals as fast as 30 seconds. Using a standard microSD card, users can record thousands of time-stamped data points. The data logs can be downloaded as a .CSV file or delivered using Modbus TCP and BACnetIP protocols. The onboard event logs record alarm indications for sequence of events correlation.
EnerSure® iBCPM allows you to manage your circuit amperage capacities with greater reliability. Our CTs are 0.5% accurate from 1 to 100% of the scale, giving you more visibility into your usage. The system has the ability to provide both L-N and L-L voltage readings on individual circuits, EnerSure® iBCPM allows measurement of voltage in various configurations.
Power factor is measure at the circuit level. The system and software measures power factor on each circuit and provides the ability to detect troubled equipment and energy waste.
Wattage is the true measurement of heat. By associating each circuit with the cabinet or rack that it feeds, the actual wattage of heat in each cabinet and adjust loads as necessary.
kWh energy charge backs and related carbon emission reporting are increasing. Laws such as California Public Utilities Commission 07-09-004 require that any charge back for power usage MUST be done with meters that meet a utility grade standard at the individual circuit level.
Thus, specific embodiments of a system to connect and multiplex sensor signals have been disclosed. It should be apparent, however, to those skilled in the art that many more modifications besides those described are possible without departing from the inventive concepts herein. The inventive subject matter, therefore, is not to be restricted except in the spirit of the appended claims.
This application claims the benefit of Provisional Application 61/761,542 filed Feb. 6, 2013 the entire contents of which is hereby expressly incorporated by reference herein.
Number | Name | Date | Kind |
---|---|---|---|
2362372 | Halfmann | Nov 1944 | A |
4794327 | Fernandes | Dec 1988 | A |
4855671 | Fernandes | Aug 1989 | A |
5426360 | Maraio et al. | Jun 1995 | A |
5498956 | Kinney et al. | Mar 1996 | A |
5502374 | Cota | Mar 1996 | A |
6236949 | Hart | May 2001 | B1 |
6330516 | Kammeter | Dec 2001 | B1 |
6622097 | Hunter | Sep 2003 | B2 |
6937003 | Bowman et al. | Aug 2005 | B2 |
7039532 | Hunter | May 2006 | B2 |
7124655 | Blossfeld | Oct 2006 | B2 |
7174261 | Gunn et al. | Feb 2007 | B2 |
7215109 | Angerame et al. | May 2007 | B2 |
7221145 | Bowman et al. | May 2007 | B2 |
7234954 | Srage et al. | Jun 2007 | B1 |
7252543 | Caggiano et al. | Aug 2007 | B2 |
7263450 | Hunter | Aug 2007 | B2 |
7309979 | Angerame et al. | Dec 2007 | B2 |
7330022 | Bowman et al. | Feb 2008 | B2 |
7412338 | Wynans et al. | Aug 2008 | B2 |
7453267 | Westbrock, Jr. et al. | Nov 2008 | B2 |
7474088 | Bowman et al. | Jan 2009 | B2 |
7477501 | Nelson et al. | Jan 2009 | B2 |
7493221 | Caggiano et al. | Feb 2009 | B2 |
7546214 | Rivers, Jr. et al. | Jun 2009 | B2 |
7558651 | DeBoer et al. | Jul 2009 | B2 |
7630863 | Zweigle et al. | Dec 2009 | B2 |
7652871 | Caggiano et al. | Jan 2010 | B2 |
8212548 | Parker et al. | Jul 2012 | B2 |
8421443 | Bitsch et al. | Apr 2013 | B2 |
8494686 | Masters et al. | Jul 2013 | B2 |
8560256 | Gu et al. | Oct 2013 | B2 |
8600695 | Cook | Dec 2013 | B2 |
8659286 | Reynolds | Feb 2014 | B2 |
20010040446 | Lapinksi et al. | Nov 2001 | A1 |
20030184279 | Bruno et al. | Oct 2003 | A1 |
20040186672 | Howell et al. | Sep 2004 | A1 |
20040254654 | Donnelly | Dec 2004 | A1 |
20060121785 | Caggiano | Jun 2006 | A1 |
20060241880 | Forth et al. | Oct 2006 | A1 |
20070213956 | Nasle et al. | Sep 2007 | A1 |
20090125158 | Schweitzer et al. | May 2009 | A1 |
20090228224 | Spanier et al. | Sep 2009 | A1 |
20100002348 | Donolo et al. | Jan 2010 | A1 |
20100020475 | Spitaels et al. | Jan 2010 | A1 |
20100114390 | Stevenson et al. | May 2010 | A1 |
20100176960 | Bitsch et al. | Jul 2010 | A1 |
20100207604 | Bitsch et al. | Aug 2010 | A1 |
20100235122 | McCrea et al. | Sep 2010 | A1 |
20100308792 | Rupert et al. | Dec 2010 | A1 |
20110035065 | Schweitzer et al. | Feb 2011 | A1 |
20110035066 | Schweitzer et al. | Feb 2011 | A1 |
20110035076 | Schweitzer et al. | Feb 2011 | A1 |
20110251732 | Schweitzer et al. | Oct 2011 | A1 |
20120063039 | Shah et al. | Mar 2012 | A1 |
20120271570 | Paik et al. | Oct 2012 | A1 |
20120300348 | Franks et al. | Nov 2012 | A1 |
20120323397 | Schweitzer et al. | Dec 2012 | A1 |
20130147367 | Cowburn | Jun 2013 | A1 |
20130211754 | Herzog et al. | Aug 2013 | A1 |
20140025321 | Spanier | Jan 2014 | A1 |
Number | Date | Country |
---|---|---|
05161223 | Jun 1993 | JP |
2002071734 | Mar 2002 | JP |
Entry |
---|
EnerSure iBCPM Product Specification Sheet, Apr. 12, 2013, retrieved from http://www.trendpoint.com/branch-circuit-monitoring/integrated-branch-circuit-meter/. |
Number | Date | Country | |
---|---|---|---|
20140218882 A1 | Aug 2014 | US |
Number | Date | Country | |
---|---|---|---|
61761542 | Feb 2013 | US |