The present invention relates generally to system cooling techniques. In particular, embodiments of the present invention provide a method and system for providing an alternate cooling to an outdoor shelter housing electrical equipment. Merely by way of example, the invention has been applied to telecommunications shelters, but it would be recognized that the invention has a much broader range of applicability.
Telecommunication (telecom) shelters are typically constructed as an outdoor facility in either steel or pre-cast concrete structure for housing an electrical system. Physical dimensions for such shelters: are about 20 ft in length, 10 ft in width, 10 ft in height with an access door and several access hatches for cable access. These shelters are usually attached to split system air-conditioning units for providing cooling for the electrical system therein. A conventional air conditioning (A/C) system associated with the shelter is typically powered from standard Alternating Current (AC) power supply and hence only operates and provides cooling as long as there is AC power available.
However, the electrical system within the telecom shelter usually needs to operate from a Direct Current (DC) voltage converted from the AC input by one or more DC power supplies disposed inside the shelter. This DC voltage is typically +24 VDC or −48 VDC and there are typically banks of batteries provided in the shelter to store this DC Power. The batteries are installed so that the systems can operate during events where the AC power is interrupted to the shelter. Cooling for outdoor telecom shelters is critical for proper operation of the electronics housed therein. Typically the telecom equipment installed in the shelters has an over-temperature shutdown monitor built into the equipment. Thus, the time that the telecom systems can operate is not limited by the battery life, but is limited by the time that the system can operate before it reaches the over-temperature shutdown threshold when the A/C system for providing cooling to the shelter is no longer functioning. This time depends on the external ambient conditions but is typically quite short (approx 20 minutes to 1 hour) for conventional telecom shelter. One potential solution is to use a DC to AC inverter in the event of a standard AC power failure. However, this is considered to be not practical, because it would require a very large battery storage capability.
In conditions where a large amount of the telecom shelters lose power at the same time (such as in a hurricane event), the telecom equipment installed in the shelter is not available for subsequent rescue efforts. If cellular phone systems are used to communicate, 20 minutes is not enough time to restore power to so many systems. Due to a recent event that caused a sustained lack of communication (hurricane Katrina, the federal regulations have been changed. Telecom shelters are now required to operate for 4-8 hours after loss of standard AC power.
Therefore, an alternate system and method for providing cooling to the outdoor shelter of electrical equipment are desired.
The present invention relates generally to system cooling techniques. In particular, embodiments of the present invention provide a method and system for providing an alternate cooling to an outdoor shelter with telecom equipment installed therein.
Embodiments according to the invention lead to a system configured to provide controlled cooling of electronic equipment in an outdoor shelter in combination with an air conditioning (A/C) system powered by AC power supply. The electronic equipment is powered by a DC supply. The system includes one or more blowers configured to be mounted to the outdoor shelter to draw exterior air into the outdoor shelter. Additionally, the system includes a damper arrangement configured to be mounted at an air exhaust region of the outdoor shelter. Moreover, the system includes a controller powered by the DC supply and coupled to the one or more blowers, the damper arrangement, and the A/C system. The controller is configured to receive at least a first analog input signal associated with a shelter-interior temperature, a second analog input signal associated with a shelter-exterior temperature, and a plurality of alarm input signals. The controller is further configured to generate the one or more first control signals, the second control signal, and a third control signal based on at least the first analog input signal, or the second analog input signal, or a plurality of alarm input signals, or a combination of thereof. In one embodiment, the one or more first control signals respectively control an on/off operating state of the one or more blowers including rotational speeds of the one or more blowers. The second control signal controls opening and closing of the damper arrangement in correspondence of the on/off operating state of the one or more blowers. The third control signal inhibits/activates the A/C system.
In an alternative embodiment, the present invention leads to a system for providing alternative cooling, in addition to an air conditioning (A/C) system, to a cabinet housing electrical equipment. The system includes a blower subsystem including one or more blowers for drawing air into the cabinet. The system further includes a damper subsystem including a louver arrangement for controlling air exhaust. Additionally, the system includes a controller operated from a DC supply. The controller includes a microprocessor having at least a first analog input, a second analog input, a plurality of alarm inputs, one or more first control outputs, a second control output, and a third control output. The first analog input connects to a first thermistor to measure a first temperature inside the cabinet. The second analog input connects to a second thermistor to measure a second temperature outside the cabinet. The third control output connects to the A/C system for inhibiting or re-activating the A/C system based on at least the first temperature and the second temperature. The one or more first control outputs connect to the blower subsystem for respectively operating the one or more blowers based on at least the first temperature when the A/C system is inhibited or stopped for any reason. The second control output connects to the damper subsystem for opening/closing the louver arrangement when the one or more blowers are operating/stopped.
In another alternative embodiment, the present invention provides a method for providing an alternative cooling in addition to an air conditioning (A/C) system to a cabinet housing electrical equipment. The method includes providing a cooling system to the cabinet. The cooling system includes a blower subsystem including one or more blowers for drawing air into the cabinet and a damper subsystem including a louver arrangement for controlling air exhaust. Additionally, the cooling system includes a controller operated from a DC supply. The controller includes a microprocessor having at least a first analog input, a second analog input, a plurality of alarm inputs, one or more first control outputs, a second control output, and a third control output. The method further includes activating the controller by starting up power from the DC supply. Additionally, the method includes receiving information associated with an interior temperature from the first analog input and information associated with an exterior temperature from the second analog input and monitoring information associated with a general alarm and a plurality of specific alarms received through the plurality alarm inputs. Moreover, the microprocessor processes information associated with the exterior temperature and information associated with a general alarm and a plurality of specific alarms. If the exterior temperature is lower than a predetermined value, or no general alarm or one of the plurality of specific alarms is triggered, the microprocessor processes information associated with the interior temperature.
If a first criterion based on information associated with the interior temperature is satisfied, then the method includes a process of inhibiting the A/C system through the third control output. The method also includes another process of operating each of the one or more blowers, respectively through the one or more first control outputs, at a rotation speed depending on the information associated with the interior temperature. The method further includes a process of closing/opening the louver arrangement through the second control output when the rotation speed is/isn't zero.
If a second criterion based on information associated with the interior temperature is satisfied, then the method includes a process of activating the A/C system in cooling mode through the third control output and a process of stopping the one or more blowers through the one or more first control outputs.
If a third criterion based on information associated with the interior temperature is satisfied, then the method includes a process of activating the A/C system in heating mode through the third control output and a process of stopping the one or more blowers through the one or more first control outputs.
Many benefits are achieved by way of the present invention over conventional techniques. For example, embodiments of the present invention provide an alternate cooling system in place of conventional air conditioning system, which can be used for cooling outdoor shelter housing electrical equipment in the events where standard AC power is interrupted or failed. Certain embodiments of the present invention significantly reduces energy use and operation costs of the telecommunication shelter. Some embodiments further provide sustained operation of the communication electronics within the shelter in the event of a power failure during hurricane or earthquake. Under updated field application requirement for 4-8 hours after loss of power, the exiting telecom shelter can be kept for using with minimum amount of modification and installation of the direct air cooling system based on present invention. Further, some embodiments of the present invention provide additional cooling system redundancy for providing controlled cooling in response to various alarming situations. For example, in the event of an excess hydrogen alarm event, the system according to an embodiment of the present invention also serves to accelerate exhausting of the shelter. Or in the event of detecting fire-related smoke inside the shelter, the system according to an embodiment of the present invention can has a function to starve the fire by closing the oxygen supply. Depending upon the embodiment, one or more of these benefits, as well as other benefits, may be achieved. These and other benefits will be described in more detail throughout the present specification and more particularly below in conjunction with the following drawings.
The present invention relates generally to system cooling techniques. In particular, embodiments of the present invention provide a method and system for providing an alternate cooling to an outdoor shelter housing electrical equipment. Merely by way of example, the invention has been applied to a telecommunication shelter, but it would be recognized that the invention has a much broader range of applicability.
Additionally, the cooling system 100 includes a microprocessor-based controller 120 disposed within a same enclosure that houses the one or more blowers 101. In certain embodiments, the controller 120 is configured to send one or more control signals to operate the one or more blowers 101 when an existing air conditioning (A/C) system (not shown) for the shelter is optionally inhibited (by the same controller 120) or stopped subjecting to power failure or other electrical or mechanical faults. In some embodiments, the controller 120 also is configured to send a control signal through connection 125 to the damper arrangement 105 to open or close the plurality of louver blades. In a specific embodiment, the one or more blowers 101 are configured to draw in cool exterior air into the shelter for cooling the electrical equipment therein. Accordingly, the damper arrangement 105 is operated to an open position to allow heated air to exhaust out of the shelter when the one or more blowers 101 are operating, and can be closed to seal the shelter when the one or more blowers are not operating. In another specific embodiment, the damper arrangement 105 can have a spring return feature that allows it to he open when DC power is on and automatically closed when power is removed for any reason.
In a specific embodiment, the controller 120 of the direct air cooling system 100 is coupled to one or more temperature measuring devices. The one or more temperature measuring devices include at least a first thermistor for measuring a shelter-interior temperature and a second thermistor for measuring a shelter-exterior temperature. For example, though not explicitly shown in
In another specific embodiment, the controller 120 further is coupled with a plurality of sensing devices disposed at various locations of the shelter (schematically shown in
In a specific embodiment, each blower 101 can be a DC powered radial blower. For example, in a specific implementation a NMB 48V 225 mm radial blower can be used (NMB Part No. 225R103 D0801). In one example, the four blowers 101 are configured into two channels, each channel has two blowers under closed-loop speed control by the controller 120. The controller 120 can be seen in the blower subsystem 300 in
The telecom shelter 401 includes an access door 200 built OR one side. In one embodiment, a direct air cooling system 100 is mounted on the access door 200 in a manner the same as one shown in
Referring to
The direct air cooling system 100 described above is designed to withstand harsh outdoor environmental conditions. In particular, the direct air cooling system, or simply the cooling system, should not suffer damage when mounted to a shelter and exposed to temperatures in the range of about −45 Deg C. to about +85 Deg C. The cooling system itself should be operational within a temperature range between about −40 Deg C. and about +50 Deg C. Additionally, the system is designed to withstand certain external vibrations. For example, the cooling system should not suffer any damage and be able to continue operating when it is subjected to the following vibration conditions. 1) Random vibration during operating: for 20 minutes along all each of three axes sustain axial vibration force with a vibration intensity of 0.0001 g2/Hz within a frequency range from 5 to 350 Hz and a vibration intensity dropped from its maximum in a rate of −6 dB/octave within a frequency range of 350 to 500 Hz. 2) Random vibration for survival: for 20 minutes along all each of three axes sustain axial vibration force with a vibration intensity of 0.015 g2/Hz within a frequency range from 3 to 100 Hz and a vibration intensity dropped from its maximum in a rate of−6 dB/octave within a frequency range of 100 to 137 Hz, and a vibration intensity of 0.008 g2/Hz within a frequency range from 137 to 350 Hz and a vibration intensity dropped from its maximum in a rate of −6 dB/octave within a frequency range of 350 to 500 Hz. 3) Swept sine vibration for survival: 0.5 g acceleration (from 0 to peak) within a frequency variation from 3 to 500 and to 3 Hz. The test is for resonant search along all three axes with 15 minutes dwell at all resonances and with 1 octave/minute sweep rate. Furthermore, the cooling system should withstand certain shock test. For example, the system should not suffer any damage when subjected to the following test: a half sine shock test with duration less than 3 milliseconds and a speed difference of about 1.65 meters per second. The shock test should be conducted minimum 3 times on each of 6 faces of the system. Moreover, the cooling system is designed to meet regulatory requirement of UL/EN 60950. More detail about a control method of the direct air cooling system using one or more DC operated blowers in association with a damper arrangement to provide controlled cooling for the outdoor telecom shelter can be found in following paragraphs.
In one embodiment, the controller 500 includes function to monitor the DC supply voltage. In one example, the interface of the power input 510 is via a connector J1 which has 5 pins J1-1 through J1-5 shown in Table 1. As shown, connector pins J1-1 and J1-2 are connected for 0 V Return signal. Connector pin J1-3 is for chassis ground. Connector pins J1-4 and J1-5 are connected for −DC voltage supply. The connector can be ¼ PCB mounted “Faston” Blade Terminals. For example, a power connector with AMP Part No 62409-1 can be used.
Additionally, the controller 500 incorporates its own on-board DC power supplies including a +24V supply 540, +10.5V supply, and a +5V supply 530. The +24V power supply 540 is to generate the necessary power for the smoke alarm, the hydrogen alarm and the operation of damper arrangement. The +10.5V supply is for generating the PWM speed control signals and for energizing relays. Another on-board +5V supply 530 is directly coupled to the microprocessor 501 via a connection 535 for logic supply required by the microprocessor 501,
The microprocessor 501 is configured to directly couple with one or more blowers through one or more blower output ports 550. In one implementation, the controller 500 is designed to control variable speed blowers and deliver DC power to up to four motorized impellers which are controlled in two channels of two blowers dependent on the profile information programmed into the microprocessor 501. Each blower output 550 can be individually fused to prevent a single blower failure pulling the whole system down. The DC voltage supplied to these blowers is the same voltage supplied from the DC input 510 less any volt drop in the EMC filter 520. The interface associated with each of these blower output ports between the microprocessor 501 and each of the blowers can be via a 6-way connector. For example, 4 connectors, named as J2 through J5, are respectively used for four DC-driven radial blowers. Table 2 shows an example of the pin layout for the connector J2 though J5. For example, a Molex Minifit Jnr Right angle PCB mounted connector (Molex Part No. 39-30-0060) can be used.
Referring to
Referring again to
Furthermore, the controller 500 includes a plurality of alarm output ports 575 each through an isolated Form C relay contact to couple with the microprocessor 501. In one embodiment, the controller 500 is fitted with five isolated Form C relay contact alarm outputs. The common of each of the alarm outputs is connected to a single point. The Form C (normally open) NO contact and (normally closed) NC contact of each alarm relay coil are available fix connection to a corresponding external device. Each relay coil is characterized by its capability of switching power up to 500 mA at 30V DC. In a specific embodiment, the alarm output ports 575 include functions of a general alarm output, a smoke alarm output, a hydrogen alarm output, an over-temperature, alarm output, and a filter alarm output.
The general alarm output is triggered to indicate a blower failure (for example, a blower has stopped or failed to reach a predefined percentage of its target speed) and a thermistor failure (when thermistor has open or short circuit), or a DC supply failure (when DC supply of the system has dropped below a predefined voltage). The relay coil associated with the general alarm output is directly controlled from the microprocessor 501 and is typically energized in the no-alarm condition so that an alarm (associated with one of above three failures) output will be given in the event of a total power failure to the controller PCB or a failure in the controller itself.
The smoke alarm output provides an isolated output depending on a smoke alarm input signal from the smoke sensor connected to the microprocessor 501. In one embodiment, the relay coil associated with the smoke alarm output is energized during alarm condition, but open in normal condition.
The hydrogen alarm output provides an isolated output depending on a hydrogen alarm input signal from the hydrogen sensor connected to the microprocessor 501. In one embodiment, the relay coil of the hydrogen alarm output is energized during alarm condition, but open in normal condition.
The over-temperature alarm output provides an isolated output depending on a temperature measured inside the shelter and a set point defined in the functionality specification of the microprocessor 501. In one embodiment, the relay coil of the over-temperature alarm output is energized during alarm condition, but open in normal condition.
The filter alarm output provides an isolated output depending on an input signal from a pressure switch 580 connected to the microprocessor 501 for detecting if a filter arrangement associated with the blowers of the direct air cooling system is normal or abnormal. In one embodiment, the relay coil of the filter alarm output is energized during alarm condition, but open in normal condition.
In a specific embodiment, the relay contact alarm outputs are interfaced with the microprocessor 501 via a 12 way connector. For example, the connector, namely J9, can be a Molex 12 way KK type 2.54 mm pitch header with friction lock connector (Molex Part No. 22-23-2121). Table 5 shows an exemplary connector pinout.
Furthermore, the controller 500 is configured to receive an input from a pressure switch 580 which is used monitor the pressure drop across the filter to detect if the filter is clogged. As mentioned earlier, the input signal from the pressure switch 580 is used to directly drive the filter alarm relay and a LED for indicating filter alarm (to be described later). The pressure switch 580 is driven by the on-board +5V DC supply 530. The interface between the microprocessor 501 and the pressure switch 580 is realized by a connector, namely J10. For example, a 2 way Molex KK type 2.54 mm pitch header with friction lock connector can be used (Molex Part No. 22-23-2020). Table 6 shows a pinout of the connector.
Moreover, the controller 500 includes an on-board programming/test port 590 and a communications port 595 associated with the microprocessor 501. In one embodiment, the on-board programming/test port 590 is an In Circuit Serial Programming (ICSP) port which allows the flash memory in the microprocessor 501 to be programmed or reprogrammed after the controller 500 has been assembled. The capability of reprogramming with an appropriate programmer facilitates the production programming of the microprocessor 501 and also facilitates update of the program at a later date when necessary. This ICSP port 590 also is used for easy access to the +5V DC supply 530 and 10.5V DC supply for production testing (but not using ICSP), The interface between the on-board programming/test port 590 and the microprocessor 501 can be established via a 6 way connector, namely J11. For example, the connector can be a Molex KK type 2.54 mm pitch header friction lock connector (Molex Part No. 22-23-2061). Table 7 shows an exemplary connector pinout.
In another embodiment, the communications port 595 allows the controller 500 to be connected via an adaptor to the RS232 type port or USB type port of a personal computer. The communications port 595 is typically used for production testing of the system which is managed by the controller 500. The communications port 595 also can be set to broadcast performance and status information during normal operation and can be used for performance analysis. The interface to the system through the communications port 595 can be established via a connector, namely J12. For example, the connector J12 can be a 3 way Molex KK type 2.54 mm pitch friction lock header connector (Molex Part No. 22-23-2031). Table 8 shows an exemplary pinout for this connector.
In a specific embodiment, the controller 500 also includes a plurality of LED displays 577 coupled with the microprocessor 501. These LED displays 577 are triggered by the plurality of relay contact alarm outputs 575 to show different colored light. In one example, the controller 500 is tined with seven 5 mm diameter round LED's which will be visible through an aperture on the front of the fan trays sheet metal structure (e.g., blower subsystem 300 in
Alternatively, Embodiments of the present invention disclose a method for providing direct air cooling of electrical equipment operated within outdoor shelters supplemental to an existing air conditioning (A/C) system. In one embodiment, a simplified flow chart of the control method is illustrated in
Process 610: Providing a cooling system to a shelter with an A/C system, the cooling system comprising one or inure blowers, a damper, and a controller;
Process 615: Activating the controller operated from a DC supply;
Process 620: Receiving information associated with an interior temperature and an exterior temperature;
Process 625: Monitoring information associated with general alarm and a plurality of specific alarms;
Process 630: Processing information associated with the exterior temperature and information associated with the general alarm and the plurality of specific alarms;
Process 640: Determining whether a general alarm is triggered, or one or more specific alarms are triggered, or exterior temperature is greater than a predetermined value;
Process 645: If none of above occurs, processing information associated with the interior temperature;
Process 650: Determining whether a first criterion, or a second criterion, or a third criterion associated with the interior temperature is satisfied;
Process 660: if the first criterion is satisfied, inhibiting the A/C system; then
Process 662: Operating the one or more blowers at a rotation speed depending on the interior temperature; then
Process 664: Closing/Opening the damper as the rotation speed of one or more blowers is/isn't zero;
Process 670: if the second criterion is satisfied, activating the A/C system in cooling mode; then
Process 672: Stopping the one or more blowers;
Process 680: If the third criterion is satisfied, activating the A/C system in heating mode; then
Process 682: Stopping the one or more blowers;
Subsequently, the method 600 requires to perform, after each of the Process 672 and Process 682, the Process 664. followed by rerouted back to the Process 625 again in a closed loop.
The above sequence of processes provides a method according to an embodiment of the present invention. Other alternatives can also be provided where processes are added, one or more processes are removed, or one or more processes are provided in a different sequence without departing from the scope of the claims herein.
In one example, the cooling system used in the method 600 is the same as the direct air cooling system 100 shown in
The method 600 further includes a process of activating the controller by starting up DC power from the DC supply (Process 615) to make the microprocessor ready for executing preprogrammed control routines. In addition, the activation process involves an activation of a general alarm relay coil and activations of a plurality of sensing devices associated with the controller. For example, a general alarm relay coil is activated and a two-color LED indicates green during a start up period (approximate 5 seconds). Among the plurality of sensing devices, a first thermistor and a second thermistor are activated for temperature measurements. Other sensing devices includes a smoke sensor, a hydrogen sensor, a pressure switch, one or more AC power monitoring modules. DC voltage monitor, and the like.
Subsequently, the controller starts working with the activated plurality of sensing devices. In particular, at the Process 620, the microprocessor is receiving information associated with an interior temperature and from the first analog input and information associated with an exterior temperature from the second analog input. In one implementation, the first analog input is a port called Input Temp 1 connected to the microprocessor for delivering information associated with the interior temperature for the controller. Similarly, the second analog input is a port called Input Temp 2 connected to the microprocessor for delivering information associated with the exterior temperature for the controller. This process, in one implementation, is to start executing a closed-loop PWM control routine for the cooling system. In particular, the microprocessor, in response to at least the received information associated with the interior and exterior temperatures, should generate adequate control signals for controlling the speed of the one or more blowers. At the process 625, the controller also monitors information associated with the general alarm and a plurality of specific alarms received through the plurality of alarm inputs. In one implementation, the microprocessor is able to adjust the control signals based on received information associated with various alarms indicating abnormal operational status of the cooling system.
At the Process 630 following the previous Processes 620 and 625, the microprocessor firstly carries out a step for processing the received information associated with the exterior temperature and information associated with the general alarm and the plurality of specific alarms. In one embodiment, the cooling system sets to prioritize certain operational and environmental conditions to generate adequate control signals. For example, a general alarm involving a blower failure, or thermistor failure, or DC supply fault, has high priority and needs to be cleared first before performing rest operations. In certain exceptional case, during the starting up period, if the interior temperature is such that the one or more blowers would normally he stopped, the one or more blowers will start up and run during the start up period to allow installation engineers to establish that the blower is working normally. There is about 30 seconds delay to trigger general alarm to prevent the controller from issuing alarms during the blower starting up period. After the start up period they will be turned off or work to follow preprogrammed control routines. Additionally, some specific alarms including smoke alarm and hydrogen alarm and the shelter's exterior temperature are determining factors on how the various control signals are formulated for controlling the cooling system. More details about the control method at various environmental and operational conditions can be found below.
Based on the Process 630, the microprocessor is able to determine (at the Process 635) whether the exterior temperature is lower than a predetermined value, or whether a general alarm or one or more specific alarms is triggered.
In case that a negative result is obtained at the Process 640, then the microprocessor is to execute the next Process 645 for processing information associated with the interior temperature. Based on this process, the microprocessor is able to determine (at the Process 650) whether one of the three criteria associated with the interior temperature is satisfied. The three criteria simply corresponds to three predetermined temperature ranges. If the interior temperature measured by the first thermistor, determined by the microprocessor, falls into one particular range, a particular criterion is satisfied. Accordingly based on the programmed routine designed for the particular temperature, the controller generates adequate control signals to inhibit or re-activate the A/C system, to control a speed of each blower, and to open/close the damper whenever the speed of each blower isn't/is zero.
In an event when the first criterion is satisfied. Process 660 will be executed. In one embodiment, the first criterion is defined as limiting the interior temperature within a temperature window between a lower temperature limit and a higher temperature limit. For example, if the interior temperature is within a range of 0 Deg C. to 38 Deg C., the first criterion is satisfied. At Process 660 the microprocessor provides a control signal to inhibit the operation of the A/C system in this condition. Then (or essentially at the same time), Process 662 is executed to provide one or more control signals respectively to control speed of the blowers. Specific speed control depends on a specific value of the interior temperature detected by the first thermistor which can he installed near the one or more blowers at the interior side of the shelter. Process 664 (also can occur at substantially the same time) is executed to open the damper when the one or more blowers are blowing air into the shelter while to close the damper when the one or more blowers are stopped (for any reason).
In one example, as the interior temperature is below 7 Deg C., all blowers will be turned off. If the interior temperature is rising (as the electrical equipment in operation gradually heats up the shelter) to 10 Deg C. the controller may decide to start turn the blowers on at a speed of a certain speed, for example, about 1080 rpm. As the interior temperature further increases above 10 Deg C., the average speed of the blowers will increase linearly to reach a higher speed, for example, up to about 3000 rpm, at about 35 Deg C. In one embodiment, at temperature above 35 Deg C. but still below the higher temperature limit for the first criterion, the blowers will operate at the full speed of 3000 rpm unless stopped by other conditions including unsatisfied first criterion and some alarming situations.
If the interior temperature increases (as the electrical equipment keeps its operation) above the higher temperature limit, for example 39 Deg C., the second criterion becomes true. The Process 670 would be triggered in this condition. In particular, assuming no AC power supply alarm input is received, the controller would providing a control signal to remove the inhibit of the A/C system to enable it to take over the cooling of the shelter. In other words, Process 672 is executed at a substantially same time to stop the blowers. In fact, this is the condition that the shelter is cooled under conventional way. However, if the interior temperature measured by the first thermistor drops from a temperature above the higher temperature limit to a temperature below that limit, for example 35 Deg C. or lower, then the controller will send a control signal to inhibit the A/C system again and reestablish direct air cooling by turning on the blowers at the proper speed depending on the interior temperature.
If the interior temperature is below the lower temperature limit set for the first criterion, the third criterion is satisfied. In this condition, the Process 680 is triggered. At this process the controller is providing a control signal to remove the inhibit of the A/C system to allow it to operate in its heating mode to heat up the shelter. Accordingly, Process 682 is executed to stop the blowers. Usually, this occurs during a cold soak recovery process after an extended power failure at low temperature environment. However, it will disable the A/C system again once the interior temperature is above certain value above 0 Deg C., for example 5 Deg C.
In either situation above, the damper arrangement associated with the direct air cooling, system is controlled in response to the operation status of the blowers. In one embodiment, whenever, the blower is turned on, the damper arrangement will be instructed to open by a control signal sent by the controller. Whenever, the blower stops, the damper arrangement will be instructed to close by another control signal sent by the controller. In another embodiment, some events associated with on/off status of the blowers are related to one or more alarming events.
Referring back to
In another embodiment, the general alarm includes a thermistor fail alarm. In particular, if the thermistor connected to either first analog input or the second analog input is detected as either being open or short circuited then a general alarm is triggered by de-energizing the general alarm relay coil. Correspondingly in one implementation, the general alarm LED is changing color to flashing red color. In this case, the controller will also remove the inhibit to the A/C system to allow it to take over the cooling of the shelter unless there is also an AC power failure. If there is an AC power failure, i.e., the AC power fail alarm has been triggered, the DC powered controller will keep on operating the one or more blowers at full speed to draw cool air from exterior into the shelter.
In yet another embodiment, the general alarm also includes a DC supply fail alarm. The controller will monitor the DC supply voltage to the direct air cooling system and has been programmed to take action at different supply voltage. In one example, if the DC supply to the controller drops below 40V the controller will turn off all the blowers and close the damper to minimize the deep discharge of the batteries. The controller will also issue a general alarm in this condition. Thus Process 1100 will be executed. The controller will resume normal function when the DC supply voltage to the controller reaches 42.5V.
In the event that there are multiple alarms priority of the general alarms must be set In one example, the controller will prioritize the alarm indications as follows. Priority 1 (highest priority): Blower Fail, indicating by a continuous RED LED: Priority 2: Thermistor Fail, indicating by a flashing RED LED. In one embodiment, there is an about 30 seconds delay in blower alarms to prevent the controller from issuing alarms during the time that blowers are starting up.
There are some alarm situations that no immediate actions on either the operation of blower/damper combination or inhibit/activation of A/C system. For example, if the controller detects an input alarm signal from a pressure sensor (or a pressure switch) the controller will energize a filter alarm relay and illuminate the corresponding filter alarm LED in red color. The controller may also sent a message through its communication port to remote manager to make a request of filter change. Similarly, if the temperature detected by the thermistor connected to Input Temp 1 reaches 44 Deg C. In reading, the controller will indicate an over-temperature alarm via an over-temperature alarm relay and turn the corresponding LED to be illuminated RED. In this situation, the cooling of the shelter has been taken over by the A/C system (assuming no AC power fault). However, certain message can be sent to remote manager through the controller about the status of the shelter. The over-temperature alarm will be turned off if the temperature drops to 42 Deg C., all other functions of the controller will remain as normal.
Many benefits can be achieved by embodiments of the present invention. Certain embodiments of the invention provide a simple addition of a direct air cooling system to existing telecommunications shelters by mounting the fan tray on the door of the shelter. The damper arrangement is conveniently mounted over one of the existing cable duets in order to allow the field upgrade of the shelter. This structural design of the direct air cooling system keeps the structural integrity of the existing telecom shelter while providing a minimally invasive rework event. Some embodiments of the present invention utilizing the direct air cooling to provide a supplemental thermal management with significant amount of energy saving and reduce overall system operating cost. Because for quite portion of time period, the operation of existing A/C system associated with the shelter are inhibited and the shelter is cooled by the direct air cooling system based on embodiments of the present invention. In a specific embodiment, in the event of a power failure, the direct air cooling system can continue to operate normally from the battery back up allowing the entire shelter to operate for as long as there is power in the battery. Comparing to conventional shelter with A/C system only, the operation of the equipment within the shelter may quickly become over-heated since no alternate cooling is provided.
it is also understood that the examples and embodiments described herein are for illustrative purposes only and that various modifications or changes in light thereof will be suggested to persons skilled in the art and are to be included within the spirit and purview of this application and scope of the applied claims.
Number | Date | Country | |
---|---|---|---|
Parent | 12146409 | Jun 2008 | US |
Child | 13648901 | US |