The present invention relates to fluid-operated heat activated pumping devices for the transport of heat, and especially those adapted for the removal of the waste heat generated by electronic devices, at the chip, board, rack, or datacenter level.
Electronics, microelectronics, and opto-electronic devices convert most of the power they consume into waste heat. The devices need to be maintained within a narrow operating temperature to ensure optimal performance and long-term reliability. If they run too hot, they will degrade faster. If they are cooled excessively, the amount of cooling infrastructure required can be prohibitively expensive.
Electronics cooling can be classified by the amount of heat being dissipated. For instance, data center level cooling is performed on the order of tens to thousands of kilowatts. Printed Circuit Board (PCBA) level cooling is on the order of tens to thousands of watts. Chip level cooling can be order of milliwatts to tens or hundreds of watts. Different cooling solutions are deployed at each level depending on the amount of heat dissipated and the geometric space available.
Demand for data center cooling is a growing global market driven by ever increasing data usage. A common metric for measuring data center cooling is the PUE (Power Usage Effectiveness). This is the ratio of the total power consumed and the actual power used by the IT equipment. A PUE of 1 means 100% of the power consumed was used by IT equipment. Common PUE values range from 1.11-3. That means cooling infrastructure roughly adds an additional 11-300% overhead to the data center. This additional overhead is in the form of air handling units, pumps, condensers etc.
There is clearly an economic and environmental benefit in making the PUE of datacenters as close to 1 as possible. However, there are several challenges involved in achieving this:
1. Air is a very poor heat conductor. In air-cooled data centers, the exhaust side air in a data center is at a relatively low temperature (28° C.-45° C.). Air at this temperature cannot be used for much heat recovery or for other processes directly. Often, the air must be heated to a higher, more useful temperature around 80° C. for use in other applications like residential/commercial hot water needs, laundry services, industrial kitchens etc. Significant infrastructure, investment and installation costs are incurred in performing the pre-heating. This in turns raises the PUE. While most data centers are still air cooled due to its convenience and low installation cost, with ever increasing heat densities, there is a push towards liquid cooled data centers.
2. Liquid cooling is much more efficient for heat transfer from the data center, even though it has a higher upfront cost due to the piping required. A key benefit of liquid cooling is that the waste heat is stored in higher fluid temperatures. This hot fluid is then used to perform useful work, and in some cases generate electricity. The efficiency of the process is still too low to justify the infrastructure investment required. Moreover, with liquid cooling, there is a need for efficient pumps to move the cooling fluid around and transfer the heat.
Within a datacenter, there are usually multiple racks of servers, networking, and other equipment. Within each rack are multiple PCBAs which house a number of electronics components (chips, memories, optical devices, power delivery devices etc.) interconnected together. Aside from datacenters, PCBAs are also used in other applications such as in automobiles, aircraft, wind turbines, transformers etc.
At the PCBA level, in non-hermetic applications, air flows from one end of the PCBA to the other, thus cooling the components on the PCBA. In hermetic applications, cooling is achieved by conduction to a cooler surface for subsequent convective and radiative heat dissipation. Current mainstream solutions rely on the following technologies to maintain stable operating temperatures, in increasing order of sophistication and cost:
Pros and cons of passive and active cooling techniques (4 and 5) are:
A device mounted downstream from another device must be cooled even more to account for the warmer air exiting from the upstream chip. This “shadowing” effect is quite prevalent in most PCBAs because the airflow is unidirectional across the entire board. Generally, the higher heat dissipating devices are placed closer to the front, where cooler air is entering. Consequently, other devices like power supplies downstream have a lower temperature margin and must contend with warmer incoming air while maintaining their temperature below a target limit. To ensure these downstream components remain functional, the fans, heatsinks, airflow etc. need to be increased at entry, which adds more cost, complexity, and inefficiency to the cooling solutions.
A challenge with conventional PCBA level cooling techniques, like heatsinks, heat pipes and vapor chambers, is that they are designed to operate at constant (worst case) power dissipation and ambient temperature conditions upfront during the design process. While cooling fans can be variable speed; that is only helpful within a narrow range and fan speed control is a very coarse tool: if even one device is running hot, the fans will run faster to keep that device cool but will also inevitably cool the other devices that don't require the additional cooling. For instance, a heatsink is designed upfront to operate at 55° C. ambient temperature and the highest expected power dissipation of the chips. So even if the ambient temperature is 27° C. and the actual power dissipation of the chip is 10% lower than expected, the heatsink or heat pipe cannot be resized dynamically to account for the lower actual thermal cooling needs. This makes electronic systems bulkier and more expensive because they are designed to fit the worst-case environment.
Another challenge with conventional PCBA level cooling is that there is little ability to “tune” the device temperature to optimize field reliability. Newer silicon technologies make devices very sensitive to operating temperature and reliability. If the target lifetime of the device is 10 years and it has been used in a relatively benign environment where most of its lifetime is not yet consumed; the device could be operated at a higher duty cycle (above its recommended temperature) so that more of its useful life can be consumed. Conversely, if a device has been used in an excessively harsh environment, it could be run at a lower temperature, so it lasts closer to its target lifetime. Such “tuning” of device reliability is not possible to achieve with the current conventional cooling solutions.
In some high-performance applications, conventional pumped liquid cooling can be used to cool PCBAs. However, these liquid cooling solutions require dynamic pump control (sensors, controller circuitry etc.) to maintain pump speed. This in turn adds more cost, overhead, reliability and operational risk and real estate to the PCBA cooling solution.
Another key shortcoming of current PCBA level cooling solutions is that all the heat dissipated from the electronic devices is simply transferred to the ambient air or cooling liquid. None of the dissipated heat is actually used to do any useful work, not even work to actually cool the devices in the first place. For instance, assume a PCBA has five (5) devices, each device dissipating 500 W (total board heat dissipation is 2500 W). A conventional liquid cooling system would require 10 W per device to operate a cooling pump (total pumping power of 50 W required). If even 0.1% of the heat dissipated is converted into useful work (e.g., to pump cooling fluid around), the overall heat dissipated will be reduced from 2550 W to 2547 W (a 1.9% reduction). Scaling this to hundreds or even thousands of boards used across multiple products, the savings can be tremendous.
Going deeper from the PCBA to the silicon chips, the closer the cooling solutions get to the heat source itself, the more efficient they can be. At the chip level, electronics cooling is facing several challenges:
Conventional chip level cooling solutions vary depending on the amount of heat to be dissipated. Pumped direct liquid cooling through chip microchannels, two phase jet impingement cooling or immersion-cooling are used in applications where the heat dissipation is on the order of hundreds to thousands of watts. These solutions rely on connectivity to the larger system to enable the circulation of fluid in and out of the chip and off-chip fluid cooling.
Low wattage devices (on the order of 0.1 milliwatts to tens or a few hundreds of watts) require specific cooling solutions especially if they are in a constrained space. Smartphones are becoming more sophisticated and power hungry. Smartphone capability is limited by power consumption and heat loss. More computation capability means more power consumption, which means more heat generation and larger battery size.
Heat from smartphones is dissipated by conductive heat transfer from the transistors through the phone body to the surrounding atmosphere, human skin etc. Due to space limitations, there are no active cooling devices like fans or pumps to remove the heat faster. In some advanced smartphones, miniature heat pipes/vapor chambers are used to speed up the heat transfer from the transistors to the smartphone chassis. Heat pipe fluid return capability is limited by the amount of pumping power the capillary wicks can provide. This capillary return capability is both space and material limited. A miniature wick structure can only pump so much fluid even in best case conditions. While heat pipes are somewhat more effective than thermal interface materials, there is still a need for better heat dissipation without consuming too much space. There is a need to use active cooling techniques (like pumped liquid cooling) to speed up the heat transfer without significantly changing the size, thickness, cost, or reliability of the smartphone device.
Wearable devices (fitness monitors, watches etc.) have the same, if not even more critical, challenges of power consumption, size, cost, and battery power as smartphones. With such limited space and close contact with human skin, there is even greater need for better cooling of electronics in a small space. A typical smartwatch is expected to last at least 15 hours with a 2200 mAh battery. Operating at 1.1V, that translates to 2.42 Wh. This energy is mostly converted into heat and dissipated from the battery chassis to ambient air and human skin. Human skin is very sensitive to high temperature and a typical chip in the smartwatch can run as high at 40° C. This limits the capability of the wearable device. Current efforts are focused on using advanced thermal interface materials (graphite etc.), heat pipes, vapor chambers etc. to enhance heat transfer. These techniques are passive solutions which have limited effectiveness for temperature control and heat transfer.
Due to limited power availability, there is also a need to recapture the heat lost so it can be used to power the device rather than being dissipated/wasted into the environment. Even a small amount of energy recapture can help prolong the operating time of the device or reduce the size or cost of the battery. Efforts have been made in the past to use thermoelectric generators that utilize the difference in temperature between the device and human skin to generate electricity. However, this approach has been shown to be insufficient to generate enough useful energy to justify the space consumed by the thermoelectric generator and the cost involved.
There is a need for a scalable solution that can be deployed at the system level (e.g., datacenter), PCBA and chip level to address several of these issues and be cost effective and reliable.
A heat activated pump is provided for the removal of waste heat from one or more electronics components, either at the chip, board, rack, or datacenter level. An evaporator contains a working fluid and is directly coupled against one or more electronics components to receive external heat therefrom to convert the working fluid into vapor. A pressure-control valve is coupled to an exit port of the evaporator, maintains the working fluid in the evaporator at a set target pressure and allows vaporized working fluid to escape through the exit port whenever the target pressure is exceeded. A liquid-piston chamber coupled to the pressure-control valve receives the vaporized working fluid from the evaporator at the target pressure. The vaporized working fluid expands adiabatically and displaces liquid within the liquid-piston chamber, expelling it therefrom in a pumping stage of a thermodynamic cycle. A unidirectional pump-exit check valve is coupled to an exit port of the liquid-piston chamber to allow the displaced liquid to exit the liquid-piston chamber. A unidirectional liquid suction-entry check valve is coupled to a return port of the liquid-piston chamber. A condenser with a heatsink is coupled to the pump-exit and suction-entry check valves to receive displaced liquid and allow it to return to the liquid-piston chamber in a suction stage of the thermodynamic cycle. The heatsink radiates heat away to a flow of cooler air. Finally, a unidirectional vapor-injector return check valve is coupled to both an exit port of the liquid-piston chamber and to an input port of the evaporator. Periodic pressure pulses from the liquid-piston chamber that temporarily exceed the pressure in the evaporator facilitate jets of condensed working fluid to return to the evaporator in successive brief spurts.
The solution presented with this heat-activated multiphase fluid-operated pump technique for electronics cooling provides all the benefits of liquid cooling without some of the challenges of conventional pumps, piping and connectors involved in liquid cooling:
In terms of operating conditions, the present heat activated pump solution sits between the two extremes of active and passive cooling solutions. It uses vapor, not liquid, pressure to drive the pumping.
Working Fluid: The fluid whose change in phase is utilized to performing the pumping operation. The working fluid could be selected from a variety of fluid options: water, as well as commonly used or new refrigerants (e.g., R-130, R-245fa, R-407c, R-410a, R-454b, R-1234yf, etc.). In addition to performance and desired temperature range, safety (flammability and exposure limits) will be factors in the choice of working fluid.
Pumped Fluid: The fluid which needs to be pumped from one location to another. This could be the same as the working fluid or it could be a different fluid material altogether. If the pumped fluid is different, it would need to be immiscible with the working fluid. In that case, a separator 113 may be provided (as seen in
Ambient Temperature: The temperature in the general environment around the region or device in focus.
The Heat-Activated Multiphase Fluid-Operated Pump
The HAMFOP pump utilizes heat to pump a fluid. The heat is used to convert a working fluid from liquid to vapor. The vapor is then used to displace the fluid that needs to be pumped.
The principle of operation is as follows, as referenced by the numbered elements in
In the case where the pumped fluid 114 (and 106) is composed of a different material from the working fluid 102 (and 110), and not merely a different liquid-vapor phase of the same material, a difference in density between the working and pumped fluids can be leveraged to separate them. The elements of such an embodiment are largely identical to structure and operation to those in
Heat Activated Pump for Cooling of Large Systems Such as Racks of PCBAs, Datacenters and Other Such Large Electronic Systems
A heat activated pump system can be used to move fluid around a datacenter as illustrated in
Heat activated pumps on devices attached to PCBAs in a rack pump the cooling fluid around in piping running throughout the data center. The datacenter-level heat activated pump system uses this hot pumped fluid from each individual heat activated pump to pump the fluid to the condenser and return the fluid back to the PCBA level devices at a cool temperature to close the circuit as shown in
Heat Activated Pump for Cooling of Electronic Devices Mounted on PCBAs
As seen especially in
This specific embodiment is for a chip and board horizontally oriented with the heat activated pump mounted on top of the chip. This design can easily be modified to operate with a chip and board vertically oriented as well. In situations where multiple chips are mounted close together (as in chiplets on a single substrate) and some of the chips have lower operating temperature requirements as compared to others (as in memories and logic devices); then their heat paths can be completely separated into two distinct pumps operating independently. The vapor pressure of each pump can be tuned to match the target operating temperature of each chip to be cooled. This way, cross heating is mitigated, and each chip operates close to its own target temperature.
Evaporator
The details of the evaporator are outlined in
1. An enclosure 203 that holds the evaporator core 204 and facilitates the transfer of heat from an external heat source to the evaporator core 204. The region of the enclosure 203 exposed to the heat source needs to be designed to be very high thermal conductivity and low thermal resistance. The rest of the evaporator enclosure 204 is insulated to prevent heat loss.
2. An evaporator core 204, in which the working fluid is converted from liquid to vapor or maintained in vapor form. The key design features of the core 204 are very high surface area to enable effective heat transfer to the liquid. Some embodiments of the core include but are not limited to:
The details of the pressure control valve are outlined in
1. A gasket 208 that seals the vapor in the evaporator 203, 204 and 205. In very precisely machined structures, the gasket 208 can be dispensed with, and pure solid-solid pressure could be relied upon.
2. A valve shaft 216 that transmits the load from the counterweight 213 to the gasket 208 to keep the pressure below a set value as determined by the weight of the counterweight load 213.
3. A larger second cavity in which the valve shaft 216 sits, which ensures that a force applied by the vapor is still high enough to keep the seal open as the vapor exits the evaporator into the piston.
4. A diaphragm 210 that deflects when the vapor pressure exceeds the counterweight load 213. The diaphragm 210 also prevents the vapor from leaking out of the valve.
5. A load seat 209 that applies a mechanical advantage: one end has a small area and the other has a much larger area to accommodate the larger load 213. The seat 209 also has a cavity in it to hold the load 213 in place.
6. A load 213 that could be a dead-weight or a liquid that keep the valve closed at a set pressure. The load 213 could also be a spring-loaded structure to achieve the same end objective: an applied force.
7. A load cover 214 that encases the dead weight load 213 and holds it all in place. A small hole can be made in the cover to ensure that the air around the dead-weight load 213 always remains constant (atmospheric).
Piston Chamber
The details of the piston are outlined in
1. The encasing body 206 (seen in
2. A piston chamber 207d in which the vapor expands and pushes out the pumped fluid. A key benefit of a liquid piston is that infinite potential shapes can be used to make the design compact, space efficient and versatile.
3. The chamber walls of the piston-suction chamber 207d need to be smooth and can be coated with fluid repelling coating to reduce friction losses. The curves in the structure need to be smooth to prevent localized sudden area increases which may cause the vapor to condense prematurely.
Valves
The details of the valves 207a-207c are outlined in
Condenser
The details of the condenser and heatsink 211 are outlined in
Multiple Chips on PCBA Implementation
The aforementioned implementations are for cooling only one individual electronics device on a PCBA 200. When multiple devices 217 are mounted on a PCBA 200, an example arrangement is shown in
The fluid-operated heat activated pumps 218 of multiple devices can be joined together to a common condenser 219, as seen in
The condenser 219 can also be placed in front of the target device so the condenser receives the coolest incoming air and the hot air it releases downstream can be directed at the device to ensure it runs hot.
The heat activated pumps on each device interconnected, convert part of the collective heat dissipated by the devices into useful work to pump the cooling fluid around the devices, to maintain them at a constant target temperature.
Heat Activated Pump for Cooling of Low Wattage Electronics (Smartphones, Wearables, Flat Panels, Etc.)
A fluid-operated heat activated pump for space-constrained devices (smartphones, wearables, etc.) is shown in
In vertical space constrained applications, a deadweight load cannot be used, especially if the operating temperature is high. In such situations, the diaphragm itself could be stiffened to act as the load by selecting the appropriate thickness, material, and diameter. In situations where a diaphragm cannot be used, a spring or a liquid dead weight (like Gallium) can be used. The operating principle is Pascal's law: the pressure in a fluid is always the same and the pressure is a function of the height of the fluid.
Taller columns produce higher counterweight. In some situations, the counterweight load may need to be dynamically changed (increased or decreased) while the unit is operating. For instance: the ambient temperature temporarily increases beyond nominal values. A higher ambient temperature means a higher flowrate is required through the condenser to transfer the same amount of heat. If the duty load on the chip is low, the temperature of the chip can be raised slightly, so the pump does more work and increases the flowrate through the condenser. This increase in chip temperature can be accomplished by raising the deadweight value: by increasing the height of the liquid column. This can be achieved by using a bimetallic strip which contracts in diameter, thus raising the height of the liquid column.
In applications where the ambient temperature is too high (e.g., a smartphone left on a car dashboard or an electronic device in a higher than specified ambient environment), the pump will act as a “thermal switch” where heat from outside the device will not be conducted back into the device. It accomplishes this because the pump is designed to transfer heat from the evaporator to the condenser. If the condenser temperature exceeds the evaporator temperature, the pump will cease to function until the condenser temperature drops below the evaporator temperature.
The present application claims priority under 35 U.S.C. 119(e) from U.S. Provisional Application 63/076,546, filed Sep. 10, 2020.
Number | Name | Date | Kind |
---|---|---|---|
1781541 | Einstein et al. | Nov 1930 | A |
2927434 | MacCracken | Mar 1960 | A |
4769997 | Pandak | Sep 1988 | A |
5129788 | Okayasu | Jul 1992 | A |
5966957 | Malhammer et al. | Oct 1999 | A |
6042342 | Orian | Mar 2000 | A |
6123512 | Benner | Sep 2000 | A |
6820684 | Chu et al. | Nov 2004 | B1 |
7263848 | Bhatti | Sep 2007 | B2 |
7380584 | Ippoushi et al. | Jun 2008 | B2 |
7503176 | Yatsuzuka et al. | Mar 2009 | B2 |
7841385 | Campbell et al. | Nov 2010 | B2 |
7971449 | Peterson et al. | Jul 2011 | B2 |
8120916 | Schmidt et al. | Feb 2012 | B2 |
8240165 | Novotny | Aug 2012 | B2 |
8322154 | Campbell et al. | Dec 2012 | B2 |
8419378 | Fenton et al. | Apr 2013 | B2 |
8820114 | Charamko et al. | Sep 2014 | B2 |
9069532 | Campbell et al. | Jun 2015 | B2 |
9239063 | Fenton et al. | Jan 2016 | B2 |
9285129 | Novotny et al. | Mar 2016 | B2 |
9332671 | Schult et al. | May 2016 | B2 |
9618244 | Blouberg et al. | Apr 2017 | B2 |
9829253 | Mishkinis et al. | Nov 2017 | B2 |
9869274 | Fuhrman | Jan 2018 | B2 |
10041708 | Sedlak et al. | Aug 2018 | B2 |
10369863 | Connell et al. | Aug 2019 | B2 |
10436521 | Cho et al. | Oct 2019 | B2 |
10605501 | Bangheri | Mar 2020 | B2 |
10712100 | Adamson et al. | Jul 2020 | B2 |
10724772 | Connell et al. | Jul 2020 | B2 |
10746440 | Donovan et al. | Aug 2020 | B2 |
10830503 | Kopko | Nov 2020 | B2 |
10914266 | Rolandson | Feb 2021 | B2 |
10948241 | Joshi | Mar 2021 | B2 |
10962304 | Adamson et al. | Mar 2021 | B2 |
20090129946 | Toubia et al. | May 2009 | A1 |
20120136954 | Davis et al. | May 2012 | A1 |
Number | Date | Country |
---|---|---|
102410187 | Apr 2012 | CN |
0251664 | Apr 1990 | EP |
2927038 | Oct 2015 | EP |
303065 | May 1930 | GB |
1329567 | Sep 1973 | GB |
2015654 | Sep 1979 | GB |
1020120056521 | Jun 2012 | KR |
WO2005035987 | Apr 2005 | WO |
WO2005042981 | May 2005 | WO |
WO2005121539 | Dec 2005 | WO |
WO2012091816 | Jul 2012 | WO |
WO2013149621 | Oct 2013 | WO |
WO2020030933 | Feb 2020 | WO |
Entry |
---|
Printout: David Mytton, “How much energy do data centers use?”, https://davidmytton.blog/how-much-energy-do-data-centers-use/, published in Cloud, Data Center Energy, Environment, IT Energy, Feb. 10, 2020, 12 pages. |
Printout: Electric Cooling, “Thermal management and safety regulation of smart watches”, https://www electronics-cooling.com/2017/09/thermal-management-safety-regulation-of-smart-watches/, Sep. 11, 2017, 10 pages. |
Printout: K.Heslin, “10 Data center trends to watch in 2020”, https://facilityexecutive.com/2020/04/data-center-management-10-data-center-trends/, Apr. 22, 2020, 5 pages. |
Printout: Data Center Cooling Market Growth, https://www.fortunebusinessinsights.com/industry-reports/data-center-cooling-market-growth/, Jan. 2020, 10 pages. |
Wikipedia: “Einstein refrigerator”, https://en.wikipedia.org/w/index.php?title=Einstein_refrigerator&oldid=973585763, Aug. 18, 2020, 3 pages. |
Wikipedia: “Heat pipe”, https://en.wikipedia.org/w/index.php?title=Heat_pipe&oldid=973161839, Aug. 15, 2020, 15 pages. |
Wikipedia: “Immersion cooling”, https://en.wikipedia.org/w/index.php“title=Immersion_cooling&oldid=1043510651”, Sep. 10, 2021, 8 pages. |
Wikipedia: “Injector”, https://en.wikipedia.org/w/index.php?title=Injector&oldid=967631660, Jul. 14, 2021, 7 pages. |
Wikipedia: “List of refrigerants”, https://en.wikipedia.org/w/index.php?title=List_of_refrigerants&oldid=1035339680, Jul. 26, 2021, 17 pages. |
Wikipedia: “Loop heat pipe”, https://en.wikipedia.org/w/index.php?title=Loop_heat_pipe&oldid=952560728, Apr. 22, 2020, 3 pages. |
Wikipedia: “Metal foam”, https://en.wikipedia.org/w/index.php?title=Metal_foam&oldid=1044893829, Sep. 17, 2021, 13 pages. |
Wikipedia: “Relief valve”, https://en.wikipedia.org/w/index.php?title=Relief_valve&oldid=974509246, Aug. 23, 2020, 4 pages. |
Wikipedia: “Safety valve”, https://en.wikipedia.org/w/index.php?title=Safety_valve&oldid=957512538, May 19, 2020, 11 pages. |
Wikipedia: “Thermal management (electronics)”, https://en.wikipedia.org/w/index.php?title=Thermal_management_ (electronics)&oldid=1038841962, Aug. 15, 2021, 11 pages. |
Wikipedia: “Thermosiphon”, https://en.wikipedia.org/w/index.php?title=Thermosiphon&oldid=960989907, Jun. 6, 2020, 4 pages. |
Printout: “Capillary limit”, Advanced Cooling Technologies, https://www.1-act.com/resources/heat-pipe-performance/capillary-limit/, Nov. 20, 2017, 5 pages. |
Printout: “IGBT Cold Plates ATS-CP-1002”, Advanced Thermal Solutions, Inc., Cold plates data sheet, Apr. 24, 2018, 2 pages. |
Printout: “Closed loop liquid cooling for high power electronics”, Advanced Thermal Solutions, Inc., Qpedia, vol. 1, Issue 9, Oct. 2007, 5 pages. |
Printout: “Liquid cooling systems and their components”, Qpedia Newsletter, Apr. 2009, 4 pages. |
Article: James D. Van de Ven et al., “Liquid piston gas compression”, Applied Energy, Jan. 6, 2009, 9 pages. |
Printout: “Futuristic engine for the new hybrid cars: free piston linear alternator (FPLA)”, Bright Hub Engineering, Oct. 8, 2001, 2 pages. |
Printout: “Which pump should you use? D5 or DDC?”, https://www.ekwb.com/blog/which-pump-should-you-use-d5-or-ddc/, Nov. 11, 2016, 6 pages. |
Article: S. Langdon-Arms et al., “Development of a solar-powered liquid piston Stirling refrigerator”, Energy Procedia, 142, 570-575, 9th Int'l Conference, ICAE2017, Aug. 21, 2017, 6 pages. |
CN 102410187A, English translation, 12 pages, Year: 2012. |
KR 20120056521A, English translation, 12 pages, Year: 2012. |
Wikipedia: “Absorption refrigerator”, https://en.wikipedia.org/w/index.php?title=Absorption_refrigerator&oldid=970309157, Jul. 30, 2020, 5 pages. |
Wikipedia: “Check valve”, https://en.wikipedia.org/w/index.php?title=Check_valve&oldid=973253068, Aug. 16, 2020, 7 pages. |
Wikipedia: “Computer cooling”, https://en.wikipedia.org/w/index.php?title=Computer_cooling&oldid=1045406650, Sep. 20, 2021, 23 pages. |
Article: J.W. Mason et al., “Design and construction of a solar-powered fluidyne test bed”, Proceedings of the ASME 2011 Mechanical Engineering Conference, Nov. 11, 2011, 12 pages. |
Paper: T.M. Kuzay et al., “Enhanced heat transfer with metal wool filled tubes”, Conference-910375-1, DE91 005831, (osti.gov 6329405), Aug. 1990, 32 pages. |
Printout: MicroCool, 3000 series coldplates data sheet, www.microcooling.com, Mar. 15, 2016, 2 pages. |
Printout: “Liquid cooling vs. air cooling: What you need to know”, https://www.pcworld.com/article/2028293/liquid-cooling-vs-traditional-cooling-what-you-need-to-know.html, by David Murphy, Feb. 19, 2013, 2 pages. |
Article: G. Dannen, “The Einstein-Szilard Refrigerators”, Scientific American, Jan. 1997, 6 pages. |
Printout: “Introduction to safety valves”, Spirax Sarco, https://www.spiraxsarco.com/learn-about-steam/safety-valves/safety-valves, Sep. 1, 2020, 29 pages. |
Printout: “Heat conducting 3D printing plastics”, TCPoly, High performance plastic cold plates datasheet, www.tcpoly.com/products/coldplates, Sep. 10, 2019, 2 pages. |
Article: James D. Van de Ven et al., “Developments towards a liquid piston Stirling Engine”, American Institute of Aeronautics and Astronautics, Tracking# 132055, Paper #5635, Jun. 20, 2008, 9 pages. |
Article: A.H. Zamanian et al., Identification and compensation of cogging and friction forces in tubular permanent magnet linear motors, Proceedings of the ASME 2017 Dynamic Systems and Control Conference, Oct. 11, 2017, 8 pages. |
Article: B. Zohuri, “Basic principles of heat pipes and history”, Heat Pipe Design and Technology, DOI 10.1007/978-3-319-29841-2_1, Apr. 2016, 41 pages. |
Article: Jinwang Li et al., “Experimental study on evaporation-capillary pumping flow in capillary wick and working fluid system”, Thermal Science, Jan. 2019, 12 pages. |
Number | Date | Country | |
---|---|---|---|
63076546 | Sep 2020 | US |