The present disclosure relates generally to estimating trapped charge on a power line and, more particularly, to estimating the trapped charge for a controlled automatic reclose.
Non-limiting and non-exhaustive embodiments of the disclosure are described herein, including various embodiments of the disclosure with reference to the figures listed below.
One or more specific embodiments will be described below. In an effort to provide a concise description of these embodiments, not all features of an actual implementation are described in the specification. It should be appreciated that in the development of any such actual implementation, as in any engineering or design project, numerous implementation-specific decisions must be made to achieve the developers' specific goals, such as compliance with system-related constraints, which may vary from one implementation to another. Moreover, it should be appreciated that such a development effort might be complex and time consuming, but would nevertheless be a routine undertaking of design, fabrication, and manufacture for those of ordinary skill having the benefit of this disclosure.
Electric power delivery systems include equipment, such as generators, power lines, and transformers, to provide electrical energy from sources to loads. Various intelligent electronic devices (IEDs) may be used in monitoring, control, and protection of the power delivery system. For example, IEDs may obtain voltage measurements and/or current measurements and send signals to circuit breakers to protect the electric power delivery system from exceeding designed operating conditions due to faults. While some faults are persistent and remain on the power line, other faults are transient and may be resolved with power being disconnected, by opening the circuit breaker for a period of time, and restored, by automatically closing the circuit breaker.
When the circuit breaker is opened, electric charge may be trapped on the power line (e.g., due to capacitance of the line). When the circuit breaker is subsequently closed to restore service, a voltage difference between the disconnected power line and the voltage of the remaining online power system may cause transients (e.g., traveling waves). These transients may exceed voltages that the power line was designed to withstand. Exceeding the designed operating conditions of the power system may affect equipment or cause faults that would otherwise clear as transient faults to become persistent faults.
As explained below, an IED may obtain voltage measurements of a power line when the power line is disconnected from a power system. The IED may determine an amount of trapped charge on the power line based on the voltage measurements. The IED may control operation of the circuit breaker based on the amount of trapped charge. Further, the amount of trapped charge may be an analog estimation. For instance, the trapped charge may be determined as various per-unit values limited by the precision of voltage measurements obtained by the IED By estimating the analog value of trapped charge on the power line, the IED may close the circuit breaker at a time that reduces the voltage differences between the disconnected power line and the remaining online power system.
The power system 20 is monitored by a local IED 40 and a remote IED 42 located at the local terminal 26 and the remote terminal 28 respectively, although additional IEDs may also be utilized to monitor other locations of the system. As used herein, an IED (such as IEDs 40 and 42) may refer to any microprocessor-based device that monitors, controls, automates, and/or protects monitored equipment within the power system 20. Such devices may include, for example, remote terminal units, differential relays, distance relays, directional relays, feeder relays, overcurrent relays, voltage regulator controls, voltage relays, breaker failure relays, generator relays, motor relays, automation controllers, bay controllers, meters, recloser controls, communications processors, computing platforms, programmable logic controllers (PLCs), programmable automation controllers, input and output modules, and the like. The term IED may be used to describe an individual IED or a system comprising multiple IEDs. IEDs 40 and 42 may obtain electric power system information using current transformers (CTs) 44, 46, 48, and 50, and capacitor voltage transformers (CVTs) 52, 54, 56, and 58. The IEDs 40 and 42 may detect fault events on the power line 30 using current and voltage signals from the CTs 44, 4648, and 50 and/or the CVTs 52, 54, 56, and 58. In some embodiments, the IEDs 40 and 42 may communicate power system data via a communication link between the IEDs 40 and 42.
When a fault 70 occurs on the power line 30, the IEDs 40 and 42 may detect, for example, an overcurrent on the power line via the CTs 44 and 46. The IEDs 40 and 42 may send a signal to the circuit breakers (CBs) 60 and 62 to trip the breakers, thereby disconnecting the power line 30 from the power sources 22 and 24. While an overcurrent is used as an example, other suitable conditions may be used to disconnect the power line 30.
The IEDs 40 and 42 may send signals to the CBs 60 and 62 to trip at different times. For example, the remote CB 62 may be disconnected before the local CB 60 due to a lower threshold overcurrent, a lower threshold current-over-time, a faster trip time, or detecting the overcurrent first. Upon disconnecting the remote CB 62, the power line 30 may remain energized by the power being delivered from the power source 22. Due to the fault 70, the IED 40 may then disconnect the CB 60. When the CB 60 is disconnected, charge may remain on the power line 30, referred to as trapped charge.
The IED 40 may further include one or more processors 80, a computer-readable medium (e.g., memory 82), a communication interface 84, a display terminal 86, and detection circuitry 88 communicatively coupled to each other via one or more communication buses 90 The processor 80 may be embodied as a microprocessor, a general-purpose integrated circuit, an application specific integrated circuit (ASIC), a field programmable gate array (FPGA), and/or other programmable logic devices. It should be noted that the processor 80 and other related items in
In the IED 40 of
In the illustrated embodiment, the IED 40 includes detection circuitry 88 that detects various electrical conditions of the power line based on the input signals. The detection circuitry 88 may include a voltage conversion circuit 96 (e.g., transformer) and a current conversion circuit 98 (e.g., transformer) that transform the input signals to levels that may be sampled by the IED 40. The detection circuitry 88 may include analog-to-digital converter(s) 100 that sample the current and voltage signals and produce digital signals representative of measured current and measured voltage on the power line, which may be transmitted to the processor 80. The IED 40 may compare the current and/or voltage to thresholds to detect faults and to disconnect the power line 30 from the power source 22. For example, if current exceeds a preset threshold and/or current-over-time exceeds a preset threshold, the processor 80 may detect a fault event on the power line 30 and send a signal to open the CB 60.
The communication interface 84 may include a fiber optic transceiver that communicates with another IED, such as the remote IED 42, to receive signals indicating one or more measurements from the other IED While the illustrated embodiment communicates with the remote IED 42, in other embodiments, the IED 42 may communicate with many devices or may operate as an independent device without communication. In some embodiments, the IED 40 may include a display terminal 86 to allow operators to review events on the power line 30, change settings, etc.
The IED 40 may detect a fault event on the power line 30. As mentioned above, some faults are transient faults that may be cleared by opening the CB 60 and waiting for a period of time. To allow the temporary fault to clear, the IED 40 may open the CB 60 and subsequently attempt to reclose the CB 60 after a period of time to allow the power line 30 to continue to provide power to loads.
Due to the trapped charge on the power line 30, there may be a voltage difference between the power line 30 and the power being provided by the power source 22, which may cause voltage transients (e.g., traveling waves). Depending on the line characteristics, the voltage transients may exceed the expected designed ratings, such as basic insulation level, of the power line 30. In some cases, the voltage transients may cause what would otherwise be a transient fault to become a persistent fault that remains on the power line 30 due to exceeding the designed ratings of the power line.
As explained below, the amount of trapped charge may be estimated by the IED 40 using the voltage measurements received from the CVT 54. The trapped charge may then be used to obtain a closing point-on-wave (POW) at which to close the CB 60 during the reclose process to match the voltage of the remaining power system with the voltage from the trapped charge. Further, using the process described below, the IED 40 may be commissioned without user settings related to trapped charge.
The process 138 begins with detection that the CB 60 has opened. For example, the CB 60 may be opened to prevent overcurrents, overvoltages, or other events on the power line 30. Upon the opening signal sent to CB 60, the processor 80 may detect a rising edge of a trapped charge algorithm assertion (diamond 140). The rising edge of a trapped charge run algorithm assertion of the A-phase (TCRUNA) may refer to a signal that is asserted when the power line 30 is energized (e.g., in steady state) and the CB 60 is subsequently tripped. Upon assertion in which TCRUNA is true (diamond 142), the processor 80 may calculate potential trapped charge values of the A-phase based on the voltage measurements from the CVT 54 using the process described with respect to
Returning to
The processor 80 may detect a rising edge CLA signal indicating that the IED 40 may close the CB 60 (block 158). For example, a predetermined time (e.g., 12 cycles) may pass prior to receiving the rising edge CLA signal asserting that sufficient time for transient faults to clear has passed. Depending on the amount of time that passes (diamond 160), QTCA may be reset to zero (block 162). That is, if enough time passes (e.g., 10 seconds), the trapped charge on the power line 30 may be asserted as being zero. Upon determining the estimated trapped charge of each of the phases, the IED 40 may determine a closing point-on-wave (POW) to close each of the poles of the CB 60 using the TCpow process (block 164). The process of determining the trapped charge POW is described with respect to
As described in
Closing the CB 60 of one phase begins to affect the trapped charge of the remaining unclosed poles. By limiting the total amount of time from closing of the first phase to closing of the last phase, the open pole duration and the coupling effect between the phases may be minimized. The B phase and the C phase POW times may be adjusted to be aligned in time with the A phase to determine the minimum close time for the phases based on the first and second trapped charge point-on-wave values (blocks 308-314).
The processor 80 may use the system phase rotation (PHROT) for the relationship between the phases (block 308). Depending on the order of the phases, the B-phase and the C-phase may be adjusted with a different angle to align the time of the A-phase with the B-phase and C-phase (blocks 310 and 312). As illustrated in
The processor 80 may then select the value of k for each of the A phase, B phase, and C phase, such that time difference between the closing of the first pole and the closing of the last pole is minimized (block 316). With respect to
Returning to
The specific embodiments described above have been shown by way of example, and it should be understood that these embodiments may be susceptible to various modifications and alternative forms. It should be further understood that the claims are not intended to be limited to the particular forms disclosed, but rather to cover all modifications, equivalents, and alternatives falling within the spirit and scope of this disclosure.
The techniques presented and claimed herein are referenced and applied to material objects and concrete examples of a practical nature that demonstrably improve the present technical field and, as such, are not abstract, intangible or purely theoretical. Further, if any claims appended to the end of this specification contain one or more elements designated as “means for [perform]ing [a function] . . . ” or “step for [perform]ing [a function] . . . ”, it is intended that such elements are to be interpreted under 35 U.S.C. 112(f). However, for any claims containing elements designated in any other manner, it is intended that such elements are not to be interpreted under 35 U.S.C. 112(f).
Number | Name | Date | Kind |
---|---|---|---|
2209810 | Cordray | Jul 1940 | A |
3401304 | Woodworth | Sep 1968 | A |
3546534 | Kotos | Dec 1970 | A |
3558984 | Smith | Jan 1971 | A |
4322768 | Maeda | Mar 1982 | A |
4757263 | Cummings | Jul 1988 | A |
4914382 | Douville | Apr 1990 | A |
5367426 | Schweitzer, III | Nov 1994 | A |
5418776 | Purkey | May 1995 | A |
5430599 | Charpentier | Jul 1995 | A |
5627415 | Charpentier | May 1997 | A |
5638296 | Johnson | Jun 1997 | A |
5671112 | Hu | Sep 1997 | A |
5703745 | Roberts | Dec 1997 | A |
5805395 | Hu | Sep 1998 | A |
6028754 | Guzman | Feb 2000 | A |
6256592 | Roberts | Jul 2001 | B1 |
6341055 | Guzman-Casillas | Jan 2002 | B1 |
6356421 | Guzman-Casillas | Mar 2002 | B1 |
6392390 | Ito | May 2002 | B1 |
6456947 | Adamiak | Sep 2002 | B1 |
6518767 | Roberts | Feb 2003 | B1 |
6571182 | Adamiak | May 2003 | B2 |
6590397 | Roberts | Jul 2003 | B2 |
6879917 | Turner | Apr 2005 | B2 |
6919717 | Ghassemi | Jul 2005 | B2 |
7345863 | Fischer | Mar 2008 | B2 |
7425778 | Labuschagne | Sep 2008 | B2 |
7469190 | Bickel | Dec 2008 | B2 |
7472026 | Premerlani | Dec 2008 | B2 |
7812615 | Gajic | Oct 2010 | B2 |
8289668 | Kasztenny | Oct 2012 | B2 |
8553379 | Kasztenny | Oct 2013 | B2 |
9008982 | Tziouvaras | Apr 2015 | B2 |
9263213 | Mori | Feb 2016 | B2 |
9870879 | Taillefer | Jan 2018 | B2 |
20010012984 | Adamiak | Aug 2001 | A1 |
20020101229 | Roberts | Aug 2002 | A1 |
20070070565 | Benmouyal | Mar 2007 | A1 |
20090059447 | Gajic | Mar 2009 | A1 |
20090091867 | Guzman-Casillas | Apr 2009 | A1 |
20100002348 | Donolo | Jan 2010 | A1 |
20120306290 | Fanget | Dec 2012 | A1 |
20130054177 | Montenegro | Feb 2013 | A1 |
20130234731 | Tziouvaras | Sep 2013 | A1 |
20170358404 | Talluri | Dec 2017 | A1 |
Number | Date | Country | |
---|---|---|---|
20210218239 A1 | Jul 2021 | US |